DeviceNet is a registered trademark of Open DeviceNet Vendor Association, Inc.
Modbus is a registered trademark of Schneider Electric.
The name of each programmable controller (PLC) means the products of each manufacturer.
Company names and product names used in this manual are the trademarks or registered trademarks of
the respective companies.
This product has been self-tested by RKC at DeviceNet Protocol Conformance Test Software Version
Thank you for purchasing this RKC product. In order to achieve maximum performance and ensure
proper operation of your new instrument, carefully read all the instructions in this manual. Please
place the manual in a convenient location for easy reference.
SYMBOLS
WARNING
CAUTION
!
An external protection device must be installed if failure of this instrument
could result in damage to the instrument, equipment or injury to personnel.
: This mark indicates precautions that must be taken if there is danger of electric
shock, fire, etc., which could result in loss of life or injury.
: This mark indicates that if these precautions and operating procedures are no
taken, damage to the instrument may result.
: This mark indicates that all precautions should be taken for safe usage.
: This mark indicates important information on installation, handling and operating
procedures.
: This mark indicates supplemental information on installation, handling and
operating procedures.
: This mark indicates where additional information may be located.
WARNING
!
All wiring must be completed before power is turned on to prevent electric
shock, fire or damage to instrument and equipment.
This instrument must be used in accordance with the specifications to
prevent fire or damage to instrument and equipment.
This instrument is not intended for use in locations subject to flammable or
explosive gases.
Do not touch high-voltage connections such as power supply terminals, etc.
to avoid electric shock.
RKC is not responsible if this instrument is repaired, modified or
disassembled by other than factory-approved personnel. Malfunction can
occur and warranty is void under these conditions.
IMR01Y36-E2
i-1
Page 4
CAUTION
This product is intended for use with industrial machines, test and measuring equipment.
(It is not designed for use with medical equipment and nuclear energy.)
This is a Class A instrument. In a domestic environment, this instrument may cause radio
interference, in which case the user may be required to take additional measures.
This instrument is protected from electric shock by reinforced insulation. Provide reinforced
insulation between the wire for the input signal and the wires for instrument power supply,
source of power and loads.
Be sure to provide an appropriate surge control circuit respectively for the following:
- If input/output or signal lines within the building are longer than 30 meters.
- If input/output or signal lines leave the building, regardless the length.
This instrument is designed for installation in an enclosed instrumentation panel. All
high-voltage connections such as power supply terminals must be enclosed in the
instrumentation panel to avoid electric shock by operating personnel.
All precautions described in this manual should be taken to avoid damage to the instrument or
equipment.
All wiring must be in accordance with local codes and regulations.
All wiring must be completed before power is turned on to prevent electric shock, instrument
failure, or incorrect action.
The power must be turned off before repairing work for input break and output failure including
replacement of sensor, contactor or SSR, and all wiring must be completed before power is
turned on again.
To prevent instrument damage or failure, protect the power line and the input/output lines from
high currents with a protection device such as fuse, circuit breaker, etc.
Prevent metal fragments or lead wire scraps from falling inside instrument case to avoid
electric shock, fire or malfunction.
Tighten each terminal screw to the specified torque found in the manual to avoid electric shock,
fire or malfunction.
For proper operation of this instrument, provide adequate ventilation for heat dispensation.
Do not connect wires to unused terminals as this will interfere with proper operation of the
instrument.
Turn off the power supply before cleaning the instrument.
Do not use a volatile solvent such as paint thinner to clean the instrument. Deformation or
discoloration will occur. Use a soft, dry cloth to remove stains from the instrument.
To avoid damage to instrument display, do not rub with an abrasive material or push front
panel with a hard object.
Do not connect modular connectors to telephone line.
When high alarm with hold action/re-hold action is used for Event function, alarm does not turn
on while hold action is in operation. Take measures to prevent overheating which may occur if
the control device fails.
NOTICE
This manual assumes that the reader has a fundamental knowledge of the principles of electricity,
process control, computer technology and communications.
The figures, diagrams and numeric values used in this manual are only for purpose of illustration.
RKC is not responsible for any damage or injury that is caused as a result of using this instrument,
instrument failure or indirect damage.
RKC is not responsible for any damage and/or injury resulting from the use of instruments made by
imitating this instrument.
Periodic maintenance is required for safe and proper operation of this instrument. Some components
have a limited service life, or characteristics that change over time.
Every effort has been made to ensure accuracy of all information contained herein. RKC makes no
warranty expressed or implied, with respect to the accuracy of the information. The information in this
manual is subject to change without prior notice.
No portion of this document may be reprinted, modified, copied, transmitted, digitized, stored,
processed or retrieved through any mechanical, electronic, optical or other means without prior written
approval from RKC.
DeviceNet communication converter COM-JH [For SRZ] (hereafter called COM-JH) is communication
converter to connect the RKC module type controller SRZ (hereafter called controller) to a
programmable controller (hereafter called PLC) for DeviceNet.
This chapter describes features, package contents, model code, system configuration, etc.
• A combined total of up to 31 Z-TIO and Z-DIO modules can be connected to one COM-JH.
• On DeviceNet, a PLC is a master device, and the COM-JH is a slave device.
• There are two DeviceNet connector types: open-style connector and micro-style connector.
Programmable controller (PLC)
[Master]
DeviceNet
Controller (SRZ)
(Z-TIO or Z-DIO module)
[Up to 31 modules]
12331
DeviceNet
communication
converter
COM-JH
[Slave]
Power supply (24 V DC)
Controller communication
(RS-485: Modbus)
For DeviceNet, refer to the website of ODVA (Open DeviceNet Vendor Association).
URL: http://www.odva.org
IMR01Y36-E2 1
Page 8
1. OUTLINE
1.1 Checking the Product
Before using this product, check each of the following:
Model code
Check that there are no scratches or breakage in external appearance (case, front panel, terminal, etc).
Check that all of the items delivered are complete. (Refer to below)
COM-JH [For SRZ] Installation Manual
(IMR01Y24-E)
COM-JH [For SRZ] Quick Operation Manual
(IMR01Y28-E)
COM-JH [For SRZ] Communication Data List
(IMR01Y32-E)
COM-JH [For SRZ] Instruction Manual (IMR01Y36-E2)
Accessories Q’TY Remarks
1 Enclosed with instrument
1 Enclosed with instrument
1 Enclosed with instrument
This manual
1
(Download free or purchase hard copy)
EDS file * 1 Download free
If any of the products are missing, damaged, or if your manual is incomplete, please contact
RKC sales office or the agent.
* EDS file
The EDS file for COM-JH can be downloaded from the official RKC website:
(URL: http://www.rkcinst.com/english/download/field_network.htm)
Use the EDS file when recognizing the COM-JH on the DeviceNet by using a configurator (tool used
to set a master or slave environment on the DeviceNet) of each manufacturer.
For how to use EDS file, refer to Configuration Tool Instruction Manual of each company or
Instruction Manual of the master product.
1.2 Model Code
Check that the product received is correctly specified by referring to the following model code list:
If the product is not identical to the specifications, please contact RKC sales office or the agent.
• Communication environment setting mode by the switch:
Flashes
RUN [Green]
• When normally: Turns on
• Self-diagnostic error: Flashes slowly
• Data collection just after the power is turned on: Flashes rapidly
NS or NET (Network status)
[Green/Red]
• Network is operating normally, but communications have not yet
been established: A green lamp flashes
• Network is operating normally (communications established):
A green lamp turns on
• I/O connection is timeout: A red lamp flashes
• A fatal communications error has occurred,
Network communications are not possible: A red lamp turns on
MS or MOD (Module status)
[Green/Red]
• When DeviceNet communication is normal: A green lamp turns on
• Controller communication error: A green lamp flashes
• Memory backup error: A red lamp turns on
DeviceNet connector
COM. PORT
[Open-style or
Micro-style
Connector for PLC (Master) connection
connector]
Switches
Node address setting switch
DeviceNet communication
speed setting switch
DIP switch
• Set the node address for DeviceNet
• Used for the PLC communication environment setting
• Set the communication speed for DeviceNet
• Used for the PLC communication environment setting
• Set the communication speed for controller communication
• Set the number of communication data items when conducting
DeviceNet Polling I/O communication
Others
Terminal cover Terminal covers above and below the COM-JH
Mounting bracket
• Used for the DIN rail mounting
• When panel mounted, two mounting brackets are required for the
upper and lower sides (one required for the upper side: separately
sold).
Terminal base Part of the terminal and base of COM-JH
(There is the Termination resistor transfer switch in the inside of
terminal base)
Mainframe Part of the mainframe of COM-JH
4
IMR01Y36-E2
Page 11
2. HANDLING PROCEDURES
Conduct necessary setting before communication according to the procedure described below.
communication setting
COM-JH
Communication
environment setting
Mounting
Set the node address, DeviceNet communication speed, controller
communication speed and number of communication data items when
conducting DeviceNet Polling I/O communication of COM-JH.
Refer to 5. SETTING (P. 20).
Set the Communication environment of DeviceNet Polling I/O communication.
Refer to 5.4 Communication Environment Setting by Rotary Switch (P. 23),
Number of communication data items setting by DIP switch (P. 32),
Communication parameter setting by configuration tool (P. 33) or
Communication parameter setting by Explicit message communication
(P. 43)
Mount the COM-JH, Controller and PLC.
• Refer to 3. MOUNTING (P. 7).
• For controller (SRZ) mounting, refer to Z-TIO Instruction Manual
(IMS01T01-E).
• For PLC mounting, refer to Instruction Manual for the used PLC.
Wiring and Connection
Connect power supply wires to the COM-JH, and also connect the COM-JH
to the controller and the COM-JH to the PLC, respectively.
• Refer to 4. WIRING (P. 11).
• For controller (SRZ) wiring, refer to Z-TIO Instruction Manual
(IMS01T01-E).
Power ON
To avoid error at operation start-up, COM-JH must be powered
on LAST (after the controller, PLC, etc.).
When turn on the power supply of DeviceNet communication, slave including
COM-JH, and master (PLC etc.), the COM-JH performs as follows.
1. The COM-JH starts collecting data on each controller connected from the
time when the power is turned on.
2. The RUN lamp flashed at very short intervals.
3. After data collection is finished and DeviceNet communication becomes
enabled *, the RUN lamp keeps lighting.
*
Time required for enabling DeviceNet communication is about 30 seconds.
A
IMR01Y36-E2 5
Page 12
2. HANDLING PROCEDURES
A
PLC setting
Controller setting
Installation of
the EDS file
DeviceNet
communication setting
Data download
Programming
Set communication parameters of PLC.
Refer to 8.3 Setting of Use Instruments (P. 85) and Instruction
Manual for the used PLC.
Set communication parameters of controller.
• Refer to 8.3 Setting of Use Instruments (P. 85)
• Refer to Z-TIO Host Communication Quick Instruction Manual
(IMS01T02-E).
Install the EDS file of COM-JH in a configuration tool of DeviceNet.
The EDS file for COM-JH can be downloaded from the official RKC website.
Refer to the Instruction Manual of Configuration Tool.
Set COM-JH communication parameters relating to Polling I/O
communication by using the DeviceNet configuration tool.
Refer to 6.2.1 Polling I/O communication (P. 27) and the Instruction
Manual of Configuration Tool.
Download each device parameter created by the DeviceNet configuration tool
to device on the actual network.
Refer to the Instruction Manual of Configuration Tool.
Create the sequence program.
Refer to 8.4 Sample Programs (P. 86).
6
IMR01Y36-E2
Page 13
3. MOUNTING
This chapter describes installation environment, mounting cautions, dimensions and mounting
procedures.
To prevent electric shock or instrument failure, always turn off the power before
mounting or removing the instrument.
WARNING
!
3.1 Mounting Cautions
(1) This instrument is intended to be used under the following environmental conditions. (IEC61010-1)
[OVERVOLTAGE CATEGORY II, POLLUTION DEGREE 2]
(2) Use this instrument within the following environment conditions:
• Allowable ambient temperature: −10 to +50 °C (14 to 122 °F)
• Allowable ambient humidity: 5 to 95 % RH
(Absolute humidity: MAX.W.C 29.3 g/m
• Installation environment conditions: Indoor use
Altitude up to 2000 m
(3) Avoid the following conditions when selecting the mounting location:
• Rapid changes in ambient temperature which may cause condensation.
• Corrosive or inflammable gases.
• Direct vibration or shock to the mainframe.
• Water, oil, chemicals, vapor or steam splashes.
• Excessive dust, salt or iron particles.
• Excessive induction noise, static electricity, magnetic fields or noise.
• Direct air flow from an air conditioner.
• Exposure to direct sunlight.
• Excessive heat accumulation.
3
dry air at 101.3 kPa)
(4) Mount this instrument in the panel considering the following conditions:
• Ensure at least 50 mm space on top and bottom of the instrument for maintenance and
environmental reasons.
• Do not mount this instrument directly above equipment that generates large amount of heat
(heaters, transformers, semi-conductor functional devices, large-wattage resistors).
• If the ambient temperature rises above 50 °C (122 °F), cool this instrument with a forced air fan,
cooler, etc. Cooled air should not blow directly on this instrument.
• In order to improve safety and the immunity to withstand noise, mount this instrument as far
away as possible from high voltage equipment, power lines, and rotating machinery.
High voltage equipment: Do not mount within the same panel.
Power lines: Separate at least 200 mm.
Rotating machinery: Separate as far as possible.
(5) If this instrument is permanently connected to equipment, it is important to include a switch or
circuit-breaker into the installation. This should be in close proximity to the equipment and within
easy reach of the operator. It should be marked as the disconnecting device for the equipment.
IMR01Y36-E2 7
Page 14
3. MOUNTING
3.2 Dimensions
(Unit: mm)
109.5
2
3
30
125
5
Depth in connector mounting
Conduct installation in consideration of the sizes of the connector and cable when connector-connected.
[Usage example of micro-style connector]
78
109.5
Approx. 100 *
(Unit: mm)
* For open-style connector: Approx. 50 mm
8
IMR01Y36-E2
Page 15
3. MOUNTING
t
3.3 DIN Rail Mounting
Mounting procedures
1. Pull down the mounting bracket at the bottom of the instrument (A). Attach the hooks on the top
of the instrument to the DIN rail and push the lower section into place on the DIN rail (B).
2. Slide the mounting bracket up to secure the instrument to the DIN rail (C).
DIN rail
Mounting
bracke
(A) Pull down
Removal procedures
(B)
Push
(C) Locked
1. Turn the power OFF.
2. Remove the wiring.
3. Pull down a mounting bracket with a
slotted screwdriver (A). Lift the
instrument from bottom, and take it
off (B).
(B) Lift and
take off
(A) Pull down
IMR01Y36-E2
9
Page 16
3. MOUNTING
)
3.4 Panel Mounting
1. Pull down the mounting bracket (A) until locked and that a mounting hole appears.
2. Prepare one mounting bracket per instrument (B) sold separately (KSRX-55) and then insert it in
the rear of the terminal board at top of the instrument until locked but a mounting hole does not
disappear.
3. Mount each module directly on the panel with screws which are inserted in the mounting holes of
the top and bottom mounting brackets.
Recommended tightening torque: 0.3 N⋅m (3 kgf⋅cm)
The customer needs to provide the M3 size screws. Select the screw length that matches the
mounting panel.
(B) Insert
Mounting dimensions
(Unit: mm
Mounting
holes
Mounting bracket
(Sold separately)
[KSRX-55]
(A) Pull down
M3
130.5 ± 0.2
10
IMR01Y36-E2
Page 17
4. WIRING
This chapter describes wiring cautions, wiring layout and wiring of terminals.
4.1 Wiring Cautions
To prevent electric shock or instrument failure, do not turn on the power until all
wiring is completed. Make sure that the wiring is correct before applying power
to the instrument.
• To avoid noise induction, keep input signal wire away from instrument power line, load lines and
power lines of other electric equipment.
• If there is electrical noise in the vicinity of the instrument that could affect operation, use a noise
filter.
WARNING
!
− Shorten the distance between the twisted power supply wire pitches to achieve the most effective
noise reduction.
− Always install the noise filter on a grounded panel. Minimize the wiring distance between the
noise filter output and the instrument power supply terminals to achieve the most effective noise
reduction.
− Do not connect fuses or switches to the noise filter output wiring as this will reduce the
effectiveness of the noise filter.
• Power supply wiring must be twisted and have a low voltage drop.
• For an instrument with 24 V power supply, supply power from a SELV circuit.
• A suitable power supply should be considered in end-use equipment. The power supply must be in
compliance with a limited-energy circuits (maximum available current of 8 A).
• Use the solderless terminal appropriate to the screw size (M3).
• Make sure that the any wiring such as solderless terminal is not in contact with the adjoining terminals.
5.9 mm or less
3.2 mm or more
Recommended tightening torque:
0.4 N⋅m (4 kgf⋅cm)
IMR01Y36-E2 11
Page 18
4. WIRING
4.2 Terminal Configuration
The terminal configuration is as follows.
Upper-side
terminal
3
7 654
21
Controller
communication
RS-485
T/R(A)
1
T/R(B)
5
SG
4
: The part of internal wiring
Power supply
9
12
DC
+
24 V
11 1098
−
14 1312
Lower-side
terminal
Ground
8
FG
As controller communication terminal Nos. 1, 4 and 5 are internally connected to terminal
Nos. 3, 6 and 7, any terminals can be used.
As ground and power supply terminal Nos. 8, 9 and 12 are internally connected to terminal
Nos. 10, 11 and 14, any terminals can be used.
Terminal No. 2 and No. 13 is not used.
12
IMR01Y36-E2
Page 19
4.3 Connection to DeviceNet
To prevent electric shock or instrument failure, turn off the power before
connecting or disconnecting the instrument and peripheral equipment.
4.3.1 Connection outline of DeviceNet
The following diagram shows the configuration of a DeviceNet network.
WARNING
!
4. WIRING
Communication
power
Terminating
resistor
Trunk
line
Node
Trunk
line
Power
supply tap
Trunk
line
T-branch
tap
Node
Node
Drop line
Drop line
Trunk
line
T-branch
tap
Trunk
line
Terminating
Drop line
Node
• Nodes:
There are two kinds of nodes of master and slave in DeviceNet. The master and slaves can be
connected at any location in the network.
resistor
• Trunk/Drop lines:
The trunk line refers to the cable that has termination resistors on both ends. Cables branching from
the trunk line are known as drop lines.
Use the DeviceNet communication cable (thick or thin cable) for Trunk/Drop lines.
• Connection methods:
Two methods can be used to connect DeviceNet nodes: The T-branch method and the multi-drop
method. With the T-branch method, the node is connected to a drop line created with a T-branch Tap.
With the multi-drop method, the node is directly connected to the trunk line or the drop line.
IMR01Y36-E2
13
Page 20
4. WIRING
• Termination resistors:
Install termination resistors to both ends of a trunk line in DeviceNet.
Specification of termination resistor: 121 Ω, ±1 %, 1/4 W (Metal film resistance)
• Communications power supplies:
To use DeviceNet, connect a communications power supply (24 V DC) to the communications
connector of each node with a cable.
• Communication length:
Communication
speed
125 kbps 500 m 156 m or less
250 kbps 250 m 100 m 6 m 78 m or less
500 kbps 100 m 39 m or less
For details of DeviceNet Network installation conditions and methods, refer to the
instruction manual of the DeviceNet master unit or DeviceNet Specifications.
DeviceNet specifications are available at ODVA (Open DeviceNet Vendor Association).
URL: http://www.odva.org
Maximum network length *
Thick trunk length Thin trunk length
Maximum
drop length
* Maximum distance between nodes
Cumulative
drop length
14
IMR01Y36-E2
Page 21
4.3.2 Pin layout of connector
Open-style connector
4. WIRING
DeviceNet connector
Open-style connector
(COM. PORT)
1: V−
2: CAN_L
3: Drain
4: CAN_H
5: V+
Pin No. and signal details
Pin No. Signal name SymbolCable color
1
Power supply, minus (−) V−
2 Communication data, low CAN_L Blue
3 Shield Drain
4 Communication data, high CAN_H White
5
Power supply, plus (+) V+
Connection plugs (Recommended model)
MSTB2.5/5-STF-5.08AUM (PHOENIX CONTACT, Inc.)
Multi-drop type (recommended model)
TMSTBP2.5/5-STF-5.08AUM (PHOENIX CONTACT, Inc.)
Black
⎯
Red
IMR01Y36-E2
15
Page 22
4. WIRING
+
−
Micro-style connector
DeviceNet connector
Micro-style connector
(COM. PORT)
3: V
2: V
5: CAN_L
1: Drain
4: CAN_H
Pin No. and signal details
Pin No. Signal name SymbolCable color
1 Shield Drain
2
3
Power supply, plus (+) V−
Power supply, minus (−) V+
⎯
Red
Black
4 Communication data, high CAN_H White
5 Communication data, low CAN_L Blue
Connection socket (Recommended model)
SACC-M12FS-5CON-PG 9-M (PHOENIX CONTACT, Inc.)
(This socket is a type to use thin cable.)
Cable
Use the communication cable (thick cable or thin cable) that matched specification of DeviceNet.
By thickness of a cable to use and connection method, usable connection connector type is
different.
For cable specifications, connection method and vendor, refer to the website of ODVA
(Open DeviceNet Vendor Association).
URL: http://www.odva.org
16
IMR01Y36-E2
Page 23
4. WIRING
4.4 Wiring to the Controllers
Conduct wiring between the COM-JH and controller (SRZ) as shown in the following.
SRZ (Z-TIO/Z-DIO module) communication terminal number and signal details
Terminal No. Signal name Symbol
3 Send/receive data T/R (A)
4 Send/receive data T/R (B)
5 Signal ground SG
Wiring
Communication
terminal number
2 1
3 4 5
R1: Internal termination resistor (120 Ω 1/2 W)
R2: Termination resistor for external connection
COM-JH
(−)
(+)
(Example: 120 Ω 1/2 W)
T/R (A)
T/R (B)
R1
SG
Terminal block
Shielded twisted
pair wire
1
5
4
RS-485
Connected by
the internal
communication
line
Controller (SRZ)
Paired
wire
R2
Up to 16 Z-TIO modules can be connected.
Z-TIO module
3
T/R (A)
4
T/R (B)
5
SG
Z-TIO module
3
T/R (A)
4
T/R (B)
5
SG
(−)
(+)
(−)
(+)
IMR01Y36-E2
The maximum number of SRZ modules (including other
function modules) on the same communication line is 31.
If communication errors occur frequently due to the operation environment or the
communication distance, connect termination resistors.
The customer provides the cable and termination resistor for external connection.
The termination resistor existing within the COM-JH can be connected or disconnected by
the switch. (Factory set value: Termination resistor connected)
[Refer to 4.5 Termination Resistor (P. 18)]
17
Page 24
4. WIRING
4.5 Termination Resistor
Procedure for setting a termination resistor to Controller communication (RS-485) and its setting
position are described in the following.
If communication errors occur frequently due to the operation environment or the
communication distance, connect termination resistors.
Termination resistor setting position
It the COM-JH is connected to the extreme end of the communication line, install one termination
resistor each to the COM-JH and the controller located most distantly from the COM-JH.
Termination
resistor ON
(Factory
set value)
COM-JH
Controller communication
(RS-485: Modbus)
Setting procedure of termination resistor (COM-JH)
Controller (SRZ)
Z-TIO or Z-DIO module
Internal communication line
(RS-485)
Termination resistor
Connect a termination
resistor to the terminals
from exterior.
Refer to 4.4 Wiring
to the Controllers
(P. 17)
As the COM-JH is internally provided with a selector switch for choosing the ON/OFF of a
termination resistor, it is not required to externally install the termination resistor.
(Factory set value: Termination resistor connected)
1. Turn off the power supply of the module.
Do not separate the mainframe from the terminal base with the power turned on. If
so, instrument failure may result.
2. Pull out the mainframe itself toward you (2) while pushing the locks at its top and bottom (1),
and then separate it from the terminal base.
Upper-side
lock
Top view
Terminal base
Mainframe
(1) Push
(2) Pull out
18
Lower-side
lock
Bottom view
(1) Push
Removing the module mainframe
IMR01Y36-E2
Page 25
3. Turn on the Termination resistor transfer switch in the terminal base.
The COM-JH is shipped from the factory with the selector switch set to “ON: Termination
resistor connected.”
Termination resistor
transfer switch
ON
OFF
4. WIRING
Termination
resistor OFF
Factory set value: ON
Termination
resistor ON
(120 Ω 1/2 W)
A terminal base of the state which removed module mainframe
4. Push the mainframe thus separated in the terminal base until firmly locked.
Terminal base
Mainframe
Push the module
mainframe until firmly
locked
IMR01Y36-E2
Mounting the module mainframe
19
Page 26
5. SETTING
To prevent electric shock or instrument failure, always turn off the power
before setting the switch.
To prevent electric shock or instrument failure, never touch any section other
than those instructed in this manual.
CAUTION
Do not separate the module mainframe from the terminal base with the power turned on.
If so, instrument failure may result.
WARNING
!
5.1 Node Address Setting
To identify each device connected to the network, it is necessary to set a different address to each
device (node). For the DeviceNet, as it is possible to connect up to 64 devices including a master to
the network, node address (MAC ID) from 0 to 63 can be set.
For this setting, use a small slotted screwdriver.
Set the address such that it is different to the other addresses on the same line.
Otherwise, problems or malfunction may result.
Node address setting switch
MSD: High-order digit setting
(set value × 10)
LSD: Low-order digit setting
(set value × 1)
Setting range: 0 to 63
(Factory set value: 63)
The above figure is open-style connector type. The figure of micro-style connector type is
the same as an open-style connector type.
When any number exceeding 64 is set, the node address number becomes “63.”
20IMR01Y36-E2
Page 27
t
5.2 DeviceNet Communication Speed Setting
Set a communication speed for the DeviceNet using a small slotted screwdriver.
5. SETTING
DeviceNe
Setting range: 0: 125 kbps
(Factory set value: 0)
communication
speed setting switch
(DR or RATE)
1: 250 kbps
2: 500 kbps
The above figure is open-style connector type. The figure of micro-style connector type is
the same as an open-style connector type.
When any number between 3 and 9 is set, the communication speed becomes “500 kbps.”
IMR01Y36-E2 21
Page 28
5. SETTING
5.3 DIP Switch Setting
With the DIP switch which there is on the left side of mainframe, set the controller communication
speed and set the number of communication data items when conducting DeviceNet Polling I/O
communication.
DIP switch
ON
ON
ON
12345678
12345678
Left side view
OFF
1 2 Controller communication speed
OFF OFF38400 bps
ON OFF9600 bps
OFF ON 19200 bps
ON ON 38400 bps
Factory set value: 19200 bps
4 5
OFF OFF7 words
ON OFF25 words
OFF ON 45 words
ON ON 100 words
Number of communication data items when
conducting DeviceNet Polling I/O communication
22
Factory set value: 25 words
Switch No. 3, 6, 7 and 8: OFF fixed. (Do not change this one)
The number of communication data items can be calculated from the following equation.
Number of communication data items
1
1
1
)
• • •
2
IMR01Y36-E2
= (Number of words of first communication item for one module
+ Number of words of next communication item for one module
+ Number of words of last communication item for one module
× Number of communication controllers + Fixed communication date items: 5 words
1
In the case of two-channel type (Z-TIO-B modules), the number of words per one module is
the same as four-channel type (Z-TIO-A modules).
2
Measured data items (IN)
Receive counter: 1 word, Alarm state: 2 words, RUN/STOP state: 2 words
Setting data items (OUT)
Setting state selection: 3 words, RUN/STOP transfer: 2 words
Page 29
5. SETTING
The number of communication data items when conducting Polling I/O communication can
also be set via Explicit message communication, or by the configuration tool or rotary switch.
However, when the number of communication words is set via Explicit message
communication, or by the configuration tool or rotary switch, the value set by the DIP switch
may be ignored.
5.4 Communication Environment Setting by Rotary Switch
Set communication environment of Polling I/O communication of DeviceNet by using the Node
address setting switch and the DeviceNet communication speed setting switch which are the rotary
switch of the COM-JH.
The setting details cannot be check afterwards. When checking the details thus set, check
them via Explicit message communication. In addition, as each switch position is moved
during the setting, record the switch setting state before making the setting.
Setting procedure
1. Turn off the power supply.
2. Before communication environment, record the switch positions of Node address setting switch
and DeviceNet communication speed setting switch. (When this module is used for the first
time, no recording is required.)
3. Set all the values of a Node address setting
switch and a DeviceNet communication speed
setting switch to “9.”
Node address setting switch
and
DeviceNet communication speed
setting switch
8
7
9
6
0
5
1
4
2
3
4. Turning on the power sets the module to the
Communication environment setting mode. If
set to the Communication environment setting
mode, the RUN lamp goes off and the FAIL
FAIL lamp
(red) flashing
RUN lamp
turns off
lamp flashes.
5. Select a setting item number with MSD of the Node address setting switch, and set data with
LSD of the Node address setting switch.
Refer to List of communication environment setting items (P. 24).
6. Set the DeviceNet communication speed setting switch in the order of “9,” “0” and “1.”
The RUN lamp turns on and then it turns off after registration of the set data is complete (after a
lapse about 3 seconds).
7. Repeat the steps from 5. to 6. of above, and set other setting items.
However, set the DeviceNet communication speed setting switch in the order of “1,” “0” and
“1” from the second setting.
8. First check that the RUN lamp goes off, and then turn off the power.
9. Return the switch positions of Node address setting switch and DeviceNet communication
speed setting switch to the positions already recorded.
10. Turn on the power again.
The set data validate if the power is turned on again.
The addresses that are set in object
instances 1 to 31 of the controller address
settings * must be set in order from the
lowest instance.
Free setting:
The addresses that are set in object
instances 1 to 31 of the controller address
settings * can be set freely.
* The Attribute ID: 246 of controller object
(0x64: 64Hex).
1 Number of Polling I/O
communication controllers
0: 1 controller
1 to 8: 2 to 30 controllers
(= set value × 4 − 2)
9: 31 controllers
Set the number of controller communicating
by Polling I/O communication.
2 Unused Do not set this one ⎯
3 Unused Do not set this one ⎯
4 Number of communication
measured data items (IN) when
conducting Polling I/O
communication
0 to 8: 0 to 80 words (= set value × 10)
9: 200 words
Set the number of measured data items (IN)
communicating via Polling I/O
Based on the
communication.
5 Number of communication setting
data items (OUT) when
conducting Polling I/O
communication
0 to 8: 0 to 80 words (= set value × 10)
9: 200 words
Set the number of setting data items (OUT)
communicating via Polling I/O
Based on the
communication.
1
The PID/AT transfer by Polling I/O communication is invalidated.
2
The PID/AT transfer by Polling I/O communication is validated.
0 to 5: 0 to 20 ms (= set value × 4)
6: 30 ms
7: 50 ms
8: 70 ms
9: 100 ms
Set the standby time until the COM-JH
starts sending data after receiving data from
the controller.
7 Unused Do not set this one
8 Controller address setting
0: Controller 1 to 31: 1 to 31
1: Controller 1: 1
Controller 2 to 31: 0
2 to 8: Do not set this one
9: Automatic acquisition of controller
address
Set the address of the controller that is
connected to COM-JH to have communication
take place with only that address.
Set “9: Automatic acquisition of controller
address” and turn on the power again to
acquire the connected controller address
automatically.
Factory
set value
0
⎯
0
9 Set value initialization 0 to 8: Unused
9: Communication environment
setting initialization execution
Initialize each communication environment
setting data item which can be set by the
rotary switch.
The number of communication data items can be calculated from the following equation.
Number of communication data items
= (Number of words of first communication item for one module
+ Number of words of next communication item for one module
+ Number of words of last communication item for one module
× Number of communication controllers + Fixed communication date items: 5 words
1
In the case of two-channel type (Z-TIO-B modules), the number of words per one module is
the same as four-channel type (Z-TIO-A modules).
2
Measured data items (IN)
Receive counter: 1 word, Alarm state: 2 words, RUN/STOP state: 2 words
Setting data items (OUT)
Setting state selection: 3 words, RUN/STOP transfer: 2 words
The number of Polling I/O communication controllers, the number of communication
measured data items (IN) and the number of communication setting data items (OUT) can
also be set via Explicit message communication, or by the configuration tool.
1
1
1
)
• • •
⎯
2
IMR01Y36-E2
25
Page 32
6. DeviceNet COMMUNICATION
6.1 Features and Functionality
One DeviceNet Network can have a maximum of 64 Media Access Control Identifiers (MAC ID:
Node address).
Network length changes with communication speed.
Communication
speed
Maximum network length *
Thick trunk length Thin trunk length
Maximum
drop length
Cumulative
drop length
125 kbps 500 m 156 m or less
250 kbps 250 m 100 m 6 m 78 m or less
500 kbps 100 m 39 m or less
* Maximum distance between nodes
Install termination resistors to both ends of a trunk line in DeviceNet.
Specification of termination resistor: 121 Ω, ±1 %, 1/4 W (Metal film resistance)
A DeviceNet node is modeled as a collection of objects.
The object model provides a template for organizing and implementing the Attributes (data),
Services and Behaviors of the components of a DeviceNet product.
This model has represented the construction of address designation to consist of four levels of
Node address (MAC ID), Object class ID, Instance ID and Attribute ID.
An address of this 4 level is used as an identification factor of data in Explicit message
communication.
Address Lowest Highest
Node 0 63
Object class 1 65535
Instance 0 65535
Attribute 1 255
DeviceNet incorporates CAN (Controller Area Network). CAN defines the syntax or form of the
data movement. Data on DeviceNet is transmitted using CAN data frame.
Identifier Control Data (0 to 8 bytes) CRC
Start of Frame
RTR Bit
CAN data frame
ACK
End of Frame
For details on the communication specification of DeviceNet, refer to DeviceNet
specifications. DeviceNet specifications are available from ODVA (Open DeviceNet Vendor
Association).
URL: http://www.odva.org
26IMR01Y36-E2
Page 33
6. DeviceNet COMMUNICATION
6.2 Communication Method
COM-JH has supported Polling I/O communication and Explicit message communication as a
communication method of DeviceNet.
6.2.1 Polling I/O communication
Polling I/O communication is the communication that master and slave always execute transmission
and reception of data. Used always when checking data items such as measured values, etc.
Set the following items before communication start.
• Communication items (setting data items and measured data items)
• Number of communication controllers
• Number of communication data items
• Controller address
• Action mode
• Automatic acquisition of controller address
Polling made once enables the following data items to be read or written via Polling I/O communication.
Request: setting data items (OUT) Response: measured data items (IN)
Setting state selection Receive counter
RUN/STOP transfer Alarm state
Selected set items RUN/STOP state
Selected measured items
Master
(PLC)
DeviceNet
Request
Setting state selection
RUN/STOP transfer
Selected set items
Slave
(COM-JH)
Outline of Polling I/O communication
Response
Receive counter
Alarm state
RUN/STOP state
Selected measured items
For data processed in actual communication, its decimal point is ignored. In addition,
data with a minus sign is expressed as 2’s complement data.
[Example 1]
For a set value of “120.0,” set “1200.”
[Example 2]
For a set value of “−1,” set “65535.”
(10000H − 1 = FFFFH = 65535)
IMR01Y36-E2 27
Page 34
6. DeviceNet COMMUNICATION
Data to send from a master [Request: setting data items (OUT)]
A master transmits data of the following for slave (COM-JH).
Communication data (setting data items) contents
No. Items Data range
1 Setting state selection
(All controller)
Bit data
Bit 0: Data setting disabled/enabled
0: Depending on the setting contents of
communication data No. 2 and No. 3
1: All-controller setting enabled
(include RUN/STOP)
Bit 1 to 15: Unused
[Decimal number: 0 to 1]
2 Setting state selection
(Controller 1 to 16)
Bit data
Bit 0 to 15: Data setting disabled/enabled
(Controller 1 to 16)
0: Setting disabled
1: Setting enabled
[Decimal number: 0 to 65535]
3 Setting state selection
(Controller 17 to 31,
RUN/STOP)
Bit data
Bit 0 to 14: Data setting disabled/enabled
(Controller 17 to 31)
Bit 15: RUN/STOP transfer disabled/enabled
0: Setting disabled
1: Setting enabled
[Decimal number: 0 to 65535]
Factory
set value
0
0
0
4 RUN/STOP transfer
(Controller 1 to 16)
Bit data
Bit 0 to 15: RUN/STOP transfer *
(Controller 1 to 16)
0: RUN 1: STOP
[Decimal number: 0 to 65535]
5 RUN/STOP transfer
(Controller 17 to 31)
Bit data
Bit 0 to 14: RUN/STOP transfer *
(Controller 17 to 31)
0: RUN 1: STOP
Bit 15: Unused
[Decimal number: 0 to 32767]
* It is possible to change the logic of RUN/STOP by Explicit message communication.
Communication data Nos. 1 to 5 (corresponding to 5 words) are fixed communication data items.
Continued on the next page.
28
Same as
RUN/STOP
state of
controller
Same as
RUN/STOP
state of
controller
IMR01Y36-E2
Page 35
Continued from the previous page.
6. DeviceNet COMMUNICATION
No. Items Data range
On
and
after
6
Selected set items
Setting items are set by the
configuration tool or via Explicit
message communication are
Same as the range of setting items selected Same as the
assigned by the number of
controllers similarly set.
[Factory set value:
Set value (SV)]
In order to validate data after communication data No. 6, it is necessary to set the controllers
corresponding to communication data Nos. 2 and 3 to “1: Setting enabled” or to
communication data No. 1 to “1: All-controller setting enabled.”
For the setting method of the number of communication data items, refer to the following.
− 5.3 DIP Switch Setting (P. 22),
− 5.4 Communication Environment Setting by Rotary Switch (P. 23)
− Number of communication data items setting by DIP switch (P. 32)
− Communication parameter setting by configuration tool (P. 33)
− Communication parameter setting by Explicit message communication (P. 43)
Factory
set value
factory set
value of
setting data
items
selected
For the setting method of the number of communication controllers, controller address and
automatic acquisition of controller address, refer to the following.
− 5.4 Communication Environment Setting by Rotary Switch (P. 23)
− Communication parameter setting by configuration tool (P. 33)
− Communication parameter setting by Explicit message communication (P. 43)
For the setting method of the action mode, refer to the following.
− 5.4 Communication Environment Setting by Rotary Switch (P. 23)
− Communication parameter setting by Explicit message communication (P. 43)
For contents of setting data items, refer to 7. COMMUNICATION DATA LIST (P. 47).
IMR01Y36-E2
29
Page 36
6. DeviceNet COMMUNICATION
Data which a master receives [Response: measured data items (IN)]
A master transmits data of the following for slave (COM-JH).
Communication data (measured data items) contents
No. Items Data range
1 Receive counter 1 0 to 65535
Increments each time the COM-JH receives the setting item
(OUT) data.
2 Alarm state
(Controller 1 to 16)
Bit data
Bit 0 to 15: Alarm state
2
(Controller 1 to 16)
0: Alarm OFF 1: Alarm ON
[Decimal number: 0 to 65535]
3 Alarm state
(Controller 17 to 31, Setting
update flag/Flag during polling
I/O communication updating)
Bit data
Bit 0 to 14: Alarm state
2
(Controller 17 to 31)
0: Alarm OFF 1: Alarm ON
Bit 15: OR operation is performed to the Setting update
3
flag
and the Flag during polling I/O
communication updating.
0: Setting update is completed
1: During setting update
[Decimal number: 0 to 65535]
4 RUN/STOP state
(Controller 1 to 16)
Bit data
Bit 0 to 15: RUN/STOP state
0: RUN
4
(Controller 1 to 16)
1: STOP
[Decimal number: 0 to 65535]
5 RUN/STOP state
(Controller 17 to 31)
Bit data
Bit 0 to 14: RUN/STOP state
0: RUN
4
(Controller 17 to 31)
1: STOP
Bit 15: Unused
[Decimal number: 0 to 32767]
1
The counter is reset when the power is turned on or when it exceeds 65535.
2
Set to “1” if any bit in “Controller state 1” of the controller object (0x64) is set to ON.
3
Set to 1 if the item whose setting was changed from among data items on and after measured item
(IN) No.4 is being updated while set to 0 if the same item has been update.
No setting change has been finished as for as this value remains set at 1. In addition, ReadOnly items
can always be read regardless of this value.
4
It is possible to change the logic of RUN/STOP by Explicit message communication.
Communication data Nos. 1 to 5 (corresponding to 5 words) are fixed communication data
items.
Continued on the next page.
30
IMR01Y36-E2
Page 37
6. DeviceNet COMMUNICATION
Continued from the previous page.
No. Items Data range
On
and
after
6
Selected measured items
Same as the range of measured items selected
Measured items set by the
configuration tool or via
Explicit message
communication are assigned by
the number of controllers
similarly set.
[Factory set value:
Measured value (PV)]
For the setting method of the number of communication words, refer to the following.
− 5.3 DIP Switch Setting (P. 22),
− 5.4 Communication Environment Setting by Rotary Switch (P. 23)
− Number of communication data items setting by DIP switch (P. 32)
− Communication parameter setting by configuration tool (P. 33)
− Communication parameter setting by Explicit message communication (P. 43)
For the setting method of the number of communication controllers, controller address and
automatic acquisition of controller address, refer to the following.
− 5.4 Communication Environment Setting by Rotary Switch (P. 23)
− Communication parameter setting by configuration tool (P. 33)
− Communication parameter setting by Explicit message communication (P. 43)
For the setting method of the action mode, refer to the following.
− 5.4 Communication Environment Setting by Rotary Switch (P. 23)
− Communication parameter setting by Explicit message communication (P. 43)
IMR01Y36-E2
For contents of setting data items, refer to 7. COMMUNICATION DATA LIST (P. 47).
31
Page 38
6. DeviceNet COMMUNICATION
Number of communication data items setting by DIP switch
Use the switch Nos. 4 and 5 of the DIP switch which there is on the left side of COM-JH, sets the
number of communication data items when conducting Polling I/O communication.
DIP switch
ON
ON
ON
OFF
Left side view
12345678
12345678
4 5
OFF OFF7 words
ON OFF25 words
OFF ON 45 words
ON ON 100 words
Number of communication data items when
conducting DeviceNet Polling I/O communication
Factory set value: 25 words
Switch No. 3, 6, 7 and 8: OFF fixed. (Do not change this one)
The number of communication data items can be calculated from the following equation.
Number of communication data items
= (Number of words of first communication item for one module
+ Number of words of next communication item for one module
+ Number of words of last communication item for one module
× Number of communication controllers + Fixed communication date items: 5 words
1
In the case of two-channel type (Z-TIO-B modules), the number of the words per one module is
the same as four-channel type (Z-TIO-A modules).
2
Measured data items (IN)
Receive counter: 1 word, Alarm state: 2 words, RUN/STOP state: 2 words
Setting data items (OUT)
Setting state selection: 3 words, RUN/STOP transfer: 2 words
1
1
1
)
• • •
2
The number of communication data items when conducting Polling I/O communication can
also be set via Explicit message communication, or by the configuration tool or rotary switch.
However, when the number of communication data items is set via Explicit message
communication, or by the configuration tool or rotary switch, the value set by the DIP switch
may be ignored.
For switch Nos. 1 and 2, refer to 5.3 DIP Switch Setting (P. 22).
32
IMR01Y36-E2
Page 39
Communication parameter setting by configuration tool
Set the following items with the configuration tool.
• Communication items (setting data items and measured data items)
• Number of communication controllers
• Number of communication data items
• Controller address
• Automatic acquisition of controller address
Time-out may occur if trying to read any COM-JH parameter from the configuration
tool while in Polling I/O communication between the master station and COM-JH.
When reading or setting the parameters by the configuration tool, stop Polling I/O at
the master station.
For operation of the configuration tool, refer to each configuration tool instruction manual.
It is also possible to set communication items, the number of communication controllers, the
number of communication data items, the controller address and the automatic acquisition of
controller address using Explicit message communication.
For details, refer to Communication parameter setting by Explicit message communication (P. 43).
Setting procedure
6. DeviceNet COMMUNICATION
1. Connect a personal computer installed with the configuration tool to the COM-JH via DeviceNet.
2. Install the EDS file of COM-JH on the configuration tool.
3. Open a parameter setting screen of COM-JH after having added COM-JH to network
configuration by using a configuration tool.
< Reference screen 1: Configuration tool made by OMRON >
Set attribute ID of the communication item,
the number of communication controllers,
the number of communication data items,
the controller address and the automatic
acquisition of controller address.
IMR01Y36-E2
Continued on the next page.
33
Page 40
6. DeviceNet COMMUNICATION
Continued from the previous page.
<Reference screen 2: Configuration tool made by Rockwell>
Set attribute ID of the communication item,
the number of communication controllers,
the number of communication data items,
the controller address and the automatic
acquisition of controller address.
4. Sets the attribute ID of communication items, the number of communication controllers, the
number of communication data items, the controller address and the automatic acquisition of
controller address with a parameter setting screen.
“The number of communication controllers” corresponds to number of controllers
communicating via Polling I/O communication.
For the attribute ID of communication items, refer to 7. COMMUNICATION DATA LIST (P. 47).
34
IMR01Y36-E2
Page 41
6. DeviceNet COMMUNICATION
Parameter setting example of Polling I/O communication
An example of how to set each parameter for polling of the following data is shown.
• Measured data items (IN): Alarm state
RUN/STOP state
Fixed assignment
Measured value (PV)
Manipulated output value (MV) monitor [heat-side]
• Setting data items (OUT): Setting state selection
RUN/STOP transfer
Fixed assignment
Set value (SV)
Event 1 set value
• Number of communication controllers: 2 controllers Z-TIO-A module: 1 controller (4-channel type)
Z-TIO-B module: 1 controller (2-channel type)
• Number of communication data items:
21 words (IN), 21 words (OUT)
• Controller address: 1, 2 (Address of controller 1 and controller 2)
• Automatic acquisition of controller address:
0 (Do not execute the automatic acquisition)
Fixed five communication data words are assigned to the measured data items of Alarm state
and RUN/STOP state. In addition, fixed five communication data words are assigned to the
setting data items of Setting state selection and RUN/STOP transfer.
The number of communication data items can be calculated from the following equation.
Number of communication data items
1
1
• • •
1
)
2
= (Number of words of first communication item for one module
+ Number of words of next communication item for one module
+ Number of words of last communication item for one module
× Number of communication controllers + Fixed communication date items: 5 words
1
In the case of two-channel type (Z-TIO-B modules), the number of the words per one module is
the same as four-channel type (Z-TIO-A modules).
2
Measured data items (IN)
Receive counter: 1 word, Alarm state: 2 words, RUN/STOP state: 2 words
Setting data items (OUT)
Setting state selection: 3 words, RUN/STOP transfer: 2 words
When the number of communication data items is set via Explicit message communication, or
by the configuration tool or rotary switch, the value set by the DIP switch may be ignored.
IMR01Y36-E2
35
Page 42
6. DeviceNet COMMUNICATION
Conduct parameter set according to the procedure described below.
1. Set measured data items (IN) with a parameter setting screen of COM-JH.
• Set attribute ID “1” of Measured value (PV) in “IN ch1 (Parameter 1).”
• Set attribute ID “14” of Manipulated output value (MV1) monitor in “IN ch2 (Parameter 2).”
• “0” is set to unused IN ch (Parameter 3 to 32).
Parameter Value
1 IN ch1 1
2 IN ch2 14
3 IN ch3 0
4 IN ch4 0
32 IN ch32 0
Attribute ID of Measured value (PV): 1
Attribute ID of Manipulated output value
(MV1) monitor: 14
Set “0” in unused items
In addition to Alarm state and RUN/STOP state assigned as fixed, up to 32 types of
measured data items can be selected.
Set measured data items in order starting from IN ch1 (Parameter 1). If any of the
following values is set, all items from that item to IN ch32 (Parameter 32) are the same as
those when set at “0.”
• If at “0”
• If set to attribute ID to which no communication data items are assigned
• If at 231 to 236 or 238 to 243 as attribute ID
36
When setting the communication items of a Z-TIO module extended object (0x65: 65Hex)
or Z-DIO module object (0x66: 66Hex), set the attribute ID number with the appropriate
offset value (1000 or 2000) added.
• 0x65: 65Hex: Attribute ID + 1000
• 0x66: 66Hex: Attribute ID + 2000
For attribute ID of the communication items, refer to 7. COMMUNICATION DATA
LIST (P. 47).
Continued on the next page.
IMR01Y36-E2
Page 43
6. DeviceNet COMMUNICATION
Continued from the previous page.
2. Set the setting data item (OUT) on the same COM-JH parameter setting screen.
• Set attribute ID “45” of Set value (SV) in “OUT ch1 (Parameter 33).”
• Set attribute ID “39” of Event 1 set value in “OUT ch2 (Parameter 34).”
• “0” is set to unused OUT ch (Parameter 35 to 64).
Parameter Value
33 OUT ch1 45
34 OUT ch2 39
35 OUT ch3 0
36 OUT ch4 0
64 OUT ch32 0
Attribute ID of Set value (SV): 45
Attribute ID of Event 1 set value: 39
Set “0” in unused items
In addition to Setting state selection and RUN/STOP transfer assigned as fixed, up to 32
types of setting data items can be selected.
Set the setting data items in order starting from OUT ch1 (Parameter 33). If any of the
following values is set, all items from that item to OUT ch32 (Parameter 64) are the same
as those when set at “0.”
• If at “0”
• If set to attribute ID to which readable communication data items are assigned
• If set to attribute ID to which no communication data items are assigned
• If at 231 to 236 or 238 to 243 as attribute ID
• If at 33 as attribute ID (when “Bit 1: PID/AT transfer by polling I/O communication” of
attribute ID “246” (Action mode selection) is “0: Invalidate”)
When setting the communication items of a Z-TIO module extended object (0x65: 65Hex)
or Z-DIO module object (0x66: 66Hex), set the attribute ID number with the appropriate
offset value (1000 or 2000) added.
• 0x65: 65Hex: Attribute ID + 1000
• 0x66: 66Hex: Attribute ID + 2000
For attribute ID of the communication items, refer to 7. COMMUNICATION DATA
LIST (P. 47).
Continued on the next page.
IMR01Y36-E2
37
Page 44
6. DeviceNet COMMUNICATION
Continued from the previous page.
3. Set the number of communication controllers on the same COM-JH parameter setting screen.
Set “2” which is the number of controllers communicating via Polling I/O communication to
Number of I/O Controllers (Parameter 65).
1 IN ch1 1
64 OUT ch32 0
65 Number of I/O Controllers2
66 I/O IN WORDS 0
67 I/O OUT WORDS 0
Parameter Value
Number of communication controllers: 2
4. Set the number of communication data items on the same COM-JH parameter setting screen.
Number of communication data items
= (Number of words of first communication item for one module + Number of words of next communication item for one module
•••
+ Number of words of last communication item for one module)
× Number of communication controllers + Fixed communication date items: 5 words
(4 + 4) × 2 + 5 = 21
• Set “21 words” which is the number of communication measured data items communicating via
Polling I/O communication to I/O IN WORDS (Parameter 66).
• Set “21 words” which is the number of communication setting data items communicating via
Polling I/O communication to I/O OUT WORDS (Parameter 67).
1 IN ch1 1
64 OUT ch32 0
65 Number of I/O Controllers2
66 I/O IN WORDS 21
67 I/O OUT WORDS 21
Parameter Value
Number of communication measured data items:
21 words
Number of communication setting data items:
21 words
Continued on the next page.
38
IMR01Y36-E2
Page 45
6. DeviceNet COMMUNICATION
Continued from the previous page.
5. Set the controller address on the same COM-JH parameter setting screen.
Set address “1” of controller 1 in Address of Controller 1 (Parameter 68).
Set address “2” of controller 2 in Address of Controller 2 (Parameter 69).
Set “0” in non-connected controllers 3 to 31 (Parameters 70 to 98).
68 Address of Controller 1 1
69 Address of Controller 2 2
70 Address of Controller 3 0
71 Address of Controller 4 0
98 Address of Controller 31 0
99 Auto acquisition of address0
Parameter Value
Address of controller 1: 1
Address of controller 2: 2
Set “0” in non-connected controllers *
* Controllers with addresses set to “0” will not
perform communication. If a value other than
“0” (1 to 31) is set in a non-connected controller,
communication will take place, however, all data
will be “0.”
6. Set the automatic acquisition of controller address on the same COM-JH parameter setting screen.
Set “0,” no automatic acquisition of controller address, in "Auto acquisition of address (Parameter
99).”
Parameter Value
68 Address of Controller 1 1
69 Address of Controller 2 2
70 Address of Controller 3 0
71 Address of Controller 4 0
98 Address of Controller 31 0
99 Auto acquisition of address 0
0: Do not execute the automatic acquisition
1: Execute the automatic acquisition *
* Automatically reverts to “0: Do not execute the
automatic acquisition” after automatic acquisition
When automatic acquisition of controller address
is executed, the “number of communication
controllers” and “controller address” parameters
are updated.
IMR01Y36-E2
The controller address automatic acquisition set “1: Execute the automatic acquisition,”
performs the automatic acquisition of the controller address by turning on the power
again.
39
Page 46
6. DeviceNet COMMUNICATION
Example of communication data list
This is a list of communication data items in the previous parameter setting example (P. 35).
(Communication data items IN and OUT corresponding to 21 words, respectively.)
• Measured and setting data items from No. 1 to 5 (corresponding to 5 words) are those assign as fixed.
( section)
• Communication items set on and after No. 6 are assigned by the specified number of
communication controllers.
• Data of unused items become “0.”
No. Measured data items (IN) No.Setting data items (OUT)
Receive counter
1
Alarm state (Controller 1 to 16)
2
Alarm state
3
(Controller 17 to 31, Setting update flag)
RUN/STOP state (Controller 1 to 16)
4
RUN/STOP state (Controller 17 to 31)
5
Measured value (PV) [CH1 of controller 1]
6
Measured value (PV) [CH2 of controller 1]
7
Measured value (PV) [CH3 of controller 1]
8
Measured value (PV) [CH4 of controller 1]
9
Measured value (PV) [CH1 of controller 2]
10
Measured value (PV) [CH2 of controller 2]
11
Measured data is fixed in “0”
12
Measured data is fixed in “0”
13
Manipulated output value (MV) monitor [heat-side]
14
1
1
Setting state selection (All controller)
1
Setting state selection (Controller 1 to 16)
2
Setting state selection
3
(Controller 17 to 31, RUN/STOP)
RUN/STOP transfer (Controller 1 to 16)
4
RUN/STOP transfer (Controller 17 to 31)
5
Set value (SV) [CH1 of controller 1]
6
Set value (SV) [CH2 of controller 1]
7
Set value (SV) [CH3 of controller 1]
8
Set value (SV) [CH4 of controller 1]
9
Set value (SV) [CH1 of controller 2]
10
Set value (SV) [CH2 of controller 2]
11
Setting data are invalidated 2
12
Setting data are invalidated 2
13
Event 1 set value [CH1 of controller 1]
14
[CH1 of controller 1]
Manipulated output value (MV) monitor [heat-side]
15
Event 1 set value [CH2 of controller 1]
15
[CH2 of controller 1]
Manipulated output value (MV) monitor [heat-side]
16
Event 1 set value [CH3 of controller 1]
16
[CH3 of controller 1]
Manipulated output value (MV) monitor [heat-side]
17
Event 1 set value [CH4 of controller 1]
17
[CH4 of controller 1]
Manipulated output value (MV) monitor [heat-side]
18
Event 1 set value [CH1 of controller 2]
18
[CH1 of controller 2]
Manipulated output value (MV) monitor [heat-side]
19
Event 1 set value [CH2 of controller 2]
19
[CH2 of controller 2]
Measured data is fixed in “0”
20
Measured data is fixed in “0”
21
1
Because controller 2 is 2-channel type, as for the measurement data, “0” becomes fixed.
2
Because controller 2 is 2-channel type, the setting data become invalidated.
1
1
Setting data are invalidated 2
20
Setting data are invalidated 2
21
For details of communication items, refer to 7. COMMUNICATION DATA LIST (P. 47).
40
IMR01Y36-E2
Page 47
6. DeviceNet COMMUNICATION
6.2.2 Explicit message communication
Explicit message communication uses an Explicit message defined with DeviceNet, and be
communication to execute transmission and reception of data between nodes when it is necessary.
Explicit message communication is executed like the following, when COM-JH (slave) is connected to
a master instrument with DeviceNet.
In Explicit message communication, not only data relating to the COM-JH but also all of the
attributes (data) described in APPENDIX A. DEVICE PROFILES (P. 103) are subject to
being sent or received.
When read data
If the node address (MAC ID), service code (0EH: Get_Attribute_Single), object class ID, instance ID
and attribute ID are sent from the master, the node address (MAC ID) thus sent and service code (0EH
+ 80H *) as well as the data requested are sent from the slave.
* 80H represents a response message.
[Normal response]
Master
(PLC)
[Error response]
Master
(PLC)
Service code 14H of Error response has shown that it is error response.
DeviceNet
Request
Node address (MAC ID)
Service code (0EH)
Object class ID
Instance ID
Attribute ID
Slave
(COM-JH)
Response
Node address (MAC ID)
Service code (0EH
Request data
+ 80H)
DeviceNet
Request
Node address (MAC ID)
Service code (0EH)
Object class ID
Instance ID
Attribute ID
Slave
(COM-JH)
Response
Node address (MAC ID)
Service code (14H
Error code
+ 80H)
IMR01Y36-E2
For Error code of Error response, refer to DeviceNet specifications.
41
Page 48
6. DeviceNet COMMUNICATION
When write data
If the node address (MAC ID), service code (10H: Set_Attribute_Single), object class ID, instance ID
attribute ID and write data are sent from the master, the node address (MAC ID) thus sent and service
code (10H + 80H *) are sent from the slave.
* 80H represents a response message.
[Normal response]
Master
[Error response]
Master
For data processed in actual communication, its decimal point is ignored. In addition,
data with a minus sign is expressed as 2’s complement data.
[Example 1] For a set value of “120.0,” set “1200.”
[Example 2] For a set value of “−1,” set “65535.”
(10000H − 1 = FFFFH = 65535)
DeviceNet
Request
Node address (MAC ID)
Service code (10H)
Object class ID
Instance ID
Attribute ID
Write data
Response
Node address (MAC ID)
Service code (10H
+ 80H)
DeviceNet
Request
Node address (MAC ID)
Service code (10H)
Object class ID
Instance ID
Attribute ID
Write data
Response
Node address (MAC ID)
Service code (14H
Error code
+ 80H)
Slave
(COM-JH)
Slave
(COM-JH)
42
Service code 14H of Error response has shown that it is error response.
For Error code of Error response, refer to DeviceNet specifications.
For Explicit message communication specification of data relating to COM-JH,
refer to Z-TIO Module Object (0x64: 64Hex) (P. 109), Z-TIO Module Extended
Object (0x65: 65Hex) (P. 116), Z-DIO Module Object (0x66: 66Hex) (P. 117) of
APPENDIX A. DEVICE PROFILES.
IMR01Y36-E2
Page 49
6. DeviceNet COMMUNICATION
Communication parameter setting by Explicit message communication
Communication item setting, Setting the number of communication controllers, Controller address
setting, Action mode selection and Automatic acquisition of controller address necessary when
conducting Plling I/O communication are described by referring to the same settings made via Explicit
message communication.
Communication item setting
Each communication data item when conducting Polling I/O communication is set by object instance
(instance ID) 1 in Controller communication item setting object (0xC7: C7Hex).
Controller communication item setting object (0xC7: C7Hex): Object instance 1
Attribute
ID
1 Measured data item (IN) 11: Measured value (PV)
2 Measured data item (IN) 2
3 Measured data item (IN) 3
4 Measured data item (IN) 4
5 Measured data item (IN) 5
32 Measured data item (IN) 32
33 Setting data item (OUT) 1 45: Set value (SV)
Contents Data range
Select the measured data item and
setting data item from among
Z-TIO module object (0x64: 64
Hex), Z-TIO module extended
object (0x65: 65Hex) *, or Z-DIO
module object (0x66: 66Hex) *,
and set the corresponding attribute
ID.
Attribute ID: 1 to 255
34 Setting data item (OUT) 2
35 Setting data item (OUT) 3
36 Setting data item (OUT) 4
37 Setting data item (OUT) 5
64 Setting data item (OUT) 32
* When setting the communication items of a Z-TIO module extended object (0x65: 65Hex) or
Z-DIO module object (0x66: 66Hex), set the attribute ID number with the appropriate offset
value (1000 or 2000) added.
• 0x65: 65Hex: Attribute ID + 1000
• 0x66: 66Hex: Attribute ID + 2000
Set measured data items in order starting from “Measured data item (IN) 1.” If any of the
following values is set, all items from that item to “Measured data item (IN) 32” are the
same as those when set at “0.”
• If at “0”
• If set to attribute ID to which no communication data items are assigned
• If at 231 to 236 or 238 to 243 as attribute ID
Set the setting data items in order starting from “Setting data item (OUT) 1.” If any of the
following values is set, all items from that item to “Setting data item (OUT) 32” are the same
as those when set at “0.”
• If at “0”
• If set to attribute ID to which readable communication data items are assigned
• If set to attribute ID to which no communication data items are assigned
• If at 231 to 236, or 238 to 243 as attribute ID
• If at 33 as attribute ID (when “Bit 1: PID/AT transfer by polling I/O communication” of
attribute ID “246” (Action mode selection) is “0: Invalidate”)
For attribute ID of communication item, refer to 7. COMMUNICATION DATA LIST (P.47).
Factory set value
0
0
IMR01Y36-E2
43
Page 50
6. DeviceNet COMMUNICATION
Number of communication controllers setting
The number of communication controllers when conducting Polling I/O communication is set by the
attribute ID 236 of object instance (instance ID) 1 in Z-TIO module object (0x64: 64Hex).
Object class ID: 64
Instance ID: 1
Attribute ID: 236 (Number of polling I/O communication controllers)
Write data: 1 to 31
Number of communication data items setting
The number of communication data items when conducting Polling I/O communication is set by the
attribute IDs, 240 and 241 of object instance (instance ID) 1 in Z-TIO module object (0x64: 64Hex).
Attribute ID 240: Number of communication measured data items (IN)
Attribute ID 241: Number of communication setting data items (OUT)
Object class ID: 64
Instance ID: 1
Attribute ID: 240 (Number of communication measured words)
241 (Number of communication setting words)
Write data: 0 to 200 words
The number of communication data items can be calculated from the following equation.
Number of communication data items
= (Number of words of first communication item for one module
+ Number of words of next communication item for one module
+ Number of words of last communication item for one module
1
1
1
)
• • •
× Number of communication controllers + Fixed communication date items: 5 words
1
In the case of two-channel type (Z-TIO-B modules), the number of the words per one module is
the same as four-channel type (Z-TIO-A modules).
2
Measured data items (IN)
Receive counter: 1 word, Alarm state: 2 words, RUN/STOP state: 2 words
Setting data items (OUT)
Setting state selection: 3 words, RUN/STOP transfer: 2 words
2
44
IMR01Y36-E2
Page 51
6. DeviceNet COMMUNICATION
Controller address setting
The controller address setting when conducting Polling I/O communication is set by the attribute ID
245 of object instance (instance ID) 1 to 31 in Z-TIO module object (0x64: 64Hex).
Object class ID: 64
Instance ID: 1 to 31
Attribute ID: 245 (Controller address setting)
Write data: 0 to 32 *
* For a Z-TIO module, set the data within the range 1 to 16. For a Z-DIO
module, set the data within the range 17 to 32.
(A combined maximum of 31 modules can be connected, with a maximum of
16 Z-TIO modules and a maximum of 16 Z-DIO modules)
Set “0” in non-connected controllers
Controllers with addresses set to “0” will not perform communication. If a value other than “0”
(1 to 32) is set in a non-connected controller, communication will take place, however, all data
will be “0.”
Action mode selection
The action mode selection when conducting Polling I/O communication is set by the attribute ID 246
of object instance (instance ID) 1 in Z-TIO module object (0x64: 64Hex).
Write data: Bit data
Bit 0: Address setting method transfer
0: Continuous setting
1: Free setting
Bit 1: PID/AT transfer by Polling I/O communication
0: Invalidate
1: Validate
[Decimal number: 0 to 3]
Automatic acquisition of controller address setting
The Automatic acquisition of controller address when conducting Polling I/O communication is set by
the attribute ID 247 of object instance (instance ID) 1 in Z-TIO module object (0x64: 64Hex).
Attribute ID: 247 (Automatic acquisition of controller address)
Write data: 0: Do not execute the automatic acquisition
1: Execute the automatic acquisition *
* Automatically reverts to “0: Do not execute the automatic acquisition”
after automatic acquisition.
When automatic acquisition of controller address is executed, the
“number of communication controllers” and “controller address”
The controller address automatic acquisition set “1: Execute the automatic acquisition,”
performs the automatic acquisition of the controller address by turning on the power again.
When set in “100” in set value (SV) of CH3 of Z-TIO module 1
Node address (MAC ID) 1
Service code 10H (Set_Attribute_Single)
Object class ID 64
Instance ID 3 (CH3 of Z-TIO module 1)
Attribute ID 45 (Set value (SV))
Write data 100
When set in “50” in proportional band [heat-side] of CH2 of Z-TIO module 2
Node address (MAC ID) 1
Service code 10H (Set_Attribute_Single)
Object class ID 64
Instance ID 6 (CH2 of Z-TIO module 2)
Attribute ID 46 (Proportional band [heat-side)
Write data 50
When set in “Unused” in operation mode of CH4 of Z-TIO module 1
Node address (MAC ID) 1
Service code 10H (Set_Attribute_Single)
Object class ID 65
Instance ID 4 (CH4 of Z-TIO module 1)
Attribute ID 1022 (Operation mode)
Write data 0 (Unused)
When set in “ON” in DO1 manual output of Z-DIO module 1
Node address (MAC ID) 1
Service code 10H (Set_Attribute_Single)
Object class ID 66
Instance ID 1 (Z-DIO module 1)
Attribute ID 2007 (DO manual output)
Write data 1
Z-TIO module
extended object
ttribute ID + 1000
Z-DIO module object
ttribute ID + 2000
46
IMR01Y36-E2
Page 53
7. COMMUNICATION DATA LIST
7.1 Reference to Communication Data List
Attribute contents of the controller object are described to the communication data list.
The controller objects consist of the three types below.
• Z-TIO module object (0x64: 64Hex)
• Z-TIO module extended object (0x65: 65Hex)
• Z-DIO module object (0x66: 66Hex)
(1) (2)(3) (4)(5)(6)
Number
ID
1
(0x0001)
2
(0x0002)
3
(0x0003)
Name
Measured value (PV) 64 RO Input scale low to Input scale high
Current transformer (CT)
input value monitor
Unused
of data
items
(1) ID: Attribute ID
Attribute ID is written using both of decimal and hexadecimal (in
parentheses) numbers.
Attribute
64 RO
⎯
⎯
Data range
CTL-6-P-N: 0.0 to 30.0 A
CTL-12-S56-10L-N: 0.0 to 100.0 A
⎯
Factory
set value
⎯
⎯
⎯
(2) Name: The communication item name is written.
(3) Number of data items: The number of data items is written.
1: Only object instance 1 is validated
2: Only object instance 1 and 2 are validated
16: Validate for object instance 1 to 16
31: Validate for object instance 1 to 31
64: Validate for object instance 1 to 64
128: Validate for object instance 1 to 128
With respect to the following communication data of the Z-TIO module,
the data of the indicated channels are “0”.
• Two-channel type module:
Data of the 3rd and 4th channels
• Heat/cool control and position proportioning control:
Data of the 2nd and 4th channels *
• Cool-only communication data of heat/cool control:
Data of the 2nd and 4th channels *
* Communication data with a ♣ mark in the name column
IMR01Y36-E2 47
Page 54
7. COMMUNICATION DATA LIST
(4) Attribute: A method of how communication data items are read or written when
viewed from the PLC is described.
RO: Only reading data is possible. (Get: Yes, Set: No)
Correspond to Service code: 0EH (Get_Attribute_Single) of
DeviceNet. For data request of a master, data is read from slave.
Master (PLC etc.)
Data direction
The controller
R/W: Reading and writing data is possible. (Get: Yes, Set: Yes)
Correspond to Service code: 0EH (Get_Attribute_Single)/Service
code: 10H (Set_Attribute_Single) of DeviceNet.
In Get_Attribute_Single, data is read for data request of a master
from Slave.
In Set_Attribute_Single, write in data for Slave from a master.
Master (PLC etc.)
Data direction
The controller
(5) Data range: The data range of communication item is written.
Bit image of bit data is as follows.
16-bit data
…………….……………………
Bit 15
Bit 0
(6) Factory set value: The factory set value of communication item is written.
For controller object (0x64: 64Hex, 0x65: 65Hex, 0x66: 66Hex), refer to APPENDIX A.
DEVICE PROFILES (P. 103).
Communication includes both Normal setting data and Engineering setting data.
During RUN (control), the attribute of Engineering setting data is RO. To configure
Engineering setting data, the RUN/STOP switch must be set to STOP (control stopped).
Z-TIO module object (0x64: 64Hex):
Engineering setting data: ID83 to 203, 205 to 209, 211 to 224
Z-TIO module extended object (0x65: 65Hex):
Engineering setting data: ID24 to 42
Z-DIO module object (0x66: 66Hex):
Engineering setting data: ID13 to 26
The Engineering setting data should be set according to the application before setting any
parameter related to operation. Once the Engineering setting data are set correctly, those
datas are not necessary to be changed for the same application under normal conditions. If
they are changed unnecessarily, it may result in malfunction or failure of the instrument. RKC
will not bear any responsibility for malfunction or failure as a result of improper changes in
the Engineering setting.
48
IMR01Y36-E2
Page 55
7. COMMUNICATION DATA LIST
When data is changed using SRZ loader communication, or when data is changed using DI
of a Z-DIO module, up to 5 minutes (when 31 modules are connected) may be required for
the data to be updated on DeviceNet. In addition, when the engineering setting data in the
SRZ is changed from DeviceNet, up to 5 minutes may be required for the data to be updated
on DeviceNet, depending on the item. [For example, the Set value (SV) and Event set value
when the input type, input scale upper limit, or input scale lower limit is changed]
If you changed the engineering setting data, turn off the power of the COM-JH and then turn
it back on.
Reading/writing operation of undefined attribute ID
When the master read/write data with an undefined attribute ID, an error response is sent by
the slave.
Error response occurs at the following attribute IDs:
[Z-TIO module object (0x64: 64Hex)]
• form 228 (0x00E4) to 230 (0x00E6)
• 248 (0x00F8) or later
[Z-TIO module extended object (0x65: 65Hex)]
• 43 (0x002B) or later
[Z-DIO module object (0x66: 66Hex)]
• 27 (0x001B) or later
Reading/writing operation of unused controller object (unused item) *
When the master reads/writes data of an unused item, an error response does not occur.
• For reading, the slave sends default value to the master.
• For writing, data sent by the master to the slave becomes invalidated. Data of the slave
remains.
* Unused items
• Controller object is for an optional function not specified at time of order.
Example: Heater break alarm function
• Controller object is for a function set to “None.”
Example: Event hold action, Event interlock
IMR01Y36-E2 49
Page 56
7. COMMUNICATION DATA LIST
7.2 Z-TIO Module Object (0x64: 64Hex)
Number
ID
Measured value (PV) 64 RO Input scale low to Input scale high ⎯
1
(0x0001)
2
Current transformer (CT)
(0x0002)
(0x0003)
(0x0004)
(0x0005)
(0x0006)
(0x0007)
(0x0008)
(0x0009)
10
(0x000A)
11
(0x000B)
12
(0x000C)
13
(0x000D)
14
(0x000E)
15
(0x000F)
16
(0x0010)
17
(0x0011)
♣ Parameters only used for Heat/Cool PID control or position proportioning control, therefore data for CH2 and
CH4 of Z-TIO modules are unused.
input value monitor
Unused ⎯ ⎯ ⎯ ⎯
3
Set value (SV) monitor 64 RO Setting limiter low to Setting limiter high ⎯
4
5
Remote setting (RS) input
value monitor
Burnout state monitor 64 RO
6
Unused ⎯ ⎯ ⎯ ⎯
7
Event 1 state monitor 64 RO⎯
8
Event 2 state monitor 64 RO⎯
9
Event 3 state monitor * 64 RO⎯
Event 4 state monitor 64 RO
Heater break alarm (HBA)
state monitor
Unused ⎯ ⎯ ⎯ ⎯
Manipulated output value
(MV) monitor [heat-side] ♣
Manipulated output value
(MV) monitor [cool-side] ♣
Error code 64 RO
Unused ⎯ ⎯ ⎯ ⎯
Name
of data
items
Attri-
bute
64 RO
64 ROSetting limiter low to Setting limiter high ⎯
64 RO
64 RO
64 RO
CTL-6-P-N: 0.0 to 30.0 A
CTL-12-S56-10L-N: 0.0 to 100.0 A
0: OFF
1: ON
0: OFF
1: ON
* If the Event 3 type is temperature rise
completion, check the temperature rise
completion state in the comprehensive
event state [Z-TIO module extended
object (0x65: 65Hex) ID: 1].
(The Event 3 state monitor does not turn
ON.)
0: OFF
1: ON
PID control or Heat/Cool PID control:
−5.0 to +105.0 %
Position proportioning control with
feedback resistance (FBR) input:
0.0 to 100.0 %
−5.0 to +105.0 %
Bit data
Bit 0: Adjustment data error
Bit 1: Data back-up error
Bit 2: A/D conversion error
Bit 3, Bit 4: Unused
Bit 5: Logic output data error
Bit 6 to Bit 15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 63]
Data range
Factory
set value
⎯
⎯
⎯
⎯
⎯
⎯
⎯
Continued on the next page.
50
IMR01Y36-E2
Page 57
7. COMMUNICATION DATA LIST
Continued from the previous page.
Number
ID
Name
of data
items
18
Output state monitor 64 RO
(0x0012)
19
(0x0013)
20
(0x0014)
21
(0x0015)
22
(0x0016)
23
Operation mode state
monitor
Memory area soak time
monitor
Integrated operating time
monitor
Holding peak value ambient
temperature monitor
Unused ⎯ ⎯ ⎯ ⎯
(0x0017)
24
(0x0018)
25
(0x0019)
32
Backup memory state
monitor
Unused ⎯ ⎯ ⎯ ⎯
•
•
•
(0x0020)
33
PID/AT transfer
1, 2
64 R/W
(0x0021)
1
When used in Polling I/O communication, set “PID/AT transfer by Polling I/O communication” in the action mode
selections (ID: 246) to “1: Validate.”
2
When PID/AT transfer is set to “1: Autotuning (AT)” in Polling I/O communication, do not change any of the other
communication data for controllers with AT set until AT ends, as “1: Autotuning (AT)” may set again when AT
ends.
Attri-
bute
Data range
Bit data
Factory
set value
⎯
Bit 0: The state of OUT1
Bit 1: The state of OUT2
Bit 2: The state of OUT3
Bit 3: The state of OUT4
Bit 4 to Bit 15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 15]
64 RO
Bit data
⎯
Bit 0: Control STOP
Bit 1: Control RUN
Bit 2: Manual mode
Bit 3: Remote mode
Bit 4 to Bit 15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 15]
64 RO
0 minutes 00 seconds to
⎯
199 minutes 59 seconds:
0 to 11999 seconds
0 hours 00 minutes to
99 hours 59 minutes:
0 to 5999 minutes
Data range of Area soak time can be
selected on the Soak time unit.
16 RO0 to 19999 hours ⎯
64 RO −10.0 to +100.0 °C or 14 to 212 °F ⎯
64 RO
0: The content of the backup memory does
⎯
not coincide with that of the RAM.
1: The content of the backup memory
coincides with that of the RAM.
0: PID control
0
1: Autotuning (AT) *
* Automatically reverts to 0 after
autotuning ends.
Continued on the next page.
IMR01Y36-E2
51
Page 58
7. COMMUNICATION DATA LIST
Continued from the previous page.
ID
34
(0x0022)
35
(0x0023)
36
(0x0024)
37
(0x0025)
38
(0x0026)
39
(0x0027)
40
(0x0028)
41
(0x0029)
42
(0x002A)
Auto/Manual transfer 64 R/W
Remote/Local transfer 64 R/W
RUN/STOP transfer 64 R/W
Memory area transfer 64 R/W
Interlock release 64 R/W
Event 1 set value (EV1) ★ 64 R/W50
Event 2 set value (EV2) ★ 64 R/W50
Event 3 set value (EV3) ★ 64 R/W50
Event 4 set value (EV4) ★ 64 R/W
Name
Number
of data
items
Attri-
bute
Data range
0: Auto mode
1: Manual mode
0: Local mode
1: Remote mode
When performing remote control by remote
setting input and also performing cascade
control and ratio setting, transfer to the
remote mode.
0: STOP mode (Control stop)
1: RUN mode (Control start)
1 to 8
0: Normal state
1: Interlock release execution
Deviation action, Deviation action
between channels, Temperature rise
completion range*:
−Input span to +Input span
Process action, SV action:
Input scale low to Input scale high
MV action:
−5.0 to +105.0 %
* When temperature rise completion is
selected at Event 3 action type.
If the Event type corresponds to “0: None,”
set to RO (Only reading data is possible).
If Event 4 corresponds to “9: Control loop
break alarm (LBA),” the Event 4 set value
becomes RO (Only reading data is
possible).
Factory
set value
0
0
0
1
0
50
43
(0x002B)
44
Control loop break alarm
(LBA) time ★
LBA deadband ★64 R/W 0 (0.0) to Input span
(0x002C)
45
Set value (SV) ★64 R/W Setting limiter low to Setting limiter high TC/RTD: 0
(0x002D)
★: Data related to multi-memory area function
It is possible to change only the data of the control area which is selected by the memory area transfer (ID: 37).
52
64 R/W 0 to 7200 seconds (0: Unused)
Continued on the next page.
480
0 (0.0)
V/I: 0.0
IMR01Y36-E2
Page 59
7. COMMUNICATION DATA LIST
Continued from the previous page.
Number
ID
Name
of data
items
46
(0x002E)
47
(0x002F)
48
(0x0030)
49
(0x0031)
50
(0x0032)
Proportional band
[heat-side] ★♣
Integral time
[heat-side] ★♣
Derivative time
[heat-side] ★♣
Control response
parameter ★ ♣
Proportional band
[cool-side] ★ ♣
★: Data related to multi-memory area function
It is possible to change only the data of the control area which is selected by the memory area transfer (ID: 37).
Parameters only used for Heat/Cool PID control or position proportioning control, therefore data for CH2 and
♣
CH4 of Z-TIO modules are unused.
Attri-
bute
64 R/W
64 R/W
64 R/W
64 R/W
64 R/W
Data range
TC/RTD inputs:
0 (0.0) to Input span (Unit: °C [°F])
Varies with the setting of the Decimal
point position selection.
Voltage (V)/Current (I) inputs:
0.0 to 1000.0 % of Input span
0 (0.0): ON/OFF action
(ON/OFF action for both heat and cool
actions in case of a Heat/Cool PID control
type.)
PID control or Heat/Cool PID control:
0 to 3600 seconds or
0.0 to 1999.9 seconds
(0, 0.0: PD action)
Position proportioning control:
1 to 3600 seconds or
0.1 to 1999.9 seconds
Varies with the setting of the
Integral/Derivative time decimal point
position selection.
0 to 3600 seconds or
0.0 to 1999.9 seconds
(0, 0.0: PI action)
Varies with the setting of the
Integral/Derivative time decimal point
position selection
.
0: Slow
1: Medium
2: Fast
When the P or PD action is selected, this
setting becomes invalidate.
TC/RTD inputs:
1 (0.1) to Input span (Unit: °C [°F])
Varies with the setting of the Decimal
point position selection.
Voltage (V)/Current (I) inputs:
0.1 to 1000.0 % of Input span
If control is other than Heat/Cool PID
control, set to RO (Only reading data is
possible).
Continued on the next page.
Factory
set value
TC/RTD: 30
V/I: 30.0
240
60
PID control,
Position
proportioning
control: 0
Heat/Cool PID
control: 2
TC/RTD: 30
V/I: 30.0
IMR01Y36-E2
53
Page 60
7. COMMUNICATION DATA LIST
Continued from the previous page.
Number
ID
Name
of data
items
51
(0x0033)
52
(0x0034)
53
Integral time
[cool-side] ★ ♣
Derivative time
[cool-side] ★ ♣
Overlap/Deadband ★ ♣ 64 R/W
(0x0035)
54
Manual reset ★ 64 R/W −100.0 to +100.0 %
(0x0036)
55
(0x0037)
56
(0x0038)
57
Setting change rate limiter
(up) ★
Setting change rate limiter
(down) ★
Area soak time ★ 64 R/W
(0x0039)
58
Link area number ★ 64 R/W
(0x003A)
★: Data related to multi-memory area function
It is possible to change only the data of the control area which is selected by the memory area transfer (ID: 37).
Parameters only used for Heat/Cool PID control or position proportioning control, therefore data for CH2 and
♣
CH4 of Z-TIO modules are unused.
Attri-
bute
64 R/W
64 R/W
64 R/W
64 R/W
Data range
0 to 3600 seconds or
0.0 to 1999.9 seconds (0, 0.0: PD action)
Varies with the setting of the
Integral/Derivative time decimal point
position selection.
If control is other than Heat/Cool PID
control, set to RO (Only reading data is
possible).
0 to 3600 seconds or
0.0 to 1999.9 seconds (0, 0.0: PI action)
Varies with the setting of the
Integral/Derivative time decimal point
position selection.
If control is other than Heat/Cool PID
control, set to RO (Only reading data is
possible).
TC/RTD inputs:
−Input span to +Input span
(Unit:°C [°F])
Voltage (V)/Current (I) inputs:
−100.0 to +100.0 % of Input span
Minus (−) setting results in Overlap.
However, the overlapping range is within
the proportional range.
If control is other than Heat/Cool PID
control, set to RO (Only reading data is
possible).
If the Integral function is validated, set to
RO (Only reading data is possible).
When integral action (heating or cooling
side) is zero, manual reset value is added to
the control output.
0 (0.0) to Input span/unit time *
(0 (0.0): Unused)
* Unit time: 60 seconds
(factory set value)
0 minutes 00 seconds to
199 minutes 59 seconds:
0 to 11999 seconds
0 hours 00 minutes to
99 hours 59 minutes:
0 to 5999 minuts
Data range of Area soak time can be
selected on the Soak time unit.
0 to 8
(0: No link)
Continued on the next page.
Factory
set value
240
60
0
0.0
0 (0.0)
0 (0.0)
0
0
54
IMR01Y36-E2
Page 61
Continued from the previous page.
ID
59
(0x003B)
60
(0x003C)
61
(0x003D)
62
(0x003E)
63
(0x003F)
64
(0x0040)
65
(0x0041)
66
(0x0042)
67
(0x0043)
68
(0x0044)
69
(0x0045)
70
(0x0046)
71
(0x0047)
Heater break alarm (HBA)
set value
Heater break
determination point
Heater melting
determination point
Unused ⎯ ⎯ ⎯ ⎯
Unused ⎯ ⎯
Unused ⎯ ⎯
PV bias 64 R/W −Input span to +Input span 0
PV digital filter 64 R/W
PV ratio 64 R/W 0.500 to 1.500 1.000
PV low input cut-off 64 R/W 0.00 to 25.00 % of input span
RS bias * 64 R/W −Input span to +Input span 0
RS digital filter * 64 R/W
RS ratio * 64 R/W 0.001 to 9.999
Name
Number
of data
items
64 R/W
64 R/W
64 R/W
7. COMMUNICATION DATA LIST
Attri-
bute
Data range
When CT is CTL-6-P-N:
0.0 to 30.0 A (0.0: Not used)
When CT is CTL-12-S56-10L-N:
0.0 to 100.0 A (0.0: Not used)
If there is no Current transformer (CT) or
CT is assigned to “0: None,” set to RO
(Only reading data is possible).
0.0 to 100.0 % of HBA set value
(0.0: Heater break determination is
invalidated)
If there is no Current transformer (CT) or
CT is assigned to “0: None,” set to RO
(Only reading data is possible).
If Heater break alarm (HBA) corresponds
to “0: Type A,” set to RO (Only reading
data is possible).
0.0 to 100.0 % of HBA set value
(0.0: Heater melting determination is
invalidated)
If there is no Current transformer (CT) or
CT is assigned to “0: None,” set to RO
(Only reading data is possible).
If Heater break alarm (HBA) corresponds
to “0: Type A,” set to RO (Only reading
data is possible).
⎯ ⎯
⎯ ⎯
0.0 to 100.0 seconds
(0.0: Unused)
If the Input square root extraction
corresponds to “0: Unused,” set to RO
(Only reading data is possible).
0.0 to 100.0 seconds
(0.0: Unused)
Factory
set value
0.0
30.0
30.0
0.0
0.00
0.0
1.000
* Data on RS bias, RS ratio and RS digital filter is that in Cascade control or Ratio setting.
Continued on the next page.
IMR01Y36-E2
55
Page 62
7. COMMUNICATION DATA LIST
Continued from the previous page.
Number
ID
Name
of data
items
72
(0x0048)
73
Proportional cycle time
Unused
(0x0049)
74
(0x004A)
75
(0x004B)
82
Manual manipulated
output value ♣
Unused
•
•
•
(0x0052)
♣ Parameters only used for Heat/Cool PID control or position proportioning control, therefore data for CH2 and
CH4 of Z-TIO modules are unused.
Attri-
bute
Data range
64 R/W 0.1 to 100.0 seconds
Factory
set value
M output:
M: Relay contact output
V: Voltage pulse output
V, T, D output:
T: Triac output
D: Open collector output
This item becomes RO (Only reading data
is possible) for the Voltage/Current output
specification.
This parameter is validated when
“0: control output” has been selected at
“ID96: Output assignment.”
⎯⎯⎯⎯
64 R/W
PID control:
Output limiter low to
Output limiter high
Heat/Cool PID control:
−Cool-side output limiter (high) to
+Heat-side output limiter (high)
Position proportioning control:
When there is Feedback resistance
(FBR) input and it does not break:
Output limiter low to
Output limiter high
When there is no Feedback resistance
(FBR) input or the Feedback resistance
(FBR) input is disconnected:
0: Close-side output OFF,
Open-side output OFF
1: Close-side output ON,
Open-side output OFF
2: Close-side output OFF,
Open-side output ON
⎯⎯⎯⎯
Continued on the next page.
20.0
2.0
0.0
56
IMR01Y36-E2
Page 63
Continued from the previous page.
ID
Name
ID83 to ID203 are Engineering setting data. [Writable in the STOP mode]
Number
of data
items
Attri-
bute
7. COMMUNICATION DATA LIST
Data range
Factory
set value
83
(0x0053)
84
(0x0054)
85
(0x0055)
Input type 64 R/W 0: TC input K
1: TC input J
2: TC input R
3: TC input S
4: TC input B
5: TC input E
6: TC input N
7: TC input T
8: TC input W5Re/W26Re
9: TC input PLII
12: RTD input Pt100
13: RTD input JPt100
14: Current input 0 to 20 mA DC
15: Current input 4 to 20 mA DC
16: Voltage (high) input 0 to 10 V DC
17: Voltage (high) input 0 to 5 V DC
18: Voltage (high) input 1 to 5 V DC
19: Voltage (low) input 0 to 1 V DC
20: Voltage (low) input 0 to
100 mV DC
21: Voltage (low) input 0 to 10 mV DC
22: Feedback resistance input 100 to
150 Ω
23: Feedback resistance input 151 Ω to
6 kΩ
If changed to Voltage (high) input from
TC/RTD/Current/Voltage (low)/Feedback
resistance input, select the hardware by the
input selector switch at the side of the
module. For the selecting procedure,
refer to SRZ Instruction Manual (IMS01T04-E).
Display unit 64 R/W
0: °C
1: °F
Use to select the temperature unit for
Thermocouple (TC) and RTD inputs.
Decimal point position 64 R/W
0: No decimal place
1: One decimal place
2: Two decimal places
3: Three decimal places
4: Four decimal places
TC input:
• K, J, T, E: Only 0 or 1 can be set.
• R, S, B, N, PLII, W5Re/W26Re:
Only 0 can be set.
RTD input: Only 0 or 1 can be set.
Voltage (V)/Current (I) inputs:
From 0 to 4 can be set.
Based on
model code.
When not
specifying: 0
0
Based on
model code.
When not
specifying:
TC/RTD: 0
V/I: 1
Continued on the next page.
IMR01Y36-E2
57
Page 64
7. COMMUNICATION DATA LIST
Continued from the previous page.
ID
86
(0x0056)
87
(0x0057)
88
(0x0058)
89
(0x0059)
90
(0x005A)
91
(0x005B)
92
(0x005C)
•
•
•
95
(0x005F)
96
(0x0060)
97
(0x0061)
•
•
•
100
(0x0064)
101
(0x0065)
102
(0x0066)
•
•
•
113
(0x0071)
Input scale high 64 R/W
Input scale low 64 R/W
Input error determination
point (high)
Input error determination
point (low)
Burnout direction 64 R/W
Square root extraction 64 R/W
Unused ⎯ ⎯ ⎯ ⎯
Output assignment
(Logic output selection
function)
Unused ⎯ ⎯ ⎯ ⎯
Energized/De-energized
(Logic output selection
function)
Unused ⎯ ⎯ ⎯ ⎯
Name
Number
of data
items
64 R/W
64 R/W
64 R/W
64 R/W
Attri-
bute
Data range
TC/RTD inputs:
Input scale low to Maximum value of
the selected input range
Voltage (V)/Current (I) inputs:
−19999 to +19999
(However, a span is 20000 or less.)
Varies with the setting of the Decimal
point position
TC/RTD inputs:
Minimum value of the selected input
range to Input scale high
Voltage (V)/Current (I) inputs:
−19999 to +19999
(However, a span is 20000 or less.)
Varies with the setting of the Decimal
point position
Input error determination point (low) to
(Input range high + 5 % of input span)
(Input range low − 5 % of input span) to
Input error determination point (high)
0: Upscale
1: Downscale
Validate only when the TC input and
Voltage (low) input are selected.
0: Unused
1: Used
0: Control output
1: Logic output result
2: FAIL output
0: Energized
1: De-energized
Factory
set value
TC/RTD:
Maximum
value of the
selected input
range
V/I: 100.0
TC/RTD:
Minimum value
of the selected
input range
V/I: 0.0
Input scale high
+ (5 % of input
span)
Input scale low
− (5 % of input
span)
0
0
0
0
58
Continued on the next page.
IMR01Y36-E2
Page 65
Continued from the previous page.
ID
114
(0x0072)
115
(0x0073)
116
(0x0074)
117
(0x0075)
Event 1 type 64 R/W
Event 1 hold action 64 R/W
Event 1 interlock 64 R/W
Event 1 differential gap 64 R/W
Name
Number
of data
items
7. COMMUNICATION DATA LIST
Attri-
bute
Data range
0: None
1: Deviation high
(Using SV monitor value)
2: Deviation low
(Using SV monitor value)
3: Deviation high/low
(Using SV monitor value)
4: Band (Using SV monitor value)
5: Process high
6: Process low
1
1
7: SV high
8: SV low
9: Unused
10: MV high [heat-side]
11: MV low [heat-side]
12: MV high [cool-side]
13: MV low [cool-side]
1, 2
1
1, 2
1
14: Deviation high (Using local SV) 1
15: Deviation low (Using local SV)
16: Deviation high/low
(Using local SV)
1
17: Deviation (Using local SV)
18: Deviation between channels high
19: Deviation between channels low
20: Deviation between channels
high/low
1
21: Deviation between channels band
1
Event hold action is available.
2
If there is Feedback resistance (FBR)
input in Position proportioning control,
set to the Feedback resistance (FBR)
input value.
0: OFF
1: Hold action ON
(when power turned on; when
transferred from STOP to RUN)
2: Re-hold action ON
(when power turned on; when
transferred from STOP to RUN;
SV changed)
This function is validated when input value,
deviation or manipulated value action has
been selected.
In case of a deviation action, this function
is not available while in Remote mode and
while Setting changing rate limiter is
working.
0: Unused
1: Used
c Deviation, Process, Set value or
Deviation action between channels:
0 to Input span (Unit: °C [°F])
d MV: 0.0 to 110.0 %
Factory
set value
Based on
1
1
1
1
model code.
When not
specifying: 0
1
1
1
1
1
Based on
model code.
When not
specifying: 0
0
c 1
d 1.0
IMR01Y36-E2
Continued on the next page.
59
Page 66
7. COMMUNICATION DATA LIST
Continued from the previous page.
ID
118
(0x0076)
119
(0x0077)
120
(0x0078)
Event 1 delay timer
Force ON of Event 1
action
Event 2 type 64 R/W
Name
Number
of data
items
Attri-
bute
Data range
64 R/W 0 to 18000 seconds 0
64 R/W
Bit data
Bit 0: Event output turned on at input
error occurrence
Bit 1: Event output turned on in Manual
mode
Bit 2: Event output turned on during the
Autotuning (AT) function is being
executed
Bit 3: Event output turned on during the
Setting change rate limiter is being
operated
Bit 4 to Bit 15: Unused
Data 0: Invalidate 1: Validate
[Decimal number: 0 to 15]
0: None
1: Deviation high
(Using SV monitor value)
2: Deviation low
(Using SV monitor value)
3: Deviation high/low
(Using SV monitor value)
4: Band (Using SV monitor value)
5: Process high
6: Process low
1
1
1
1
1
1
7: SV high
8: SV low
9: Unused
10: MV high [heat-side]
11: MV low [heat-side]
12: MV high [cool-side]
13: MV low [cool-side]
14: Deviation high (Using local SV) 1
15: Deviation low (Using local SV)
16: Deviation high/low
(Using local SV)
17: Deviation (Using local SV)
18: Deviation between channels high
19: Deviation between channels low
20: Deviation between channels
high/low
1
21: Deviation between channels band
1
Event hold action is available.
2
If there is Feedback resistance (FBR)
1, 2
1, 2
1
1
1
1
1
1
1
1
input in Position proportioning control,
set to the Feedback resistance (FBR)
input value.
Factory
set value
0
Based on
model code.
When not
specifying: 0
60
Continued on the next page.
IMR01Y36-E2
Page 67
Continued from the previous page.
ID
121
(0x0079)
122
(0x007A)
123
(0x007B)
124
(0x007C)
125
(0x007D)
Event 2 hold action 64 R/W
Event 2 interlock 64 R/W
Event 2 differential gap 64 R/W
Event 2 delay timer 64 R/W 0 to 18000 seconds 0
Force ON of Event 2
action
Name
Number
of data
items
Attri-
bute
0: OFF
1: Hold action ON
(when power turned on; when
transferred from STOP to RUN)
2: Re-hold action ON
(when power turned on; when
transferred from STOP to RUN;
SV changed)
This function is validated when input value,
deviation or manipulated value action has
been selected.
In case of a deviation action, this function
is not available while in Remote mode and
while Setting changing rate limiter is
working.
0: Unused
1: Used
c Deviation, Process, Set value or
Deviation action between channels:
0 to Input span (Unit: °C [°F])
d MV: 0.0 to 110.0 %
64 R/W Bit data
Bit 0: Event output turned on at input
Bit 1: Event output turned on in Manual
Bit 2: Event output turned on during the
Bit 3: Event output turned on during the
Bit 4 to Bit 15: Unused
Data 0: Invalidate 1: Validate
[Decimal number: 0 to 15]
7. COMMUNICATION DATA LIST
Data range
error occurrence
mode
Autotuning (AT) function is being
executed
Setting change rate limiter is being
operated
Factory
set value
Based on
model code.
When not
specifying: 0
0
c 1
d 1.0
0
IMR01Y36-E2
Continued on the next page.
61
Page 68
7. COMMUNICATION DATA LIST
Continued from the previous page.
ID
126
(0x007E)
127
(0x007F)
128
(0x0080)
129
(0x0081)
Event 3 type 64 R/W
Event 3 hold action 64 R/W
Event 3 interlock 64 R/W
Event 3 differential gap 64 R/W
Name
Number
of data
items
Attri-
bute
Data range
0: None
1: Deviation high
(SV monitor value used)
2: Deviation low
(SV monitor value used)
3: Deviation high/low
(SV monitor value used)
4: Band (SV monitor value used)
5: Process high
6: Process low
1
1
7: SV high
8: SV low
9: Temperature rise completion
10: MV high [heat-side]
11: MV low [heat-side]
12: MV high [cool-side]
13: MV low [cool-side]
1, 2
1
1, 2
1
14: Deviation high
(Local SV value used)
15: Deviation low
(Local SV value used)
16: Deviation high/low
(Local SV value used)
17: Deviation (Local SV value used)
18: Deviation between channels high
19: Deviation between channels low
20: Deviation between channels
high/low
1
21: Deviation between channels band
1
Event hold action is available.
2
If there is Feedback resistance (FBR)
input in Position proportioning control,
set to the Feedback resistance (FBR)
input value.
0: OFF
1: Hold action ON
(when power turned on; when
transferred from STOP to RUN)
2: Re-hold action ON
(when power turned on; when
transferred from STOP to RUN;
SV changed)
This function is validated when input value,
deviation or manipulated value action has
been selected.
In case of a deviation action, this function
is not available while in Remote mode and
while Setting changing rate limiter is
working.
0: Unused
1: Used
c Deviation, Process, Set value or
Deviation action between channels:
0 to Input span (Unit: °C [°F])
d MV: 0.0 to 110.0 %
Continued on the next page.
Factory
set value
Based on
1
1
1
1
model code.
When not
specifying: 0
1
1
1
1
1
1
1
Based on
model code.
When not
specifying: 0
0
c 1
d 1.0
62
IMR01Y36-E2
Page 69
Continued from the previous page.
ID
130
(0x0082)
131
(0x0083)
132
(0x0084)
Event 3 delay timer 64 R/W 0 to 18000 seconds
Force ON of Event 3
action
Event 4 type 64 R/W
Name
Number
of data
items
Attri-
bute
If Event 3 corresponds to “9: Temperature
rise completion,” the Event 3 delay timer
becomes the Temperature rise completion
soak time.
64 R/W Bit data
Bit 0: Event output turned on at input
Bit 1: Event output turned on in Manual
Bit 2: Event output turned on during the
Bit 3: Event output turned on during the
Bit 4 to Bit 15: Unused
Data 0: Invalidate 1: Validate
[Decimal number: 0 to 15]
0: None
1: Deviation high
(SV monitor value used)
2: Deviation low
(SV monitor value used)
3: Deviation high/low
(SV monitor value used)
4: Band (SV monitor value used)
5: Process high
6: Process low
7: SV high
8: SV low
9: Control loop break alarm (LBA)
10: MV high [heat-side]
11: MV low [heat-side]
12: MV high [cool-side]
13: MV low [cool-side]
14: Deviation high
(Local SV value used)
15: Deviation low
(Local SV value used)
16: Deviation high/low
(Local SV value used)
17: Deviation (Local SV value used)
18: Deviation between channels high
19: Deviation between channels low
20: Deviation between channels
high/low
21: Deviation between channels band
1
Event hold action is available.
2
If there is Feedback resistance (FBR)
input in Position proportioning control,
set to the Feedback resistance (FBR)
input value.
7. COMMUNICATION DATA LIST
Data range
error occurrence
mode
Autotuning (AT) function is being
executed
Setting change rate limiter is being
operated
1
1
1
1
1
1
1, 2
1, 2
1
1
1
1
1
1
1
1
1
1
Factory
set value
0
0
Based on
model code.
When not
specifying: 0
IMR01Y36-E2
Continued on the next page.
63
Page 70
7. COMMUNICATION DATA LIST
Continued from the previous page.
ID
133
(0x0085)
134
(0x0086)
135
(0x0087)
136
(0x0088)
137
(0x0089)
138
(0x008A)
139
(0x008B)
Event 4 hold action 64 R/W
Event 4 interlock 64 R/W
Event 4 differential gap 64 R/W
Event 4 delay timer 64 R/W 0 to 18000 seconds 0
Force ON of Event 4
action
CT ratio 64 R/W 0 to 9999
CT assignment 64 R/W
Name
Number
of data
items
64 R/W
Attri-
bute
Data range
0: OFF
1: Hold action ON
(when power turned on; when
transferred from STOP to RUN)
2: Re-hold action ON
(when power turned on; when
transferred from STOP to RUN;
SV changed)
This function is validated when input value,
deviation or manipulated value action has
been selected.
In case of a deviation action, this function
is not available while in Remote mode and
while Setting changing rate limiter is
working.
0: Unused
1: Used
c Deviation, Process, Set value or
Deviation action between channels:
0 to Input span (Unit: °C [°F])
d MV: 0.0 to 110.0 %
Becomes invalidated when the Event 4
type corresponds to “9: Control loop break
alarm (LBA).”
Bit data
Bit 0: Event output turned on at input
error occurrence
Bit 1: Event output turned on in Manual
mode
Bit 2: Event output turned on during the
Autotuning (AT) function is being
executed
Bit 3: Event output turned on during the
Setting change rate limiter is being
operated
Bit 4 to Bit 15: Unused
Data 0: Invalidate 1: Validate
[Decimal number: 0 to 15]
0: None
1: OUT1
2: OUT2
3: OUT3
4: OUT4
Factory
set value
Based on
model code.
When not
specifying: 0
0
c 1
d 1.0
0
CTL-6-P-N:
800
CTL-12-S56-
10L-N: 1000
1
64
Continued on the next page.
IMR01Y36-E2
Page 71
7. COMMUNICATION DATA LIST
Continued from the previous page.
Number
ID
Name
of data
items
140
(0x008C)
141
(0x008D)
142
(0x008E)
145
Heater break alarm (HBA)
type
Number of heater break
alarm (HBA) delay times
Unused ⎯ ⎯ ⎯ ⎯
•
•
•
(0x0091)
146
Hot/Cold start 64 R/W
(0x0092)
147
Start determination point 64 R/W 0 to Input span
(0x0093)
148
Unused ⎯ ⎯ ⎯ ⎯
(0x0094)
149
Unused ⎯ ⎯ ⎯ ⎯
(0x0095)
150
SV tracking 64 R/W
(0x0096)
151
(0x0097)
MV transfer function
[Action taken when
changed to Manual mode
from Auto mode]
152
Control action 64 R/W 0: Brilliant II PID control (direct action)
(0x0098)
153
(0x0099)
Integral/Derivative time
decimal point position ♣
♣ Parameters only used for Heat/Cool PID control or position proportioning control, therefore data for CH2 and
CH4 of Z-TIO modules are unused.
Attri-
bute
64 R/W
Data range
0: Heater break alarm (HBA) type A
(Time-proportional control output)
Factory
set value
Based on
model code
1: Heater break alarm (HBA) type B
(Continuous control output)
64 R/W 0 to 255 times 5
0: Hot start 1
1: Hot start 2
2: Cold start
Based on
(The unit is the same as input value.)
specifications.
(0: Action depending on the Hot/Cold
start selection)
0: Unused
1: Used
64 R/W
0: MV in Auto mode is used.
[Balanceless-bumpless function]
1: MV in previous Manual mode is used.
Based on
1: Brilliant II PID control (reverse action)
model code.
2: Brilliant II Heat/Cool PID control
[water cooling]
3: Brilliant II Heat/Cool PID control
When not
specifying: 1
[air cooling]
4: Brilliant II Heat/Cool PID control
[Cooling gain linear type]
5: Position proportioning control
Odd channel: From 0 to 5 can be set.
Even channel: Only 0 or 1 can be set. *
* In Heat/Cool PID control and Position
proportioning control, control action is
not performed. Only PV monitor and
event action is performed.
64 R/W 0: 1 second setting (No decimal place)
1: 0.1 seconds setting
(One decimal place)
Continued on the next page.
0
1
0
0
IMR01Y36-E2
65
Page 72
7. COMMUNICATION DATA LIST
Continued from the previous page.
Number
ID
Name
of data
items
154
Derivative action ♣ 64 R/W
(0x009A)
155
(0x009B)
156
Undershoot suppression
factor ♣
Derivative gain ♣ 64 R/W
(0x009C)
157
(0x009D)
158
(0x009E)
159
(0x009F)
160
(0x00A0)
161
(0x00A1)
162
(0x00A2)
ON/OFF action
differential gap (upper) ♣
ON/OFF action
differential gap (lower) ♣
Action (high) at input error
♣
Action (low) at input error
♣
Manipulated output value
at input error ♣
Manipulated output value
at STOP mode [heat-side]
♣
163
(0x00A3)
Manipulated output value
at STOP mode [cool-side]
♣
164
(0x00A4)
165
(0x00A5)
166
(0x00A6)
Output change rate limiter
(up) [heat-side] ♣
Output change rate limiter
(down) [heat-side] ♣
Output limiter high
[heat-side] ♣
♣ Parameters only used for Heat/Cool PID control or position proportioning control, therefore data for CH2 and
CH4 of Z-TIO modules are unused.
Attri-
bute
Data range
Factory
set value
0: Measured value derivative
1: Deviation derivative
64 R/W 0.000 to 1.000
Water cooling:
Air cooling:
Cooling gain
linear type:
0.1 to 10.0
64 R/W
64 R/W
64 R/W
TC/RTD inputs:
0 (0.0) to Input span (Unit: °C [°F])
Voltage (V)/Current (I) inputs:
0.0 to 100.0 % of input span
0: Normal control
TC/RTD: 1
V/I: 0.1
TC/RTD: 1
V/I: 0.1
1: Manipulated output value at input
64 R/W
64 R/W
64 R/W−5.0
64 R/W
64 R/W0.0
error
−105.0 to +105.0 %
Actual output values become those
restricted by the output limiter.
Position proportioning control:
If there is no Feedback resistance (FBR)
input or the Feedback resistance (FBR)
input is disconnected, an action taken
when abnormal is in accordance with
the value action setting during STOP.
−5.0 to +105.0 %
Position proportioning control:
Only when there is Feedback resistance
(FBR) input and it does not break, the
Manipulated output value [heat-side] at
STOP is output.
0.0 to 100.0 %/seconds
(0.0: OFF)
64 R/W
64 R/W
Becomes invalidated when in Position
proportioning control.
Output limiter low [heat-side] to 105.0 %
Position proportioning control:
Becomes validated only when there is
Feedback resistance (FBR) input and it
does not break.
Continued on the next page.
0
0.100
0.250
1.000
6.0
0
0
0.0
−5.0
0.0
105.0
66
IMR01Y36-E2
Page 73
7. COMMUNICATION DATA LIST
Continued from the previous page.
Number
ID
Name
of data
items
167
(0x00A7)
168
(0x00A8)
169
(0x00A9)
170
(0x00AA)
171
(0x00AB)
172
Output limiter low
[heat-side] ♣
Output change rate limiter
(up) [cool-side] ♣
Output change rate limiter
(down) [cool-side] ♣
Output limiter high
[cool-side] ♣
Output limiter low
[cool-side] ♣
Unused ⎯ ⎯ ⎯ ⎯
(0x00AC)
173
Unused ⎯ ⎯ ⎯ ⎯
(0x00AD)
174
AT bias ♣ 64 R/W
(0x00AE)
175
AT cycles ♣ 64 R/W
(0x00AF)
176
(0x00B0)
177
(0x00B1)
178
(0x00B2)
Output value with AT
turned on ♣
Output value with AT
turned off ♣
AT differential gap time ♣
♣ Parameters only used for Heat/Cool PID control or position proportioning control, therefore data for CH2 and
CH4 of Z-TIO modules are unused.
Attri-
bute
64 R/W
64 R/W0.0
−5.0 % to Output limiter high [heat-side]
Position proportioning control:
Becomes validated only when there is
Feedback resistance (FBR) input and it
does not break.
0.0 to 100.0 %/seconds
Data range
Factory
set value
(0.0: OFF)
64 R/W
Becomes invalidated when in Position
proportioning control.
the setting will automatically returns to
“0: ST unused.”
The Startup tuning (ST) function is
activated according to the ST start
condition selected.
If control is other than Position
proportioning control, set to RO (Only
reading data is possible).
64 R/W1.00
0.01 to 10.00 times
64 R/W1.00
64 R/W
0: Activate the Startup tuning (ST)
function when the power is turned on;
when transferred from STOP to RUN;
or when the Set value (SV) is changed.
1: Activate the Startup tuning (ST)
function when the power is turned on;
or when transferred from STOP to
RUN.
2: Activate the Startup tuning (ST)
function when the Set value (SV) is
changed.
64 R/W
0 to 16
(0: Automatic temperature rise function
OFF)
64 R/W
0: Unused
1: Learning *
* When the automatic temperature rise
learning is finished, the setting will
automatically returns to “0: Unused.”
If the Automatic temperature rise group
corresponds to “0: Automatic temperature
rise function OFF,” set to RO (Only
reading data is possible).
Continued on the next page.
0
1.00
0
0
1
70
IMR01Y36-E2
Page 77
7. COMMUNICATION DATA LIST
Continued from the previous page.
Number
ID
Name
of data
items
ID211 to ID224 are Engineering setting data. [Writable in the STOP mode]
211
(0x00D3)
212
(0x00D4)
213
Automatic temperature
rise dead time ♣
Automatic temperature
rise gradient data ♣
Unused ⎯ ⎯ ⎯ ⎯
(0x00D5)
214
(0x00D6)
215
Setting change rate limiter
unit time
Soak time unit 64 R/W
(0x00D7)
216
Setting limiter high 64 R/W Setting limiter low to Input scale high Input scale high
(0x00D8)
217
Setting limiter low 64 R/W Input scale low to Setting limiter high Input scale low
(0x00D9)
218
PV transfer function ♣ 64 R/W
(0x00DA)
219
(0x00DB)
224
Unused ⎯ ⎯ ⎯ ⎯
•
•
•
(0x00E0)
ID225 to ID235 are normal setting data.
225
Controller state 1 31 RO
(0x00E1)
♣ Parameters only used for Heat/Cool PID control or position proportioning control, therefore data for CH2 and
CH4 of Z-TIO modules are unused.
Attri-
bute
Data range
Factory
set value
64 R/W 0.1 to 1999.9 seconds 10.0
64 R/W 0.1 to Input span/minutes
Varies with the setting of the Decimal
point position selection.
64 R/W 1 to 3600 seconds 60
0: 0 to 5999 minutes
[0 hours 00 minutes to
99 hours 59 minutes]
1: 0 to 11999 seconds
[0 minutes 00 seconds to
199 minutes 59 seconds:]
Set the data range of Memory area soak
time monitor and Area soak time.
0: Unused
1: Used
Bit data
Z-TIO module:
Bit 0: Burnout state
Bit 1: Unused
Bit 2: Event 1 state
Bit 3: Event 2 state
Bit 4: Event 3 state
Bit 5: Event 4 state
Bit 6: Heater break alarm (HBA) state
Bit 7 to Bit 15: Unused
OR data for each Z-TIO module.
Z-DIO module:
Bit 0 to Bit 15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 125]
Continued on the next page.
1.0
1
0
⎯
IMR01Y36-E2
71
Page 78
7. COMMUNICATION DATA LIST
Continued from the previous page.
Number
ID
Name
of data
items
226
Controller state 2 31 RO
(0x00E2)
227
(0x00E3)
230
Unused ⎯ ⎯ ⎯ ⎯
•
•
•
(0x00E6)
231
(0x00E7)
232
Comprehensive alarm
1
state
Controller alarm state
1
2 RO
(0x00E8)
233
Error state
1
2 RO
(0x00E9)
1
Validate only when Explicit message communication is used.
Attri-
bute
1 RO
Data range
Bit data
Z-TIO module:
Bit 0: Adjustment data error
Bit 1: Data back-up error
Bit 2: A/D conversion error
Bit 3: Unused
Bit 4: Unused
Bit 5: Logic output data error
Bit 6 to Bit 14: Unused
Bit 15: Controller communication error
Z-DIO module:
Bit 0: Unused
Bit 1: Data back-up error
Bit 2 to Bit 14: Unused
Bit 15: Controller communication error
Data 0: OFF 1: ON
[Decimal number: 0 to 32807]
Bit data
Bit 0: Burnout state
Bit 1: Unused
Bit 2: Event 1 state
Bit 3: Event 2 state
Bit 4: Event 3 state
Bit 5: Event 4 state
Bit 6: Heater break alarm (HBA) state
Bit 7 to Bit 15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 127]
Bit data
Object instance 1:
Bit 0 to Bit 15: Controller 1 to 16
Object instance 2:
Bit 0 to Bit 14: Controller 17 to 31
Data 0: OFF 1: ON
[Decimal number: 0 to 65535]
OR of Controller state 1 (ID: 225)
Bit data
Object instance 1:
Bit 0 to Bit 15: Controller 1 to 16
Object instance 2:
Bit 0 to Bit 14: Controller 17 to 31
Data 0: OFF 1: ON
[Decimal number: 0 to 65535]
OR of Controller state 2 (ID: 226)
Continued on the next page.
Factory
set value
⎯
⎯
⎯
⎯
72
IMR01Y36-E2
Page 79
7. COMMUNICATION DATA LIST
Continued from the previous page.
Number
ID
Name
of data
items
234
RUN/STOP
1
2 R/W
(0x00EA)
235
Setting update flag
1
1 RO
(0x00EB)
ID236, ID237 are communication environment setting data.
236
(0x00EC)
Number of Polling I/O
communication
controllers 1
237
Unused ⎯ ⎯ ⎯ ⎯
(0x00ED)
ID238 is normal setting data.
238
COM-JH error code
1
1 RO
(0x00EE)
After ID239 are communication environment setting data.
239
(0x00EF)
240
(0x00F0)
241
(0x00F1)
1
Validate only when Explicit message communication is used.
2
The setting is validated when the power is turned off once after the setting is changed and it is turned on again.
Number of connected
controller in Controller
communication
1
Number of communication
measured data items (IN)
when conducting Polling
I/O communication
1, 2
Number of communication
setting data items (OUT)
when conducting Polling
I/O communication
1, 2
Attri-
bute
Data range
Factory
set value
Bit data
Object instance 1:
Bit 0 to Bit 15: Controller 1 to 16
Object instance 2:
Bit 0 to Bit 14: Controller 17 to 31
Data RUN/STOP state is depending on
the value of RUN/STOP logic
selection (ID: 242)
[Decimal number: 0 to 65535]
Link RUN/STOP transfer (ID: 36)
0: Setting update is completed
1: During setting update
1 R/W 1 to 31 10
Bit data
Bit 0: Back-up error
Bit 1: Controller communication error
Bit 2 to Bit 15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 3]
1 RO0 to 31 ⎯
1 R/W
0: Based on the DIP switch setting
1 to 5: 5 words
6 to 200: 6 to 200 words
1 R/W
0: Based on the DIP switch setting
1 to 5: 5 words
6 to 200: 6 to 200 words
: It is possible to set in the communication environment setting by the rotary switch of COM-JH (Refer
to P. 23) or configuration tool (Refer to P. 33).
Continued on the next page.
0
⎯
⎯
0
0
IMR01Y36-E2
73
Page 80
7. COMMUNICATION DATA LIST
Continued from the previous page.
Number
ID
Name
of data
items
242
(0x00F2)
243
RUN/STOP logic
selection
1, 2
Setting validity selection
1
1 R/W
(0x00F3)
244
Unused ⎯ ⎯ ⎯ ⎯
(0x00F4)
245
(0x00F5)
246
(0x00F6)
247
(0x00F7)
248
(0x00F8)
255
Controller address
1, 2
setting
Action mode selection
1, 2,
♦
Automatic acquisition of
controller address
1, 2
Unused ⎯ ⎯ ⎯ ⎯
•
•
•
(0x00FF)
1
Validate only when Explicit message communication is used.
2
The setting is validated when the power is turned off once after the setting is changed and it is turned on again.
Attri-
bute
1 R/W
Data range
0: RUN = 0, STOP = 1
Factory
set value
1: RUN = 1, STOP = 0
Validate to RUN/STOP (ID: 234) and the
4th word and the 5th word in the Polling
I/O communication setting item (OUT).
However, invalidate to the RUN/STOP
transfer (ID: 36) and the ID6 of Z-DIO
module object (0x66: 66Hex).
0: The setting is validated when the
power is turned off once after the
setting is changed and it is turned on
again.
1: The setting is validated just after the
setting is changed.
Object data
• The data of “Controller
communication item setting object
(0xC7)”
• The data of “Number of Polling I/O
communication controllers (ID: 236)”
1 R/W 0 to 32 (0: No communication) 1 to 31
1 R/W
Bit data
Bit 0: Address setting method transfer
0: Continuous setting
1: Free setting
Bit 1: PID/AT transfer Polling I/O
communication
0: Invalidate
1: Validate
Bit 2 to Bit 15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 3]
1 R/W
0: Do not execute the automatic acquisition
1: Execute the automatic acquisition
: It is possible to set in the communication environment setting by the rotary switch of COM-JH (Refer
to P. 23) or configuration tool (Refer to P. 33).
♦ Communication environment setting by rotary switch of COM-JH is possible.
0
0
1
0
74
IMR01Y36-E2
Page 81
7. COMMUNICATION DATA LIST
7.3 Z-TIO Module Extended Object (0x65: 65Hex)
ID
1
(0x0001)
2
(0x0002)
3
(0x0003)
4
(0x0004)
5
(0x0005)
6
(0x0006)
7
(0x0007)
8
(0x0008)
9
(0x0009)
10
(0x000A)
11
(0x000B)
12
(0x000C)
13
(0x000D)
Number
Name
Comprehensive event state 64 ROBit data
Logic output monitor Bit data
Output distribution
selection
Output distribution bias 64 R/W −100.0 to +100.0 % 0.0
Output distribution ratio 64 R/W −9.999 to +9.999 1.000
Minimum ON/OFF time
of proportioning cycle
Area soak time stop
function
EDS mode
(for disturbance 1)
EDS mode
(for disturbance 2)
EDS value 1
(for disturbance 1)
EDS value 1
(for disturbance 2)
EDS value 2
(for disturbance 1)
EDS value 2
(for disturbance 2)
of data
items
Attri-
bute
Bit 0: Event 1 state
Bit 1: Event 2 state
Bit 2: Event 3 state
Bit 3: Event 4 state
Bit 4: Heater break alarm state
Bit 5: Temperature rise completion
Bit 6: Burnout
Bit 7 to Bit 15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 127]
Bit 0: Logic output 1
Bit 1: Logic output 2
Bit 2: Logic output 3
Bit 3: Logic output 4
Bit 4: Logic output 5
Bit 5: Logic output 6
Bit 6: Logic output 7
Bit 7: Logic output 8
Bit 8 to Bit 15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 255]
64 R/W 0: Control output
1: Distribution output
64 R/W 0 to 1000 ms
This item becomes RO (Only reading data is
possible) for the Voltage/Current output
specification.
64 R/W 0: No function
1: Event 1
2: Event 2
3: Event 3
4: Event 4
64 R/W0
64 R/W
64
64
64
64 R/W
0: No function
1: EDS function mode
2: Learning mode
3: Tuning mode
EDS function: External disturbance
−100.0 to +100.0 %
R/W0.0
R/W0.0
R/W0.0
Data range
suppression function
Factory
set value
⎯
⎯
0
0
0
0
0.0
Continued on the next page.
IMR01Y36-E2
75
Page 82
7. COMMUNICATION DATA LIST
Continued from the previous page.
ID
14
(0x000E)
15
(0x000F)
16
(0x0010)
17
(0x0011)
18
(0x0012)
19
(0x0013)
20
(0x0014)
21
(0x0015)
22
(0x0016)
23
(0x0017)
EDS transfer time
(for disturbance 1)
EDS transfer time
(for disturbance 2)
EDS action time
(for disturbance 1)
EDS action time
(for disturbance 2)
EDS action wait time
(for disturbance 1)
EDS action wait time
(for disturbance 2)
EDS value learning times 64 R/W 0 to 10 times (0: No learning mode) 1
EDS start signal 64 R/W
Operation mode 64 R/W
Communication switch for
logic
Name
After ID24 are Engineering setting data. [Writable in the STOP mode]
Number
of data
items
Attri-
bute
64 R/W
Data range
0 to 3600 seconds or
Factory
set value
0.0 to 1999.9 seconds
64 R/W
64 R/W600
64 R/W
1 to 3600 seconds
600
64 R/W 0.0 to 600.0 seconds
64 R/W 0.0
0: EDS start signal OFF
1: EDS start signal ON (for disturbance 1)
2: EDS start signal ON (for disturbance 2)
0: Unused
1: Monitor
2: Monitor + Event function
3: Control
16 R/W Bit data
Bit 0: Communication switch 1
Bit 1: Communication switch 2
Bit 2: Communication switch 3
Bit 3: Communication switch 4
Bit 4 to Bit 15: Unused
0: Remote SV function
1: Cascade control function
2: Ratio setting function
3: Cascade control 2 function
64 R/W
−1
(Master channel is selected from itself)
0 to 99
(Master channel is selected from other
modules)
64 R/W 1 to 99 1
64 R/W −1
(Master channel is selected from itself)
0 to 99
(Master channel is selected from other
modules)
64 R/W 1 to 99 1
64 R/W −1
(Master channel is selected from itself)
0 to 99
(Master channel is selected from other
modules)
64 R/W
1 to 99
Becomes validated when the selected module
is “Z-TIO module.”
Continued on the next page.
1 (1.0)
0
0
−1
−1
−1
1
IMR01Y36-E2
77
Page 84
7. COMMUNICATION DATA LIST
Continued from the previous page.
ID
40
(0x0028)
41
(0x0029)
42
(0x002A)
43
(0x002B)
•
•
•
255
(0x00FF)
Selection switch of
interacting modules
Control RUN/STOP
holding setting
Interval time 16 R/W 0 to 250 ms 10
Unused ⎯ ⎯ ⎯ ⎯
Name
Number
of data
items
64 R/W
16
Attri-
bute
Data range
Bit data
Bit 0: Memory area number
Bit 1: Operation mode
Bit 2: Auto/Manual
Bit 3: Remote/Local
Bit 4: EDS start signal
Bit 5: Interlock release
Bit 6: Suspension of area soak time
Bit 7 to Bit 15: Unused
Data 0: No interaction
1: Interact with other channels
[Decimal number: 0 to 127]
R/W
0: Not holding (STOP start)
1: Holding (RUN/STOP hold)
Factory
set value
0
1
78
IMR01Y36-E2
Page 85
7.4 Z-DIO Module Object (0x66: 66Hex)
ID
1
(0x0001)
2
(0x0002)
3
(0x0003)
4
(0x0004)
5
(0x0005)
6
(0x0006)
7
(0x0007)
8
(0x0008)
9
(0x0009)
10
(0x000A)
Number
Name
Digital input (DI) state 16 ROBit data
Digital output (DO) state 16 ROBit data
Error code
Integrated operating time
monitor
Backup memory state
monitor
RUN/STOP transfer 16 R/W 0: STOP (Control stop)
DO manual output 16 R/W Bit data
DO output distribution
selection
DO output distribution
bias
DO output distribution
ratio
of data
items
128 R/W 0: DO output
128 R/W −100.0 to +100.0 % 0.0
128 R/W −9.999 to +9.999 1.000
Attri-
bute
Bit 0: DI1 state Bit 5: DI6 state
Bit 1: DI2 state Bit 6: DI7 state
Bit 2: DI3 state Bit 7: DI8 state
Bit 3: DI4 state Bit 8 to Bit 15:
Bit 4: DI5 state Unused
Data 0: Contact open
1: Contact closed
[Decimal number: 0 to 255]
Bit 0: DO1 state Bit 5: DO6 state
Bit 1: DO2 state Bit 6: DO7 state
Bit 2: DO3 state Bit 7: DO8 state
Bit 3: DO4 state Bit 8 to Bit 15:
Bit 4: DO5 state Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 255]
16 RO Bit data
Bit 1: Data back-up error
Bit 0, Bit 2 to Bit 15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 2]
16 RO
16 RO
0 to 19999 hours
0: The content of the backup memory
does not coincide with that of the RAM.
1: The content of the backup memory
coincides with that of the RAM.
1: RUN (Control start)
Bit 0: DO1 manual output
Bit 1: DO2 manual output
Bit 2: DO3 manual output
Bit 3: DO4 manual output
Bit 4: DO5 manual output
Bit 5: DO6 manual output
Bit 6: DO7 manual output
Bit 7: DO8 manual output
Bit 8 to Bit 15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 255]
1: Distribution output
7. COMMUNICATION DATA LIST
Data range
Factory
set value
⎯
⎯
⎯
⎯
⎯
0
0
0
IMR01Y36-E2
Continued on the next page.
79
Page 86
7. COMMUNICATION DATA LIST
Continued from the previous page.
ID
11
(0x000B)
12
(0x000C)
13
(0x000D)
14
(0x000E)
15
(0x000F)
16
(0x0010)
17
(0x0011)
18
(0x0012)
19
(0x0013)
20
(0x0014)
21
(0x0015)
22
(0x0016)
23
(0x0017)
24
(0x0018)
25
(0x0019)
26
(0x001A)
27
(0x001B)
•
•
•
255
(0x00FF)
DO proportional cycle
time
DO minimum ON/OFF
time of proportioning cycle
DI function assignment 16
Memory area setting signal 16 R/W 0: Validate
DO signal assignment
module address 1
DO signal assignment
module address 2
DO output assignment 1
[DO1 to DO4]
DO output assignment 2
[DO5 to DO8]
DO
energized/de-energized
DO output distribution
master channel module
address
DO output distribution
master channel selection
DO manipulated output
value (MV) at STOP mode
DO output limiter (high)
DO output limiter (low)
Control RUN/STOP
holding setting
Interval time 16 R/W 0 to 250 ms 10
Unused ⎯ ⎯
Name
After ID13 are engineering setting data. [Writable in the STOP mode]
Number
of data
items
128 R/W 0.1 to 100.0 seconds
Attri-
bute
Data range
set value
Relay contact
output: 20.0
Open collector
output: 2.0
128 R/W 0 to 1000 ms 0
R/W 0 to 29
(Refer to P. 81)
model code.
specifying: 0
1: Invalidate
16 R/W−1
16 R/W
−1, 0 to 99
When “-1” is selected, all of the signals of
the same type (except temperature rise
completion and DO manual output value)
are OR-operated and produced as outputs
from DO.
16 R/W 0 to 13
(Refer to P. 82)
model code.
specifying: 0
16 R/W
0 to 13
(Refer to P. 82)
model code.
specifying: 0
128 R/W
0: Energized
1: De-energized
128 R/W −1
128 R/W
(Master channel is selected from itself)
0 to 99
(Master channel is selected from other modules)
1 to 99
128 R/W −5.0 to +105.0 % −5.0
128 R/W DO output limiter (low) to 105.0 %
128
16 R/W
R/W −5.0 % to DO output limiter (high) −5.0
0: Not holding (STOP start)
1: Holding (RUN/STOP hold)
⎯
Factory
Based on
When not
1
−1
Based on
When not
Based on
When not
0
−1
1
105.0
1
⎯
80
IMR01Y36-E2
Page 87
7. COMMUNICATION DATA LIST
0
assignment
z DI assignment table
Set value DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8
No
1 AUTO/MAN
2 REM/LO C
3 Interlock release EDS start signal 1
4 Soak stop
5 RUN/STOP
6 REM/LO C
7 AUTO/MAN
8 Operat ion mode
9 RUN/STOP
10 ED S start signal 1
11 REM/LOC
12 RUN/STOP
13 Area set 2 Soak stop
14
15 Soak stop
16 ED S start signal 1
17 REM/LOC
18 Interlock releaseAUTO/MAN
19 Soak stop
20
21 Soak stop
22 Soak stop
23 AUTO/MAN REM/LOC
24 RUN/STOP
25
26 Memory area
transfer (1, 2)
27 Memory area transfer (1 to 8) 1 Area set
28 Memory area
transfer (1, 2)
29 EDS start signal 1 EDS start signal 2
RUN/STOP: RUN/ST OP transfer (Contact closed: RUN)
AUTO/MAN: Auto/Manual transfer (Contact closed: Manual mode)
REM/LOC: Remote/Local transfer (Contact closed: Remote mode)
Interlock release (Contact closed: Interlock release)
EDS start signal 1 (Contact closed: EDS start signal ON [for disturbance 1])
EDS start signal 2 (Contact closed: EDS start signal ON [for disturbance 2])
Soak stop (Contact closed: Soak stop)
1
Memory area transfer(×:Contact open −: Contact closed)
Memory area transfer (1 to 8)
2
Interlock releaseRUN/STOP 4 AUTO/MAN 4 REM/LOC 4
Area set
1
2
Area set
1
1
REM/ LOC EDS start signal 1
Interlock releaseRUN/STOP
Memory area number
2
Operation mode
4
AUTO/MAN 4 REM/LOC 4
DI signal will become validate at rising edge after the closed contact is held for 250ms.
Contact closed
Contact open
3
Soak stop
EDS start sig nal 1
4
RUN/STOP
EDS start sig nal 1
EDS start sig nal 1
3
EDS start sig nal 1 EDS start signal 2
250 ms or more
(Rising edge)
4
EDS start signal 1
4
Soak stop
4
Soak stop
Soak stop
Operation mode
Operation mode
RUN/STOP
RUN/STOP 4
3
3
1 2 3 4 5 6 7 8
DI1
DI2
DI3
2
Area set becomes invalidate prior to factory shipment.
3
Operation mode transfer (×:Contact open −: Contact closed)
12 Burnout status (CH1) Burnout status (CH2) Burnout status (CH3) Burnout status (CH4)
13 Temperature rise completion 5 HBA comprehensive output 6 Burnout state comprehensive output 7 DO8 manual output
1
Logical OR of Event 1 (ch1 to ch4)
2
Logical OR of Event 2 (ch1 to ch4)
3
Logical OR of Event 3 (ch1 to ch4)
4
Logical OR of Event 4 (ch1 to ch4)
5
Temperature rise completion status (ON when temperature rise completion occurs for all channels for which event 3 is set to temperature rise completion.)
This chapter describes a usage example of DeviceNet communication when connected with the
COM-JH and controller (SRZ) with the PLC set to a master.
8.1 Handling Procedures
Preparations of
configuration instrument
Mounting and Wiring
Setting of use instruments
Communication items
setting
Programming
To avoid error at operation start-up, COM-JH must be powered on LAST (after the
controller, PLC, etc.).
Refer to 8.2 System Configuration (P. 84).
For mounting/wiring of COM-JH, refer to 3. MOUNTING
(P. 7) and 4. WIRING (P. 11).
• For mounting/wiring of controller, refer to Z-TIO
Instruction Manual (IMS01T01-E).
• For mounting/wiring of PLC, refer to Instruction Manual
for the used PLC.
For network laying requirement of DeviceNet/method, refer
to Instruction Manual of master product or website of ODVA
(Open DeviceNet Vender Association).
URL: http://www.odva.org
Refer to 5. SETTING (P. 20) and 8.3 Setting of Use Instruments (P. 85).
Refer to 6. DeviceNet COMMUNICATIONS (P. 26) and
the Instruction Manual of Configuration Tool.
Refer to 8.4 Sample Programs (P. 86) and PLC Instruction
Manual.
IMR01Y36-E2 83
Page 90
8. USAGE EXAMPLE
8.2 System Configuration
OMRON
SYSMAC CJ series
PLC (Master)
Node address: 0
DeviceNet communication
speed: 125 kbps
Unit number: 0
Personal computer
DeviceNet
Controller (SRZ)
Z-TIO-A module: 4-channnel type)
(
COM-JH (Slave)
Node address: 1
DeviceNet communication speed:
125 kbps
Number of communication data items:
13 words
Controller communication speed:
19200 bps
(Factory set value)
• Communication speed: 19200 bps (factory set value)
.
• Data bit configuration: Data 8-bit, without parity, stop 1-bit
For setting procedure, refer to Z-TIO Host Communication Quick Instruction Manual (IMS01T02-E).
IMR01Y36-E2
85
Page 92
8. USAGE EXAMPLE
8.4 Sample Programs
8.4.1 Polling I/O communication (When the SYSMAC CJ)
Polling I/O communication is called “Remote I/O communication” in OMRON PLC related
instruction manuals.
Communication requirement
Contents of communication parameter setting
Communication data items: Measured data item (IN): Measured value (PV) [Attribute ID: 1]
Set data item (OUT): Set value (SV) [Attribute ID: 45]
Number of communication controllers: 2 modules
Number of communication data items: 13 words
Controller address: 1, 2 (Factory set value: 1 to 31)
Module address 1 and Module address 2
Action mode: 1 (Factory set value)
Address setting method: Free setting
PID/AT transfer Polling I/O communication: Invalidate
Automatic acquisition of controller address:
0 (Factory set value)
Do not execute the Automatic acquisition
The above communication parameters can be set via Explicit message communication or by the
configuration tool *.
For details, refer to Communication parameter setting by configuration tool (P. 33), or
Communication parameter setting by Explicit message communication (P. 43).
*
Except the setting of the Action mode.
Memory allocation
Allocate the memory by using the configuration tool.
Allocation method: User-set
Data area: Measured data item (IN) area: D00000 to D00012 (13 words)
Setting data item (OUT) area: D10000 to D10012 (13 words)
86
IMR01Y36-E2
Page 93
8. USAGE EXAMPLE
Data which a master receives [Response: measured data items (IN)]
No. Items Storage location of read data
1 Receive counter D00000
2 Alarm state (Controller 1 to 16) D00001
3 Alarm state (Controller 17 to 31, Setting update flag) D00002
4 RUN/STOP state (Controller 1 to 16) D00003
5 RUN/STOP state (Controller 17 to 31) D00004
6 Measured value (PV) [CH1 of controller 1] D00005
7 Measured value (PV) [CH2 of controller 1] D00006
8 Measured value (PV) [CH3 of controller 1] D00007
9 Measured value (PV) [CH4 of controller 1] D00008
10 Measured value (PV) [CH1 of controller 2] D00009
11 Measured value (PV) [CH2 of controller 2] D00010
12 Measured value (PV) [CH3 of controller 2] D00011
13 Measured value (PV) [CH4 of controller 2] D00012
Communication data Nos. 1 to 5 (corresponding to 5 words) are fixed communication data items.
Data to send from a master [Request: setting data items (OUT)]
No.
1 Setting state selection
Items Data contents
0
(All controller)
2 Setting state selection
(Controller 1 to 16)
As there are two controllers, only
Bit 0 (controller 1) and Bit 1
(controller 2) can be used.
0000000000000000
Bit 1 Bit 0
[Decimal number: 0 to 3]
Storage location
of write data
D10000
D10001
3 Setting state selection
IMR01Y36-E2
(Controller 17 to 31,
RUN/STOP)
Only Bit 15 (RUN/STOP transfer
disabled/enabled) can be used.
0000000000000000
Bit 15
[Decimal number: 0 to 32768]
Continued on the next page.
D10002
87
Page 94
8. USAGE EXAMPLE
Continued from the previous page.
No.
Items Data contents
4 RUN/STOP transfer
(Controller 1 to 16)
5 RUN/STOP transfer
(Controller 17 to 31)
Set value (SV)
6
[CH1 of controller 1]
Set value (SV)
7
[CH2 of controller 1]
Set value (SV)
8
[CH3 of controller 1]
Set value (SV)
9
[CH4 of controller 1]
Storage location
of write data
As there are two controllers, only
D10003
Bit 0 (controller 1) and Bit 1
(controller 2) can be used.
0000000000000000
Bit 1 Bit 0
[Decimal number: 0 to 3]
0 D10004
100 D10005
120 D10006
150 D00007
150 D00008
Set value (SV)
10
[CH1 of controller 2]
Set value (SV)
11
180 D00009
180 D00010
[CH2 of controller 2]
Set value (SV)
12
[CH3 of controller 2]
Set value (SV)
13
200 D00011
250 D00012
[CH4 of controller 2]
Communication data Nos. 1 to 5 (corresponding to 5 words) are fixed communication data
items.
88
IMR01Y36-E2
Page 95
8. USAGE EXAMPLE
•
•
Sample program (ladder)
Measured data items (IN)
Data corresponding to the Measured data item (IN) ca be checked only by reading the data storage
register assigned by the configuration tool.
Setting data items (OUT)
The following procedure is required for setting data to the controller.
1. Sets 100 to CH1 “Set value (SV): D10005” of Controller 1.
•
•
•
Sets 250 to CH4 “Set value (SV): D10006” of Controller 2.
2. Set Bit 0 (Controller 1) and Bit 1 (Controller 2) for “Setting state selection: D10001” to
“1: Setting enabled.”
3. Set Bit 0 (Controller 1) and Bit 1 (Controller 2) for “Setting state selection: D10001” to
“0: Setting disabled” after a lapse of preset time* (Example: 200 ms).
* Sets any time longer than the “communication cycle time” set to the PLC.
4. Sets 0 (reset) to CH1 “Set value (SV): D10005” of Controller 1.
•
•
•
Sets 0 (reset) to CH4 “Set value (SV): D10012” of Controller 2.
1.00
T0000
1.00
1.01
MOV
&100
D10005
•
MOV
&250
D10012
1.00 1.00
TIMH
0000
#20
MOV
#3
D10001
DIFD
1.01
MOV
#0
D10001
MOV
#0
D10005
•
MOV
#0
D10012
Sets 100 to D10005 when
relay 1.00 is turned ON.
•
•
•
Sets 250 to D10012 when
relay 1.00 is turned ON.
Activate timer T0000 by setting
to 200 ms when relay 1.00 is
turned ON.
Sets 0003H (Bit 0: 1, Bit 1: 1)
to D10001 when relay 1.00 is
turned ON.
Differentiating the fall signal of the
relay1.00 activates the relay 1.01.
Sets 0000H (Bit 0: 0, Bit 1: 0) to
D10001 when relay 1.01 is turned ON
Sets 0 (data reset) to D10005 when
relay 1.01 is turned ON.
Sets 0 (data reset) to D10012 when
relay 1.01 is turned ON.
•
•
•
IMR01Y36-E2
89
Page 96
8. USAGE EXAMPLE
8.4.2 Explicit message communication (When the SYSMAC CJ)
In order to conduct Explicit message communication using the OMRON SYSMAC CJ PLC,
the FINS command for FINS communication (communication protocol developed by
OMRON) is used.
For the FINS command and the CMND instruction, refer to the Instruction Manual of
OMRON SYSMAC CJ PLC.
Communication requirement
The vendor code is read from the COM-JH (slave). (RKC vendor code: 394 = 018AH)
• Using the “Explicit message send” command (2801) of FINS command.
• The “CMND instruction” is used to send FINS commands.
• Write location of request data from the PLC (master): On and after D01000
• Storage location of response data from the COM-JH (slave): On and after D02000
• The completion code is stored in D00006 when execution of CMND has been completed abnormally
and then the command is executed again.
• When an Explicit message is sent by the SYSMAC CJ, the send location of the FINS command is
assigned to the DeviceNet master unit of its own node instead of the actual send location (COM-JH).
The COM-JH node address is specified within Explicit message send command data.
SYSMAC CJ
FINS command
Explicit
message
COM-JH
CPU unit
CMND
Node address: 11
DeviceNet master unit
Unit No.: 0
Node address: 05
Unit address: FEH or 10H
90
IMR01Y36-E2
Page 97
8. USAGE EXAMPLE
Command data format
Command data format at communicating by an Explicit message with SYSMAC CJ is shown with the
following.
[Request data format from the PLC (master)]
28 01
534 bytes
max.
Command
code
Destination node address
Object
class ID
Service code
Instance ID
Service data
[Response data format]
• Normal response
28 01 00 00
534 bytes
max.
Command
code
Response
code
No. of bytes
received
Service code
Source node address
Service data
• Error response
28 01 00 00 94
Command
code
Response
code
No. of bytes
received
Source node address
Service code (94H): 14H + 80H = 94H
Error code
• Cannot be sent/Timeout
14H: Error response
80H: Response data
28 01
Command
code
As this response (Cannot be sent/Timeout) is an error response sent to the CPU unit from
the DeviceNet master unit of the SYSMAC CJ, this is not an error in DeviceNet
communication.
IMR01Y36-E2
Response
code
91
Page 98
8. USAGE EXAMPLE
Description of CMND
[CMND S D C]
CMND
S
D
C
S: First command word
D: First response word
C: First control data word
Command data is set in order starting with the word specified for the CMND operand S (first
command word) and continuing with words with higher addresses in I/O memory in the command
block format.
15 0
C+0
15 0
C+1
15 0
C+2
0 0
Number of command bytes to send
0000H to 02E1H (0 to 542 bytes)
Number of response data bytes to receive
0000H to 02E1H (0 to 542 bytes)
15 0
C+3
Destination network address
00H: Local network
01H to 7FH: 1 to 127
Destination node address
00 to 3FH: 0 to 63
Destination unit FINS address
FEH: The local unit
10H to 1FH: Unit numbers + 10H
15 10 8 3 0
0 0 0 0 0
C+4
0: Response returned
1: No response
Transmission port number: 0 to 7
Number of retries: 0H to FH (0 to 15 times)
15 0
C+5
Response monitoring time
0000H: 2 seconds
0001H to FFFFH: 0.1 to 6553.5 seconds
92
IMR01Y36-E2
Page 99
[Sample program]
S D01000+ 0 2801H Command code (2801H)
+ 1 0B0EH Slave node address: 11 (0BH), Service code (0EH)
+ 2 0001H Object class ID (0001H)
+ 3 0001H Instance ID (0001H)
+ 4 0100H Attribute ID (01H)
D D02000 First response word at local node
C D00000+ 0 0009H Number of command bytes (9 bytes)