RKC INSTRUMENT COM-ML-1 Quick Instruction Manual

8 (
A
6

Ethernet Communication Converter
COM-ML-1
IMR02E14-E1
Thank you for purchasing this RKC product. In or der to achieve maximum p erformance and ensure proper operation of the instrument, carefully read all the instructions in this manual. Please place the manual in a convenient location for easy reference. This manual describes the basi c operation method of th e COM-ML-1. For the in stallation, the communication data, the detail ed handling procedures and various function settings, please refer to the following separate manuals.
COM-ML-1 [For SRZ] Installation Manual (IMR02E13-E): Enclosed with COM-ML COM-ML-1 [For SRZ] Host Communication Data List (IMR02E15-E): Enclosed with COM-ML COM-ML-1 [For SRZ] PLC Communication Data List (IMR02E16-E): Enclosed with COM-ML COM-ML-1 [For SRZ] Instruction Manual (IMR02E17-E): Separate
(Download or sold separately)
These manuals can be d ownlo aded f rom t he of ficia l RKC webs ite: http://www.rkcinst.com/english/manual_load.htm
[For SRZ]
All Rights Reserved, Copyright 2018, RKC INSTRUMENT INC.
Quick Instruction
Manual
1. HANDLING PROCEDURES
Host communication settings
Refer to 2. HOST COMMUNICATION SETTINGS
Installation and wiring
Function module settings
IP address settings
Refer to COM-ML-1 [For SRZ] Installation Manual
(IMR02E13-E).
For information on the SRZ, refer to Z-TIO Instruction
Manual (IMS01T01-E), Z-DIO Instruction Manual (IMS01T03-E) or Z-CT Instruction Manual (IMS01T1
-E).
Refer to 3. COMMUNICATION SETTING OF FUNCTION
MODULES
Refer to Z-TIO
Manual (IMS01T02-E), Z-DIO Instruction Manual (IMS01T03-E) or Z-CT Instruction Manual (IMS01T16-E).
Host Communication Quick Instruction
Refer to 4. IP ADDRESS SETTINGS.
PLC communication environment settings
Refer to 5. PLC COMMUNICA TION ENVIR ONMENT SETTINGS [Only PLC communication]
Other communication
data settings
Refer to 6. OTHER COMMUNI CATION DA TA SETTIN GS.
2. HOST COMMUNICATION SETTINGS
To prevent electric shock or instrument failure , always tur n off th e power
before setting the switch.
To prevent electric shock or instrument failure, never t ouch any section
other than those instructed in this manual.
2.1 Address Settings
Set the address for host comm unication. Use a small flat-blade screwdri ver to configure the setting.
Set the address such that it is di fferent to the ot her addresses on the same li ne. Otherwise, problems or malfunction may result.
Host communication address switch
Setting range: 0 to F [0 to 15: Decimal number] Factory set value:
0
2.2 DIP Switch Settings
Use the DIP switch to set the speed and protocol of host communication, default IP address setting, and DIP switch enable/disable.
Left side view
DIP switch
ON
ON OFF
8 7 6 5 4 3 2
1
1 2 Host communication speed
OFF OFF
ON OFF
OFF ON
ON ON
4800 bps
9600 bps 19200 bps 38400 bps
Factory set value:
19200 bps
3 Communication protocol/Data bit configuration
RKC communication
OFF
(Data 8-bit, Without parity, Stop 1-bit) Modbus
ON
(Data 8-bit, Without parity, Stop 1-bit)
* Fac tory set value wh en the Host comm unication prot ocol is not specifi ed
at the time of ordering.
Factory set value:
RKC communication *
4 5
OFF OFF Fixed
6 7 Default IP address setting
OFF OFF
ON OFF Do not set this one
OFF ON Do not set this one
ON ON
* Refer to 4.2 Default IP Address Setting.
Do not execute the default IP address setting
Execute the default IP address setting *
Factory set value:
Do not execute the default IP address setting
8 DIP switch enable/disable
OFF Enable (enable the DIP switch settings)
Disable (enable the host communication or loader communication
ON
settings)*
* The only host communic ation or loader communication s ettings that are
enabled are the host commu nication spe ed and protoc ol and the dat a bit configuration.
When the communication p rotocol is set with the DIP s witch, the data bit configurati on is automatically set to “Data 8-b it, Without parity, Stop 1-bit.” To c hange to another data bit configuration, set the configuration in host communication or loader communication.
If you wish to set the data bi t con figur ation , ho st co mmun icati on spe ed, and c ommu nicatio n
Factory set value:
Enabled
protocol in host communication or loader communication, first set DIP switch No. 8 to ON.
3. COMMUNICATION SETTING OF FUNCTION
MODULES
3.1 Address Setting of Function Modules
Only make the module addr ess setting to make the function module (Z-TIO, Z-DIO and Z-CT) communication setting s. The SRZ unit performs internal communication (RS-48 5) between the COM-ML- 1 (hereafter called COM-ML) and the function module (Z-TIO, Z-DIO and Z-CT), so the communication protocol, communication speed and data bit conf igurati on do not nee d to be set . A module address is set for each function module type. In this example, the module address is set to the address shown below.
To avoid problems or malfunction, do not duplicate an address in a function module of the same type on the same communication line.
0 1 0 0
Z-TIO
module 1
Z-TIO
module 2
Z-DIO
module 1
Setting of the address setti ng switch (module address)
Z-TIO module Z-DIO module
Z-CT module
ddress setting switch
Setting range: 0 to F [0 to 15: Decimal number]
Z-CT
module 1
Factory set value: 0
3.2 For the SRZ Unit’s Temperature Control Channel
Setting the Z-TIO module address determines the temperature control channel number used for communication. To each Z-TIO module address, the relevant temperature control channel is assigned. Each temperatur e control channel number ca n be calcu lated fro m the foll owing eq uation.
Temperature control channel number of communication [Module address setting + [Cha nnel numb er in a modu le]
Example: When three Z-TIO modules (4-channel type) are joined
0 1 2
a
] [Maximum channel number of the function module b]
a
When the setting is A to F, it is a decimal number.
b
For the Z-TIO module, it is calcula ted by “4. ”
Module address setting
Z-TIO module 3:
The temperature control channel number used for communication of channel 2 2 4 + 2 = 10
4. IP ADDRESS SETTINGS
To use the COM-ML on Ethernet [MODBUS/TCP or PLC communication (MAPMAN) ], IP address setting is necessary. The IP address can be set in host communication or loader communication.
4.1 Host Communication Settings
When setting via host c ommunicat ion, refer to the f ollowing R KC commun ication id entifiers and Modbus register addresses to set the I P address. The set IP address is enabled by turning OFF the power and then turning it ON again.
Name
RKC
identifier
First-byte of IP address QB 801B 32795 0 to 255 192 Second-byte of IP address QC 801C 32796 0 to 255 168 Third-byte of IP address QD 801D 32797 0 to 255 1
Modbus
register address
HEX DEC
Data range
Factory
set value
Fourth-byte of IP address QE 801E 32798 0 to 255 1
Z-TIO module 1
CH3
CH4
CH1
CH2
Z-TIO module 2
CH7
CH8
CH5
CH6
Z-TIO module 3
CH11
CH12
CH9
CH10
3.3 Digital Input/Output Channel of Z-DIO Module
Setting the Z-DIO module add ress determines t he digital input/o utput channel num ber of SRZ unit. To each Z-DIO module ad dress, the relevant digit al input/output channel is assigned. Each digit al input/output channel can be calculated from the following equation.
Digital input (or output) channel nu mber [Module address setting + [Input (or output) channel number in a module]
Example: When two Z-DIO modules are joined
a
] [Maximum channel number of the function module b]
a
When the setting is A to F, it is a decimal number.
b
For the Z-DIO module, it is calculated by “8.”
01
Module address setting
For the IP address, check with the administrator of the network (LAN) to which the COM-ML is connected.
Our Communication tool “PROTEM 2 ” can be used for the communication setup. This tool can be downloaded f rom the off icial RK C website :
http://www.rkcinst.com/
For information on connecting the COM-ML to a host computer, refer to COM-ML-1 [For
SRZ] Installation Manual ( IMR02E13 -E).
4.2 Loader Communication Settings
To perform Loader communication, our converter and a communication cable are required. US B communi cation c onverte r COM-K2 ( With USB cab le)
To use the Loader communicati on, USB driver for COM-K2 must be installed on the personal computer. The USB drive r for COM- K2 can be down loade d from the of ficia l RKC website: http://www.rkcinst.com/
Loader communication c able W-BV- 01 [Op tions for COM-K2 ] Communication tool PROTEM 2
This tool can be downloaded from the official RKC website: http://www.rkcinst.com/
(Factory set value for COM-M L IP addre ss: 192. 168.1.1 )
Connection method
Digital output channel number of digital output
(DO) channel 1 of Z-DIO module 2 1 8 + 1 = 9
Z-DIO module 1
DI4 (CH4) DI3 (CH3) DI2 (CH2) DI1 (CH1)
DI8 (CH8) DI7 (CH7) DI6 (CH6) DI5 (CH5)
DO1 (CH1) DO2 (CH2) DO3 (CH3) DO4 (CH4)
DO5 (CH5) DO6 (CH6) DO7 (CH7) DO8 (CH8)
DI4 (CH12) DI3 (CH11) DI2 (CH10) DI1 (CH9)
DI8 (CH16) DI7 (CH15) DI6 (CH14) DI5 (CH13)
Z-DIO module 2
DO1 (CH9) DO2 (CH10) DO3 (CH11) DO4 (CH12)
DO5 (CH13) DO6 (CH14) DO7 (CH15)
CH16)
DO
3.4 CT Input Channel of Z-CT Module
Setting the Z-CT module addr ess determines the current t ransformer (CT ) input channe l number of SRZ unit. To each Z-CT module address, the relevant current transformer (CT) input channel is assigned. Each curren t tra nsfor mer ( CT) i nput channe l can be c alcul ated f rom t he fo llow ing e quati on.
Current transformer (CT) input cha nnel nu mber [Module address setting + [Channel number in a module]
Example: When two Z-CT modules are joined
CT9 (CH9) CT8 (CH8) CT7 (CH7)
CT12 (CH12) CT11 (CH11) CT10 (CH10)
a
] [Maximum channel number of the function module b]
a
When the setting is A to F, it is a decimal number.
b
For the Z-CT module, it is calculated by “12.”
01
Z-CT module 1
Module address setting
CT1 (CH1) CT2 (CH2) CT3 (CH3)
CT4 (CH4) CT5 (CH5) CT6 (CH6)
Channel number of current transformer
(CT) input channel 1 of Z-CT module 2 1 12 + 1 = 13
CT9 (CH21) CT8 (CH20) CT7 (CH19)
CT12 (CH24) CT11 (CH23) CT10 (CH22)
Z-CT module 2
CT1 (CH13) CT2 (CH14) CT3 (CH15)
CT4 (CH16) CT5 (CH17) CT6 (CH18)
Connect the COM-ML, the CO M-K 2, an d th e pe rs ona l com pu te r with a U SB ca bl e a nd a lo ad er communication cable.
Connect to loader communication connector of the COM-ML
Loader communication
cable (W-BV-01)
[Options for COM-K2]
During the loader communication, the COM-ML requires an external power source. The COM-ML will not function on the USB power from a personal computer alone.
USB communication
COM-K2 (RKC product)
Connect to loader communication connector
converter
The termination resistor is built into the COM-K2
USB cable
(COM-K2 accessory)
Connect to USB connector of the COM-K2
Connect to USB port of a personal computer
Personal computer
Setting of loader communication
The device address, the communication speed and the data bit configuration are fixed as follows for the loader communicati on.
Device address: 0 Communication speed: 38400 bps Data bit configuration: Data 8-bit, Without parity, Stop 1-bit
Setting of PROTEM 2
1. Turn on the power of the COM-ML (SRZ unit).
2. Start PPROTEM 2
If you use the PROTEM 2 for the first time, you have to create a new project and set a communication port.
3. Click “Base Tool: Select model”
Click
Continued on the next page
X
A
A
4. Select the “COM-ML” and “Loader Communication,” and click “OK”
5. Set “Address” setting “ 0” and “Comm. Port” settin g “38400 bps, Data 8-bit, Without parity,
Stop 1-bit.” (The COM port nu mber depe nds on the co nnected personal computer .)
6. Click the menu bar in order of “Operation,” “Online,” and “Online(All).”
7. Click the menu bar in order of “Setting” and “User level” to activate the “Engineer level.”
The Engineer level is enabled.
8. Select “COM-ML ENG(1)” under the “Engineering settings.”
9. Set IP address.
IP address
Factory set value: 192.168.1.1
10. The set IP address is enabled by turning OFF the power and then turning it ON again.
4.3 Default IP Address Setting
The IP address can be set to the factory set value using the DIP switches.
1. Turn off the power of COM-ML.
2. Turn on No. 6 and No. 7 of DIP switch.
Left side view
3. Turn on the power of COM-ML.
DIP switch
ON
ON OFF
8 7 6 5 4 3 2
Turn on
1
4. The FAIL/RUN lamp will flash green for about 5 seconds and then light solidly. At this point, the IP address changes to the factory set value “192.168.1.1.”
FAIL/RUN
LOADER
RX/T
COM-ML
green lamp flashes
green lamp is on
5. Turn off the power of the COM-ML once again and return DIP switches No. 6 and No. 7 to OFF.
If DIP switches No. 6 and No. 7 are left ON , the set I P address will revert t o the facto ry set value every time the power is t urned on.
6. Turn the power of the COM-ML back on. This completes the procedure.
5. PLC COMMUNICATION ENVIRONMENT
SETTINGS
The PLC communication environmental (system data) settings must be made to perform PLC communication. The Syste m data settings are made by th e Loader communication (Syst em data settings can also be made in the Host communication). The System data contains setting items (ref er to th e Setting item table of below) and monitor items. The monitor items require sp ace (cor respondi ng to 8 word s) in the PL C registe r.
For the monitor items, re fer to CO M-ML-1 [For SRZ] PLC Commu nica tion Data List
(IMR02E16-E).
5.1 Setting of System Data (setting items)
Set the items in the same way as “4.2 Loader Commun ication Set tings” (same procedures up to Step 8 of “Setting of PROTEM 2.” (Refer to the Setting item table for details)
Setting item table R/W: Read/Write
Name
PC number (CPU number)
System data register type 1
System data register start
1, 2
number (High-order 4 bit) System data
register start
1
number (Low-order 16 bit) System data
address bias
1
Usable register ranges and type s vary depending on used CPU types. Fo r register ranges and types that can actually be used, see the PLC instruction manual.
2
Only enabled when the ZR register is selected.
3
Used in the factory setting when the SRZ unit is connected to the PLC by 1 to 1 (1:1) connection.
1, 3
This item is not used
System Data (setting items)
RKC
Iden-
tifier
Modbus
Register address
HEX DEC
QW 8009 32777 7 R/W This item is not used
QZ 800A 32778 7 R/W MIRSUBISHI MELSEC series
QS 800B 32779 7 R/W 0 to 15 0
QX 800C 32780 7 R/W
QQ 800D 32781 7 R/W
Digits
Attri­bute
Data range
Setting will be ignored, even if it is set.
0: D register (Data register) 1: R register (File register) 2: W register (Link register) 3: ZR register (Method of specifying consecutive numbers when 32767 of R register is exceeded.)
4 to 29: Unused
0 to 65535 1000
0 to 65535 0
Factory
set value
1
0
6. OTHER COMMUNICATION DATA SETTINGS
Set each communication data (PID constants and event set values of the Z-TIO modules and DO manual outputs of the Z-DIO modules, etc.) using loader communication or host communication.
Host communication or loader com munication is used to con figure the IP address setting, and thus it is possible to con ti nu e c onf ig uri ng other communication data settin gs af ter t he I P address setting.
For each of the communication setting items, COM-ML-1 [For SRZ] Host Communication
Data List (IMR02E15 -E) or COM-ML-1 [For SRZ] Instruction Manual (IMR02E017-E).
Host communication settings by loader communication
Communication protocol, c ommunication speed and data bit configuration can be set by loader communication.
Set switch No.8 to “ON” when perfo rming communication by the communication settings set via Host communication or Loader communication. When set to “ON,” the DIP switch settings are disabled.
Set the items in the same way as “4.2 Loader Commun ication Set tings” (same procedures up to Step 7 of “Setting of PROTEM 2.” Select “COM-ML ENG(2)” under the “Engineering settings.”
R/W: Read/Write
Name
Host communication Protocol
Host communication Communication speed
Host communication Data bit configuration
Host communication Interval time
Data bit configuration table
Set value Data bit Parity bit Stop bit Modbus RKC communication
0 8 Without 1 1 8 Even 1 2 8 Odd 1 3 7 Without 1 4 7 Even 1 5 7 Odd 1
RKC
iden-
tifier
Modbus
register address
HEX DEC
VP 8004 32772 1 R/W 0: RKC communication
VU 8005 32773 1 R/W 0: 4800 bps
VW 8006 32774 7 R/W
VX 8007 32775 7 R/W
Digits
Attri­bute
Data range
1: Modbus
1: 9600 bps 2: 19200 bps 3: 38400 bps
Modbus: 0 to 2 RKC communication: 0 to 5
Refer to Data bit configuration table
0 to 250 ms
Can be set
Cannot be set
set value
Can be set
Factory
0
2
0
10
Ethernet is a registered trademark of Xerox Corp. Modbus is a registered trademark of Schneider Electric. The name of each programmable controller (PLC) means the products of each manufacturer. Company names and product names used in this manual are the trademarks or registered trademarks of the respective companies.