RKC INSTRUMENT CZ-100P, PCT-300 Instruction Manual

Page 1
A
Resin Pressure Measuring System
CZ-100P PCT-300
Instruction Manual
Thank you for purchasing this RKC product. In order to achieve maximum performance and ensure proper operation of your new instrument, carefully read all the instructions in this manual. Please place the manual in a convenient location for easy reference.

CONTENTS

1. OUTLINE ··························································· 2
2. PRODUCT CHECK ·············································· 2
3. MOUNTING ························································ 2
4. WIRING ····························································· 5
5. ADJUSTMENT ···················································· 6
6. CALIBRATION ···················································· 6
7. LINEARIZING FUNCTION SETTING ······················· 8
8. TROUBLES AND CAUSE······································ 8
9. EXPLANATION OF EACH TERMS·························· 9
10. SPECIFICATIONS ··········································· 10

SYMBOLS

WARNING

CAUTION

To prevent injury to persons, damage to instrument and
equipment, a suitable external protection device shall be required.
All wiring must be completed before power is turned on
to prevent electric shock, fire or damage to instrument and equipment.
This instrument must be used in accordance with the
specifications to prevent fire or damage to instrument and equipment.
This instrument is not intended for use in locations
subject to flammable or explosive gases.
Do not touch high-voltage connections such as power
supply terminals, etc. to avoid electric shock.
RKC is not responsible if this instrument is repaired,
modified or disassembled by other than factory-approved personnel. Malfunction can occur and warranty is void under these conditions.
This product is intended for use with industrial machines, test and
measuring equipment. (It is not designed for use with medical equipment and nuclear energy.)
This is a Class A instrument. In a domestic environment, this
instrument may cause radio interference, in which case the user may be required to take additional measures.
This instrument is protected from electric shock by reinforced
insulation. Provide reinforced insulation between the wire for the input signal and the wires for instrument power supply, source of power and loads.
Be sure to provide an appropriate surge control circuit respectively
for the following:
- If input/output or signal lines within the building are longer than 30
- If input/output or signal lines leave the building, regardless the
ll Rights Reserved, Copyright 1995, RKC INSTRUMENT INC.
: This mark indicates precautions that must be taken if
there is danger of electr ic shock, fire, etc ., which could result in loss of life or injury.
: This mark indicates that if these precautions and
operating procedures are not taken, damage to the instrument may result.
: Th is ma rk indi ca tes th at all pr ec au tion s sh ou ld be t ak en
!
for safe usage.
: This mark indicates important information on
installation, handling and operatin g procedures.
: This mark indicates supplemental information on
installation, handling and operatin g procedures.
: This mark indicates where additional information may
be located.

WARNING

!
CAUTION
meters. length.
IM100CZ04-E4
RKC INSTRUMENT INC.
®
This instrument is designed for installation in an enclosed
instrumentation panel. All high-voltage connections such as power supply terminals must be enclosed in the instrumentation panel to avoid electric shock by operating personnel.
All precautions described in this manual should be taken to avoid
damage to the instrument or equipment.
All wiring must be in accordance with local codes and regulations. All wiring must be completed before power is turned on to prevent
electric shock, instrument failure, or incorrect action. The power must be turned off before repairing work for input break and output failure including replacement of sensor, contactor or SSR, and all wiring must be completed before power is turned on again.
To prevent instrument damage as a result of failure, protect the power
line and the input/output lines from high currents with a suitable overcurrent protecti on device with adequate breaking capacity such as fuse, circuit breaker, etc.
Prevent metal fragments or lead wire scraps from falling inside
instrument case to avoid electric shock, fire or malfunction.
Tighten each terminal screw to the specified torque found in the
manual to avoid electric shock, fire or malfunction.
For proper operation of this instrument, provide adequate ventilation for
heat dispensation.
Do not connect wires to unused terminals as this will interfere with
proper operation of the instrument.
Turn off the power supply before cleaning the instrument. Do not use a volatile solvent such as paint thinner to clean the instrument.
Deformation or discoloration will occur. Use a soft, dry cloth to remove stains from the instrument.
To avoid damage to instrument display, do not rub with an abrasive
material or push front panel with a hard object.
The resin adhered to this instrument should be cleaned to dry cloth
with a clean while the resin is still hardened, be careful of burns.
Tools such as wire wheels or abrasive cloths should never be used to
clean the process diaphragm.
Do not apply impact to nor drop this product. If so, its damage or fault
may result.
As precise parts are incorpora ted, do not give any shock and handle
carefully during transportation and installation. Take great care not to scratch the diaphragm.
Do not wipe or rub the nameplate on the outer case of the resin
pressure sensor with a cloth moistened with an organic solvent, or a glove. If so, the printed section may be erased.
This product uses stainless steel, aluminum, and fluororesin (O-rings
and leadwire covering materials). When disposing of each part used for this product, always follows the procedure for disposing of industrial wastes stipulated by the respective local community.
If the output from the resin press ure sensor is found to be abnormal
during the operation, immedia tely stop the operation and inspect for any distortion or damage of the diaphragm. If the diaphragm is damaged, the pressure of the measured me dia (e.g. resin) is applied to the inside of the resin pressure sensor. Continued use under such conditions may result in the damage of the screw which fixes the folder in the housing, and the folder in the housing may come off in the worst case.
Do not use the pressure sensor in stead of a blind bol t.

NOTICE

Thi s manual assume s that the reade r has a funda mental knowled ge of
the principles of electricity, process control, computer technology and communications.
The figures, diagrams and numeric values used in this manual are only
for purpose of illustration.
RKC is not responsible for any damage or injur y that is caused as a
result of using this instrument, instrument failure or in d ire ct damage.
RKC is not responsible for any damage and/or injury resulting from the
use of instruments made by imitating this instrument.
Periodic mainte nance is required for safe and proper operation of th is
instrument. Some components have a limited service life, or characteristics that change over time.
Every effort has been made to ensure accuracy of all information
contained herein. RKC makes no warranty expressed or implied, with respect to the accuracy of the information. The information in this manual is subject to change without prior notice.
No portion of this document may be reprinted, modified, copied,
transmitted, digitized, stored, processed or retrieved through any mechanical, electronic, optical or other means without prior written approval from RKC.
Page 2

1. OUTLINE

A

1.1 Principle of Operation

When pressure is applied to a diaphragm in the resin pressure sensor (CZ-100P), force acts upon a pressure sensing element through a metal rod located near the diaphragm. The pressure sensing element used in CZ-100P has 4 gauges adhered to a metallic elastic body and connected to Wheatstone bridge. Each strain gauge made of metal resistance foil with small temperature coefficient slightly changes its gauge resistance due to strain occurring by the application of force to the elastic body. In this case, as shown in the attached diagram (Fig. 1), the elastic body is in such construction that by the application of force stretching strain occurs in R1 and R3, while shrinking strain in R2 and R4 to increase the gauge resistances of R1 and R3 and to decrease those of R2 and R4. These resistance changes are detected as bridge voltage change to generate the output proportional to the force applied. The output thus generated is input to the PCT-300 output converter which can finally output the DC voltages of 0 to 10 V, 0 to 10 mV, 1 to 5 V and 4 to 20 mA from its output terminals via a 3-stage amplifier circuit.

1.2 Features

The detection of strain caused by the deformation of an elastic
metal body within its elasticity limit using the highly reliable strain gauge enables highly accurate pressure measurement.
The dual construction of connecting pipe and pressure sensing
element portions extremely lessens output indication change caused by external transient temperature change.
Calibration normally performed to a strain gauge sensor becomes
easy and accurate without monitoring the output due to the employment of the PCT-300 output converter.
4-core shielded cable
Fig. 2 Block diagram of resin pressure system
Output converter
PCT-300
CZ-100P
Pressure sensor
R4
R1 R2
pplied voltage
0 to 10 V 0 to 10 mV 1 to 5 V 4 to 20 mA
Fig. 1
R3
Signal (output) voltage
Indicator
Recorder
Pressure controller
N: Standard K: CERAMIC Kanigin plate (Optional)
(4) Intrinsically safe
N: Standard (For non-explosionproof specification type) G: Explosionproof specification type (For indoor use) H: Explosionproof specification type (For outdoor use)
Accessories
Instruction Manual [IM100CZ04-E4] Copper Gasket
(Included in only the Loose nut type [thickness: t = 2 mm])
If any of the products are missing, damaged, or if your manual is incomplete, please contact RKC sales office or the agent.
Blind bolt (Sold separately)
This is a bolt to be used to fill the hole on the machine from which a pressure sensor has been removed. If a blind bolt is necessary, please contact with our sales staff or the nearest distributor.
Output converter
PCT-300
(1) Intrinsically safe
N: Standard type (Non-explosionproof construction) E: Intrinsically safe explosionproof construction pass type
(2) Number of outputs
2: For two output points (0 to 10 V DC, 0 to 10 mV DC) 3: For three output points (0 to 10 V DC, 0 to 10 mV DC, 1 to 5 V DC) 4: For four output points (0 to 10 V DC, 0 to 10 mV DC, 1 to 5 V DC, 4 to 20 mA DC)
(3) Optional function
N: None G: With gain selector switch L: With linearizing function (Linearity error for using this product with the CZ-100P becomes within 0.5 % of span)
Sensor connection cable (Sold separately) W-AB-N*-PA-5000: Standard (For nonintrinsic safety)
[Cable length: 5 m] W-AB-Y*-PB-5000: Intrinsically safety (Hazardous side) [Cable length: 5 m] W-AB-N*-BA-1000: Non-intrinsic safety (Non-hazardous side) [Cable length: 1 m]
*: Cable cover type (G: Heat-resistant glass coated cable, V: Vinyl coated cable, S: Silicon coated cable)
□-
□ □
(1) (2) (3)

2. PRODUCT CHECK

(3) Diaphragm surface treatment
Before using this product, check each of the following:
Model code Check that all of the items delivered are complete. Check that there are no scratch or breakage in external
appearance.
Resin pressure sensor
CZ-100P-
□-□ □ □
(1) (2) (3) (4)
(1) Specification type
HB: Fixed nut type Standard PF3/8 L 150 HC: Fixed nut type Standard PF3/8 L 180 HZ: Fixed nut type Nonstandard size PF3/8 HL: Loose nut type Standard PF3/4 (20 to 100 MPa) HLZ: Loose nut type Nonstandard size PF3/4 (20 to 100 MPa) LL: Loose nut type Standard PF3/4 (5 to 10 MPa) LLZ: Loose nut type Nonstandard size PF3/4 (5 to 10 MPa) LLA: Loose nut type Standard PF3/4 (0.5 to 1 MPa)
(2) Diaphragm section material
S: SUS630 (Standard) H: HASTELLOY C (Optional)
IM100CZ04-E4
2

3. MOUNTING

3.1 Pressure Sensors (CZ-100P)

3.1.1 Mounting cautions

Mounting environment
Ensure that no cooling pipes directly contact the pressure sensor
or connector, since the pressure reading accuracy may be affected or the connector may be damaged.
Do not locate any heat source near the pressure sensor or directl y
expose it to heat. Otherwise, high-temperature deterioration of the sensor block may occur. If the temperature could rise in the strain gauge block located within the housing, cover possible heat sources with insulation materials.
Do not use the pressure sensor under any of the following
environmental conditions:
- Where the sensor is exposed directly to cold air, warm air or hot air.
- Where temperature variations are large.
- Where the sensor is exposed to direct sunlight.
- Where the sens or is directly splashed with water or rain, or the humidity is high.
Do not bring ma gnetic devices such as magnetic relays, etc. near
the pressure indicator. Also, keep power lines from the resin pressure sensor cable.
Page 3
If the pressure sensor is used for screen changer operation, it may
A
A
suffer an impact during screen changer operation, causing sensor troubles. In such a case, carefully consider the position and direction when installing the sensor.
Mounting pressure sensors When the diaphragm at the end of CZ-100P and its surroundings
completely touch with its mounting hole, large indication error may occur. In this case, temperature may exert a large influence especially upon the zero point. Therefore, much attention should be paid when a mounting hole is drilled.
Do not wind sealing tapes, etc. round this section for preventing oil or resin leakage.
When using a lead pipe cover, pay attention that the lead pipe
Packing surface (Sealing surface) [Flat tightening or tapered tightening surface] (Oil or resin leakage is prevented at this point.)
cover end does not directly touch the barrel. (Refer to the “ Exposed length at the bottom of the sensor outer case”)
Barrel
Lead pipe cover
Prior to mounting the pressure sensor, check the appearance of
the diaphragm. If the diaphragm has a deformed or abnormal end, it needs to be repaired or re-calibrated. As there is a case where the diaphragm is already deformed by the application of overload when used previously, carefully check its condition before the pressure sensor is re-used.
Mount the sensor so that this block does not directly touch the barrel.
Mounting hole When mounting the pressure sensor, check its mounting hole
dimensions. (Do not overtighten its screw.)
If resin or its carbide still remains in the mounting hole, this may
damage the pressure sensor. Therefore, prior to mounting the sensor, always remove any residue from the mounting hole.
Check that the diaphragm surface does not protrude from the
inner wall of the barrel, since this may score the diaphragm surface with the screw, etc. If necessary, adjust the position between the diaphragm surface and the inner wall of the barrel using stainless steel gaskets, etc.
For the loose nut type, resin leakage may occur more easily than
the fixed nut type, as the pressure sealing surface becomes wider. If any resin leaks through the mounting gap of the sensor, use copper gaskets (thickness: (thickness: the diaphragm surface and the inner wall of the barrel. (Copper Gasket: Included in only the Loose nut type)
t  2
mm) by taking into account the position between
t  2
mm) or aluminum gaskets
Mounting direction If the sensor is installed in the upright direction (Fig.1-A), it may be
affected directly by heat flow from heater or heat source (rising current of heated air). In such a case, the temperature of the strain gauge in the sensor may exceed an allowable maximum temperature of 150 C. In order not to exceed this limit temperature, it is necessary to keep the sensor outer cylinder surface at a temperature of less than 134 C (Fig.2). Conduct the following treatments.
1. In order to avoid heat flow, wind a heat insulating material round such a heat source (heater, etc.).
2. Further extend the length of the exposed lead pipe.
In order to keep the specified sensor performance longer, it is
recommended that the sensor outer cylinder surface temperature be keep at less than 134 C.
When the sensor is installed in the upright position, thermal e ffects
on the sensor may not sufficiently lessen even if the length of the exposed lead pipe is further extended. In this case, take measures of 1.
The effect of heat flow lessens as the installing direction of the
sensor changes from the slanting direction (Fig.1-B) to the horizontal direction (Fig.1-C) in this order. In this case, take measures of 1 and 2 if necessary by checking the sensor outer cylinder surface temperature. (To the relevant manufacturer: It is recommended that the sensor be installed in the horizontal or slanting direction in order to lessen the effect of heat on the strain gauge.)
B
C
: Upper mounting B: Oblique mounting C: Side mounting
A section of a extruder (Fig. 1)
The aims of a temperature measurement position
(Fig. 2)
Exposed length at the bottom of the sensor
outer case
Cases where the temperature of the strain gauge in the sensor
become less than 150 C is as follows:
The effect of heat flow is small. The sensor is installed in the upright position. The diaphragm is at a temperature of 400 C. The length of the exposed sensor outer cylinder is more than
70 mm. (Refer to below)
However, as the effect of heat flow from an actual extruder is serious, if there is no enough exposed section below the sensor outer cylinder even at a diaphragm temperature of less than 200 C, the operating temperature of the sensor strain gauge may exceed its limit. Therefore, check the temperature environment where the sensor is installed (by indirectly checking the temperature of the sensor outer cylinder surface), and take necessary measures to lessen the temperature of the sensor strain gauge by using a heat insulating material, if necessary.
A lead pipe cover is mainly for protecting the exposed section below
If the temperature of the sensor outer cylinder surface exceeds 160 C, the outer cylinder surface changes its color from black to dark brown and then brown in this order. If it exceeds 180 C, the color may change to silver.
Mounting environment: Ambient temperatures at room temperatures
25 C
Mounting adapter
Temperature of heater
400 C
the sensor outer cylinder from being exposed to cold wind. Therefo re, do not install the sensor such that i t is embedded in the heat source (such as in the barrel or heater) together with th e lead pipe cover. This may heighten thermal conductivity from the heat source, resulting in a temperature increase in the sensor strain gauge.
CZ-100P
60
70
(Unit: mm)
90

3.1.2 Caution in removing pressure sensors

Alw ays remove the sensor while resin is being melted, since
the diaphragm of the sensor may be damaged if the sensor is removed after the resin has hardened. If the sensor is re-mounted under this condition the repeatability may deteriorate.
When removing the pressure sensor, remove it under the same
temperature as that during installation. Removing the pressure sensor under the different temperature as that during installation cause irregular engagement of the thread.
If resin flows into the gap between the lead pipe and the mounting
hole, it may be impossible to remove the sensor even with the threads completely disengaged. In this case, if the sensor is forcibly removed using a puller, the sensor may be knocked when removed, damaging the diaphragm and reducing the accuracy. Slowly remove the sensor without knocking it.
IM100CZ04-E4
3
Page 4
Remove the resin attach ed to the pressure sensin g part (diaphragm
and its surrounding section) after melting it by applying light heat to the side of the pressure sensing p art using a burner (Do not l et the temperature exceed 400 C). In addition, care should be taken not to scratch the pressure sensing block. If not, diaphragm damage or resin leakage may result.

3.1.3 Cautions during extruder cooling down

If the temperature is decreased while resin remains in the extruder with the pressure sensor installed, the diaphragm may be depressed and deformed by resin contraction, etc. As a result, a measurement error or pressure dead-band may occur. If the extruder is cooled down, completely remove all the resin remaining in the barrel, or remove the sensor. Especially take care for the low pressure sensor, as this effect becomes serious.

3.1.4 Dimensions

Measurement range: 0 to 20 MPa, 0 to 35 MPa, 0 to 50 MPa, 0 to 70 MPa,
Unit: mm
42
17
mm
Unit:
42  17
17
40
HB
0 to 100 MPa
HC
Lead pipe cover (SUS304)
Hexagon flat head bolt 23
80 13 10
Standard Dimensions
HB HC
(Loose nut type)
(Low pressure loose nut type)
LL
C type snap ring
17
Flat head bolt 14
Flat head bolt
20
80 13
Standard Dimensions
L
146
A B
195 250
C Approx. 1.2 kg
C type snap ring Tip pressure
Hexagon flat head bolt 23
17
14
60 13
20
Standard Dimensions
A
21
Set screw
L4
L
103 L
L
L1
L2
150
8
4
180
8
4
Lead pipe cover
Hexagon flat head bolt 27
20
120
133  L
L1
L2
20
6
20
55
110
20
Lead pipe cover
113 L
Z-1024 or Z-1024A type:
L1 6 L2
146 L 20
PF3/8 (JIS B grade)
L2
L3
L3 L4 Weight 30
90
30
120
Measurement range: 0 to 20 MPa, 0 to 35 MPa, 0 to 50 MPa,
Measurement range: 0 to 5 MPa, 0 to 10 MPa
(SUS403)
PF3/4
(JIS B grade)
L3
L
Weight
L3
Approx. 0.9 kg
45 45
Approx. 1.0 kg
45
Measurement range*: 0 to 0.5 MPa, 0 to 1 MPa
(SUS403)
PF3/4
(JIS B grade)
L3
120 20
L
Weight
L3
Approx. 0.9 kg
45
Tip pressure receiving side: Diaphragm (SUS630)
L1
Approx. 650 g Approx. 700 g
6
L2
24
Mounting Hold Dimensions
0.1
0.2
0.2
0
10
14
0
0.2
0 to 70 MPa, 0 to 100 MPa
Tip pressure receiving side: Diaphragm (SUS630)
0
L1
0.2
0.1
0.2
0.2
0.1
L2
18
24
* Z-1024 or Z-1024A type: 0 to 1 MPa
receiving side: Diaphragm (SUS630)
0
0.1
0.2
0.1
0.2
L1
0.2
18
24
0
0.2
Fixing screws of sensor finished to JIS B grade. Finish to allow loose fitting.
L22 L1
L3
20
PF3/8
Install the sensor so that the diaphragm surface does not protrude from this surface.
Fixing screws of sensor finished to JIS B grade. Finish to allow loose fitting.
Mounting Hold Dimensions
30
Install the sensor so that the diaphragm surface does not protrude from this surface.
Fixing screws of sensor finished to JIS B grade. Finish to allow loose fitting.
30
Install the sensor so that the diaphragm surface does not protrude from this surface.
0.1
10.3
L2
L1
50
PF3/4
Mounting Hold Dimensions
L2
L1
50
PF3/4
0.1
15.2
2
0.1
18.3
2
0.1
18.3
0.1
24.5
0.1
24.5
CZ-100P-
Connector receptacle PRC03-23A10-7F
CZ-100P-HL CZ-100P-HL
Connector receptacle PRC03-23A10-7F
CZ-100P-LLA
Unit: mm
Connector receptacle PRC03-23A10-7F

3.1.5 Pressure sensor installation

1. Make sure the mounting hole is correctly machined. If installing the pressure sensor into a previously used hole, make sure the hole is thoroughly cleaned to remove any plastic residue.
Lubricate the threads with a high temperature anti-seize lubricant.
2.
Tighten the hexagon nut part with a torque wrench. When tightening
3.
the pressure sensor, always tighten only the hexagon nut part. Fixed nut type (PF3/8 thread: HB, HC type): 30.0 Nm
[300 kgfcm] Loose nut type (PF3/4 thread: LL, HL, LLA type): 60.0 Nm [600 kgfcm] Fixed nut type (Unified thread: UB, UC type): 30.0 Nm [300 kgfcm]
Tighten the pressure sensor to secure it after the temperature rises.
Do not tighten any block other than the hexagonal nuts, since this may damage the pressure sensor.

3.2. Output Converter (PCT-300)

3.2.1 Mounting cautions

To prevent electric shock or instrument failure, always turn off the power before mounting or removing the instrument.
(1) This instrument is intended to be used under the following
environmental conditions. (IEC61010-1) [OVERVOLTAGE CATEGORY II, POLLUTION DEGREE 2]
(2) Use this instrument within the following environment conditions:
Allowable ambient temperature: 0 to 50 C (32 to 122 F) Allowable ambient humidity: 45 to 85 %RH Installation environment conditions: Indoor use,
Altitude up to 2000 m
(3) Avoid the following when selecting the mounting location:
Rapid changes in ambient temperature, which may cause
condensation.
Corrosive or inflammable gases. Direct vibration or shock to the mainframe. Water, oil, chemicals, vapor or steam splashes. Excessive dust, salt or iron particles. Excessive induction noise, static electricity, magnetic fields or
noise.
Direct air flow from an air conditioner. Exposure to direct sunlight. Excessive heat accumulation.
(4) Mount this instrument in the panel considering the following
conditions:
Provide adequate ventilation space so that heat does not build up. Do not mount this instrument directly above equipment that
generates large amount of heat (heaters, transformers, semi-conductor functional devices, large-wattage resistors.)
If the ambient temperature rises above 50 C, cool this instrument
with a forced air fan, cooler, etc. Cooled air should not blow directly on this instrument.
In order to improve safety and the immunity to withstand noise,
mount this instrument as far away as possible from high voltage equipment, power lines, and rotating machinery.
High voltage equipment: Do not mount within the same panel. Power lines: Separate at least 200 mm. Rotating machinery: Separate as far as possible.
For correct functioning mount this instrument in a horizontal
position.
In case this instrument is connected to a supply by means of a
permanent connection, a switch or circui t-breaker shall be includ ed in the installation. This shall be in close proximit y to the equipment and within easy reach of the operator. It shall be marked as the disconnecting device for the equipment.

3.2.2 Dimensions

(単位: mm)
(Unit: mm)
48
Panel cutout dimensions
96
25 45
0
0.6
WARNING
!
92
0.8
0
12
100
ルカット
30
91
(100)
43
4
IM100CZ04-E4
Page 5

3.2.3 Mounting procedures

A
AFA
A
A
A
A
1. Prepare the panel cutout as specified in 3.2.2 Dimensions.
2. Insert the instrument through
the panel cutout.
3. Insert an upper mounting bracket along the bracket insertion groove from the back, and then engage a projection at the bracket end with a recess at the groove front and also insert metal fitting legs into slots.
Slot
Bracket setscrew
Bracket insertion groove
4. Tighten a bracket setscrew from the rear of the bracket with Phillips screwdriver. Do not overtighten the bracket setscrew.
5. The other mounting bracket should be installed the same way as described in 3. and 4.

4. WIRING

To prevent electric shock or instrument failure, do not turn on the power until all wiring is completed. Make sure that the wiring is correct before applying power to the instrument.

4.1 Wiring Cautions

The CZ-100P (sensor) connect to the PCT-300 (output converter)
using the 4-conductor shielded cable attached.
The rated output of the CZ-100P (mV/V: Described on the
nameplate adhered) is obtained when standard cable length is 5 m. If cable length has been extended, conduct rated output correction referring to 6. CORRECTION (page 6).
If the pressure sensor is used together with the output converter
(PCT-300), always connect a grounding wire to the equipment side. (Ground the grounding terminal.)
Connect a grounding wire to the extruder. For a heat-resistant glass covered cable, the cover is made of
fibers. Therefore, the electrical insulation may deteriorate if the cable is exposed to high humidity or conductive liquid (water, etc.) and cause a pressure indication error. For this reason, avoid underground wiring or wiring within electric conduits passing through humid areas as much as possible.
This instrument with 24 V power supply is not provided with an
overcurrent protection device. For safety install an overcurrent protection device (such as fuse) with adequate breaking capacity close to the instrument.
Fuse type: Time-lag fuse (
and/or UL248-14)
Fuse rating: Rated current 0.8 A For an instrument with 24 V power supply input, supply power
from “SELV” circuit defined as IEC 60950-1.
A suitable power supply should be considered in end-use
equipment. The power supply must be in compliance with a limited-energy circuits (maximum available current of 8 A).
Use the solderless terminal appropriate to the screw size.
Screw size: M3×6 Recommended tightening torque: 0.4 N Specified solderless terminals: With isolation Applicable wire: Solid/twisted wire of 0.25 to 1.65 mm
Make sure that during field wiring parts of conductors can not
come into contact with adjacent conductive parts.

4.2 Wiring Method

Terminal configuration of output converter (PCT-300)
9 10 11
1
Grounding
terminals
OUT1
0 to 10 V DC
OUT2
0 to 10 mV DC
C
L
100 to 240 V
2 3
L
AC 24 V
2 3
DC 24 V
2
Power terminals
WARNING
!
Approved fuse according IEC60127-2
m [4 kgfcm]
12 13 14
SHD
EXC
(A)
(E)
N
N
3
5 6 7 8
4
For two output points For three output points: Use OUT 1 to O UT3 For four output points: Use OUT 1 to O UT4
8.1 mm or less
2
Input terminals Output terminals
15 16
EXC
SENSOR
OUT3 OUT4
1 to 5 V DC 4 to 20 mA DC
:
SIG
(C)
(D)
Output termina ls
Use OUT1 and O UT2
SIG
(B)
Wiring example
Pressure
Output converter
PCT-300
indicator
-+
Power supply
Recorder
100 to 240 V AC
or
24 V AC/DC
Crimp-style terminal lug
Connection cable
Plug
Pressure sensor (CZ-100P)
Do not place magnet relays or any other equipment which causes magnetic disturbance near the output converter. Install the power cable away from the 4-core shielded cable.
When connecting the sensor to a pressure indicator or recorder, check its polarity and output signal
NDI standardized connector (plug, receptacle and jack) is used.
Wiring diagram of connector and cable
Receptacle (PRC03-23A-7F)
Plug (PRC03-12A10-7M)
CZ-100P
350   4
F
Applied voltage
D
D
B
B
E
CG
CG
Standard 4-core shield cable (Insulator color)
E
Crimp-style lug terminal
Blue
Black
Shield
Brown
Red
15
D
B
16 12
E
14
C
13
Wiring example of explosionproof specification
sensor
Instrument conf i gu ration diagram
Hazardous area
C D B
Red
Brown
Blue
Black
Nonhazardous area
C D B
Pressure sensor (CZ-100P)
* PCT-300E, PG500, HA430, HA930
RZB-001A
Safety barrier
E G
Ground
C D B
Red
Brown
Blue
Black
EXC EXC
SIG
SIG
PCT-300
(D)
SIG
SIG(B) SHD (E)
EXC
(C)
(A)
EXC
Terminal No.
*
Instrument
G
Grounding terminal
IM100CZ04-E4
5
Page 6

5. ADJUSTMENT

Gain setter Monitor plug
Zero adjuster
1.
mV/V
Power lamp
Adjustment procedures
1. Check the rated output (mV/V) described on the nameplate of the CZ-100P (This output should be corrected when the cable is extended.) and then set that value on the rotary switch which is gain setter of the PCT-300.
2. The pressure reading zero point is adjusted by the zero adjuster in PCT-300. Perform this zero adjustment after the position installed with CZ-100P on the extruder reaches the desired temperature and is in the steady state after the lapse of a certain time. If an indicator is not available, adjust the zero point on the monitoring terminals using a circuit tester. In addition, perform the above adjustment after warming up for 20 minutes or more with the power switch of PCT-300 turned ON (power lamp lights) after wiring has been finished.
When the gain setter and zero adjuster are set using small
screwdriver.
When the sensor is provided with the gain selection
function (optional), the output value is doubled if the function is set to “2,” which is effective for increasing the reading at low-pressure. The valid range is within the output range of PCT-300, which corresponds to half of full-scale pressure.
Turn the FILTER switch to the OFF side (100 Hz, 3 dB)
when quick response is required. The FILTER switch is turned to the ON side (10 Hz, 3 dB) prior to shipment.
Gain selector switch (Optional)
MONI
FILTER switch
ZERO
PWR
PCT-300
For more details of indication error, refer to 6. CORRECTION in this manual.
3. Then, set the selector switch (on the side of PCT-300, refer to drawing on page 6) to “2.”
Gain setting for CZ-100P-LLA Z-1024A type:
Set the RATED OUTPUT (Rated output: mV/V) value specified on the label of the pressure sensor
at Gain setting in the Setup setting mode for PG500, and at Gain setting in the Function block F21 in the Engineering mode
for HA430 and HA930. To make indication error compensation due to operating temperature, cable length, or safety barrier, set the compensated value.
For more details of indication error, refer to 6. CORRECTION in this manual
Gain setting for CZ-100P-LLA (0.5 MPa range) type:
When a PCT-300 is used, the Gain setting procedure is the same as that for CZ-100P-LLA Z-1024 type.
Refer to “Gain setting of
CZ-100P-LLA Z-1024.” When PG500, HA430 or HA930 is used, enter a half value of the
RATED OUTPUT (Rated output: mV/V) specified on the label of the pressure sensor
at Gain setting
at Gain setting
1
in the Setup setting mode for PG500, or
2
in the Function block F21 in the Engineering mode
for HA430 and HA930. To make indication error compensation due to operating temperature, cable length or safety barrier, set a half of the compensated value.
For more details of indication error, refer to 6. CORRECTION in this manual
1
For Gain setting in Setup setting mode, refer to the PG500 Operation Manual (IMR02F02-E
2
For Gain setting in F21 in the Engineering mode, refer to the HA430/HA930 Quick Operation Manual (IMR01N16-E
).
).

6. CORRECTION

1  
2
ON  OFF
When the following types of resin pressure sensors are used, connectable instruments (output converter, indicator, etc) and gain setting procedure are different.
Sensor types and connectable instruments:
Sensor type Connectable instruments
CZ-100P-LLA Z-1024 PCT-300 CZ-100P-LLA Z-1024A PG500, HA430, HA930 CZ-100P-LLA
(0.5 MPa range)
Refer to page 6 for Gain setting adjustment of each
PCT-300, PG500, HA430, HA930
sensor type.
Gain setting for CZ-100P-LLA Z-1024 type:
1. Make sure your PCT-300 has a selectable gain function (optional) with a gain selector switch.
2. Read off the rated output value (Rated output: mV/V) from the label on the pressure sensor, and set the value with the Gain setter (rotary switch) on the PCT-300. To make indication error compensation due to operating temperature, cable length, or safety barrier, set the compensated value on the PCT-300.

6.1 Correcting Indication Error due to the Operating Temperature

The pressure indication error caused by the difference between the pressure sensor’s calibration temperature and the operating temperature can be adjusted using the instrument’s gain setting. The pressure indicator error [pressure sensor output (sensitivity) temperature affect] is within a “±0.2 % of span/10 ºC,” but the temperature affect can be corrected if necessary.
Correction procedure
1. The rated output after the correction is calculated from the following correction equation and correction factor.
e1 = [1 + Correction factor (T Calibration temp.)]  e0
e0: Rated output of the resin pressure sensor e1: Rated output after the correction T: Operating temperature Correction factor: Refer to below
Correction factor:
SUS630 150 0.1310 SUS630 Kanigen plate 150 0.1310 HASTELLOY C 150 HASTELLOY C Kanigen plate 250
(The correction factor is the actual value and not the warranted value.)
Calibration
Diaphragm material
temperature
C)
(
Correction factor
3 3
Please contact RKC sales office or the agent.
6
IM100CZ04-E4
Page 7
2. Set the value obtained in 1 above in the Gain setting section of the instrument
*.
Example: When the e pressure sensor is used at 230 C.
1.500 SUS630 diaphragm material’s
0
e1 = [1 + 0.13 10-3 (230150)] 1.500 e
= 1.516
1
Set 1.516 to the gain setting portion of the instrument.
* For PCT-300, use the Gain Setter.
For PG500, refer to Gain setting in the Setup setting mode in the PG500 Operation Manual (IMR02F02-E For HA430/HA930, refer to the Gain setting in Function block F21 in the Engineering mode in the HA430/HA930 Quick Operation Manual (IMR01N16-E
).
).
6.2 Correcting Indication Error due to the
Connection Cable Length
RKC Instrument’s resin pressure sensor is calibrated for the standard cable length (5 m). Therefore, if the total length of the pressure sensor connection cable connected to the intrinsically safe circuit and non-intrinsically safe circuit side is other than 5 m, the resin pressure sensor indication value can be corrected using the instrument’s gain setting.
Correction procedure
1. The rated output after the correction is calculated from the following correction equation and correction factor.
e1’ = e0’/[1 + K (L 5)]
e0’: Rated output of the resin pressure sensor e1’: Rated output after the correction K (Correction factor):
1.96
1.40 L: Cable total length (m) [However, when using RKC Instrument’s standard cable.]
-4
10
/m (Standard specification type)
-4
10
/m (Explosionproof specification type)
2. Set the value obtained in 1 above in the Gain setting section of the instrument
Example: Cable total length (L) 10 m Rated output of the resin pressure sensor (e
Set 1.499 to the gain setting portion of the instrument.
* For PCT-300, use the Gain Setter.
For PG500, refer to Gain setting in the Setup setting mode in the PG500 Operation Manual (IMR02F02-E For HA430/HA930, refer to the Gain setting in Function block F21 in the Engineering mode in the HA430/HA930 Quick Operation Manual (IMR01N16-E).
*.
e1’ = 1.500/[1 + 1.96 10-4 (105)] e
’ = 1.499
1
).
’) 1.500
0
6.3 Correcting Indication Error when the
Cable of Another Company is Used
The nominal cross-sectional area of our cable conductor is 0.5 mm2. If using a cable from another company, the resin pressure sensor’s indication value can be corrected by correcting the gain setting of the instrument.
Correction procedure
1. The rated output after the correction is calculated from the following correction equation and correction factor.
e1’ = e0’/[1 + 0.5/S K (L 5)]
e0’: Rated output of the resin pressure sensor e1’: Rated output after the correction S: Conductor nominal cross-sectional area (mm K (Correction factor):
1.96
1.40 L: Cable total length (m)
-4
10
/m (Standard specification type)
-4
10
/m (Explosionproof specification type)
2
)
2. Set the value obtained in 1 above in the Gain setting section of the instrument
*.
Example: Cable total length (L) 10 m Conductor nominal cross-sectional area (S) 0.75 mm Rated output of the resin pressure sensor (e0’) 1.500 mV/V
2
e1’ = 1.500/[1 + 0.5/0.75 1.96 10-4 (105)] e
’ = 1.499
1
Set 1.499 to the gain setting portion of the instrument.
* For PCT-300, use the Gain Setter.
For PG500, refer to Gain setting in the Setup setting mode in the PG500 Operation Manual (IMR02F02-E For HA430/HA930, refer to the Gain setting in Function block F21 in the Engineering mode in the HA430/HA930 Quick Operation Manual (IMR01N16-E
).
).
When anti-explosion specifications are required, use a cable with an allowable capacitance between the cable wires of 0.1F or less and an allowable inductance of
0.6 mH or less. The allowable inductance could be exceeded if the cable is
wound, so do not wind the cable when using it.
6.4 Correcting Indication Error due to the
Safety Barrier
A pressure indication error caused by the dispersion of our RZB-001 internal resistance value is within about 1 % of span. However, when this error needs to be lessened further, make the correction, if necessary. For this correction, the barrier correction factor B is used. No correction is required when the barrier correction factor B is “1.000.”
The barrier correction factor B is described on the nameplate of the RZB-001.
Correction procedure
1. The rated output after the correction is calculated from the following correction equation and correction factor.
e1’’ = B  e0’’
e0’’: Rated output of the resin pressure sensor e1’’: Rated output after the correction B: Barrier correction factor
2. Set the value obtained in 1 above in the Gain setting section of the instrument
*.
Example: Barrier correction factor (B) 1.001 Rated output of the resin pressure sensor (e Rated output after the correction
e
’’
1
e1’’ = 1.001 1.500 e
’’ = 1.502
1
Set 1.502 to the gain setting portion of the instrument.
* For PCT-300, use the Gain Setter.
For PG500, refer to Gain setting in the Setup setting mode in the PG500 Operation Manual (IMR02F02-E For HA430/HA930, refer to the Gain setting in Function block F21 in the Engineering mode in the HA430/HA930 Quick Operation Manual (IMR01N16-E
).
).
’’) 1.500 mV/V
0
IM100CZ04-E4
7
Page 8
7. LINEARIZING FUNCTION
SETTING
To prevent electric shock and instrument failure,
always turn off the power supply before pulling out the internal chassis.
To prevent injury or instrument failure, do not touch the
internal printed circuit board.
Linearizing switch changing
1. First check the output characteristic type (A, N or B) engraved at the end of the figure showing the rated output value on the rating nameplate attached to the outer chamber of the pressure sensor.
Example: Rating nameplate
P RES SUR E SEN SOR
TYPE CZ-100P-HB-SNE
G
PRESSURE RANGE 0 - 20 MPa RATED OUTPUT No. 97J21020 DATE 9710 RKC INSTRUMENT
A, N or B is engraved in this section. For products other than corresponding to the linearizing function, the output characteristic type (A, N or B) is not engraved in this section.
2. Next, check that the power to the PCT-300 output converter is turned off, then remove the internal assembly from the case.
3. Set the linearizing switch on the side of the internal assembly of the PCT-300 to the position matching the output characteristic type of the pressure sensor to be connected.
Internal assembly of PCT-300
Upper
Lower
Gain selector switch
Linearizing switch:
1 2 ON  OFF
Set the switch to the position matching the output characteristic type of the pressure sensor.
The gain selector switch or linearizing switch is optional. The above figure shows all the optional switches to simplify the explanation.
4. House the internal assembly in the case. This completes the setting.
WARNING
!
1.234A
mV/V at 150C
INC. MADE IN JAPAN
FILTER switch
Front

8. TROUBLES AND CAUSE

Problem Possible cause
Indication pointer completely defects to the left or right.
Digital display over-scale or underscale.
No pressure is indicated under pressurized condition.
Pointer or indication fluctuates du ring relay actuation.
Pressure indication is fluctuated.
Normal operation was performed, but no reading was received after a while or the reading varied and was unstable.
Indication fluctuates from the beginning.
Resin leakage.
No threads regularly engaged (no screw removed).
For taking measures, also refer to “3.1 PRESSURE SENSOR (CZ-100P).” The converter is described on a basis of the PCT-300.
For the cause of diaphragm deterioration, deformation or damage, refer to the following “*
No indicator input circuit connected.
No 4-conductor shielded cable connected. The defective connector used (standard or
water resistant connector).
Wires disconnected or shorted. No internal sensor wiring connected. The fiberglass coated cable immersed into
water or exposed to high temperature, resulting in deteriorated insulation resistance.
No rated output set to the PCT-300
(different gain).
The double gain selector switch turned ON. The strain gauge deteriorated due to exposure
to high temperature.
No zero adjuster adjusted.
Irregularly tapped hole for installing the CZ-100P. (The sensor tip strongly contacting with the tapped hole.)
The diaphragm deteriorated, deformed or
damaged.
Mechanical Lead pipe deformation by external
No measures for relay spark killing taken.
No 4-conductor cable shield perfectly wired or
grounded.
The PCT-300 located near magnetically
operated relays. Value different from the sensor rated output set
to the rated output setter for the PCT-300.
The diaphragm deteriorated, deformed or
damaged.
The sensor exposed to hot or cold wind. Some potential against the earth generated
(2-point grounding, etc.). Imperfect connecter contact.
The lead pipe deformed by external force. The diaphragm deteriorated, deformed or
damaged.
The fiberglass coated cable immersed into
water or exposed to high temperature, resulting in deteriorated insulation resistance.
The sensor exposed to hot or cold wind. The extruder now in unstable operation or
temperature rise. The sensor tip forcibly tightened due to the
small tapped hole.
The lead pipe cover contacting with the barrel,
etc. The sealed surface deformed or scratched.
Foreign material (carbide, etc.) attached on the
sealed surface.
Low sealed surface accuracy (parallelism, axis,
etc.).
No screw threaded down to the extreme end. Tightened at less than appropriate torque or not
tightened. No screw threaded down to the extreme end.
Not threaded as conforming to the standard. The screw with burrs used. Tightened with excessive torque. Tightened at temperature different from the
initial tightening temperature.
Foreign material attached on the threaded
section, or stained.
force.
*
*
*
Main causes.”
Continued on the next page.
IM100CZ04-E4
8
Page 9
* Main causes:
These causes may arise independently or in mutual relations.
Generative cause in operation
Overpressure Load pressure exceeding its limit applied. Irregular thread
engagement Metal fatigue
Corrosion
Abrasion
Shrinkage
Separation
Protrusion
Contact
The metal pressure sensing surface mechanically scratched or chipped off.
The metal sensing surface fatigued by the application of changing or repeating pressure.
The pressure sensing surface corroded due to its contact with corroding material.
The pressure sensing surface worn away due to the mixture of fillers, etc.
The pressure sensing surface deformed due to the shrinkage of resin adhered to its surface as a result of extruder cooling down.
The pressure sensing surface deformed or damaged by resin adhered to its surface due to the removal of the sensor while the resin is not yet melted or its melted condition is imperfect.
The pressure sensing surface deformed or damaged due to the protrusion of the push rod from the lead pipe as a result of an external force applied by the screen changer, etc.
The pressure sensing surface deformed due to the forced contact of the sensor outer side with the hole inner surface as a result of the finish of the hole inner surface.
Generative cause in mounting and removing
Impact
Dropping
Handling
Excessive tightening
The pressure sensing surface deformed due to its strong strike with solid material.
The pressure sensing surface or its circumference scratched or deformed due to sensor dropping.
After the resin attached to the sensor tip is heated by a gas burner, etc. for its removal at the time of inspection, the pressure sensing surface scratched with a metal brush, etc.
The diaphragm deformed or damaged as the push rod pushes the diaphragm from the inside as a result of the deformation of the sensor flange by excessive tightening torque.

9. EXPLANATION OF EACH TERMS

Term Explanation
Rated pressure
Rated output
Accuracy
Linearity
Hysteresis
Repeatability
Temperature effect on zero point
Temperature effect on output (sensitivity)
Allowable overpressure
Limit overpressure
* Short period of time: From several seconds to several minutes.
The maximum pressure which satisfies the specification. There are stipulated pressure ranges.
Value obtained by subtracting the output at no-load from that at the rated pressure load. Electrically, it is output voltage per Volt in DC (mV/V) obtained through the bridge circuit when rated pressure is applied. At an application voltage of 10 V from the converter, a voltage of mV 10 is output.
The maximum error including linearity and hysteresis.
The maximum error from a reference line (straight line without error) when pressure-loaded in the pressure rise direction continuously from no-load to the rated pressure.
The maximum difference between pressures at the same point in the rise and fall directions when the same pressure is loaded.
The difference between measured values obtained each time when pressure-loaded three times repeatedly from no-load to the rated pressure within a short period of time*.
Zero-point output variation when the diaphragm temperature changes by 10 C.
Output sensitivity (span) variation when the diaphragm temperature changes by 10 C.
The high limit of overpressure within a short period of time* at which the accuracy can be guaranteed even after the pressure returns to the rated pressure when overpressure-loaded.
The high limit of overpressure within a short period of time* at which no diaphragm is damaged when overpressure-loaded. However, no accuracy is guaranteed after the pressure returns to the rated pressure.
IM100CZ04-E4
9
Page 10

10. SPECIFICATIONS

10.1 Resin Pressure Sensor (CZ-100P)

Specification
Sensing block construction:
4-side adhesion-type strain gauge, wheatstone bridge
Rated pressure:
Fixed nut type: 20 MPa, 35 MPa, 50 MPa, 70 MPa, 100 MPa Loose nut type (LL type): 5 MPa, 10 MPa Loose nut type (HL type): 20 MPa, 35 MPa, 50 MPa, 70 MPa, 100 MPa Loose nut type (LLA type): 0.5 MPa *, 1 MPa
*
Available in combination use with PCT-300, PG500, HA430, or HA930.
Loose nut type (LLA Z-1024 type): 1 MPa *
*
Available in combination use with PCT-300.
Loose nut type (LLA Z-1024A type): 1 MPa *
*
Available in combination use with PG500, HA430, or HA930.
Rated output [Calibration temperature: At diaphragm temperature of 150 C]:
1.2 to 1.8 mV/V LLA type (0 to 1 MPa): 1.0 to 1.6 mV/V
LLA type (0 to 0.5 MPa): 0.5 to 0.8 mV/V *
*
Value 1.0 to 1.6 mV/V is specified on the sensor label.
LLA Z-1024 type: 0.5 to 0.8 mV/V *
*
Value 1.0 to 1.6 mV/V is specified on the sensor label.
LLA Z-1024A type: 0.5 to 0.8 mV/V *
*
Value 0.5 to 0.8 mV/V is specified on the sensor label.
The output of each sensor becomes a specific value within the range of 1.2 to 1.8 mV/V.
Bridge impressed voltage:
10 V DC (When using PCT-300)
7.7 V DC (When using PG500) 8 V DC (When using HA430 or HA930)
Accuracy [At diaphragm temperature of 150 C]:
SUS630 diaphragm specification type:
1.0 % of span (For type exceeding 70 MPa: 2.0 % of span)
HASTELLOY C diaphragm specification type:
1.0 % of span (For type exceeding 50 MPa: 2.0 % of span)
Linearity [At diaphragm temperature of 150 C]:
SUS630 diaphragm specification type:
1.0 % of span (For type exceeding 70 MPa: 2.0 % of span)
HASTELLOY C diaphragm specification type:
1.0 % of span (For type exceeding 50 MPa: 2.0 % of span)
Hysteresis [At diaphragm temperature of 150 C]:
SUS630 diaphragm specification type: 1.0 % of span
For type exceeding 70 MPa: 2.0 % of span LLA type: 0.2 % of span LLA Z-1024 type: 1.0 % of span LLA Z-1024A type: 1.0 % of span
HASTELLOY C diaphragm specification type: 1.0 % of span
(For type exceeding 50 MPa: 2.0 % of span)
Repeatability [At diaphragm temperature of 150 C]:
SUS630 diaphragm specification type: 0.2 % of span HASTELLOY C diaphragm specification type: 0.4 % of span
Zero balance: 0.6 mV/V (40 % of span) Bridge resistance:
Input side*: 37410 , Output side: 3505 
*
As the input side of bridge resistance, the 3505  type is also available.
This type is interchangeable with the 37410  type.
Temperature characteristics
Maximum diaphragm temperature: 400 C Maximum strain gauge temperature: 150 C
When the temperature at the bottom of outer tube (nut side) is more than 134 C, the temperature at the strain gauge exceed 150 C. *
*
If the temperature at the strain gauge exceed 150 C, the performance
cannot be assured. Therefore, cover the heat source with a heat insulating material so that the above temperature does not exceed 150 C. The temperature at the strain gauge can be expected not to rise when:
the long type of sensor is used or the sensor is installed aslant or transversely.
If any of the above measures can be taken, take it.
Zero shift due to temperature change [As to diaphragm temperature]:
SUS630 diaphragm specification type: 0.2 % of span/10 C HASTELLOY C diaphragm specification type: 0.3 % of span/10 C
LLA type 0.5 MPa: 0.4 % of span /10 C LLA Z-1024 type, LLA Z-1024A type: 0.3 % of span /10 C
Output (sensitivity) shift due to temperature change:
Same as Zero shift due to temperature change
Mechanical characteristics
Allowable over pressure: 120 % of span
LLA type 0.5 MPa: 1000 % of span LLA type 1 MPa: 500 % of span LLA Z-1024 type, LLA Z-1024A type: 500 % of span
Limited over pressure: 150 % of span
LLA type 0.5 MPa: 2000 % of span LLA type 1 MPa: 1000 % of span LLA Z-1024 type, LLA Z-1024A type: 1000 % of span
Diaphragm material: SUS630 (Standard) HASTELLOY C (Optional)
Diaphragm surface treatment:
Non surface treatment (Standard) CERAMIC Kanigen plate (Optional)
Fixing screw section material: SUS403 Lead pipe cover material: SUS304 (Fixed nut type only) Recommended tightening torque:
30 Nm (300 kgfcm) [Fixed nut type, PF3/8] 60 Nm (600 kgfcm) [Loose nut type, PF3/4]

10.2 Output Converter (PCT-300)

Input
Input sensor: Strain gauge type sensor
[Resin pressure sensor (CZ-100P: RKC product)]
Input range:
Standard specification: 0 to 19.9 mV Explosion-proof construction specification: 0 to 11.6 mV
*
Excluding bias portion that allows zero adjustment
Input impedance: 1 M or more
Action at input break:
Upscale (The sensor power supply break is the same)
Sensor power supply
Applied voltage:
Standard specification: 10 V DC (Normal current 28 mA) Explosion-proof construction specification:
8.2 V DC (Normal current 16 mA)
Accuracy: Within 0.1 %, Within 0.4 % Temperature drift: 30 ppm/C or less
* *
10
IM100CZ04-E4
Page 11
Zero point
Adjustment range:
Standard specification: 7 mV (Input conversion) Explosion-proof construction specification: 6 mV (Input conversion)
Temperature drift: Within 0.02 % of span/C
Gain
Adjustment range:
Standard specification: Input range “10.00 to 19.99 mV” can be used as rating (10 V etc.). Explosion-proof construction specification: Input range “5.80 to 11.60 mV” can be used as rating (10 V etc.).
Setting accuracy:
Within 0.2 % of span/C
Temperature drift:
100 ppm/C or less
Optional functions:
Gain selector switch provided (Selection 1  2)
Output
Output type:
0 to 10 V DC (Load resistance: 2 k or more) 0 to 10 mV DC (Load resistance: 10 k or more) 1 to 5 V DC (Load resistance: 1 k or more) 4 to 20 mA DC (Load resistance: 600 or less)
Monitor voltage:
0 to 10 V DC (Pin size of tester conforming:
2.0)
General specifications
Linearity: Within 0.01 % of span Noise: Within 0.1 % p-p of span (0.1 to 10 Hz) Response: 10 Hz/100 Hz transfer type (Factory shipment: 10 Hz) Power supply: 90 to 264 V AC (Including power supply voltage
variation), 50/60 Hz Rating: 100 to 240 V AC
21.6 to 26.4 V AC (Including power supply voltage variation), 50/60 Hz Rating: 24 V AC
21.6 to 26.4 V DC (Including power supply voltage variation) Rating: 24 V DC
Power consumption:
12.5 VA max. (at 240 V AC)
7.5 VA max. (at 100 V AC) 8 VA max. (at 24 V AC) 190 mA max. (at 24 V DC)
Insulation resistance:
Between input/output terminal and grounding: 20 M or more at 500 V DC Between power terminal and grounding: 20 M or more at 500 V DC
Withstand voltage:
Between input/output terminal and grounding: 1 minute at 1000 V AC Between power terminal and grounding: 1 minute at 1500 V AC
Weight: Approx. 290 g
Operating environment
Allowable ambient temperature:
0 to 50 C
Allowable ambient humidity:
45 to 85 %RH (Non condensing)
Ambient operating atmosphere:
There should be neither corrosive gases nor much dust.
IM100CZ04-E4
11
Page 12
The first edition: APR. 1995 The fourth edition: OCT. 2013 [IMQ00]
HEADQUARTERS: 16-6, KUGAHARA 5-CHOME, OHTA-KU TOKYO 146-8515 JAPAN
RKC INSTRUMENT INC.
®
Website: http://www.rkcinst.com/
IM100CZ04-E4 OCT. 2013
PHONE: 03-3751-9799 (+81 3 3751 9799) E-mail: info@rkcinst.co.jp FAX: 03-3751-8585 (+81 3 3751 8585)
Loading...