CC-Link is a registered trademark of Mitsubishi Electric Co. Ltd.
Modbus is a registered trademark of Schneider Electric.
The name of each programmable controller (PLC) means the products of each manufacturer.
Company names and product names used in this manual are the trademarks or registered trademarks of
the respective companies.
All Rights Reserved, Copyright 2005, RKC INSTRUMENT INC.
Page 3
t
Thank you for purchasing this RKC instrument. In order to achieve maximum performance and ensure
proper operation of your new instrument, carefully read all the instructions in this manual. Please
place this manual in a convenient location for easy reference.
SYMBOLS
WARNING
CAUTION
!
An external protection device must be installed if failure of this instrument
could result in damage to the instrument, equipment or injury to personnel.
: This mark indicates precautions that must be taken if there is danger of electric
shock, fire, etc., which could result in loss of life or injury.
: This mark indicates that if these precautions and operating procedures are no
taken, damage to the instrument may result.
: This mark indicates that all precautions should be taken for safe usage.
: This mark indicates important information on installation, handling and operating
procedures.
: This mark indicates supplemental information on installation, handling and
operating procedures.
: This mark indicates where additional information may be located.
WARNING
!
All wiring must be completed before power is turned on to prevent electric
shock, fire or damage to instrument and equipment.
This instrument must be used in accordance with the specifications to
prevent fire or damage to instrument and equipment.
This instrument is not intended for use in locations subject to flammable or
explosive gases.
Do not touch high-voltage connections such as power supply terminals, etc.
to avoid electric shock.
RKC is not responsible if this instrument is repaired, modified or
disassembled by other than factory-approved personnel. Malfunction can
occur and warranty is void under these conditions.
IMS01Y06-E3
i-1
Page 4
CAUTION
This is a Class A instrument. In a domestic environment, this instrument may cause radio
interference, in which case the user may be required to take adequate measures.
This instrument is protected from electric shock by reinforced insulation. Provide
reinforced insulation between the wire for the input signal and the wires for instrument
power supply, source of power and loads.
Be sure to provide an appropriate surge control circuit respectively for the following:
- If input/output or signal lines within the building are longer than 30 meters.
- If input/output or signal lines leave the building, regardless the length.
This instrument is designed for installation in an enclosed instrumentation panel. All
high-voltage connections such as power supply terminals must be enclosed in the
instrumentation panel to avoid electric shock by operating personnel.
All precautions described in this manual should be taken to avoid damage to the
instrument or equipment.
All wiring must be in accordance with local codes and regulations.
All wiring must be completed before power is turned on to prevent electric shock,
instrument failure, or incorrect action.
The power must be turned off before repairing work for input break and output failure
including replacement of sensor, contactor or SSR, and all wiring must be completed
before power is turned on again.
To prevent instrument damage or failure, protect the power line and the input/output lines
from high currents with a protection device such as fuse, circuit breaker, etc.
Prevent metal fragments or lead wire scraps from falling inside instrument case to avoid
electric shock, fire or malfunction.
Tighten each terminal screw to the specified torque found in the manual to avoid electric
shock, fire or malfunction.
For proper operation of this instrument, provide adequate ventilation for heat dispensation.
Do not connect wires to unused terminals as this will interfere with proper operation of the
instrument.
Turn off the power supply before cleaning the instrument.
Do not use a volatile solvent such as paint thinner to clean the instrument. Deformation or
discoloration will occur. Use a soft, dry cloth to remove stains from the instrument.
To avoid damage to instrument display, do not rub with an abrasive material or push front
panel with a hard object.
Do not connect modular connectors to telephone line.
NOTICE
This manual assumes that the reader has a fundamental knowledge of the principles of electricity,
process control, computer technology and communications.
The figures, diagrams and numeric values used in this manual are only for purpose of illustration.
RKC is not responsible for any damage or injury that is caused as a result of using this instrument,
instrument failure or indirect damage.
RKC is not responsible for any damage and/or injury resulting from the use of instruments made by
imitating this instrument.
Periodic maintenance is required for safe and proper operation of this instrument. Some
components have a limited service life, or characteristics that change over time.
Every effort has been made to ensure accuracy of all information contained herein. RKC makes no
warranty expressed or implied, with respect to the accuracy of the information. The information in
this manual is subject to change without prior notice.
No portion of this document may be reprinted, modified, copied, transmitted, digitized, stored,
processed or retrieved through any mechanical, electronic, optical or other means without prior
written approval from RKC.
This manual describes the communication specifications, mounting, wiring, setting and data
instructions for the CC-Link Communication Converter COM-JC.
CC-Link Communication Converter COM-JC (hereafter called COM-JC) is communication converter
to connect the RKC temperature controller (FB400/FB900) to a programmable controller (Mitsubishi
Electric PLC MELSEC series: hereafter called PLC) for CC-Link.
In addition, COM-JC is connected to CC-Link as the remote device station.
Mitsubishi Electric PLC
MELSEC series (Master station)
CC-Link
CC-Link
communication
converter
COM-JC (slave)
Controller communication (RS-485: Modbus)
1
Power supply (24 V DC)
Remote device station
231
FB400 or FB900
(Up to 31 controllers)
Slave station
For CC-Link, see the website of CC-Link Partner Association.
URL: http://www.cc-link.org/
Remote I/O Local station
IMR01Y06-E3 1
Page 8
1. OUTLINE
1.1 Product Check
Before using this product, check each of the following.
Model code
Check that there are no scratch or breakage in external appearance (case, front panel, terminal, etc).
Check that all of the accessories delivered are complete. (See below)
AccessoriesQ’TYRemarks
Installation Manual (IMR01Y01-E)
Quick Instruction Manual (IMR01Y11-E)
Communication Data List (IMR01Y16-E)
Instruction Manual (IMR01Y06-E3)
1
1
1
1
Enclosed with instrument
Enclosed with instrument
Enclosed with instrument
This manual (sold separately)
If any of the products are missing, damaged, or if your manual is incomplete, please contact
RKC sales office or the agent.
1.2 Model Code
Check whether the delivered product is as specified by referring to the following model code list. If
the product is not identical to the specifications, please contact RKC sales office or the agent.
(1) Corresponding to the RKC controller
COM- JC ∗ 01-
(1) (2)
01: FB400/FB900
(2) RUN/STOP logic selection
1: 0: RUN
1: STOP
2: 0: STOP
1: RUN
2
IMR01Y06-E3
Page 9
r
r
1.3 Parts Description
1. OUTLINE
Terminal cove
Indication
lamps
Station number
setting switch
CC-Link
connection
terminals
(COM.PORT)
Terminal cove
Mounting
bracket
Front view
Indication lamps
FAIL [Red]
• When instrument abnormally: ON
• CC-Link setting error: ON
• CC-Link operation error: Flashes slowly
• CC-Link setting is changed: Flashes rapidly
RUN [Green]
• When normally: ON
• Operation error: Flashes slowly
• During controller communication initialization: Flashes rapidly
SD [Green]
RD [Green]
During CC-Link data send: ON
During CC-Link data receive: ON
CC-Link connection terminals
COM. PORT
Terminals for PLC (Master) connection
Switches
Station number setting switch
CC-Link communication
Set the station number for CC-Link
Set the communication speed for CC-Link
peed setting switch
Dip switch
• Set the number of occupied station/extension cyclic for CC-Link
• Set the communication speed for controller communication
Other
Terminal cover
Mounting bracket
Terminal cover above and below the COM-JC
• Used for the DIN rail mounting
• When panel mounted, two mounting brackets are required for the upper
Terminal base
Part of the terminal and base of COM-JC
(There is the termination resistor setting switch in the inside of
terminal base)
Mainframe
Part of the mainframe of COM-JC
Terminal base
Mainframe
Dip switch
[Details of
RUN
FAIL
CC-Link communication
speed setting switch
Left side view
Indication lamps
RD
SD
and lower sides (one required for the upper side: separately sold).
]
IMR01Y06-E3
3
Page 10
2. HANDLING PROCEDURES
Conduct the setting necessary for performing communication in accordance with the following
procedure.
COM-JC setting
Set the CC-Link station number, communication speed and
occupied station/extended cyclic of COM-JC and controller
communication speed.
See 5. SETTING (P. 16)
Mounting
Install the COM-JC.
•
See 3. MOUNTING (P. 5)
•
For controller, see FB400/FB900 Installation Manual
(IMR01W01-E)
Wiring and
connection
PLC and Controller
settings
Connect power supply wires to the COM-JC, and also connect
the COM-JC to the controller and the COM-JC to the PLC,
respectively.
•
See 4. WIRING (P. 8)
•
For controller, see FB400/FB900 Installation Manual
(IMR01W01-E)
Set the PLC and controller.
• See 8.3 Use Instruments Setting (P. 78)
•
For controller,see FB400/FB900 Communication
Quick Manual (IMR01W07-E)
Device assignment
Do assignments of remote input/output and remote register.
See 8.4 Device Assignments Example (P.80)
Program creation
Create the sequence program of PLC.
See 8.5 Sample Program (P.83)
4 IMR01Y06-E3
Page 11
3. MOUNTING
This chapter describes installation environment, mounting cautions, dimensions and mounting
procedures.
To prevent electric shock or instrument failure, always turn off the power before
mounting or removing the instrument.
WARNING
!
3.1 Mounting Cautions
(1) This instrument is intended to be used under the following environmental conditions. (IEC61010-1)
[OVERVOLTAGE CATEGORY II, POLLUTION DEGREE 2]
(2) Use this instrument within the following environment conditions.
• Allowable ambient temperature: −10 to +50 °C
• Allowable ambient humidity: 5 to 95 % RH
(Absolute humidity: MAX.W.C 29.3 g/m
3
dry air at 101.3 kPa)
• Installation environment conditions: Indoor use
Altitude up to 2000 m
(3) Avoid the following conditions when selecting the mounting location.
• Rapid changes in ambient temperature which may cause condensation.
• Corrosive or inflammable gases.
• Direct vibration or shock to the mainframe.
• Water, oil, chemicals, vapor or steam splashes.
• Excessive dust, salt or iron particles.
• Excessive induction noise, static electricity, magnetic fields or noise.
• Direct air flow from an air conditioner.
• Exposure to direct sunlight.
• Excessive heat accumulation.
(4) Take the following points into consideration when mounting this instrument.
• Ensure at least 50 mm space on top and bottom of the instrument for maintenance and
environmental reasons.
• Do not mount this instrument directly above equipment that generates large amount of heat
(heaters, transformers, semi-conductor functional devices, large-wattage resistors).
• If the ambient temperature rises above 50 °C, cool this instrument with a forced air fan, cooler,
or the like. However, do not allow cooled air to blow this instrument directly.
• In order to improve safety and the immunity to withstand noise, mount this instrument as far
away as possible from high voltage equipment, power lines, and rotating machinery.
High voltage equipment: Do not mount within the same panel.
Power lines: Separate at least 200 mm.
Rotating machinery: Separate as far as possible.
IMR01Y06-E35
Page 12
3. MOUNTING
t
3.2 Dimensions
109.53
125
5
3.3 DIN Rail Mounting
9.5
78
(Unit: mm)
30
Mounting procedures
1. Pull down the mounting bracket at the bottom of the instrument (A). Attach the hooks on the top
of the instrument to the DIN rail and push the lower section into place on the DIN rail (B).
2. Slide the mounting bracket up to secure the instrument to the DIN rail (C).
DIN rail
(B) Push
Mounting
bracke
(A) Pull down
(C) Locked
6
IMR01Y06-E3
Page 13
Removing procedures
1. Turn the power OFF.
2. Remove the wiring.
3. Pull down a mounting bracket with
a blade screwdriver (A). Lift the
instrument from bottom, and take it
off (B).
3. MOUNTING
(B) Lift and take
off
(A) Pull down
3.4 Panel Mounting
Mounting procedures
1. Pull down the mounting bracket (A) until locked and that a mounting hole appears.
2. Prepare one mounting bracket per instrument (B) sold separately (KSRX-55) and then insert it in
the rear of the terminal board at top of the instrument until locked but a mounting hole does not
disappear.
3. Mount each module directly on the panel with screws which are inserted in the mounting holes of
the top and bottom mounting brackets.
Recommended tightening torque: 0.3 N⋅m (3 kgf⋅cm)
The customer needs to provide the M3 size screws. Select the screw length that matches the
mounting panel.
(B) Insert
Mounting dimensions
Mounting
holes
(Unit: mm)
IMR01Y06-E3
Mounting bracket
(Sold separately)
(KSRX-55)
(A) Pull down
0.2
±
130.5
M3
7
Page 14
4. WIRING
This chapter describes wiring cautions, terminal configuration and connections.
4.1 Wiring Cautions
To prevent electric shock or instrument failure, do not turn on the power until
all the wiring is completed.
To prevent electric shock or instrument failure, turn off the power before
connecting or disconnecting the instrument and peripheral equipment.
• To avoid noise induction, keep communication signal wire away from instrument power line, load
lines and power lines of other electric equipment.
• If there is electrical noise in the vicinity of the instrument that could affect operation, use a noise filter.
− Shorten the distance between the twisted power supply wire pitches to achieve the most effective
noise reduction.
− Always install the noise filter on a grounded panel. Minimize the wiring distance between the
noise filter output and the instrument power supply terminals to achieve the most effective noise
reduction.
− Do not connect fuses or switches to the noise filter output wiring as this will reduce the
effectiveness of the noise filter.
• Power supply wiring must be twisted and have a low voltage drop.
• For an instrument with 24 V power supply, supply power from a SELV circuit.
• A suitable power supply should be considered in the end-use equipment. The power supply must be
in compliance with a limited-energy circuits (maximum available current of 8 A).
WARNING
!
• Use the solderless terminal appropriate to the screw size (M3).
5.9 mm or less
3.2 mm or more
Recommended tightening torque:
0.4 N⋅m (4 kgf⋅cm)
8 IMR01Y06-E3
Page 15
4.2 Terminal Configuration
The terminal layout is as follows.
Upper-side
terminal
3
7 6 54
21
Controller
communication
RS-485
T/R(A)
1
T/R(B)
5
SG
4
4. WIRING
: The part of internal wiring
Power supply
11 1098
Ground
141312
9
8
12
DC
−
+
24 V
Lower-side
terminal
FG
As controller communication terminal Nos. 1, 4 and 5 are internally connected to terminal Nos. 3,
6 and 7, any terminals can be used.
As ground and power supply terminal Nos. 8, 9 and 12 are internally connected to terminal Nos.
10, 11 and 14, any terminals can be used.
Terminal No. 2 and No. 13 is not used.
IMR01Y06-E3
9
Page 16
4. WIRING
4.3 Connection to PLC
Connection method
The PLC (Master station) and COM-JC make multi-drop connection in CC-Link dedicated cable Ver. 1.10.
Termination
PLC
resistor
Master station
COM-JC
Termination
resistor
CC-Link dedicated cable
Ver. 1.10
Station to station cable length: 20 cm or more
Up to 61 stations
Communication speed and maximum transmitter distance
(Use the CC-Link dedicated cable Ver. 1.10)
Communication
speed
Station to station
cable length
Maximum transmitter distance
(maximum length of network)
10 Mbps 100 m
5 Mbps 160 m
2.5 Mbps 400 m
20 cm or more
625 kbps 900 m
156 kbps
1200 m
10
IMR01Y06-E3
Page 17
A
Terminal numbers and signal details
Terminal No. Signal name SymbolCable color
CC-Link connection terminals
Terminal screws
Screws size: M3
Recommended tightening torque: 0.4 N⋅m
1 Data A DA Blue
2 Data B DB White
3 Data ground DG Yellow
4 Shield SLD Grounding wire (Shield)
5 Frame ground FG
4. WIRING
1: D
2: DB
3: DG
4: SLD
5: FG
The CC-Link connecting terminal cannot do on-line installation or dismount for terminal
block of dismount impossibility. This instrument exchanges all the links after being downed.
In addition, FG (flame ground) terminal of terminal number 5 is FG in a CC-Link function,
and it is not FG of instrument all.
Ground both ends of the shield wire on the twisted pair cable via the SLD or FG
terminal of each module. In addition, the SLD terminal is internally connected with the
FG terminal.
Do not ground the instrument together with other equipment.
In addition, use grounding wires with across section of 2.0 mm
resistance: 100 ohm or less)
2
or more. (Ground
For cable specifications, connection method and vendor, see the website of CC-Link Partner
Association.
URL: http://www.cc-link.org/
IMR01Y06-E3
11
Page 18
4. WIRING
Connection diagram
Always connect a termination resistor between the DA and DB terminals of the module to
be located at the far end.
Termination resistor: 110 Ω± 5 % 1/2 W
Master station
COM-JC
COM-JC
TR
DA
DB
DG
SLD
FG
CC-Link dedicated
cable Ver. 1.10
DA
DB
DG
SLD
FG
CC-Link dedicated
cable Ver. 1.10
DA
DB
TR
DG
SLD
FG
TR: Termination resistor
The CC-Link dedicated cable Ver. 1.10 is provided by the customer.
12
IMR01Y06-E3
Page 19
4.4 Connection to Controller
Conduct wiring between the COM-JC and controller (FB400/FB900) as shown in the following.
When conducting wiring to the FB400/FB900, always conduct wiring to the
Communication 1 terminal.
FB400/FB900 communication terminal number and signal details
Terminal No. Signal name Symbol
25 Signal ground SG
26 Send/receive data T/R (A)
27 Send/receive data T/R (B)
Wiring
COM-JC
SG
RS-485
4
Paired wire
Controller
25
SG
4. WIRING
T/R (A)
1
T/R (B)
*R
Terminal block
5
Shielded twisted
pair wire
T/R (A)
26
T/R (B)
27
Communication terminals
(communication 1 side)
Controller
SG
25
T/R (A)
26
T/R (B)
*R: Termination resistors (Example: 120 Ω 1/2 W)
Maximum controller connections: 31 controllers
27
*R
Communication terminals
(communication 1 side)
The cable is provided by the customer.
The termination resistor existing within the COM-JC can be connected or disconnected by
the switch. (Factory set value: Termination resistor connected)
[See 4.5 Installation of Termination Resistor (P. 14)]
IMR01Y06-E3
13
Page 20
4. WIRING
4.5 Installation of Termination Resistor
Procedure for setting a termination resistor to controller communication (RS-485) and its setting
position are described in the following.
Termination resistor setting position
If the COM-JC is connected to the extreme end of the communication line, install one termination
resistor each to the COM-JC and the controller located most distantly from the COM-JC.
Termination
resistor ON
(Factory
set value)
Controller communication (RS-485: Modbus)
COM-JC
FB400
or
FB900
FB400
or
FB900
1
2
FB400
or
FB900
31
Connect a termination
resistor to the terminals
from exterior.
Setting procedure of termination resistor (COM-JC)
As the COM-JC is internally provided with a selector switch for choosing the ON/OFF of a
termination resistor, it is not required to externally install the termination resistor.
(Factory set value: Termination resistor connected)
1. Turn off the power supply of the COM-JC.
Do not separate the mainframe from terminal base with the power turned on. If so,
instrument failure may result.
2. Pull out the mainframe itself toward you while pushing the locks at its top and bottom (1), and
then separate it from the terminal base (2).
Upper-side
lock
Top view
Terminal base
Mainframe
(1) Push
(2) Pull out
14
Lower-side
lock
Bottom view
(1) Push
Removing the module mainframe
IMR01Y06-E3
Page 21
3. Turn on the termination resistor transfer switch in the terminal base.
The COM-JC is shipped from the factory with the selector switch set to “ON: Termination
resistor connected.”
ON
OFF
Termination resistor
transfer switch
4. WIRING
Termination
resistor
OFF
Factory set value
Termination
resistor
(120 Ω 1/2 W)
ON
: ON
A terminal base of the state which removed module mainframe
4. Push the mainframe thus separated in the terminal base until firmly locked.
Terminal base
Push the module
mainframe until
firmly locked
Mainframe
IMR01Y06-E3
Mounting the module mainframe
15
Page 22
w
5. SETTING
To prevent electric shock or instrument failure, always turn off the power
before setting the switch.
WARNING
!
To prevent electric shock or instrument failure, never touch any section other
than those instructed in this manual.
CAUTION
Do not separate the mainframe from the terminal base with the power turned on.
If so, instrument failure may result.
5.1 Station Number Setting
Set the station number of CC-Link. For this setting, use a small blade screwdriver.
When set to any value out of the setting range, the COM-JC becomes the FAIL state.
1 to 64 (1 station occupied 1 time)
Factory set value: 0
Station number
setting switch
16 IMR01Y06-E3
Page 23
5.2 Communication Speed Setting
The rotary switch at the left side of the mainframe sets the communication speed of the CC-Link.
For this setting, use a small blade screwdriver.
When set to any value out of the setting range, the COM-JC becomes the FAIL state.
Communication speed
setting switch
5. SETTING
Setting range: 0 to 4
Factory set value: 0 (156 kbps)
Left side view
Communication speed and maximum transmitter distance
(Use the CC-Link dedicated cable Ver. 1.10)
Communication
speed setting
Communication
speed
Maximum transmitter distance
(maximum length of network)
0 156 kbps 1200 m
1 625 kbps 900 m
2 2.5 Mbps 400 m
3 5 Mbps 160 m
4 10 Mbps 100 m
IMR01Y06-E3 17
Page 24
5. SETTING
ON O
5.3 Occupied Station/Extended Cyclic and Controller
Communication Speed Setting
The Dip switch at the left side of the mainframe sets the occupied station/extended cyclic and
controller communication speed.
Dip switch
ON
FF
Left side view
12345678
12345678
1 2 Controller communication speed
OFF OFF
ON OFF
OFF ON
ON ON
38400 bps
9600 bps
19200 bps
38400 bps
Factory set value: 19200 bps
3 4 5 Number of occupied stations/extended cyclic
OFF
ON
OFFOFF
OFFOFF
4 stations occupied 1 time (8 controllers assignment)
4 stations occupied 1 time (16 controllers assignment)
OFF
ON
ON ON
OFF OFF
ON
Factory set value: 4 stations occupied 1 time (8 controllers assignment)
OFF
OFF
OFF
4 stations occupied 2 times (16 controllers assignment)
4 stations occupied 2 times (31 controllers assignment)
ON 1 station occupied 1 time (1 controller assignment)
ON 1 station occupied 1 time (2 controllers assignment)
6 7 8
OFF OFF OFF
Fixed
18
IMR01Y06-E3
Page 25
A
A
A
A
6. CC-Link COMMUNICATION
6.1 Communication Between Master Station and COM-JC
(Remote Device Station)
The COM-JC which is a remote device station can process remote input (RX), remote output (RY) and
remote registers (RWw and RWr).
Outline of communication between master station and COM-JC (remote device station)
COM- JC
CPU of PLC
Network
parameters
Automatic refresh
parameters
X
(1)
(3)
utomatic refresh
Master station
Network
parameters
Buffer memory
Remote input
(RX)
(2)
Link scan
(Remote device station)
Remote input
(RX)
[Event state, etc. ]
(4)
Y
W
utomatic refresh
(6)
utomatic refresh
W
utomatic refresh
Remote output
register (RWw)
register (RWr)
(RY)
Remote
Remote
(5)
Link scan
(7)
Link scan
(8)(9)
Link scan
(1) When the PLC system is powered on, the network parameters in the
PLC CPU are transferred to the master station, and the CC-Link
system automatically starts up.
(2) The remote input RX of a COM-JC (remote device station) is stored
automatically (for each link scan) in the master station’s “remote
input RX” buffer memory.
(3) The input status stored in the “remote input RX” buffer memory is
stored in the CPU device set with the automatic refresh parameters.
(4) The on/off data of the CPU device set with the automatic refresh
parameters is stored in the “remote output RY” buffer memory.
(5) Remote output RY is automatically set to on/off (for each link scan)
according to the output status stored in the “remote output RY”
buffer memory.
Remote output
(RY)
Remote
register (RWw)
Remote
register (RWr)
[Data link startup]
[Remote input]
[Remote output]
[RUN/STOP
transfer, extension
No. setting, etc.]
[Set value (SV)]
[Measured value
(PV)]
IMR01Y06-E3 19
Page 26
6. CC-Link COMMUNICATION
(6) The transmission data of the CPU device set with the automatic
refresh parameters is stored in the “remote register RWw” buffer
memory.
(7) The data stored in the “remote register RWw” buffer memory is
automatically sent to the remote register RWw of COM-JC (remote
device station).
(8) The remote register RWr data of a COM-JC (remote device station)
is automatically stored in the “remote register RWr” buffer memory
of the master station.
(9) The remote register RWr data of a COM-JC (remote device station)
stored in the “remote register RWr” buffer memory is stored in the
CPU device set with the automatic refresh parameters.
With the master station (PLC) set to the STOP state, neither the remote output (RY) nor data
write to the remote register (RWw) is reflected to the COM-JC.
For details of the communication, see the Instruction manual for PLC.
[Writing to the remote
register RWw]
[Reading from the remote
register (RWr)]
20
IMR01Y06-E3
Page 27
6. CC-Link COMMUNICATION
6.2 CC-Link Flag Operation
Remote input/output and remote register flag operations are as follows.
[Example] When the occupied station/extended cyclic of COM-JC is set to 1 station occupied 1 time.
Initialize request processing at power on
Initialize processing request from remote device station (COM-JC)
If the COM-JC is initialized at power on, the initialize data processing request flag [RX(n+1)8] is
turned on. Thus, turn on the initialize data processing completion flag [RY(n+1)8].
When COM-JC becomes a ready state, a remote ready [RX(n+1)B] is turned on.
Initialize data processing
ON
request flag [RX(n+1)8]
OFF
ON
Initialize data processing
completion flag [RY(n+1)8]]
OFF
ON
Remote ready [RX(n+1)B]
OFF
Initialize processing request from master station (PLC)
This is an COM-JC initialize setting request. As there is no initialize data specifically, no processing is
required.
Initialize data setting
request flag [RY(n+1)9]
Initialize data setting
completion flag [RX(n+1)9]
Remote ready [RX(n+1)B]
ON
OFF
ON
OFF
ON
OFF
IMR01Y06-E3
21
Page 28
6. CC-Link COMMUNICATION
Error flag/error reset processing
When the error status flag [RX(n+1)A] is turned on, the error code is stored in the remote register.
If the error reset request flag [RY(n+1)A] is turned on when an error occurs, [RX(n+1)A] is turned off
to clear the error code.
Error status flag
[RX(n+1)A]
Error reset
request flag
[RY(n+1)A]
Remote ready
[RX(n+1)B]
ON
OFF
ON
OFF
ON
OFF
Extension number for display selection processing
The content of the extended display remote register is selected.
After the extension number for display [RYn0 to RYn5] is set, turn on the extended display flag
[RYnC]. After the data in the remote register [RWrn to RWrn+3] is displayed, check that extended
display completion [RXnC] is turned on and then turn off the extended display flag [RYnC]. If the
extended display flag is turned off, the extended display completion is turned off.
Extension number
for display
[RYn0 to RYn5]
Extended display flag
[RYnC]
Extended display
completion
[RXnC]
Remote register
[RWrn to RWrn+3]
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Extension number 0
Extension number 0
(R/O data: Automatically updated)
Extension number 1
Extension number 1
22
IMR01Y06-E3
Page 29
6. CC-Link COMMUNICATION
]
Extension number for setting selection processing
The content of the extended setting remote register is selected and the set value is changed.
After the extension number for setting [RYn6 to RYnB] is set, turn on the extended setting flag
[RYnD]. After the content of the remote register [RWwm to RWwm+3] is set, check that extended
setting completion [RXnD] is turned on and then turn off the extended setting flag [RYnD]. If the
extended setting flag [RYnD] is turned off, the extended setting completion [RXnD] is turned off.
Extension number
for setting
[RYn6 to RYnB]
Extended setting
flag
[RYnD]
Extended setting
completion
[RXnD]
ON
OFF
ON
OFF
ON
OFF
Remote register
[RWwm to RWwm+3]
ON
OFF
AT start procedure
Instructs AT execution.
Remote register [RWwn
(Extension number 4:
PID/AT transfer)
Extended setting flag
[RYnD]
Extended setting
completion
[RXnD]
AT setting status
ON
OFF
ON
OFF
ON
Data = 1
Data usage Data usage
Data = 0
IMR01Y06-E3
PID/AT transfer status
[RXn4]
OFF
ON
OFF
2 seconds
23
Page 30
6. CC-Link COMMUNICATION
6.3 Processing of Numeric Data Values
Numeric data values used via communication with the PLC and processed by COM-JC include those
with and without decimal points and also those with minus signs.
For numeric data value without decimal point
If there is no decimal point, the value is processed as it is.
In parameters which only have ON or OFF status, 1 = ON, 0 = OFF.
[Example]
A signal wire for temperature input is disconnected and the burnout state occurs.
→ Read value corresponding to extension number 63 (comprehensive event state):
1 (Hexadecimal number: 0001H)
For numeric data value with decimal point
The decimal point is omitted.
[Example]
When temperature measured value (PV) of controller (device address 1) is 120.5 °C → Read value of remote register (RWrn) [measured value (PV) of device address 1]:
1205 (Hexadecimal number: 04B5H)
→ Read value corresponding to extension number 0 [measured value (PV)]:
1205 (Hexadecimal number: 04B5H)
For numeric data value with minus sign
The value is expressed as a 2’s complement value which is obtained by subtracting the minus value
from the hexadecimal number 10000H.
[Example]
When temperature measured value (PV) of controller (device address 1) is −2.5 °C → Read value of remote register (RWrn) [measured value (PV) of device address 1]:
Any attempt to write to an unused item is not processed as an error. Data cannot be written
into an unused item.
24
IMR01Y06-E3
Page 31
7. COMMUNICATION DATA LIST
7.1 Remote Input/Output
Remote input (RX) and remote output (RY) is ON/OFF data.
“n” in the table is the address assigned to the master station by the station number setting.
It can be calculated by the following equation. However, the computing equation is when a
network is configured only by using our COM-JCs and the number of all exclusive
stations/extended cyclic are at the same setting.
Number of occupied stations/
extended cyclic setting
Equation
1 station occupied 1 time n = (Station number − 1) × 2
4 stations occupied 1 time n = (Station number − 1) × 8
4 stations occupied 2 times n = (Station number − 1) × 14
As the calculation result is expressed in decimal number it is converted to hexadecimal
number before substituted for “n” in the table.
Example: When the COM-JC is set to 4 stations occupied 1 time and its station number is “5.”
Display area number are specified by
the ON/OFF states of RY(n+2)0 to
RY(n+2)3.
Data 0: OFF 1: ON
[Decimal number: 0 to 16]
(0, 9 to 16: Control area)
RY(n+2)6 b6
RY(n+2)7 b7
RY(n+2)8 b0
RY(n+2)9 b1
RY(n+2)A b2
RY(n+2)B b3
RY(n+2)C b4
RY(n+2)D b5
Area number for setting
b4 to b7: Unused
Setting area number are specified by
the ON/OFF states of RY(n+2)8 to
RY(n+2)B.
Data 0: OFF 1: ON
[Decimal number: 0 to 16]
(0, 9 to 16: Control area)
RY(n+2)E b6
RY(n+2)F b7
RY(n+3)0 Unused
RY(n+C)F
RY(n+D)0 Reserved
RY(n+D)7
RY(n+D)8 Initialize data processing completion
flag
0: OFF
1: ON
RY(n+D)9 Initialize data setting request flag 0: OFF
1: ON
RY(n+D)A Error reset request flag 0: OFF
1: ON
RY(n+D)B Reserved
RY(n+D)F
Factory
set value
0
0
0
0
0
IMR01Y06-E3
43
Page 50
7. COMMUNICATION DATA LIST
7.2 Remote Register
Remote registers (RWr, RWw) are numeric data.
“n” in the table is the address assigned to the master station by the station number setting. It
can be calculated by the following equation. However, the computing equation is when a
network is configured only by using our COM-JCs and the number of all exclusive
stations/extended cyclic are at the same setting.
Number of occupied stations/
extended cyclic setting
1 station occupied 1 time n = (Station number − 1) ×4
4 stations occupied 1 time n = (Station number − 1) ×16
4 stations occupied 2 times n = (Station number − 1) ×32
As the calculation result is expressed in decimal number it is converted to hexadecimal
number before substituted for “n” in the table.
Example: When the COM-JC is set to 4 stations occupied 1 time and its station number is “5.”
RWrn to RWrn+F → RWr40 to RWr4F
RWwn to RWwn+F → RWw40 to RWw4F
“Device address from 1 to 31” in the table correspond to controller device address.
44
IMR01Y06-E3
Page 51
7. COMMUNICATION DATA LIST
7.2.1 1 station occupied 1 time (1 controller assignment)
Remote register (RWr)
Data direction: COM-JC (Remote device station) → Master station (PLC)
Data capacity: 4-word
Address Communication item Data range
RWrn Measured value (PV) Input scale low to
RWrn+1
RWrn+2 Unused
RWrn+3
Device address 1
Manipulated output value
(MV1)
For extended area display
Input scale high
−5.0 to +105.0 %
Data corresponding to the
extension number specified by
setting the display extension
number from RYn0 to RYn5.
Factory
set value
Remote register (RWw)
Data direction: Master station (PLC) → COM-JC (Remote device station)
Data capacity: 4-word
Address Communication item Data range
RWwn
RWwn+1 Event 1 set value 50
RWwn+2 Event 2 set value
RWwn+3
Device address 1
Set value (SV) Setting limiter (low) to
For extended area setting
Setting limiter (high)
Deviation:
−Input span to +Input span
Process and set value:
Input scale low to
Input scale high
Manipulated output value
(MV1/MV2):
−5.0 to +105.0 %
Data corresponding to the
extension number specified by
setting the setting extension
number from RYn6 to RYnB.
Factory
set value
0
50
IMR01Y06-E3 45
Page 52
7. COMMUNICATION DATA LIST
7.2.2 1 station occupied 1 time (2 controllers assignment)
Remote register (RWr)
Data direction: COM-JC (Remote device station) → Master station (PLC)
Data capacity: 4-word
Address Communication item Data range
RWrn Device address 1 Measured value (PV)
RWrn+1 Device address 2 Measured value (PV)
RWrn+2 Device address 1 For extended area display
RWrn+3 Device address 2 For extended area display
Remote register (RWw)
Input scale low to
Input scale high
Data corresponding to the
extension number specified by
setting the display extension
number from RYn0 to RYn5.
Factory
set value
Data direction: Master station (PLC) → COM-JC (Remote device station)
Data capacity: 4-word
Address Communication item Data range
RWwn
RWwn+1
RWwn+2 Device address 1 For extended area setting
RWwn+3 Device address 2 For extended area setting
Device address 1 Set value (SV) 0
Device address 2 Set value (SV)
Setting limiter (low) to
Setting limiter (high)
Data corresponding to the
extension number specified by
setting the setting extension
number from RYn6 to RYnB.
Factory
set value
0
46
IMR01Y06-E3
Page 53
7. COMMUNICATION DATA LIST
7.2.3 4 stations occupied 1 time (8 controllers assignment)
Remote register (RWr)
Data direction: COM-JC (Remote device station) → Master station (PLC)
Data capacity: 16-word
Address Communication item Data range
RWrn Device address 1 Measured value (PV)
RWrn+1 Device address 2 Measured value (PV)
RWrn+2
RWrn+3 Device address 4 Measured value (PV)
RWrn+4 Device address 5 Measured value (PV)
RWrn+5 Device address 6 Measured value (PV)
RWrn+6 Device address 7 Measured value (PV)
RWrn+7 Device address 8 Measured value (PV)
RWrn+8 Device address 1 For extended area display
RWrn+9 Device address 2 For extended area display
RWrn+A Device address 3 For extended area display
RWrn+B Device address 4 For extended area display
RWrn+C Device address 5 For extended area display
RWrn+D Device address 6 For extended area display
RWrn+E Device address 7 For extended area display
RWrn+F Device address 8 For extended area display
Device address 3 Measured value (PV)
Remote register (RWw)
Input scale low to
Input scale high
Data corresponding to the
extension number specified by
setting the display extension
number from RYn0 to RYn5
and from RY(n+1)0 to
RY(n+1)2.
Factory
set value
Data direction: Master station (PLC) → COM-JC (Remote device station)
Data capacity: 16-word
Address Communication item Data range
RWwn
RWwn+1
RWwn+2
RWwn+3
RWwn+4
RWwn+5
RWwn+6
RWwn+7
RWwn+8
RWwn+9 Device address 2 For extended area setting
RWwn+A Device address 3 For extended area setting
RWwn+B Device address 4 For extended area setting
RWwn+C Device address 5 For extended area setting
RWwn+D Device address 6 For extended area setting
RWwn+E Device address 7 For extended area setting
RWwn+F Device address 8 For extended area setting
Device address 1 Set value (SV) 0
Device address 2 Set value (SV) 0
Device address 3 Set value (SV) 0
Device address 4 Set value (SV) 0
Device address 5 Set value (SV) 0
Device address 6 Set value (SV) 0
Device address 7 Set value (SV) 0
Device address 8 Set value (SV)
Device address 1 For extended area setting
Setting limiter (low) to
Setting limiter (high)
Data corresponding to the
extension number specified by
setting the setting extension
number from RYn6 to RYnB
and from RY(n+1)8 to
RY(n+1)A.
Factory
set value
0
IMR01Y06-E3
47
Page 54
7. COMMUNICATION DATA LIST
7.2.4 4 stations occupied 1 time (16 controllers assignment)
Remote register (RWr)
Data direction: COM-JC (Remote device station) → Master station (PLC)
Data capacity: 16-word
Address Communication item Data range
RWrn Device address 1 For extended area display
RWrn+1 Device address 2 For extended area display
RWrn+2
RWrn+3 Device address 4 For extended area display
RWrn+4 Device address 5 For extended area display
RWrn+5 Device address 6 For extended area display
RWrn+6 Device address 7 For extended area display
RWrn+7 Device address 8 For extended area display
RWrn+8 Device address 9 For extended area display
RWrn+9 Device address 10 For extended area display
RWrn+A Device address 11 For extended area display
RWrn+B Device address 12 For extended area display
RWrn+C Device address 13 For extended area display
RWrn+D Device address 14 For extended area display
RWrn+E Device address 15 For extended area display
RWrn+F Device address 16 For extended area display
Device address 3 For extended area display
Remote register (RWw)
Data corresponding to the
extension number specified by
setting the display extension
number from RYn0 to RYn5
and from RY(n+1)0 to
RY(n+1)2.
Factory
set value
Data direction: Master station (PLC) → COM-JC (Remote device station)
Data capacity: 16-word
Address Communication item Data range
RWwn
RWwn+1
RWwn+2
RWwn+3
RWwn+4
RWwn+5
RWwn+6
RWwn+7
RWwn+8
RWwn+9 Device address 10 For extended area setting
RWwn+A Device address 11 For extended area setting
RWwn+B Device address 12 For extended area setting
RWwn+C Device address 13 For extended area setting
RWwn+D Device address 14 For extended area setting
RWwn+E Device address 15 For extended area setting
RWwn+F Device address 16 For extended area setting
Device address 1 For extended area setting
Device address 2 For extended area setting
Device address 3 For extended area setting
Device address 4 For extended area setting
Device address 5 For extended area setting
Device address 6 For extended area setting
Device address 7 For extended area setting
Device address 8 For extended area setting
Device address 9 For extended area setting
Data corresponding to the
extension number specified by
setting the setting extension
number from RYn6 to RYnB
and from RY(n+1)8 to
RY(n+1)A.
Factory
set value
48
IMR01Y06-E3
Page 55
7. COMMUNICATION DATA LIST
7.2.5 4 stations occupied 2 times (16 controllers assignment)
Remote register (RWr)
Data direction: COM-JC (Remote device station) → Master station (PLC)
Data capacity: 32-word
Address Communication item Data range
RWrn Device address 1 Measured value (PV)
RWrn+1 Device address 2 Measured value (PV)
RWrn+2
RWrn+3 Device address 4 Measured value (PV)
RWrn+4 Device address 5 Measured value (PV)
RWrn+5 Device address 6 Measured value (PV)
RWrn+6 Device address 7 Measured value (PV)
RWrn+7 Device address 8 Measured value (PV)
RWrn+8 Device address 9 Measured value (PV)
RWrn+9 Device address 10 Measured value (PV)
RWrn+A
RWrn+B Device address 12 Measured value (PV)
RWrn+C Device address 13 Measured value (PV)
RWrn+D Device address 14 Measured value (PV)
RWrn+E Device address 15 Measured value (PV)
RWrn+F Device address 16 Measured value (PV)
RWrn+10 Device address 1 For extended area display
RWrn+11 Device address 2 For extended area display
RWrn+12
RWrn+13 Device address 4 For extended area display
RWrn+14 Device address 5 For extended area display
RWrn+15 Device address 6 For extended area display
RWrn+16 Device address 7 For extended area display
RWrn+17 Device address 8 For extended area display
RWrn+18 Device address 9 For extended area display
RWrn+19 Device address 10 For extended area display
RWrn+1A Device address 11 For extended area display
RWrn+1B Device address 12 For extended area display
RWrn+1C Device address 13 For extended area display
RWrn+1D Device address 14 For extended area display
RWrn+1E Device address 15 For extended area display
RWrn+1F Device address 16 For extended area display
Device address 3 Measured value (PV)
Device address 11 Measured value (PV)
Device address 3 For extended area display
Input scale low to
Input scale high
Data corresponding to the
extension number specified by
setting the display extension
number from RYn0 to RYn5
and from RY(n+1)0 to
RY(n+1)2.
Factory
set value
IMR01Y06-E3
49
Page 56
7. COMMUNICATION DATA LIST
Remote register (RWw)
Data direction: Master station (PLC) → COM-JC (Remote device station)
Data capacity: 32-word
Address Communication item Data range
RWwn
RWwn+1
RWwn+2
RWwn+3
RWwn+4
RWwn+5
RWwn+6
RWwn+7
RWwn+8
RWwn+9
RWwn+A
RWwn+B
RWwn+C
RWwn+D
RWwn+E
RWwn+F
RWwn+10
RWwn+11
RWwn+12
RWwn+13
RWwn+14
RWwn+15
RWwn+16
RWwn+17
RWwn+18
RWwn+19 Device address 10 For extended area setting
RWwn+1A Device address 11 For extended area setting
RWwn+1B Device address 12 For extended area setting
RWwn+1C Device address 13 For extended area setting
RWwn+1D Device address 14 For extended area setting
RWwn+1E Device address 15 For extended area setting
RWwn+1F Device address 16 For extended area setting
Device address 1 Set value (SV) 0
Device address 2 Set value (SV) 0
Device address 3 Set value (SV) 0
Device address 4 Set value (SV) 0
Device address 5 Set value (SV) 0
Device address 6 Set value (SV) 0
Device address 7 Set value (SV) 0
Device address 8 Set value (SV) 0
Device address 9 Set value (SV) 0
Device address 10 Set value (SV) 0
Device address 11 Set value (SV) 0
Device address 12 Set value (SV) 0
Device address 13 Set value (SV) 0
Device address 14 Set value (SV) 0
Device address 15 Set value (SV) 0
Device address 16 Set value (SV)
Device address 1 For extended area setting
Device address 2 For extended area setting
Device address 3 For extended area setting
Device address 4 For extended area setting
Device address 5 For extended area setting
Device address 6 For extended area setting
Device address 7 For extended area setting
Device address 8 For extended area setting
Device address 9 For extended area setting
Setting limiter (low) to
Setting limiter (high)
Data corresponding to the
extension number specified by
setting the setting extension
number from RYn6 to RYnB
and from RY(n+1)8 to
RY(n+1)A.
Factory
set value
0
50
IMR01Y06-E3
Page 57
7. COMMUNICATION DATA LIST
7.2.6 4 stations occupied 2 times (31 controllers assignment)
Remote register (RWr)
Data direction: COM-JC (Remote device station) → Master station (PLC)
Data capacity: 32-word
Address Communication item Data range
RWrn Device address 1 For extended area display
RWrn+1 Device address 2 For extended area display
RWrn+2
RWrn+3 Device address 4 For extended area display
RWrn+4 Device address 5 For extended area display
RWrn+5 Device address 6 For extended area display
RWrn+6 Device address 7 For extended area display
RWrn+7 Device address 8 For extended area display
RWrn+8 Device address 9 For extended area display
RWrn+9 Device address 10 For extended area display
RWrn+A
RWrn+B Device address 12 For extended area display
RWrn+C Device address 13 For extended area display
RWrn+D Device address 14 For extended area display
RWrn+E Device address 15 For extended area display
RWrn+F Device address 16 For extended area display
RWrn+10 Device address 17 For extended area display
RWrn+11 Device address 18 For extended area display
RWrn+12
RWrn+13 Device address 20 For extended area display
RWrn+14 Device address 21 For extended area display
RWrn+15 Device address 22 For extended area display
RWrn+16 Device address 23 For extended area display
RWrn+17 Device address 24 For extended area display
RWrn+18 Device address 25 For extended area display
RWrn+19 Device address 26 For extended area display
RWrn+1A Device address 27 For extended area display
RWrn+1B Device address 28 For extended area display
RWrn+1C Device address 29 For extended area display
RWrn+1D Device address 30 For extended area display
RWrn+1E Device address 31 For extended area display
RWrn+1F Unused
Device address 3 For extended area display
Device address 11 For extended area display
Device address 19 For extended area display
Data corresponding to the
extension number specified by
setting the display extension
number from RYn0 to RYn5
and from RY(n+1)0 to
RY(n+1)2.
Factory
set value
IMR01Y06-E3
51
Page 58
7. COMMUNICATION DATA LIST
Remote register (RWw)
Data direction: Master station (PLC) → COM-JC (Remote device station)
Data capacity: 32-word
Address Communication item Data range
RWwn
RWwn+1
RWwn+2
RWwn+3
RWwn+4
RWwn+5
RWwn+6
RWwn+7
RWwn+8
RWwn+9
RWwn+A
RWwn+B
RWwn+C
RWwn+D
RWwn+E
RWwn+F
RWwn+10
RWwn+11
RWwn+12
RWwn+13
RWwn+14
RWwn+15
RWwn+16
RWwn+17
RWwn+18
RWwn+19 Device address 26 For extended area setting
RWwn+1A Device address 27 For extended area setting
RWwn+1B Device address 28 For extended area setting
RWwn+1C Device address 29 For extended area setting
RWwn+1D Device address 30 For extended area setting
RWwn+1E Device address 31 For extended area setting
RWwn+1F Unused
Device address 1 For extended area setting0
Device address 2 For extended area setting0
Device address 3 For extended area setting0
Device address 4 For extended area setting0
Device address 5 For extended area setting0
Device address 6 For extended area setting0
Device address 7 For extended area setting0
Device address 8 For extended area setting0
Device address 9 For extended area setting0
Device address 10 For extended area setting0
Device address 11 For extended area setting0
Device address 12 For extended area setting0
Device address 13 For extended area setting0
Device address 14 For extended area setting0
Device address 15 For extended area setting0
Device address 16 For extended area setting0
Device address 17 For extended area setting
Device address 18 For extended area setting
Device address 19 For extended area setting
Device address 20 For extended area setting
Device address 21 For extended area setting
Device address 22 For extended area setting
Device address 23 For extended area setting
Device address 24 For extended area setting
Device address 25 For extended area setting
Data corresponding to the
extension number specified by
setting the setting extension
number from RYn6 to RYnB
and from RY(n+1)8 to
RY(n+1)A.
Factory
set value
52
IMR01Y06-E3
Page 59
7. COMMUNICATION DATA LIST
7.3 Extension Number
Communication items which are handled in the extension areas of the remote registers (RWr and
RWw) are specified by the extension number, If the necessary data is selected from a list of extension
numbers and that extension number is set by remote output, the data can be handled in the remote
registers (RWr and RWw).
In addition, communication item corresponding to memory area function specifies memory area
number to use in remote register extension area for area number. Extension number and area number
set in ON/OFF of remote output.
For remote output, see 7.1 Remote Input/Output (P. 25).
For remote register, see 7.2 Remote Register (P. 44).
For memory area function, see FB400/FB900 Instruction Manual (IMR01W03-E).
When read data
Setting of extension number for display
Extension number for display sets it with remote output “RYn0 to RYn5 and RY(n+1)0 to
RY(n+1)2.”
Attribute:
RO: Read only data [Remote device station (COM-JC) → Master station (PLC)]
R/W: Read and Write data [Remote device station (COM-JC) ↔ Master station (PLC)]
Extension
number
* When the heat-side or cool-side integral time is set to zero for heat/cool PID control, PD action will take
: Data related multi-memory area function
Communication item
0 Measured value (PV) RO Input scale low to Input scale high
1
Manipulated output value
(MV1) monitor
[heat-side]
2
Current transformer 1 (CT1)
input value monitor
3 Set value (SV) R/WSetting limiter (low) to Setting limiter (high)
4 PID/AT transfer R/W
5
Proportional band
[heat-side]
6
Integral time
[heat-side]
7
Derivative time
[heat-side]
8 PV bias R/W−Input span to +Input span 0
9 Event 1 set value R/W50
10 Event 2 set value
11
Reserved
15
place for both heat-side and cool-side.
Attri-
bute
RO
RO
R/W
R/W
R/W
R/W
Data range
PID control or heat/cool PID control:
−5.0 to +105.0 %
Position proportioning control with feedback
resistance (FBR) input:
0.0 to 100.0 %
0.0 to 30.0 A (CTL-6-P-N)
0.0 to 100.0 A (CTL-12-S56-10L-N)
0: PID control
1: Autotuning (AT)
TC/RTD inputs:
0 to Input span, 0.0 to Input span or
0.00 to Input span (Unit: °C [°F])
Varies with the setting of the decimal point
position selection.
Voltage (V)/current (I) inputs:
0.0 to 1000.0 % of input span
(0, 0.0 or 0.00: ON/OFF action)
PID control or heat/cool PID control:
0 to 3600 seconds or 0.0 to 1999.9 seconds
(0, 0.0: PD action) *
Position proportioning control:
1 to 3600 seconds or 0.1 to 1999.9 seconds
Varies with the setting of the
integral/derivative time decimal point position
selection.
0 to 3600 seconds or 0.0 to 1999.9 seconds
(0, 0.0: PI action)
Varies with the setting of the
integral/derivative time decimal point position
selection.
Deviation:
−Input span to +Input span
Process and set value:
Input scale low to Input scale high
Manipulated output value (MV1 or MV2):
−5.0 to +105.0 %
If the Event type corresponds to “0: None,”
set to RO (Only reading data is possible).
Continued on the next page.
Factory
set value
TC/RTD:
0 °C [°F]
V/I: 0.0 %
0
TC/RTD:
30
V/I: 30.0
240
60
50
IMR01Y06-E3
55
Page 62
7. COMMUNICATION DATA LIST
Continued from the previous page.
Extension
number
16 Unused
17 RUN/STOP transfer R/W
18 Proportional cycle time
19 Auto/Manual transfer R/W
20
21 Setting limiter (high) R/W Setting limiter (low) to Input scale high
Logic of RUN/STOP transfer is different
bymodel code.
For COM-JC*01-1
0: RUN (Control start)
1: STOP (Control stop)
For COM-JC*01-2
0: STOP (Control stop)
1: RUN (Control start)
R/W0.1 to 100.0 seconds
M: Relay contact output
V: Voltage pulse output
T: Triac output
D: open collector output
This item becomes RO (Only reading data is
possible) for the voltage/current output
specification.
0: Auto mode
1: Manual mode
R/W
PID control, Position proportioning control:
Output limiter (low) [MV1] to
Output limiter (high) [MV1]
Heat/cool PID control:
−Output limiter (high) [MV2] to
+Output limiter (high) [MV1]
(−105.0 to +105.0 %)
0.0 to 100.0 seconds
(0.0: Unused)
R/W
0.0 to 30.0 A (CTL-6-P-N)
0.0 to 100.0 A (CTL-12-S56-10L-N)
(0.0: Unused)
If there is no current transformer 1 (CT1) or
CT1 is assigned to “0: None,” set to RO (Only
reading data is possible).
Factory
set value
0
M: 20.0
V, T, D: 2.0
0
0.0
Input scale
high
Input scale
low
0.0
0.0
56
Continued on the next page.
IMR01Y06-E3
Page 63
Continued from the previous page.
Extension
number
25 Decimal point position R/W
26
27
28 Proportional cycle time
Communication item
Manipulated output value
(MV2) monitor
[cool-side]
Proportional band
[cool-side]
[cool-side]
7. COMMUNICATION DATA LIST
Attri-
bute
Data range
0: No decimal place
1: One decimal place
Factory
set value
Depends on
model code.
2: Two decimal places
3: Three decimal places
4: Four decimal places
TC input:
• K (−200.0 to +800.0 °C, −328.0 to
When not
specifying:
TC/RTD: 0
V/I: 1
+800.0 °F), J (−200.0 to +800.0 °C,
−328.0 to +1200.0 °F), T, E (−200.0 to
+700.0 °C, −328.0 to +1292.0 °F), U, L
Only 0 or 1 can be set.
• Other than the above
Only 0 can be set.
RTD input:
• Pt (−100.00 to +100.00 °C, −199.99 to
+199.99 °F), JPt (−100.00 to +100.00 °C,
−199.99 to +199.99 °F)
From 0 to 2 can be set.
• Other than the above
Only 0 or 1 can be set.
Voltage (V)/current (I) inputs:
From 0 to 4 can be set.
RO −5.0 to +105.0 %
R/W
TC/RTD inputs:
TC/RTD:
1 to Input span, 0.1 to Input span or
0.01 to Input span (Unit: °C [°F])
Varies with the setting of the decimal point
V/I: 30.0
position selection.
Voltage (V)/current (I) inputs:
0.1 to 1000.0 % of input span
If control is other than heat/cool PID control,
set to RO (Only reading data is possible).
R/W
0.1 to 100.0 seconds
M: Relay contact output
M: 20.0
V, T, D: 2.0
V: Voltage pulse output
T: Triac output
D: open collector output
If control is other than heat/cool PID control,
set to RO (Only reading data is possible).
This item becomes RO (Only reading data is
possible) for the voltage/current output
specification.
30
IMR01Y06-E3
Continued on the next page.
57
Page 64
7. COMMUNICATION DATA LIST
Continued from the previous page.
Extension
number
29 Overlap/Deadband R/W
30 Unused
31
32 Error code RO
33
34
35 Unused
Communication item
Set value (SV) monitor RO Setting limiter (low) to Setting limiter (high)
Memory area transfer R/W1 to 8 1
Control response parameter
Attri-
bute
R/W
Data range
TC/RTD inputs:
−Input span to +Input span (Unit:°C [°F])
Voltage (V)/current (I) inputs:
−100.0 to +100.0 % of input span
Minus (−) setting results in overlap.
However, the overlapping range is within the
proportional range.
If control is other than heat/cool PID control,
set to RO (Only reading data is possible).
Bit data
b0: Adjustment data error
b1: Back-up error
b2: A/D conversion error
b3: Unused
b4: Unused
b5: Custom data error
b6: Unused
b7: Watchdog timer error
b8: Program error (stack)
b9 to b10: Unused
b11: Program error (busy)
b12 to b15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 4095]
0: Slow
1: Medium
2: Fast
[P or PD action: 2 (Fast) fixed]
Factory
set value
0
PID control,
Position
proportioning
control: 0
Heat/cool PID
control: 2
58
Continued on the next page.
IMR01Y06-E3
Page 65
Continued from the previous page.
Extension
number
36 Input type R/W
37
38 Control action R/W
Communication item
Setting change rate limiter
(up)
Attri-
bute
R/W
7. COMMUNICATION DATA LIST
Data range
0: TC input K
1: TC input J
2: TC input R
3: TC input S
4: TC input B
5: TC input E
6: TC input N
7: TC input T
8: TC input W5Re/W26Re
9: TC input PLII
10: TC input U
11: TC input L
12: RTD input Pt100
13: RTD input JPt100
14: Current input 0 to 20 mA DC
15: Current input 4 to 20 mA DC
16: Voltage (high) input 0 to 10 V DC
17: Voltage (high) input 0 to 5 V DC
18: Voltage (high) input 1 to 5 V DC
19: Voltage (low) input 0 to 1 V DC
20: Voltage (low) input 0 to 100 mV DC
21: Voltage (low) input 0 to 10 mV DC
24: Voltage (high) input ±1 V DC
25: Voltage (low) input ±100 mV DC
26: Voltage (low) input ±10 mV DC
If changed to current/voltage (high) input from
TC/RTD/voltage (low) input, select the
hardware by the input selector switch (for
measurement input) at the side of the instrument.
For the selecting procedure, see the
FB400/FB900 Instruction Manual
(IMR01W03-E).
0 to Input span/unit time * (0: Unused)
* Unit time: 60 seconds (factory set value)
0: Brilliant II PID control (direct action)
1: Brilliant II PID control (reverse action)
2: Brilliant II Heat/Cool PID control
[water cooling]
3: Brilliant II Heat/Cool PID control
[air cooling]
4: Brilliant II Heat/Cool PID control
[Cooling gain linear type]
5: Position proportioning control
Factory
set value
Depends on
model code.
When not
specifying:
TC/RTD or
V (low)/I: 0
V (high)/I: 16
0
Depends on
model code.
When not
specifying: 1
IMR01Y06-E3
Continued on the next page.
59
Page 66
7. COMMUNICATION DATA LIST
Continued from the previous page.
Extension
number
39 Event 1 type R/W
40 Event 2 type R/W
41 Event 1 differential gap R/W
42 Event 2 differential gap R/W
43 Event 1 hold action R/W
44 Event 2 hold action R/W
45 Unused
46 Output limiter (high) [MV1] R/W
47 Output limiter (low) [MV1] R/W
Communication item
Attri-
bute
Data range
0: None
1: Deviation high
2: Deviation low
3: Deviation high/low
4: Band
1
5: Process high
6: Process low
1
1
1
1
1
Factory
set value
Depends on
model code.
When not
specifying: 0
7: SV high
8: SV low
9: Unused
10: MV1 high [heat-side]
11: MV1 low [heat-side] 1,
12: MV2 high [cool-side]
13: MV2 low [cool-side] 1
1
Event hold action is available.
2
If there is feedback resistance (FBR) input in
1, 2
2
1
Depends on
model code.
When not
specifying: 0
position proportioning control, set to the
feedback resistance (FBR) input value.
Deviation, process or set value:
0 to Input span (Unit: °C [°F])
MV: 0.0 to 110.0 %
: TC/RTD:
2 °C [°F]
V/I:
0.2 %
: 0.2 %
: TC/RTD:
2 °C [°F]
V/I:
0.2 %
: 0.2 %
0: OFF
1: Hold action ON
Depends on
model code.
(when power turned on)
2: Re-hold action ON
(when power turned on and SV changed)
When not
specifying: 0
Depends on
model code.
When not
specifying: 0
Output limiter (low) [MV1] to +105.0 %
Position proportioning control:
Becomes valid only when there is feedback
resistance (FBR) input and it does not break.
−5.0 % to Output limiter (high) [MV1]
Position proportioning control:
Becomes valid only when there is feedback
resistance (FBR) input and it does not break.
105.0
−5.0
60
Continued on the next page.
IMR01Y06-E3
Page 67
Continued from the previous page.
Extension
number
48 Unused
49 Unused
50
51
52 Unused
53 Unused
54 Event 3 set value (EV3) 50
55 Event 4 set value (EV4)
56 Event 3 type R/W
57 Event 4 type R/W
Communication item
Control loop break alarm
(LBA) time
LBA deadband R/W
7. COMMUNICATION DATA LIST
Attri-
bute
Data range
Factory
set value
R/W
0 to 7200 seconds
(0: Unused)
If Event 4 is other than “9: Control loop break
alarm (LBA),” set to RO (Only reading data
is possible).
0 to Input span
If Event 4 is other than “9: Control loop break
alarm (LBA),” set to RO (Only reading data
is possible).
Deviation:
−Input span to +Input span
Process and set value:
Input scale low to Input scale high
Manipulated output value (MV1 or MV2):
−5.0 to +105.0 %
If the Event type corresponds to “0: None,”
set to RO (Only reading data is possible).
If Event 4 corresponds to “9: Control loop
break alarm (LBA),” the Event 4 set value
becomes RO (Only reading data is possible).
0: None
1: Deviation high
2: Deviation low
3: Deviation high/low
4: Band
1
5: Process high
6: Process low
1
1
1
1
1
Depends on
model code.
When not
specifying: 0
7: SV high
8: SV low
9: Unused
10: MV1 high [heat-side]
11: MV1 low [heat-side] 1,
12: MV2 high [cool-side]
13: MV2 low [cool-side] 1
1
Event hold action is available.
2
If there is feedback resistance (FBR) input in
1, 2
2
1
Depends on
model code.
When not
specifying: 0
position proportioning control, set to the
feedback resistance (FBR) input value.
480
0
50
IMR01Y06-E3
Continued on the next page.
61
Page 68
7. COMMUNICATION DATA LIST
Continued from the previous page.
Extension
number
58 Event 3 differential gap R/W
59 Event 4 differential gap R/W
60 Event 3 hold action R/W
61 Event 4 hold action R/W
62
63 Comprehensive event state RO
64
65
66
67
68
Communication item
Setting change rate limiter
(down)
Remote setting (RS) input
value monitor
Unused
Uuused
Burnout state monitor of
feedback resistance (FBR)
input
Memory area soak time
monitor
Attri-
bute
Data range
Deviation, process or set value:
0 to Input span (Unit: °C [°F])
MV: 0.0 to 110.0 %
Factory
set value
: TC/RTD:
2 °C [°F]
V/I:
0.2 %
: 0.2 %
: TC/RTD:
2 °C [°F]
V/I:
0.2 %
: 0.2 %
0: OFF
1: Hold action ON
Depends on
model code.
(when power turned on)
2: Re-hold action ON
(when power turned on and SV changed)
When not
specifying: 0
Depends on
model code.
When not
specifying: 0
R/W
0 to Input span/unit time *
(0: Unused)
* Unit time: 60 seconds
(factory set value)
Bit data
b0: Burnout b5: Event 3
b1: Event 1 b6: Event 4
b2: Event 2 b7: HBA 2
b3: HBA 1 b8: FBR burnout
b4: LBA b9 to b15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 255]
RO Setting limiter (low) to Setting limiter (high)
RO 0: OFF
1: ON
0 to 11999 seconds or 0 to 5999 minutes
RO
Data range of Area soak time can be selected
on the Soak time unit.
0
62
Continued on the next page.
IMR01Y06-E3
Page 69
Continued from the previous page.
Extension
number
69
70
71 Unused
72 Unused
73 Unused
74
75
76
89
Communication item
Digital input (DI) state
monitor
Operation mode state
monitor
Output state monitor
Current transformer 2 (CT2)
input value monitor
Unused
7. COMMUNICATION DATA LIST
Attri-
bute
RO
Data range
Bit data
Factory
set value
b0: The state of DI1
b1: The state of DI2
b2: The state of DI3
b3: The state of DI4
b4: The state of DI5
b5: The state of DI6
b6: The state of DI7
b7 to b15: Unused
Data 0: Contact open
1: Contact closed
[Decimal number: 0 to 127]
RO
Bit data
b0: Control STOP
b1: Control RUN
b2: Manual mode *
b3: Remote mode *
b4 to b15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 15]
* During operation in manual mode, the
manual mode of the operation mode state
monitor is set to the
“1: ON” state and the remote mode of the
same monitor is se to the
“0: OFF” state even if the parameter,
“Remote/Local transfer” is set to “1:
Remote mode.”
RO
Bit data
b0: The state of OUT1
b1: The state of OUT2
b2: The state of DO1
b3: The state of DO2
b4: The state of DO3
b5: The state of DO4
b6 to b15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 63]
RO 0.0 to 30.0 A (CTL-6-P-N)
0.0 to 100.0 A (CTL-12-S56-10L-N)
Continued on the next page.
IMR01Y06-E3
63
Page 70
7. COMMUNICATION DATA LIST
Continued from the previous page.
Extension
number
90
91
Communication item
Remote/Local transfer
Unused
109
110 Link area number R/W0 to 8 (0: No link) 0
111 Area soak time R/W
112
Integral time
[cool-side]
113
Derivative time
[cool-side]
114
Unused
127
128
Manual reset
129
Unused
139
140
Heater break determination
point 1
* When the heat-side or cool-side integral time is set to zero for heat/cool PID control, PD action will take
place for both heat-side and cool-side.
Attri-
bute
R/W
R/W
R/W
R/W
R/W
Data range
0: Local mode
1: Remote mode
When performing remote control by remote
setting input and also performing cascade
control and ratio setting via intercontroller
communication, transfer to the remote mode.
0 to 11999 seconds or
0 to 5999 minutes
Data range of Area soak time can be selected
on the Soak time unit.
0 to 3600 seconds or 0.0 to 1999.9 seconds
(0, 0.0: PD action) *
Varies with the setting of the
integral/derivative time decimal point position
selection.
If control is other than heat/cool PID control,
set to RO (Only reading data is possible).
0 to 3600 seconds or 0.0 to 1999.9 seconds
(0, 0.0: PI action)
Varies with the setting of the
integral/derivative time decimal point position
selection.
If control is other than heat/cool PID control,
set to RO (Only reading data is possible).
−100.0 to +100.0 %
The offset can be manually eliminated.
If the integral function is valid, set to RO
(Only reading data is possible).
0.0 to 100.0 % of HBA1 set value
(0.0: Heater break determination is invalid)
If there is no current transformer 1 (CT1) or
CT1 is assigned to “0: None,” set to RO (Only
reading data is possible).
If Heater break alarm 1 (HBA1) corresponds
to “0: Type A,” set to RO (Only reading data
is possible).
Continued on the next page.
Factory
set value
0
0:00
240
60
0.0
30.0
64
IMR01Y06-E3
Page 71
Continued from the previous page.
Extension
number
141
142 PV ratio R/W0.500 to 1.500 1.000
143
144
145 Unused
146
147 Unused
148
149
150
Communication item
Heater melting
determination point 1
PV low input cut-off
Set lock level
Backup memory state
monitor
RS bias
Cascade control:
Cascade bias
Ratio setting:
Ratio setting bias
RS digital filter
Cascade control:
Cascade digital filter
Ratio setting:
Ratio setting digital
filter
RS ratio
Cascade control:
Cascade ratio
Ratio setting:
Ratio setting ratio
7. COMMUNICATION DATA LIST
Attri-
bute
R/W
Data range
0.0 to 100.0 % of HBA1 set value
Factory
set value
(0.0: Heater melting determination is invalid)
If there is no current transformer 1 (CT1) or
CT1 is assigned to “0: None,” set to RO (Only
reading data is possible).
If Heater break alarm 1 (HBA1) corresponds
to “0: Type A,” set to RO (Only reading data
is possible).
R/W
0.00 to 25.00 % of input span
If the Input square root extraction corresponds
to “0: Unused,” set to RO (Only reading data
is possible).
R/W
Bit data
b0: Lock only setting items other
than SV and event set value
(EV1 to EV4).
b1: Lock only event set value
(EV1 to EV4)
b2: Lock only set value (SV)
b3 to b15: Unused
Data 0: Unlock
1: Lock
[Decimal number: 0 to 7]
RO
0: The content of the backup memory does
not coincide with that of the RAM.
1: The content of the backup memory
coincides with that of the RAM.
R/W
R/W
−Input span to +Input span
0.0 to 100.0 seconds
(0.0: Unused)
R/W
0.001 to 9.999
30.0
0.00
0
0
0.0
1.000
IMR01Y06-E3
Continued on the next page.
65
Page 72
7. COMMUNICATION DATA LIST
Continued from the previous page.
Extension
number
151
152
153
154
159
160
161
162
Communication item
Heater break alarm 2
(HBA2) set value
Heater break determination
point 2
Heater melting
determination point 2
Unused
Display unit
Input scale high
Input scale low
Attri-
bute
R/W
R/W
R/W
R/W
R/W
R/W
Data range
When CT is CTL-6-P-N:
Factory
set value
0.0
0.0 to 30.0 A (0.0: Not used)
When CT is CTL-12-S56-10L-N:
0.0 to 100.0 A (0.0: Not used)
If there is no current transformer 2 (CT2) or
CT2 is assigned to “0: None,” set to RO (Only
reading data is possible).
0.0 to 100.0 % of HBA2 set value
30.0
(0.0: Heater break determination is invalid)
If there is no current transformer 2 (CT2) or
CT2 is assigned to “0: None,” set to RO (Only
reading data is possible).
If Heater break alarm 2 (HBA2) corresponds
to “0: Type A,” set to RO (Only reading data
is possible).
0.0 to 100.0 % of HBA2 set value
30.0
(0.0: Heater melting determination is invalid)
If there is no current transformer 2 (CT2) or
CT2 is assigned to “0: None,” set to RO (Only
reading data is possible).
If Heater break alarm 2 (HBA2) corresponds
to “0: Type A,” set to RO (Only reading data
is possible).
0: °C
0
1: °F
The engineering unit for voltage/current input
is expressed as %.
TC/RTD inputs:
Input scale low to Maximum value of the
selected input range
Voltage (V)/current (I) inputs:
−19999 to +99999
(Varies with the setting of the decimal point
TC/RTD:
Maximum
value of the
selected
input range
V/I: 100.0
position)
TC/RTD inputs:
Minimum value of the selected input range
to Input scale high
Voltage (V)/current (I) inputs:
−19999 to +99999
(Varies with the setting of the decimal point
TC/RTD:
Minimum
value of the
selected
input range
V/I: 0.0
position)
66
Continued on the next page.
IMR01Y06-E3
Page 73
Continued from the previous page.
Extension
number
163
164
165
166
167
168
169
170
171
179
180
Communication item
Input error determination
point (high)
Input error determination
point (low)
Burnout direction
Square root extraction
Power supply frequency
Sampling cycle
Remote setting input type
Digital input (DI)
assignment
Unused
Output assignment
Attri-
bute
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
R/W
7. COMMUNICATION DATA LIST
Data range
Input scale low − (5 % of input span) to
Input scale high + (5 % of input span)
Factory
set value
TC/RTD:
Input scale
high + (5 %
of input
span)
V/I: 105.0
TC/RTD:
Input scale
low − (5 %
of input
span)
V/I: −5.0
0: Upscale
0
1: Downscale
Valid only when the TC input and voltage
(low) input are selected.
0: Unused
0
1: Used
0: 50 Hz
0
1: 60 Hz
If power frequency measurement was made
possible with CT input and/or power feed
forward (PFF) input applied, set to RO (Only
reading data is possible).
0: 50 ms
1
1: 100 ms
2: 250 ms
14: Current input 0 to 20 mA DC
15
15: Current input 4 to 20 mA DC
16: Voltage (high) input 0 to 10 V DC
17: Voltage (high) input 0 to 5 V DC
18: Voltage (high) input 1 to 5 V DC
19: Voltage (low) input 0 to 1 V DC
20: Voltage (low) input 0 to 100 mV DC
21: Voltage (low) input 0 to 10 mV DC
If changed to voltage (high) input from
current/voltage (low) input, select the hardware
by the input selector switch [for remote setting
(SR) input] at the side of the instrument.
For the selecting procedure, see the
FB400/FB900 Instruction Manual
(IMR01W03-E).
1 to 8
1
See Table 1 “Digital input (DI) assignment” (P. 78).
1 to 7
2
See Table 2 “Output assignment” (P. 78).
IMR01Y06-E3
Continued on the next page.
67
Page 74
7. COMMUNICATION DATA LIST
Continued from the previous page.
Extension
number
181
182
183
Communication item
Timer 1
Timer 2
Timer 3
Attri-
bute
R/W0.0
0.0 to 600.0 seconds
Customization tool is necessary when the
When the PV, SV, SV monitor and RS:
Input scale low to Input scale high
Factory
set value
PV/SV/RS:
Input scale
When the MV1 and MV2:
−5.0 to +105.0 %
MV1/MV2:
When the deviation value:
−Input span to +Input span
Deviation:
+Input span
R/W
PV/SV/RS:
Input scale
MV1/MV2:
Deviation:
−Input span
R/W
Bit data
b0: Event output turned on at input error
occurrence
b1: Event output turned on in manual mode
b2: Event output turned on during the
autotuning (AT) function is being
executed
b3: Event output turned on during the setting
change rate limiter is being operated
b4 to b15: Unused
Data 0: Invalid 1: Valid
[Decimal number: 0 to 15]
R/W
0: Unused
1: Used
R/W
0.0 to 600.0 seconds
R/W
Bit data
b0: Event output turned on at input error
occurrence
b1: Event output turned on in manual mode
b2: Event output turned on during the
autotuning (AT) function is being
executed
b3: Event output turned on during the setting
change rate limiter is being operated
b4 to b15: Unused
Data 0: Invalid 1: Valid
[Decimal number: 0 to 15]
Continued on the next page.
high
100.0
low
0.0
0
0
0.0
0
IMR01Y06-E3
69
Page 76
7. COMMUNICATION DATA LIST
Continued from the previous page.
Extension
number
206
207
208
209 Unused
210
211
212
213 Unused
214
215
216
219
220
Communication item
Event 2 interlock
Event 2 delay timer
Force ON of Event 3 action
Event 3 interlock
Event 3 delay timer
Force ON of Event 4 action
Event 4 interlock
Event 4 delay timer
Unused
CT1 ratio
Attri-
bute
R/W
Data range
0: Unused
Factory
set value
1: Used
R/W
0.0 to 600.0 seconds
R/W
Bit data
b0: Event output turned on at input error
occurrence
b1: Event output turned on in manual mode
b2: Event output turned on during the
autotuning (AT) function is being
executed
b3: Event output turned on during the setting
change rate limiter is being operated
b4 to b15: Unused
Data 0: Invalid 1: Valid
[Decimal number: 0 to 15]
R/W
0: Unused
1: Used
R/W
0.0 to 600.0 seconds
R/W
Bit data
b0: Event output turned on at input error
occurrence
b1: Event output turned on in manual mode
b2: Event output turned on during the
autotuning (AT) function is being
executed
b3: Event output turned on during the setting
change rate limiter is being operated
b4 to b15: Unused
Data 0: Invalid 1: Valid
[Decimal number: 0 to 15]
R/W0: Unused
1: Used
0.0 to 600.0 seconds
R/W
R/W
0 to 9999
CTL-6-P-N:
CTL-12-S56
-10L-N:
0
0.0
0
0
0.0
0
0
0.0
800
1000
70
Continued on the next page.
IMR01Y06-E3
Page 77
Continued from the previous page.
Extension
number
221
222
223
224
225
226
227
228 Unused
229 Unused
230
231
232 Unused
233 Unused
Communication item
Heater break alarm 1
(HBA1) type
Number of heater break
alarm 1 (HBA1) delay times
CT1 assignment
CT2 ratio
Heater break alarm 2
(HBA2) type
Number of heater break
alarm 2 (HBA2) delay times
CT2 assignment
Hot/Cold start
External input type
7. COMMUNICATION DATA LIST
Attri-
bute
R/W
Data range
0: Heater break alarm 1 (HBA1) type A
Factory
set value
(Time-proportional control output)
1: Heater break alarm 1 (HBA1) type B
(Continuous control output and
time-proportional control output)
0: Hot start 1
1: Hot start 2
2: Cold start
3: Stop start
R/W
0: Remote setting input (remote control)
1: Intercontroller communication cascade
control
2: Intercontroller communication ratio setting
When performing cascade control or ratio
setting, set the master controller to 0 (Remote
control). Set slave controllers to 1 (Cascade
control) or 2 (Ratio setting).
Continued on the next page.
1
5
1
800
1000
1
5
1
0
0
IMR01Y06-E3
71
Page 78
7. COMMUNICATION DATA LIST
Continued from the previous page.
Extension
number
234
235
236
237 Unused
238
239 Unused
240
241
242
243
244
245
Communication item
SV tracking
MV transfer function
[Action taken when changed
to Manual mode from Auto
mode]
Start determination point
Master channel selection
Integral/derivative time
decimal point position
Derivative gain
ON/OFF action differential
gap (upper)
ON/OFF action differential
gap (lower)
Action (high) at input error
Action (low) at input error
Attri-
bute
R/W
Data range
0: Unused
Factory
set value
1: Used
R/W
0: MV1 or MV2 in Auto mode is used.
1: When selected by digital input (DI):
MV1 or MV2 in previous Manual mode
is used.
When selected by front key:
MV1 or MV2 in Auto mode is used.
2: MV1 or MV2 in previous Manual mode is
used.
R/W
0 to Input span
(The unit is the same as input value.)
3 % of
input span
(0: Action depending on the Hot/Cold start
selection)
R/W
0 to 31
If the external input type corresponds to “1:
Cascade control” or “2: Ratio setting,” the
setting becomes valid.
R/W
0: 1 second setting (No decimal place)
1: 0.1 seconds setting
(One decimal place)
R/W
0.1 to 10.0
TC/RTD inputs:
R/W
0 to Input span (Unit: °C [°F])
Voltage (V)/current (I) inputs:
0.0 to 100.0 % of input span
R/W
TC/RTD:
1 °C [°F]
V/I: 0.1 %
TC/RTD:
1 °C [°F]
V/I: 0.1 %
R/W0
0: Normal control
1: Manipulated output value at input error
R/W
1
0
0
0
6.0
0
72
246
247
248
249
Manipulated output value at
input error
Output change rate limiter
(up) [MV1]
Output change rate limiter
(down) [MV1]
Power feed forward
selection
−105.0 to +105.0 %
R/W
0.0
Actual output values become those restricted
by the output limiter.
Position proportioning control:
If there is no feedback resistance (FBR)
input or the feedback resistance (FBR)
input is disconnected, an action taken when
abnormal is in accordance with the value
action setting during STOP.
0
Open-side output OFF
1: Close-side output ON,
Open-side output OFF
2: Close-side output OFF,
Open-side output ON
Becomes valid when there is no feedback
resistance (FBR) input or the feedback
resistance (FBR) input is disconnected.
R/W
−Input span to +Input span
R/W
0: 1.5 cycles
0
1
1: 2.0 cycles
2: 2.5 cycles
3: 3.0 cycles
R/W
0.0 to 50.0 seconds
R/W
Output value with AT turned off to +105.0 %
10.0
105.0
Actual output values become those restricted
by the output limiter.
Position proportioning control:
Becomes valid only when there is feedback
resistance (FBR) input and it does not
break (high limit of feedback resistance
input at AT).
R/W
−105.0 % to Output value with AT turned on
−105.0
Actual output values become those restricted
by the output limiter.
Position proportioning control:
Becomes valid only when there is feedback
resistance (FBR) input and it does not
break (low limit of feedback resistance
input at AT).
R/W1.00
0.01 to 10.00 times
R/W1.00
R/W1.00
R/W1.00
R/W1.00
R/W
1.00
Continued on the next page.
74
IMR01Y06-E3
Page 81
Continued from the previous page.
Extension
number
281
282
283
284
285
286
287
288
289
290
291
292
293
299
300
301
302
319
320
Communication item
Proportional band limiter
(high) [heat-side]
Proportional band limiter
(low) [heat-side]
Integral time limiter (high)
[heat-side]
Integral time limiter (low)
[heat-side]
Derivative time limiter
(high) [heat-side]
Derivative time limiter (low)
[heat-side]
Proportional band limiter
(high) [cool-side]
Proportional band limiter
(low) [cool-side]
Integral time limiter (high)
[cool-side]
Integral time limiter (low)
[cool-side]
Derivative time limiter
(high) [cool-side]
Derivative time limiter (low)
[cool-side]
Unused
Setting change rate limiter
unit time
Soak time unit
Unused
STOP display
7. COMMUNICATION DATA LIST
Attri-
bute
R/W
TC/RTD inputs:
Data range
0 to Input span, 0.0 to Input span or
0.00 to Input span (Unit: °C [°F])
Varies with the setting of the decimal point
position selection.
R/W
Voltage (V)/current (I) inputs:
0.0 to 1000.0 % of input span
R/W3600
0 to 3600 seconds or 0.0 to 1999.9 seconds
Factory
set value
TC/RTD:
Input span
V/I:
1000.0 %
TC/RTD:
0
V/I: 0.0 %
Varies with the setting of the
integral/derivative time decimal point position
R/W
0
selection.
R/W3600
0 to 3600 seconds or 0.0 to 1999.9 seconds
Varies with the setting of the
integral/derivative time decimal point position
R/W
0
selection.
R/W
TC/RTD inputs:
1 to Input span, 0.1 to Input span or
0.01 to Input span (Unit: °C [°F])
Varies with the setting of the
integral/derivative time decimal point position
R/W
selection.
Voltage (V)/current (I) inputs:
TC/RTD:
Input span
V/I:
1000.0 %
TC/RTD:
1
V/I: 0.1 %
0.1 to 1000.0 % of input span
R/W3600
0 to 3600 seconds or 0.0 to 1999.9 seconds
Varies with the setting of the
integral/derivative time decimal point position
R/W
0
selection.
R/W3600
0 to 3600 seconds or 0.0 to 1999.9 seconds
Varies with the setting of the
integral/derivative time decimal point position
R/W
0
selection.
R/W
1 to 3600 seconds
R/W
0: 0 to 5999 minutes
60
1
1: 0 to 11999 seconds
Set the data range of Memory area soak time
monitor and Area soak time.
R/W
0: “SToP” is displayed on the PV display.
1
1: “SToP” is displayed on the SV display.
IMR01Y06-E3
Continued on the next page.
75
Page 82
7. COMMUNICATION DATA LIST
Continued from the previous page.
Extension
number
321
322
323
324
325
326
331
332
333
334
340
341
342
343
344
349
Communication item
Bar graph display
Bar graph display resolution
Direct key 1
Direct key 2
Direct key 3
Unused
Direct key type
PV flashing display at input
error
Unused
Integrated operating time
monitor
Holding peak value ambient
temperature monitor
Power feed forward input
value monitor
Unused
Attri-
bute
R/W
R/W
R/W
R/W
R/W
R/W
R/W
RO
RO
RO
Data range
0: No display
Factory
set value
1
1: MV1 or MV2
2: PV
3: SV monitor
4: Deviation value
5: CT1 input value
6: CT2 input value
1 to 100 digit/dot
100
Becomes valid when the bar graph display is
“4: Deviation value,” “5: CT1 input value” or
“6: CT2 input value.”
0: Unused
1
1: A/M transfer key
(Type 1, Type 2)
0: Unused
1
1: MONI key (For type 1) or
R/L transfer key (For type 2)
0: Unused
1
1: AREA key (For type 1) or
RUN/STOP transfer key (For type 2)
1: Type 1
1
2: Type 2
Bit data
0
b0: Input error
b1 to b15: Unused
Data 0: Flashing display
1: Non-flashing display
[Decimal number: 0 to 1]
0 to 19999 hours
−10.0 to +100.0 °C
0.0 to 160.0 %
Display in the percentage of the load voltage
(rated value).
Continued on the next page.
76
IMR01Y06-E3
Page 83
Continued from the previous page.
Extension
number
350
351
352
353
354
355
356
357
358
359
360
511
Communication item
Startup tuning (ST)
ST proportional band
adjusting factor
ST integral time adjusting
factor
ST derivative time adjusting
factor
ST start condition
Automatic temperature rise
group
Automatic temperature rise
learning
Automatic temperature rise
dead time
Automatic temperature rise
gradient data
RUN/STOP group
Unused
7. COMMUNICATION DATA LIST
Attri-
bute
R/W
Data range
0: ST unused
Factory
set value
0
1: Execute once *
2: Execute always
* When the startup tuning is finished, the
setting will automatically returns to
“0: ST unused.”
The startup tuning (ST) function is activated
according to the ST start condition selected.
If control is other than position proportioning
control, set to RO (Only reading data is
possible).
R/W1.00
0.01 to 10.00 times
R/W1.00
R/W
R/W
0: Activate the startup tuning (ST) function
1.00
0
when the power is turned on; when
transferred from STOP to RUN; or when
the set value (SV) is changed.
1: Activate the startup tuning (ST) function
when the power is turned on; or when
transferred from STOP to RUN.
2: Activate the startup tuning (ST) function
when the set value (SV) is changed.
R/W
0 to 16
0
(0: Automatic temperature rise function OFF)
R/W
0: Unused
1
1: Learning *
* When the automatic temperature rise
learning is finished, the setting will
automatically returns to “0: Unused.”
If the Automatic temperature rise group
corresponds to “0: Automatic temperature rise
function OFF,” set to RO (Only reading data
is possible).
R/W
0.1 to 1999.9 seconds
R/W
0.1 to Input span/minutes
R/W
0 to 16
10.0
1.0
0
(0: Group RUN/STOP function OFF)
IMR01Y06-E3
77
Page 84
7. COMMUNICATION DATA LIST
Table 1: Digital input (DI) assignment
Set value DI 1 DI 2 DI 3 DI 4 DI 5 DI 6 DI 7
1
2
3
4
5
6
7
8
RUN/STOP: RUN/STOP transfer AUTO/MAN: Auto/Manual transfer REM/LOC: Remote/Local transfer
Memory area number selection
(1 to 8)
Memory
area set
Unused
RUN/STOPREM/LOC AUTO/MAN
RUN/STOPREM/LOC
RUN/STOPAUTO/MAN
REM/LOCAUTO/MAN
RUN/STOPUnused
REM/LOCUnused
AUTO/MANUnused
Interlock
release
Interlock
release
Interlock
release
Interlock
release
Interlock
release
Interlock
release
Table 2: Output assignment
Set value
1
Output 1
(OUT1)
Control output 1 Control output 2Event 1 Event 2 Event 3 Event 4
Output 2
(OUT2)
Digital output 1
(DO1)
Digital output 2
(DO2)
Digital output 3
(DO3)
Digital output 4
(DO4)
2
3
4
5
6
7
Control output 1 Control output 2Event 1 Event 2 Event 3 HBA
Control output 1 Control output 2Event 1 Event 2 HBA
Control output 1 Control output 2Event 1 HBA Event 3 Event 4
“Energized” or “De-energized” can be selected for the digital outputs (DO1 to DO4).
[Factory set value: Energized]
However, with the exception of “FAIL (de-energized, fixed).”
Invalid for a non-existing output/event function.
FAIL
(De-energized)
FAIL
(De-energized)
78
IMR01Y06-E3
Page 85
•
8. USAGE EXAMPLE
This chapter describes a usage example of CC-Link communication.
8.1 Handling Procedures
Preparations of
configuration instrument
Mounting and Wiring
Use Instruments Setting
Device Assignments
Program Creation
See 8.2 System Configuration (P. 80)
For mounting and wiring of the COM-JC,
see 3. MOUNTING (P. 5) and 4. WIRING (P. 8).
• For mounting and wiring of the controller (FB400),
see FB400/FB900 Installation Manual (IMR01W01-E).
• For mounting and wiring of PLC, see PLC
Instruction Manual.
For cable wiring of CC-Link network system,
see Instruction Manual of master instrument or
website of CC-Link Partner Association.
URL: http://www.cc-link.org/
See 5. SETTING (P.16) and 8.3 Use InstrumentsSetting (P. 81).
See 8.4 Device Assignments Example (P. 83).
See 8.5 Sample Program (P. 86).
IMR01Y06-E3 79
Page 86
8. USAGE EXAMPLE
8.2 System Configuration
In this usage example, described the following system configuration.
Mitsubishi PLC
MELSEC Q series
CPU unit
Q02HCPU
CC-Link system
Master local unit
QJ 61BT11N (Master station)
Station number: 0
Communication speed: 156 kbps
CC Link Ver. 1.10
Controller communication (RS-485: Modbus)
CC-Link communication converter
COM-JC
Remote device station
(Slave station)
Station number: 1
Communication speed: 156 kbps
1 station occupied 1 time
Controller 1
(Device address 1)
Controller (FB400)
Controller 2
(Device address 2)
Use instruments
• CC-Link communication converter: COM-JC ........................................................... 1
• Temperature controller: FB400 (Communication 1: with RS-485) ........ 2
• Mitsubishi Electric PLC MELSEC Q series
− CPU unit: Q02HCPU
− CC-Link system master local unit: QJ61BT11N
• CC-Link dedicated cable Ver. 1.10
• COM-JC and controller connection cable
80 IMR01Y06-E3
Page 87
8.3 Use Instruments Setting
Set the PLC, COM-JC and controller as the following.
PLC setting
For operating of CC-Link system master local unit QJ61BT11N and MELSEC sequencer
programming software GX Developer, see PLC Instruction Manual.
[CC-Link system master local unit QJ61BT11N setting]
Setting item Content
Station number 0
CC-Link communication speed 156 kbps
8. USAGE EXAMPLE
[Master station network parameter setting by GX Developer]
Setting item Content
Number of boards in module 1
Start I/O No 0000
Operational settings Parameter name: None
Data link disorder station setting: Clear
Case of CPU STOP setting: Refresh
Type Master station
CC-Link mode setting Remote net (Ver. 1 mode)
Total number of connected
1
modules
Number of retries 5
Number of automatic return
1
modules
Standby master station number Blank
Operation specification when
Stop
CPU is down
Scan mode specification Asynchronous
Delay time setting
Station information
[Number of COM-JC connection:
1 (Station number: 1)]
10 (500 µs)
Station type: Remote device station
Expanded cyclic setting: Single
Number of occupied stations: Occupies 1 station
Remote station points: 32 points
Reserved/invalid station select: No setting
Intelligent buffer select (word): No setting
IMR01Y06-E3
81
Page 88
8. USAGE EXAMPLE
[Automatic refresh parameter setting by GX Developer]
Setting item Content
Remote input (RX) refresh device X1000
Remote output (RY) refresh device Y1000
Remote register (RWr) refresh device W0
Remote register (RWw) refresh device W100
Special relay (SB) refresh device SB0
Special register (SW) refresh device SW0
COM-JC setting
[CC-Link communication conditions]
• Number of occupied station/extended cyclic: 1 station occupied 1 time (2 controllers assignment)
• Station number: 1
• CC-Link communication speed: 156 kbps
[Controller communication condition]
• Controller communication speed: 19200 bps (Factory set value)
For setting procedure, see 5. SETTING (P. 16).
Controller setting
[Controller communication conditions: Use communication 1 side]
• Device address: 1 (Controller 1) and 2 (Controller 2)
• Communication protocol: Modbus-RTU
• Communication speed: 19200 bps (Factory set value)
• Data bit configuration: Data 8-bit, Without parity bit, Stop 1-bit
For setting procedure, see FB400/FB900 Communication Quick Manual (IMR01W07-E).
82
IMR01Y06-E3
Page 89
8. USAGE EXAMPLE
8.4 Device Assignments Example
According to the contents set by 8.3 Use Instruments Setting, each device is assigned.
Assignment conditions
Station number of COM-JC: 1
Number of occupied station/extended cyclic: 1 station occupied 1 time (2 controllers assignment)
Y1018 Initialize data processing completion flag RY18
Y1019 Initialize data setting request flag RY19
Y101A Error reset request flag RY1A
Y101B Reserved RY1B
• •
• •
• •
Y101F RY1F
Communication item
Extension number for display
Extension number for setting
Remote input (RX)
address
Remote output
(RY) address
RY05
RY0B
84
IMR01Y06-E3
Page 91
Remote register (RWr, RWw)
CPU of PLC
For writes
W102 RWw2
W103 RWw3
For reads
W002 RWr2
W003 RWr3
8. USAGE EXAMPLE
COM-JC (Station number 1)
: The device that a COM-JC actually uses
1 station occupied 1 time
Device assignment table of remote register (RWw)
CPU
device number
W102
W103
For extension area setting of device address 1
(Controller 1)
For extension area setting of device address 2
(Controller 2)
Communication item
Device assignment table of remote register (RWr)
CPU
device address
W002
W003
For extension area display of device address 1
(Controller 1)
For extension area display of device address 2
(Controller 2)
Communication item
Remote register (RWw)
address
RWw2
RWw3
Remote register (RWr)
address
RWr2
RWr3
IMR01Y06-E3
85
Page 92
8. USAGE EXAMPLE
8.5 Sample Program
Program conditions
Station number of COM-JC: 1
Number of occupied station/extended cyclic:
1 station occupied 1 time (2 controllers assignment)
Automatic refresh device assignment: See 8.4 Device Assignments Example.
Special relay (M) assignment: M0: Extension number setting flag for display
M1: Measured value (PV)/Manipulated output value (MV1)
transfer
M2: Extension number setting flag for setting
Data register (D) assignment: D0: Measured value (PV) store of controller 1
D1: Measured value (PV) store of controller 2
D2: Manipulated output value (MV1) store of controller 1
D3: Manipulated output value (MV1) store of controller 2
Program operation
1. Store measured value (PV) and manipulated output value (MV1) to a data register.
2. Write in set value of controller 1 and set value (SV) of controller 2.
Controller 1 set value (SV): 150.0 °C
Controller 2 set value (SV): 200.0 °C
3. Change the controller to the control RUN.
86
IMR01Y06-E3
Page 93
q
Sample program
8. USAGE EXAMPLE
When the PLC initial processing (PLC STOP → RUN).
RST Y100F
SET Y1019
BKRSTM0 K3
When no initial data processing is finished with the initial data processing
requested.
Initialize data processing request flag (X1018: RX18) ON
Initialize data processing completion flag (Y1018: RY18) OFF
X1018 Y1018
SET Y1018
When the initial data processing is finished with no initial data processing
requested.
Initialize data processing request flag (X1018: RX18) OFF
Initialize data processing completion flag (Y1018: RY18) ON
X1018 Y1018
When the initial data processing is finished and the initial data setting is being
requested.
Initialize data setting completion flag (X1019: RX19) ON
Initialize data setting request flag (Y1019: RY19) ON
RST Y1018
X1019 Y1019
When the COM-JC is in the error state.
Error status flag (X101A: RX1A) ON
X101A
When the COM-JC is in the normal state and the error reset action is being
requested.
Error status flag (X101A: RX1A) OFF
Error reset re
X101A Y101A
uest flag (Y101A: RY1A) ON
RST Y1019
SET Y101A
RST Y101A
Control “STOP” of controller.
Trun off the control RUN/STOP transfer
(Y100F: RY0F).
Turn on the initialize data setting request
flag (Y1019: RY19).
Turn off the extension number setting flag
for display (M0).
Turn on the Initialize data processing
completion flag (Y1018: RY18).
Turn off the Initialize data processing
completion flag (Y1018: RY18).
Turn off the Initialize data setting request
flag (Y1019: RY19).
Turn on the error reset request flag
(Y101A: RY1A).
Turn off the error reset request flag
(Y101A: RY1A).
Continued on the next page.
IMR01Y06-E3
87
Page 94
8. USAGE EXAMPLE
Continued from the previous page.
When the COM-JC is in the remote ready state and no display extension
number setting is processed yet.
Remote ready (X101B: RX1B) ON
Extension number setting flag for display (M0) OFF
X101B M0 M1
When Measured value (PV)/Manipulated
output value (M1) is transferred to Measured
value (PV).
M1
When Measured value (PV)/Manipulated
output value (M1) is transferred to
Manipulated output value (M1).
The extension display completion flag (X100C: RX0C) is
turned OFF.
X100C
When the extension display is finished and the display extension
number has been set.
Extended display completion flag (X100C: RX0C) ON
Extension number setting flag for display (M0) ON
When Measured value (PV)/Manipulated
output value (M1) is transferred to Measured
X100C M0 M1
value (PV).
MOVW2 D0
MOVW3 D1
RST Y1000
SET Y1000
RST Y100C
SET Y100C
SET M0
Set the extension number for display.
Extension number 0: Turn off the
extension number setting bit 0
(Y1000: RY00) for measured value
(PV) display.
Set the extension number for display.
Extension number 1: Turn on the
extension number setting bit 0 (Y1000:
RY00) for manipulated output value
(MV1) display.
Only the bit (bit 0) necessary for
setting display extension No. “0”
or “1” is specified. Any
unspecified bit is assumed to be
the register initial value, “0.”
Turn off the extension display flag
(Y100C: RY0C).
Turn on the extension display flag
(Y100C: RY0C).
Extension number setting end for
display.
Turn on the extension number setting
flag for display (M0).
Store the measured value (PV) of
controller 1 into the data register D0.
Store the extension area for display
(W002: RWr2) of controller 1 into the
data register D0.
Store the measured value (PV) of
controller 2 into the data register D1.
Store the extension area for display
(W003: RWr3) of controller 1 into the
data register D1.
Continued on the next page.
88
IMR01Y06-E3
Page 95
N
Continued from the previous page.
M1
When a set of setting extension numbers are not processed yet.
Extension number setting flag for setting (M2) OFF
M2
When Measured value (PV)/Manipulated
output value (M1) is transferred to
Manipulated output value (M1).
MOVW2 D2
MOVW3 D3
FF M1
RST M0
SET Y1006
SET Y1007
MOVK1500 W102
MOVK2000 W103
8. USAGE EXAMPLE
Store the manipulated output value
(MV1) of controller 1 into the data
register D2.
Store the extension area for display
(W002: RWr2) of controller 1 into the
data register D2.
Store the manipulated output value
(MV1) of controller 2 into the data
register D3.
Store the extension area for display
(W003: RWr3) of controller 1 into the
data register D3.
Measured value (PV)/Manipulated
output value (M1) is inversely
transferred. Variables to be read are
alternately selected.
Turn off the extension number setting
flag for display (M0).
Set the extension number for setting.
Extension number 3: Turn on the
extension number setting bit 0 (Y1006:
RY06) for set value (SV) setting.
Turn on the extension number setting
bit 1 (Y1007: RY07)
Only the bits (bit 0 and bit 1)
necessary forsetting extension
o. “3” are specified. Any
unspecified bit is assumed to be
the register initial value, “0.”
Set “150.0 °C” to set value (SV) of
controller 1.
Write “1500” for extension area setting
(W102: RWw2) of controller 1.
Set “200.0 °C” to set value (SV) of
controller 2
Write “2000” for extension area setting
(W103: RWw3) of controller 2
Continued on the next page.
IMR01Y06-E3
89
Page 96
8. USAGE EXAMPLE
)
Continued from the previous page.
X100D
The extension setting completion flag (X100D: RX0D) is
turned OFF.
When the extension setting is finished and the setting extension
number has been set.
Extended setting completion flag (X100D: RX0D) ON
Extension number setting flag for setting (M2) ON
X100D M2 Y100F
RST Y100D
SET Y100D
SET M2
When control RUN/STOP (Y100F: RY0F
is transferred to control STOP.
SET Y100F
FEND
END
Turn off the extended setting flag
(Y100D: RY0D)
Turn on the extended setting flag
(Y100D: RY0D).
Extension number setting end for
setting. Turn on the extension number
setting flag for setting (M2).
Control “RUN” of controller.
Turn on the control RUN/STOP
transfer (Y100F: RY0F).
90
IMR01Y06-E3
Page 97
9. TROUBLESHOOTING
This section lists some basic causes and solutions to be taken when any problem would arise in this
instrument.
If you can not find a solution, please contact RKC sales office or the agent.
If the instrument is necessary to be replaced, observe the following warning.
To prevent electric shock or instrument failure, always turn off the system
power before replacing the instrument.
To prevent electric shock or instrument failure, always turn off the power
before mounting or removing the instrument.
To prevent electric shock or instrument failure, do not turn on the power until
all the wiring is completed.
To prevent electric shock or instrument failure, do not touch the inside of the
instrument.
All wiring must be performed by authorized personnel with electrical
experience in this type of work.
CAUTION
WARNING
!
Do not separate the mainframe from the terminal base with the power turned on. If so,
instrument failure may result.
IMR01Y06-E3 91
Page 98
9. TROUBLESHOOTING
COM-JC
Problem Probable cause Solution
FAIL lamp flashes
RUN lamp OFF
SD/RD lamp OFF
FAIL lamp ON
RUN lamp OFF
SD/RD lamp OFF
FAIL lamp flashes
RUN lamp ON
SD/RD lamp flashes
No connection, disconnection,
breakage or wrong wiring of
CC-Link cable
A termination resistor of CC-Link
is not connected
The number of occupied stations/
extended cyclic setting of the
COM-JC differs from that of the
master instrument (PLC).
The station number and
communication speed settings of
the COM-JC have been changed
during communication.
The station number and
communication speed settings of
COM-JC are out of their setting
ranges.
The CC-Link version of the
COM-JC differs from that of the
master instrument (PLC).
Confirm the connection method or
condition and connect correctly
Confirm the termination resistor,
and connected correctly
Coincide the number of occupied
stations/extended cyclic setting of
the COM-JC with that of the master
instrument (PLC).
• Turn on the power again.
• Return the switch setting to the
original setting.
Set the station number and
communication speed settings of
COM-JC to values within their
setting ranges.
Coincide the CC-Link version of the
COM-JC with that of the master
instrument (PLC).
RUN lamp flashes
FAIL lamp ON
Controller communication
(Between COM-JC and
controllers) is abnormal
Hardware abnormality or software
abnormality
• Check that the signal line of the
COM-JC and controller are
correctly connected.
• Check that the communication
setting (Address, protocol,
communication speed and data bit
configuration) of the COM-JC
coincides with that of the
controller.
• Confirm whether a termination
resistor is connected.
Replace the COM-JC with a new
one it in the abnormal state even
with the power turned on again.
92 IMR01Y06-E3
Page 99
10. SPECIFICATIONS
CC-Link communication
Protocol: CC-Link Ver. 2.00/Ver. 1.10
Communication speed: 156 kbps, 625 kbps, 2.5 Mbps, 5 Mbps, 10 Mbps
Communication distance: See table shown below
Communication speedMaximum network length
10 Mbps 100 m
5 Mbps 200 m
2.5 Mbps 400 m
625 kbps 900 m
Station number:1 to 61 (4 stations occupied 1 time, 4 stations occupied 2 times) 1 to 64 (1 station occupied 1 time)
(Between the DA and DB terminals: 110 Ω 1/2 W)
Communication data length:
See table shown below
Number of occupied
station/Extended cyclic
4 stations occupied 1 timeInput: 128-bit
4 stations occupied 2 times Input: 224-bit
1 station occupied 1 time Input: 32-bit
156 kbps 1200 m
Remote
Input/Output
(RX/RY)
Output: 128-bit
Output: 224-bit
Output: 32-bit
(RWr/RWw)
RWr: 16-word
RWw: 16-word
RWr: 32-word
RWw: 32-word
RWr: 4-word
RWw: 4-word
Remote
register
Number of
Controller
connection
8 controllers or
16 controllers
16 controllers or
32 controllers
1 controller or
2 controllers
Controller communication
Interface: Base on RS-485, EIA standard (Multi-drop connection is available.)
Protocol: Modbus-RTU
Synchronous method: Half-duplex start-stop synchronous type
Communication method: 2-wire system, half-duplex multi-drop connection
Communication speed: 9600 bps, 19200 bps, 38400 bps
Data bit configuration: Data 8-bit, Without parity bit, Stop 1-bit
Maximum connections: 31 controllers (FB400/FB900) [Device address setting: 1 to 31]
Connection method: Terminals
Termination resistor: Built-in terminal base of COM-JC [ON/OFF select with switch (120 Ω)]
Self-diagnostic function
Hardware error, Software error, RAM read/write error:Display: FAIL lamp ON
Communication error, Memory backup error, Configuration error (Cannot recognize
connection of a controller):
Display: RUN lamp flashes
Status: Hardware error flag (RXnF) “ON” on the CC-Link
IMR01Y06-E3 93
Page 100
10. SPECIFICATIONS
General specifications
Power supply voltage: 21.6 to 26.4 V DC [Including power supply voltage variation], (Rating 24 V DC)
Current consumption: 120 mA max. (at 24 V DC)
Rush current: 12 A or less
Insulation resistance: Between communication terminal and grounding:
20 MΩ or more at 500 V DC
Between power supply terminal and grounding:
20 MΩ or more at 500 V DC
Between power supply and communication terminals:
20 MΩ or more at 500 V DC
Withstand voltage: See table shown below
Time: 1 min.
Grounding terminal
Power terminal600 V AC
Communication terminal600 V AC 600 V AC
CC-Link ground terminal is for CC-Link communication, and be not
included in an above condition.
Power failure: A power failure of 20 ms or less will not affect the control action.
Memory backup: Backed up by non-volatile memory
Number of writing: Approx. 100,000 times.
Data storage period: Approx. 10 years
Vibration: Amplitude: < 1.5 mm (5 to 9 Hz)
Acceleration: < 5 m/s
2
(9 to 150 Hz)
Each direction of XYZ axes
Shock:Height 50 mm or less Each direction of XYZ axes (de-energized state)
Allowable ambient temperature:
−10 to +50 °C
Allowable ambient humidity:
5 to 95 % RH (Absolute humidity: MAX.W.C 29.3 g/m
3
dry air at 101.3 kPa)
Installation environment conditions:
Indoor use
Altitude up to 2000 m
Operating environment: Avoid the following conditions when selecting the mounting location.
• Rapid changes in ambient temperature which may cause condensation.
• Corrosive or inflammable gases.
• Direct vibration or shock to the mainframe.
• Water, oil, chemicals, vapor or steam splashes.
• Direct air flow from an air conditioner.
• Exposure to direct sunlight.
• Excessive heat accumulation.
Weight: Approx. 220 g
Dimensions: 30 × 125 × 109.5 mm (W × H × D)
Standard
Safety standard: UL: UL61010-1
cUL: CAN/CSA-C22.2 No.61010-1
CE marking: LVD: EN61010-1
EMC: EN61326
C-Tick:AS/NZS CISPR 11 (equivalent to EN55011)
94
IMR01Y06-E3
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.