RKC INSTRUMENT CB103, CB403, CB903 Instruction Manual

Digital Controller
CB103/CB403/CB903
INSTRUCTION MANUAL
An external protection device must be installed if failure of this instrument could result in damage to the instrument, equipment or
WARNING
injury to personnel.
All wiring must be completed before power is turned on to prevent electric shock, fire or damage to instrument and equipment.
This instrument must be used in accordance with the specifications to prevent fire or damage to instrument and equipment.
This instrument is not intended for use in locations subject to flammable or explosive gases.
Do not touch high-voltage connections such as power supply terminals, etc. to avoid electric shock.
RKC is not responsible if this instrument is repaired, modified or disassembled by other than factory-approved personnel. Malfunction can occur and warranty is void under these conditions.
This product is intended for use with industrial machines, test and
measuring equipment. (It is not designed for use with medical equipment and nuclear energy.)
This is a Class A instrument. In a domestic environment, this instrument
may cause radio interference, in which case the user may be required to take additional measures.
This instrument is protected from electric shock by reinforced insulation.
Provide reinforced insulation between the wire for the input signal and the wires for instrument power supply, source of power and loads.
Be sure to provide an appropriate surge control circuit respectively for
the following:
- If input/output or signal lines within the building are longer than 30 meters.
- If input/output or signal lines leave the building, regardless the length.
This instrument is designed for installation in an enclosed
instrumentation panel. All high-voltage connections such as power supply terminals must be enclosed in the instrumentation panel to avoid electric shock by operating personnel.
All precautions described in this manual should be taken to avoid
damage to the instrument or equipment.
All wiring must be in accordance with local codes and regulations.
All wiring must be completed before power is turned on to prevent
electric shock, instrument failure, or incorrect action. The power must be turned off before repairing work for input break and output failure including replacement of sensor, contactor or SSR, and all wiring must be completed before power is turned on again.
To prevent instrument damage of failure, protect the power line and the
input/output lines from high currents with a protection device such as fuse, circuit breaker, etc.
Prevent metal fragments or lead wire scraps from falling inside
instrument case to avoid electric shock, fire or malfunction.
Tighten each terminal screw to the specified torque found in the manual
to avoid electric shock, fire or malfunction.
For proper operation of this instrument, provide adequate ventilation for
heat dispensation.
Do not connect wires to unused terminals as this will interfere with
proper operation of the instrument.
Turn off the power supply before cleaning the instrument.
Do not use a volatile solvent such as paint thinner to clean the
instrument. Deformation or discoloration will occur. Use a soft, dry cloth to remove stains from the instrument.
To avoid damage to instrument display, do not rub with an abrasive
material or push front panel with a hard object.
When high alarm with hold action is used for Alarm function, alarm does
not turn on while hold action is in operation. Take measures to prevent overheating which may occur if the control device fails.
CAUTION
NOTICE
This manual assumes that the reader has a fundamental knowledge of the principles of electricity, process control, computer technology and communications.
The figures, diagrams and numeric values used in this manual are only for purpose of illustration.
RKC is not responsible for any damage or injury that is caused as a result of using this instrument, instrument failure or indirect damage.
RKC is not responsible for any damage and/or injury resulting from the use of instruments made by imitating this instrument.
Periodic maintenance is required for safe and proper operation of this instrument. Some components have a limited service life, or characteristics that change over time.
Every effort has been made to ensure accuracy of all information contained herein. RKC makes no warranty expressed or implied, with respect to the accuracy of the information. The information in this manual is subject to change without prior notice.
No portion of this document may be reprinted, modified, copied, transmitted, digitized, stored, processed or retrieved through any mechanical, electronic, optical or other means without prior written approval from RKC.
All Rights Reserved, Copyright © 1999, RKC INSTRUMENT INC.
IMCB11-E7
RKC INSTRUMENT INC.
®

1. PRODUCT CHECK

CB103 CB403 CB903
- - //Y
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10)
(1) Control action
F: PID action with autotuning (Reverse action) D: PID action with autotuning (Direct action)
(2) Input type, (3) Range code: Refer to 9. INPUT RANGE TABLE. (4) Control output [OUT1]
M: Relay contact T: Triac V: Voltage pulse 8: Current (4 to 20 mA DC) G: Trigger (for triac driving)
(5) Alarm 1 [ALM1], (6) Alarm 2 [ALM2]
N: No alarm H: Process high alarm A: Deviation high alarm J: Process low alarm B: Deviation low alarm K: Process high alarm with hold action C: Deviation high/low alarm L: Process low alarm with hold action D: Band alarm P: Heater break alarm (CTL-6 E: Deviation high alarm S: Heater break alarm (CTL-12 with hold action R: Control loop break alarm F: Deviation low alarm V: SV high alarm with hold action W: SV low alarm G: Deviation high/low alarm with hold action
(7) Auxiliary output [DO]
N: No auxiliary output 7: Current (0 to 20 mA DC) A to L: Temperature alarm output 8: Current (4 to 20 mA DC) (Refer to the above alarm code) Y: RUN/STOP status output
3
1
)
1
)
2
(8) Contact input
N: No contact input 2: RUN/STOP 1: STEP function (SV1/SV2 switching)
(9) Waterproof/Dustproof
N: No waterproof/Dustproof 1: Waterproof/Dustproof
(10) Case color
N: White A: Black
1
Heater break alarm can not be specified in case of ALM1. Also, it isn’t possible to
specify when control output is current output.
2
As control loop break alarm, only either the alarm 1 or alarm 2 is selected.
3
No auxiliary output is provided when control output is trigger output.
Check that power supply voltage is also the same as that specified when ordering.
<Accessories>
z Mounting frame (CB103): 1 (KCA100-526) z Mounting brackets (CB403/CB903): 2 * (KCA400-532) z Instruction manual (IMCB11-E7): 1
*CB903 waterproof/dustproof option: 4 pieces

2. MOUNTING

2.1 Mounting Cautions

(1) This instrument is intended to be used under the following environmental
conditions. (IEC61010-1)
[OVERVOLTAGE CATEGORY II, POLLUTION DEGREE 2] (2) Use this instrument within the following environment conditions:
Allowable ambient temperature: 0 to 50 °C
Allowable ambient humidity: 5 to 95 %RH
(Absolute humidity: MAX. W. C 29.3 g/m
Installation environment conditions: Indoor use, Altitude up to 2000 m (3) Avoid the following conditions when selecting the mounting location:
Rapid changes in ambient temperature which may cause condensation.
Corrosive or inflammable gases.
Direct vibration or shock to the mainframe.
Water, oil, chemicals, vapor or steam splashes.
Excessive dust, salt or iron particles.
Excessive induction noise, static electricity, magnetic fields or noise.
Direct air flow from an air conditioner.
Exposure to direct sunlight.
Excessive heat accumulation.
(4) Mount this instrument in the panel considering the following conditions:
Provide adequate ventilation space so that heat does not build up.
Do not mount this instrument directly above equipment that generates large
amount of heat (heaters, transformers, semi-conductor functional devices, large-wattage resistors.)
If the ambient temperature rises above 50 °C, cool this instrument with a forced air fan, cooler, etc. Cooled air should not blow directly on this instrument.
In order to improve safety and the immunity to withstand noise, mount this instrument as far away as possible from high voltage equipment, power lines, and rotating machinery.
High voltage equipment: Do not mount within the same panel. Power lines: Separate at least 200 mm. Rotating machinery: Separate as far as possible.
Mount this instrument in the horizontal direction for panel. If you did installation except a horizontal direction, this causes malfunction.
(5) If this instrument is permanently connected to equipment, it is important to
include a switch or circuit-breaker into the installation. This should be in close proximity to the equipment and within easy reach of the operator. It should be marked as the disconnecting device for the equipment.
3
dry air at 101.3 kPa)

2.2 Dimensions

r
91.8
CB103
(Unit: mm)
48
9.2
48
CB403
(Unit: mm)
48
(*1)
1
8.2 100
9.2
96
8.2
(*1)
1
100
CB903
(Unit: mm)
96
9.2
*2
96
*1 Rubber (option) *2 Up to four mounting brackets can be used.
z For mounting of the instrument, panel thickness must be between 1 to 10 mm.
(When mounting multiple instruments close together, the panel strength should be checked to ensure proper support.)
z Waterproof and dustproof are not effective when instruments are closely spaced.
(*1)
1
8.2 100
Individual Mounting
44.8
25
Close vertical mounting
61.6
44.8
L1=48×n3 n: Number of controllers (2 to 6)
Individual Mounting
44.8
91.8
91.8
25
Close vertical mounting
107.4
L1=48×n3 n: Number of controllers (2 to 6)
Individual Mounting
25
Close vertical mounting
107.4
L1=96×n4 n: Number of controllers (2 to 6)
0
+0.6
45
+0.6
0
25
45
25 25
+0.6
L1
0
+0.6
45
0
0
+0.8
92
30
+0.6
0
L1
+0.8
0
92
0
+0.8
92
30
+0.8
0
L1

2.3 Mounting Procedures

CB103
<Mounting Procedures>
1. Prepare the panel cutout as specified in 2.2 Dimensions.
2. Insert the instrument through the panel cutout.
3. Insert the mounting frame into the mounting from the rear of the instrument.
4. Push the mounting frame forward until the frame is firmly secured to the
panel. (Fig.1)
5. Fix the instrument to the panel by using the two screws. (Fig.2)
Fig.1
Mounting frame
The waterproof/dustproof option on the front of the instrument conforms to IP66 when mounted on the panel. For effective waterproof/dustproof, the gasket must be securely placed between instrument and panel without any gap. If the gasket is damaged, please contact RKC sales office or the agent.
<Removal Procedures>
1. Turn the power OFF.
2. Remove the wiring.
3. Loosen the screw of the mounting frame.
4. Remove the mounting frame from the case. (Fig.3)
CB403/CB903
<Mounting Procedures>
1. Prepare the panel cutout as specified in 2.2 Dimensions.
2. Insert the instrument through the panel cutout.
Fig.2
Screw
When using the mounting screws, only turn one full revolution after the screw touches the panel.
Fig.3
d
3. Insert the mounting bracket into the mounting groove of the instrument. Do not
push the mounting bracket forward. (Fig. 1)
4. Secure the bracket to the instrument by tightening the screw. Take care to
refrain from moving the bracket forward.
5. Only turn about one full revolution after the screw touches the panel. (Fig. 2)
If the screw has been rotated too tight, the screw may turn idle. In such a case, loosen the screw once and tighten it again until the instrument is firmly fixed.
6. The other mounting bracket should be installed in the same way as described
in 3. to 5.
0
+0.6
45
When the instrument is mounted, always secure with two mounting brackets so that upper and lower mounting brackets are positioned diagonally.
The waterproof/dustproof option (CB903: mounting bracket 4 pieces) on the front of the instrument conforms to IP65 when mounted on the panel. For effective waterproof/dustproof, the gasket must be securely placed between instrument and panel without any gap. If gasket is damaged, please contact RKC sales office or the agent.
<Removal Procedures>
1. Turn the power OFF.
2. Remove the wiring.
0
+0.8
3. Loosen the screw of the mounting bracket.
92
4. Hold the mounting bracket by the edge (c) and tilt it (d) to remove from the
case. (Fig. 3)
5. The other mounting bracket should be removed in the same way as described
in 3. and 4.
6. Pull out the instrument from the mounting cutout while holding the front panel
frame of this instrument. (Fig. 4)
Fig. 3
d
c
Panel
Pull out
0
+0.8
92
Front panel
frame

3. WIRING

3.1 Wiring Cautions

For thermocouple input, use the appropriate compensation wire.
For RTD input, use low resistance lead wire with no difference in resistance
between the three lead wires.
To avoid noise induction, keep input signal wire away from instrument power
line, load lines and power lines of other electric equipment.
If there is electrical noise in the vicinity of the instrument that could affect
operation, use a noise filter.
- Shorten the distance between the twisted power supply wire pitches to achieve the most effective noise reduction.
- Always install the noise filter on a grounded panel. Minimize the wiring distance between the noise filter output and the instrument power supply terminals to achieve the most effective noise reduction.
- Do not connect fuses or switches to the noise filter output wiring as this will reduce the effectiveness of the noise filter.
Instrument power
Allow approximately 4 seconds for contact output when the instrument is turned on. Use a delay relay when the output line is used for an external interlock circuit.
Power supply wiring must be twisted and have a low voltage drop.
This instrument is not furnished with a power supply switch or fuses. If a fuse or
power supply switch is required, install close to the instrument.
- Fuse type: Time-lag fuse
- Recommended fuse rating: Rated voltage 250 V Rated current: 1 A
For the current input specification, an external resistor (250 Ω ±0.02 %, 0.25 W or more, ±10 ppm/°C) must be connected between the input terminals. For
c
c
external resistor (shunt resistor), use the KD100-55: sold separately (RKC product). If this resistor is installed, close horizontal mounting is not possible.
For an instrument with 24 V power supply, supply power from a SELV circuit.
A suitable power supply should be considered in end-use equipment. The
power supply must be in compliance with a limited-energy circuits (maximum available current of 8 A).
Use the solderless terminal appropriate to the screw size.
- Screw size: M3 x 6
- Recommended tightening torque: 0.4 Nxm [4 kgfxcm]
- Specified solderless terminals: With isolation
Make sure that the any wiring such as solderless terminal is not in contact
with the adjoining terminals.
ten distance between
Sho pitches
Twist these leadwires
IN
Noise filter
OUT
Minimize distance
Fig.2Fig.1
Fig. 4
Instrument power terminals
2 IMCB11-E7

3.2 Terminal Configuration

A
/
V
V
/
V
A
A
A
/
r
A
A
y
CB103
1
13
7
2
14
8
3
15
9
4
16
10
5
17
11
6
12
18
NO: Normally open
Power terminals
L
C
1
24 V
2
N
CB403
1 2 3 4 5 6 7 8
9 10 11 12
CB903
13
1
14
2
15
3
16
4
17
5
18
6
19
7
20
8
21
9
22
10
23
11
24
12
NC: Normally closed
DC
1
24 V
2
C
L
100 - 240 V
N
13 14 15 16 17 18 19 20 21 22 23 24
1
2
Auxiliary output terminals (optional)*
Relay contact
DO
3
NO
4
Alarm output (ALM3) RUN/STOP state output
No auxiliary output is provided when control output is trigger output.
Specifications
Input:
Input type:
Thermocouple:
K, J, R, S, B, E, T, N, PLII, W5Re/W26Re, U, L Input impedance: Approx. 1 MΩ
RTD:
Pt100, JPt100
Voltage:
0 to 5 V DC, 1 to 5 V DC, 0 to 10 V DC (Z-1010)
Current:
0 to 20 mA DC, 4 to 20 mA DC
Sampling cycle: 0.5 seconds Input range: Refer to Input range table
Control method: PID control, ON/OFF, P, PI,
or PD actions is available
Control output:
Relay contact output: 250 V AC, 3A (Resistive load), 1a contact Electrical life: 300,000 times or more (Rated load) Voltage pulse output: 0/12 V DC (Load resistance 600 Ω or more) Current output: 4 to 20 mA DC (Load resistance 600 Ω or less) Trigger output (for triac driving): Zero cross method for medium capacity triac driving (100 A or less) Load voltage used: 100 V AC line, 200 V AC line Load used: Resistive load
Current
AO
3
0 to 20 mA DC
4 to 20 mA DC
4
Analog output
or
Control output terminals
Trigge
T2
T1
G
OUT1
Triac
Voltage pulse
Current
4
OUT1
5
Triac out
6
5
OUT1
6
Rela
contact
OUT1
5
6
5
NO
6
Alarm output terminals (optional)
7
Alarm 2
Alarm 1
NO
ALM 2
8
NO
ALM 1
9
Input terminals
Voltage
11
0 to 5 V DC
or
IN
1 to 5 V DC
12
Triac output:
0.5 A (Ambient temperature: 40 °C or less)
RTD
10
A
RTD B
11
B
12
Alarm output (option):
Relay contact output: 250 V AC, 1A (Resistive load), 1a contact Electrical life: 50,000 times or more (Rated load)
Auxiliary out put (option)
Relay contact output rated: 250 V AC, 3 A (Resistive load), 1a contact Current output rated: 0 to 20 mA DC or 4 to 20 mA DC (Load resistance 600 Ω or less)
Contact input (option):
Dry contact input rated At open 500 kΩ or more At close 10 Ω or less
Performance:
Display accuracy
(at the ambient temperature 23 °C ± 2 °C): Thermocouple:
± (0.3 % of display value + 1 digit) or ± 2 °C [4 °F] Whichever is greater
R, S and B input: 0 to 399 °C [0 to 799 °F] Accuracy is not guaranteed. T and U input:
199.9 to 100.0 °C [199.9 to 158.0 °F] Accuracy is not guaranteed.
Contact input terminals (optional)
13
DI
15
Current transformer input terminals (optional)
CB103
17
CT1
18
Thermocouple
11
TC
12
RTD:
± (0.3 % of display value + 1 digit) or ± 0.8 °C [1.6 °F] Whichever is greater
Voltage/Current:
± (0.3 % of span + 1 digit)
CB403/CB903
23
CT1
24
Current
11
0 to 20 mA DC
4 to 20 mA DC
12
External resistor
or
Memory backup:
Backed up by Nonvolatile Memory Number of write times: Approx. 1,000,000 times Data storage period: Approx. 10 years
Power:
Power supply voltage:
85 to 264 V AC (Power supply voltage range), 50/60 Hz Rating: 100 to 240 V AC
21.6 to 26.4 V AC (Power supply voltage range), 50/60 Hz Rating: 24 V AC
21.6 to 26.4 V DC (Power supply voltage range) Rating: 24 V DC
Power consumption:
7 VA max. (at 100 V AC), 10 VA max. (at 240 V AC) 5 VA max. (at 24 V AC), 160 mA max. (at 24 V DC)
Weight:
CB103: Approx. 170 g CB403: Approx. 250 g CB903: Approx. 340 g

4. PARTS DESCRIPTION

Measured value (PV) display [Green]
P
S
T
OUT1
SET
R
S
CB100
5
4
6
PV
S
T
OUT1
SET
R
S
CB900
5 4
1
STEP
2
ALM1
DO
ALM2
3
7
STEP
ALM1
ALM2
DO
PV
STEP
SV
T
SET
CB400
1
2
5 4
OUT1
DO
LM2
ALM1
R
S
6
7
3
7 6
c
Displays PV or various parameter symbols. The decimal point at the least significant digit lights in
1
the step state (while the contact input closed).
d Set value (SV) display [Orange]
2
Displays SV, STEP set value (SV2), or various parameter set values (or CT input value).
3
Indication lamps
e
Alarm output lamps (ALM1, ALM2) [Red]
ALM1: Lights when alarm 1 output is turned on. ALM2: Lights when alarm 2 output is turned on.
Autotuning (AT) lamp [Green]
Flashes when autotuning is activated. (After autotuning is completed: AT lamp will go out)
Control output lamps (OUT1) [Green]
OUT1: Lights when control output is turned on.*
* Lamp indication becomes as follows for current
output. For an output of less than 0 %: Extinguished For an output of more than 100 %: Lit For an output of more than 0 % but less than 100 %: Dimly lit.
IMCB11-E7 3
Auxiliary output lamp (DO) [Green]
DO: Lights when first auxiliary output (alarm 3
[ALM3], RUN/STOP state output) is turned on. When the analog output is selected as an auxiliary output, the DO lamp does not light.
f
g
(Set key)
SET
Used for parameter calling up and set value registration.
R/S
(Shift & R/S key)
Shift digits when settings are changed. Select the RUN/STOP function.
(DOWN key)
h
Decrease numerals.
(UP key)
i
Increase numerals.
To avoid damage to the instrument, never use a sharp object to press keys.

5. SETTING

JPt
t
t
Set Val
(SV1)
Set Val
(SV2)

5.1 Operation Menu

Input type and Input range Display
The controller will display the M easured value (PV) and the Set value (SV). The controller will displa y the Measured value (PV) and the Set value (SV). If the ST EP function is provided, the SV display will shows the Set value (SV1) or STEP set value (SV2) depending on whether the contact input is opened or closed.
Display in STEP State:
PV
SV
PV/SV monitor
(RUN mode)
Press and hold the <R/S key for 1 second.
SV
Factory set value: RUN
Input type and input range display
When the instrument is powered on, it immediately confirms the input type and input range Example: When sensor type of input is K thermocouple.
PV
SV
Power ON
SV Setting Mode
Automatically (in 4 sec)
PV/SV Display Mode
Digital poin
:
ON
This decimal point indicates that the instrument is in the STEP state. It also lights in the STEP state while Parameter setting mode are being displayed.
Press the SET key
STOP character display (STOP mode)
Display returns to the PV/SV display mode if no key operation is performed within 1 minute.
Symbol
Automatically
Input type symbol *
Unit for input and SV display (Celsius: °C, Fahrenheit: °F, Voltage/Current inputs: no character shown)
PV
SV
Input range high
Input range low
This is the mode used to set the Set v alue (SV).
Without STEP function:
Press the SET key
Press the SET key
Press and hold the SET key for 2 seconds.
PV
Factory Set Value: 0 °C [°F] or 0.0 °C [°F]
With STEP function:
If the STEP function is provided, th e following parameter symbols are d isplayed on the PV display.
SV
ue
SV
Press the SET key
ue
SV
SV1 Setting
SV2 Setting
SV Setting
* Input Type Symbol Table
Symbol
Input type
K J R S B E T N PL II
This mode is used to set the parameters such as alarms, PID constants, etc. (Refer to page 6.) The following parameter symbols are displayed as the SET key is pressed.
(CT1)
(AL1)
(AL2)
(AL2)
(HbA1)
(LbA)
(Lbd)
(ATU)
(STU)
(P)
Current transformer monitor
Press the SET key
Alarm 1 set value (ALM1)
Press the SET key
Alarm 2 set value (ALM2)
Press the SET key
Alarm 3 set value (ALM3)
Press the SET key
Heater break alarm 1 set value (HBA)
Press the SET key
Control loop break alarm (LBA) time
Press the SET key
LBA deadband
Press the SET key
Autotuning (AT)
Press the SET key
Self-tuning (ST)
Press the SET key
Proportional band
Parameters which are not related to existing functions on the controller are not displayed.
Thermocouple (TC)
Parameter Setting Mode
Press the SET key
W5Re/
U L
W26Re
Integral time
(I)
Press the SET key
Derivative time
Press the SET key
(D)
(Ar)
(Pb) Press the SET key
(Ao)
(AHS)
(ALS)
(LCK)
Return to the first parameter
100
Anti-reset windup
Press the SET key
Proportioning cycle
Press the SET key(T)
PV bias
Analog Output (Ao) Selection
Press the SET key
Analog output scale high (AHS)
Press the SET key
Analog output scale low (ALS)
Press the SET key
Set data lock
Press the SET key
RTD
P
(Current)
100
Voltage

5.2 Parameter List

Parameter symbols which are not related to existing functions on the controller are not displayed.
Symbol Name Setting range Description Factory set value
Current transformer
input 1
Alarm 1 set value (ALM1)
Alarm 2 set value (ALM2)
Alarm 3 set value (ALM3)
Heater break alarm 1 set value
1
(HBA) Control loop break
alarm (LBA) time
LBA deadband 3 TC/RTD inputs:
Autotuning (AT) 0: AT end or cancel
Self-tuning (ST) 0: Self-tuning OFF
Proportional band (P)
Integral time (I)
Derivative time (D)
Anti-reset windup (ARW)
Proportioning cycle (T)
PV bias (Pb) TC/RTD inputs:
0.0 to 100.0 A [Display only]
TC/RTD inputs: Deviation alarm, Process alarm, SV alarm:
−1999 to +9999 °C [°F] or
−199.9 to +999.9 ° C [°F] Voltage/Current inputs: Deviation alarm:
span to +span (Within 9999) Process alarm, SV alarm:
Same as input range
0.0 to 100.0 A
See *1.
0.1 to 200.0 minutes
2
See *2.
0 to 9999 °C [°F] Voltage/Current inputs: 0 to 100 % of span
1: AT start or execution
1: Self-tuning ON
TC/RTD inputs: 1 (0.1) to span or 9999 (999.9) °C [°F]
Voltage/Current inputs:
0.1 to 100.0 % of span 1 to 3600 seconds
(0 second: PD action)
1 to 3600 seconds (0 second: PI action)
1 to 100 % of proportional band (0 %: Integral action OFF)
1 to 100 seconds (Not displayed if the control output is current output.)
1999 to +9999 °C [°F] or
199.9 to +999.9 °C [°F]
Voltage/Current inputs:
span to +span
Display input value from the current transformer. [Displayed only when the instrument has the Heater break alarm]
Set the ALM1 set value, ALM2 set value,.and ALM3 set value.
For the alarm action type, refer to page 7. Alarm differential gap: TC/RTD inputs: 2 or 2.0 °C [°F] Voltage/Current inputs: 0.2 % of span
SV alarm can not be specified in case of ALM3. ALM3 is auxiliary output.
Alarm value is set by referring to input value from the Current transformer (CT). Used only for single-phase.
Set control loop break alarm set value.
Set the area of not outputting LBA. No LBA deadband functions with 0 set. Differential gap : TC/RTD inputs: 0.8 °C [°F ] Voltage/Current inputs: 0.8 % of span
Turns the autotuning ON/OFF.
Turns the self-tuning ON/OFF.
Set when PI, PD or PID control is performed. ON/OFF action control when set to 0 (0.0). ON/OFF action differential gap: TC/RTD inputs: 2 (0.2) °C [°F ] Voltage/Current inputs: 0.2 % of span
Set the time of integral act ion to eliminate the offset occurring in proportional control.
Set the time of derivative action to improve control stability by preparing for output changes.
Overshooting and undershooting are restricted by the integral effect.
Set control output cycle.
Sensor correction is made by adding bias value to Measured value (PV).
TC/RTD inputs: 50 (50.0)
Voltage/Current inputs:
5.0
0.0
8.0
0
0
0
TC/RTD inputs: 30 (30.0)
Voltage/Current inputs:
3.0
240
60
100
Relay contact output: 20 Voltage pulse output/
Trigger output for triac driving/Triac output: 2
0 or 0.0
4 IMCB11-E7
(
)
y
(
)
Symbol Name Setting range Description Factory set value
1
Heater Break Alarm (HBA) function
The HBA function monitors the current flowing through the load by a dedicated Current transformer (CT), compares the measured value with the HBA set value, and detects a fault in the heating circuit.
Low or No current flow (Heater break, malfunction of the control device, etc.):
When the control output is ON and the current transformer input value is equal to or less than the heater break determination point for the preset number of consecutive sampling cycle, an alarm is activated.
Over current or short-circuit:
When the control output is OFF and the current transformer input value is equal to or greater than the heater break determination point for the preset number of consecutive sampling cycle, an alarm is activated.
Precaution for HBA setting:
Displayed only for when HBA is selected as Alarm 2.
HBA is not available on a current output.
Set the set value to approximately 85 % of the maximum reading of the CT
input.
Set the set value to a slightly smaller value to prevent a false alarm if the power supply may become unstable.
When more than one heater is connected in parallel, it may be necessary to increase the HBA set value to detect a single heater failure.
When the current transformer is not connected, the HBA is turned on.
2
Control Loop Break Alarm (LBA) function
The LBA function is used to detect a load (heater) break or a failure in the external actuator (power controller, magnet relay, etc.), or a failure in the control loop caused by an input (sensor) break. The LBA function is activated when control output reaches 0 % (low limit with output limit function) or 100 % (high limit with output limit function). LBA monitors variation of the measured value (PV) for the length of LBA time. When the LBA time has elapsed and the PV is still within the alarm determination range, the LBA will be ON.
Precaution for LBA setting:
Displayed only for when LBA is selected as Alarm 1 or Alarm 2.
The LBA function can not be activated when AT function is turned on.
The LBA function is activated when control output reaches 0 % or 100 %.
The time required for the LBA output to turn on includes both the time from the initial occurrence of loop failure and the LBA setting time. Recommended setting for LBA is for the set value of the LBA to be twice the value of the Integral time (I).
If LBA setting time does not match the controlled object requirements, the LBA selling time should be lengthened. If setting time is not correct, the LBA will malfunction by turning on or off at inappropriate times or not turning on at all.
3
LBA Deadband function
The LBA may malfunction due to external disturbances. To prevent malfunctioning due to external disturbance, LBA deadband (LBD) sets a neutral zone in which LBA is not activated. When the Measured value (PV) is within the LBD area, LBA will not be activated. If the LBD setting is not correct, the LBA will not work correctly.
Alarm area Alarm area
Low High
A: During temperature rise: Alarm area During temperature fall: Non- alarm area
* TC/RTD inputs: 0.8 °C [°F] (fixed) Voltag e/Current inputs: 0.8 % of span (fixed)

5.3 Changing Parameter Settings

Procedures to change parameter settings are shown below.
To store a new value for the parameter, always press the SET key. The display changes to the next parameter and the new value will be stored.
A new value will not be stored without pressing SET key after the new value is displayed on the display.
After a new value has been displayed by using the UP and DOWN keys, the SET key must be pressed within 1 minute, or the new value is not stored and the display will return to the PV/SV monitor screen.
Analog output
(Ao) selection
Analog output scale high (AHS)
Analog output scale low (ALS)
Set data lock (LCK)
0: Measured value (PV) 1: Set value (SV) 2: Deviation value (DEV) 3: Manipulated output value (MV)
PV,SV: ALS to Setting limiter high (SLH) DEV: ALS to +span (within 9999) MV: ALS to 100.0
PV,SV: Setting limiter low (SLL) to AHS DEV: span (within 9999) to AHS MV: 0.0 to AHS
Parameters other than SV and Alarms 0: Unlock 1: Lock Alarms 0: Unlock 1: Lock SV 0: Unlock 1: Lock Initialization mode 0: Lock 1: Unlock
LBD differential gap*
Non-alarm area
A B
Set value (SV) LBD set value
B: During temperature rise: Non-alarm area
-
During temperature fall: Alarm area
Select the analog output type. Analog output is auxiliary output.
Set the analog output scale high.
Set the analog output scale low.
Performs set data change enable/disable.
0
Input range
(high limit)
Input range
(low limit)
0000
z Change the Set value (SV)
Change the Set value (SV) from 0 °C to 200 °C (No step function)
1. Select the SV setting mode
Press the SET key at PV/SV monitor screen until SV setting screen is displayed.
2. Shift the high-lighted digit
Press the <R/S key to high-light the hundreds digit. The high-lighted digit indicates which digit can be set.
3. Change the set value
Press the UP key to change the number to 2.
4. Store the set value
Press the SET key to store the new set value. The display returns to the PV/SV monitor screen.
z Change parameters other than the Set value (SV)
The changing procedures are the same as those of example 2 to 4 in the above "z Change the Set value (SV)". Pressing the SET key after the setting end shifts to the next parameter. When no parameter setting is required, return the instrument to the PV/SV display mode.
PV
SV
PV/SV monitor display (PV/SV display mode)
PV
SV
PV
SV
PV
SV
PV
STEP STEP
SV
SV setting display
SV setting mode
PV
STEP STEP
SV
PV
STEP STEP
SV
PV
STEP STEP
SV
PV/SV monitor displa
PV/SV display mode

6. OPERATIONS

z All mounting and wiring must be completed before the power is turned on.
If the input signal wiring is disconnected or short-circuited (RTD input only), the instrument determines that burnout has occurred.
Displays:
Upscale: Thermocouple input, RTD input (when input break)
Downscale: Thermocouple input (specify when ordering),
RTD input (when short-circuited), Voltage input (1 to 5 V DC), Current input (4 to 20 mA DC)
For the voltage (0 to 5 V DC, 0 to 10 V DC*) or current (0 to 20 mA DC) input, the display becomes indefinite (display of about zero value).
* Z-1010 specification
Outputs
Control output: OFF
Auxiliary output: Analog output:
RUN/STOP status output:
Alarm 3 output:
Alarm outp ut: Both of the Alarm 1 and Alarm 2 outputs of this instrument
z A power failure of 20 ms or less will not affect the control action.
When a power failure of more than 20 ms occurs, the instrument assumes that the power has been turned off. When power returns, the controller will retain the conditions that existed prior to shut down.
z The alarm hold action is activated when not only the power is turned
on or the SV is changed, including an SV change made with the STEP function.

6.1 Operation Procedures

1. Prior to starting operation, check that the mounting and wiring have been finished, and that the SV and various parameters have been set.
2. A power supply switch is not furnished with this instrument. It is ready to operate as soon as the power is turned on. (Factory set value: RUN).
This instrument holds the conditions that exist just before the power is turned on. For example, if the power is turned off in STOP mode, the instrument starts in STOP mode when the power is turned on again.
CAUTIONS
For 4 to 20 mA DC, a current of 4 mA is output and for 0 to 20 mA, the output becomes indefinite (output of about 0 mA).
Outputs the STOP state (OPEN).
Becomes the same as the following alarm output.
are turned on when burnout occurs regardless of any of the following actions taken. (High alarm, low alarm, etc.) In addition, when used for any purposes other than these alarms (event, etc.), specify the Z-124 specification (not to be forcibly turned on).
IMCB11-E7 5

6.2 RUN/STOP

RUN/STOP can be selected by contact input (optional) other than the key operation. In addition, at STOP the key operation and contact state are displayed on the PV display. Relationships between key operation, RUN/STOP and the characters to indicate the STOP state are shown in the following.
RUN/STOP
RUN
with Key
Operation
1
Contact input: Terminal No.13, 15
2
Characters in parentheses are those shown on the PV display:
Control, Alarm: Control OFF, Alarm OFF
Output: OUT1 output OFF
Autotuning (AT): AT canceled (The PID constants are not updated)
When operation is changed to the STOP mode by RUN/STOP selection, a parameter symbol to indicate the STOP mode is displayed on the SV display. Pressing the SET key with the STOP mode displayed can also check and change the Set value (SV).
STOP
(KSTP)
: Only contact input is in the STOP mode : Only key operation is in the STOP mode : Both key operation and contact inputs are in the STOP mode
Conditions when changed to STOP mode:
RUN/STOP display (Z-1018 specification):
RUN/STOP with Contact Input 1
RUN (Contact closed) STOP (Contact open)
RUN STOP
STOP is not displayed (dSTP)
STOP STOP
2
(SToP)
2
2

6.3 STEP Function (optional)

The controller has two Set value (SV). This STEP function selects these two Set values (SV) by contact input (terminal No.13, 15).
Contact open: Set value (SV1) Contact closed: STEP set value (SV2)

6.4 Auxiliary Output Function (optional)

One auxiliary output can be selected form among ALM3, analog output, and RUN/STOP mode output (RUN: contact closed, STOP: contact open).

6.5 Set Data Lock (LCK) Function

The set data lock restricts parameter setting changes by key operation. This function prevents the operator from making errors during operation. There are 8 set data lock levels. (refer to below)
Set value Parameters which can be changed
0000 All parameters [Factory set value]
0001 SV, Alarms (ALM1, ALM2, ALM3)
0010 All parameters except for Alarms (ALM1, ALM2, ALM3)
0011 SV
0100 All parameters except for SV
0101 Alarms (ALM1, ALM2, ALM3)
0110 All parameters except for SV and Alarms (ALM1, ALM2, ALM3)
0111 No parameters (All Locked)
HBA, LBA and LBD can be locked when any of 0001, 0011, 0101 and 0111 is set.
Set data lock can be changed in both RUN and STOP mode.
Parameters protected by Set data lock function are still displayed for monitoring.

6.6 Autotuning (AT) Function

Autotuning (AT) automatically measures, computes and sets the optimum PID and LBA constants. The following conditions are necessary to carry out autotuning and the conditions which will cause the autotuning to stop.
Caution for using the Autotuning (AT) When a temperature change (UP and/or Down) is 1 °C or less per minute during AT, AT may not be finished normally. In that case, adjust the PID values manually. Manual setting of PID values may also be necessary if the set value is around the ambient temperature or is close to the maximum temperature achieved by the load.
Requirements for AT start
Start the autotuning when all following conditions are satisfied:
Prior to starting the AT function, end all the parameter settings other than PID and LBA.
Confirm the LCK function has not been engaged.
When the autotuning is finished, the controller will automatically returns to PID control.
Requirements for AT cancellation
The autotuning is canceled if any of the following conditions exist.
When the Set value (SV) is changed.
When the PV bias value is changed.
When the RUN/STOP mode is changed to the STOP mode.
When the PV becomes abnormal due to burnout.
When the power is turned off.
When power failure longer than 20 ms occurs.
When the AT does not end in 9 hours after autotuning started.
If the AT is canceled, the controller immediately changes to PID control. The PID values will be the same as before AT was activated.
When AT is completed, the controller immediately changes to PID control. If the control system does not allow the AT cycling process, set each PID constant manually to meet the needs of the application.

6.7 Self-tuning (ST) Function

The ST function is used to automatically calculate and set adaptive PID constants anytime the power is turned on, the SV is changed or the controller detects unstable control conditions.
The ST function should be turned off when the controlled system is affected by rippling that occurs due to periodic external disturbances.
The power to the controlled system must be turned on before the power to the instrument is turned on or SV is changed. This is required when ST function is on.
To activate the ST function, the following parameters must not be set to zero: P0, I0, D0, ARW0.
When the AT function is activated, the ST function can not be turned on.
When the ST function is activated, the PID and ARW settings can be monitored, but not changed.

7. INITIAL SETTING

Parameters in the Initialization mode should be set according to the application before setting any parameter related to operation. Once the Parameters in the Initialization mode are set correctly, no further changes need to be made to parameters for the same application under normal conditions. If they are changed unnecessarily, it may result in malfunction or failure of the instrument. RKC will not bear any responsibility for malfunction or failure as a result of improper changes in the Initialization mode.

7.1 Go to Initialization Mode

1. Turn on the power to this controller. The instrument goes to the PV/SV display after confirming input type symbol and input range.
2. Press and hold the SET key for 2 seconds to go to the Parameter setting mode from the PV/SV display.
3. Press the SET key until “LCK” (Set data lock display) will be displayed.
4. The high-lighted digit indicates which digit can be
set. Press <R/S key to high-light the thousands digit. (The section in each image of the controller shows the digits which are not high-lighted.)
5. Press the UP key to change 0 to 1.
Set value 0: Initialization mode locked 1: Initialization mode unlocked
6. Press the SET key to store the new set value. The display goes to the next parameter, and the Initialization mode is unlocked. (The parameter displayed varies on the instrument specification.)
7. Press the <R/S key for 2 seconds while pressing the SET key to go to the Initialization mode. When the controller goes to the Initialization mode, “Cod” will be displayed.

7.2 Exit Initialization Mode

When any parameter setting is changed in the Initialization mode, check all parameter set values in SV setting mode and Parameter setting mode.
1. Press the <R/S key for 2 seconds while pressing the SET key from any display in the Initialization mode. The controller goes back to the operation mode and the PV/SV display will be displayed.
2. Press and hold the SET key for 2 seconds in the PV/SV display.
3. Press the SET key until “LCK” (Set data lock display) will be displayed.
4. The high-lighted digit indicates which digit can be set. Press <R/S key to
high-light the thousands digit. (The section in each image of the controller shows the digits which are not high-lighted.)
5. Press the DOWN key to change 1 to 0.
Set value 0: Initialization mode locked 1: Initialization mode unlocked
6. Press the SET key to store the new set value. The display goes to the next parameter, and the Initialization mode is locked. (The parameter displayed varies on the instrument specification.)
WARNING
PV
SV
CT1 input value display
STEP
PV
SV
Set data lock function dis play
PV
SV
PV
SV
CT1 input value display
PV
SV
Initialize code selection display
of initialization mode
PV
SV
Set data lock function display
PV
SV
CT1 input value display
STEP
STEP
STEP
STEP
STEP
STEP
6 IMCB11-E7

7.3 Initial Setting Menu

g
)
g
g
The “Cod” display will be displayed when the controller goes to the Initialization mode.
Do not change to any parameter in the Initialization mode which is not described in the initial setting menu above. It may result in malfunction or failure of the instrument.
Press the <R/S key while pressing th e SET key for 2 seconds with the unlocked.
Set Cod to 0000.
PV/SV display mode or Parameter setting mode
(Cod)
Input type selection
(SL1)
Alarm1 type selection
(SL4)
Alarm2 type selection
(SL5)
SV alarm type selection
(SL11)
Alarm3 type selection
(SL13)
Initialization code selection
Set Cod to 0001.
Setting limiter [high]
(SLH)
Setting limiter [low]
(SLL)
Decimal point position
(PGdP)
To PV/SV display mode
To PV/SV display mode
: Press the SET key, or press the SET key several times.
: Press the <R/S key while pressing the SET key for 2 seconds.

7.4 Input Type Selection (SL1)

When any parameter setting is changed in the Initialization mode, check all parameter set values in SV setting mode and Parameter setting mode.
Set value Input type Set value Input type
0000 K 0101 T 0001 J 0110 U 0010 L 1100 Pt100 Ω (JIS/IEC) 0011 E 1101 JPt100 Ω (JIS) 0100 N 1110 0 to 5 V DC 0111 R 1000 S 1111 1 to 5 V DC 1001 B 1110 0 to 20 mA DC 1010 W5Re/W26Re 1111 4 to 2 0 mA DC 1011 PL II
1
Any input change in TC&RT D group is possible. Any input change in Voltag e & Current group except for 0 to
10 V DC input is possible. No input change between TC&RTD group and Voltage & Current group is possible.
2
The input type of Z- 1010 specification is fixed to 0 to 10 V D C due to the hardware difference.
3
For the current input sp ecification, a resistor of 250 Ω m ust be connected between the input terminals .
Factory set value varies depending on the input type.
Thermocouple
1
(TC)
Initialization code selection
Thermocouple
1110 0 to 10 V DC 2
Voltage
Current
(TC)
RTD
1
1, 3
Change Settings
Example: Change the input type from “K” to “J”
1. Set “Cod” to 0000, and press the SET key. The display will go to SL1.
2. Press the UP key to change the number to 1.
3. Press the SET key to store the new set value.
The display goes to the next parameter.
PV
SV
Initialize code selection display
PV
STEP
SV
PV
SV
Input type selection
STEP
STEP
7.5 Alarm 1 [ALM1] Type Selection (SL4)
Alarm 2 [ALM2] Type Selection (SL5) Alarm 3 [ALM3] Type Selection (SL13)
If the alarm function is not provided with the instrument when shipped from the factory, no alarm output is available by changing SL4 and/or SL5.
SL4 is set to 0000 in the following cases.
When the instrument does not have ALM1 output
When Control Loop Break Alarm (LBA) is provided and assigned
to ALM1
When the SV alarm is provided and assigned to ALM1
SL5 is set to 0000 in the following cases.
When the instrument does not have ALM2 output
When Control Loop Break Alarm (LBA) is provided and assigned
to ALM2
When the SV alarm is provided and assigned to ALM2
When the Heater Break Alarm (HBA) is provided
When the instrument has Z-168 specification
SL13 is set to 0000 in the following cases.
When the instrument does not have ALM3 output
Set value Details of setting Set value Details of setting
* Hold action: When Hold action is ON, the alarm action is suppressed at start-up or the control set value change until the measured value enters the non-alarm range.
Factory set value varies depending on the instrument specification.
0000 No alarm 0111 Process low alarm 0001 Deviation high alarm 1001 Deviation high alarm with hold action * 0010 Deviation high/low alarm 1010 Deviation high/low alarm with hold action * 0011 Process high alarm 1011 Process high alarm with hold action * 0101 Deviation low alarm 1101 Deviation low alarm with hold action * 0110 Band alarm 1111 Process low alarm with hold action *
z Alarm action type
The Alarm 1, Alarm 2 and Alarm 3 outputs of this instrument are turned on when burnout occurs regardless of any of the following actions taken (High alarm, low alarm, etc.). In addition, when used for any purposes other than these alarms (event, etc.), specify the Z-124 specification (not to be forcibly turned on).
Deviation high alarm
(Alarm set value is greater than 0)
OFF
Low
Deviation low alarm
(Alarm set value is greater than 0)
ON
Low
Deviation high/low alarm
Low High
Process high alarm
Low
OFF ONON
OFF
ON
High
OFF
High
ON
Hi
h
: Alarm set value : Alarm differential gap)
( : SV
(Alarm set value is less than 0)
PV
PV
PV
PV
OFF
Low
(Alarm set value is less than 0)
ON
Low
Band alarm
OFF
Low
Process low alarm
ON
Low Hi
Change Settings
Example: Change the ALM1 type from “No alarm (0000)” to “Deviation high alarm (0001)”
1. Press the SET key several times at SL1 until SL4 is displayed.
2. Press the UP key to change
the number to 1.
3. Press the SET key to store the new set value. The display goes to the next parameter.

7.6 SV Alarm Type Selection (SL11)

For ALM1 setting, the first digit from the right is set to “0” in the following cases.
When the instrument does not have ALM1 output.
1
1
When the ALM1 output is used for Process/Deviation/Band alarm
z SV alarm action type
or Loop break alarm (LBA).
For ALM2 setting, the third digit from the right is set to “0” in the following cases.
When the instrument does not have ALM2 output.
When the ALM1 output is used for Process/Deviation/Band alarm,
Heater break alarm (HBA) or Loop break alarm (LBA).
When Z-168 is specified.
To make SV alarm setting effective, set SL4 to “0000” when using ALM1 for SV alarm, or set SL5 to “0000” when using ALM2 for SV alarm. SL4 and SL5 have priority to SL11 setting.
Factory set value varies depending on the instrument specification.
Alarm Details of setting
0 SV alarm not provided
Alarm 1 1 SV alarm provided
[ALM1] 0 SV high alarm
1 SV low alarm
0 SV alarm not provided
Alarm 2 1 SV alar m provided
[ALM2] 0 SV high alarm
1 SV low alarm
SV high alarm
Low
OFF ON
High
PV
SV
SV low alarm
SV
Low
ON
STEP
( : Alarm set value
Change Settings
Example: Change the SV alarm type of the ALM1 from “SV high alarm (0001)” to “SV low alarm (0011)”
1. Press the SET key several times at SL1 until SL11 is displayed.
2. Press the <R/S key to high-light
the tens digit. Next, press the UP key to change the number to 1.
3. Press the SET key to store the new set value. The display goes to the initialize code parameter.
PV
SV
STEP
High-light
7.7 Setting Limiter [High] (SLH)
Setting Limiter [Low] (SLL)
For voltage or current input, set scaling within the input range.
Refer to 9. INPUT RANGE TABLE.
K SLL to 1372 °C SLL to 2502 °F 0 to SLH °C 0 to SLH °F J SLL to 1200 °C SLL to 2192 °F 0 to SLH °C 0 to SLH °F R SLL to 1 769 °C SLL to 3216 °F 0 to SLH °C 0 to SLH °F
TC S SLL to 1769 °C SLL to 3216 °F 0 to SLH °C 0 to SLH °F B SLL to 1820 °C SLL to 3308 °F 0 to SLH °C 0 to SLH °F E SLL to 1000 °C SLL to 1832 °F 0 to SLH °C 0 to SLH °F N SLL to 1 300 °C SLL to 2372 °F 0 to SLH °C 0 to SLH °F T SLL to 400.0 °C SLL to 752.0 °F −199.9 to SLH °C −199.9 to SLH °F
Factory set value varies depending on the instrument specification.
Input type
Setting limiter [high] Setting limiter [low]
Setting range
ON
High
OFF
High
OFFON
High
OFF
: Alarm differential
PV
SV
OFF
h
High
PV
SV
PV
PV
PV
PV
STEP
ap
SV
STEP
IMCB11-E7 7
TC W5Re/W26Re SLL to 2 320 °C SLL to 4208 °F 0 to SLH °C 0 to SLH °F PLII SLL to 1390 °C SLL to 2 534 °F 0 to SLH °C 0 to SLH °F U SLL to 600.0 °C SLL to 999. 9 °F −199.9 to SLH °C −199.9 to SLH °F L SLL to 900 °C SLL to 1652 °F 0 to SLH °C 0 to SLH °F
RTD Pt100 JPt100
Voltage 0 to 5 V DC 0 to 10 V DC * 1 to 5 V DC Current 0 to 20 mA DC 4 to 20 mA DC
* Z-1010 specification
Change Settings
Example: When the display range is scaled to 0.0 to 400.0 for a voltage input of 1 to 5 V DC.
1V 5 V
1. Set Cod to 0001, and
2. The high-lighted digit indicates which digit can be
3. Press the UP key to change the number to 4.
4. Press the SET key to store the new set value. The display goes to SLL.
5. Set SLL to 0.0.
6. Press the SET key to store the new set value. The display goes to the next

7.8 Decimal Point Position (PGdP)

Use to select a Decimal point position of the input range (voltage input and current input). PGdP is displayed only for voltage or current input.
Set value Description
Factory set value varies depending on the instrument specification.
Input type
Factory set value 0.0 100.0 Scaling 0.0 400.0
press the SET key. The display will go to SLH.
set. Press <R/S key to high-light the first digit from the left. (The **** section in each image of the controller shows the digits which are not high-lighted.)
Setting limiter [high] Setting limiter [low]
SLL to 649.0 °C SLL to 9 99.9 °F −199.9 to SLH °C −199.9 to SLH °F
SLL to 9999
(Programmable scale)
Setting range
PV
SV
Initialize code selection display
STEP
1999 to SLH
(Programmable scale)
PV
SV
Setting limiter [high ] display
PV
SV
PV
SV
parameter.
Inappropriate settings may result in malfunction.
0000 No decimal place () 0001 One decimal place (.) [Factory set value] 0002 Two decimal places (.) 0003 Three decimal places (.)

9. INPUT RANGE TABLE

zTC/RTD inputs
Input type Range Code Range Code Range Code
K 0 to 200 °C K 01 0 to 400 °C K 02 0 to 600 °C K 03
TC
STEP
STEP
STEP
W5Re/W26Re
RTD
1
Accuracy is not guaranteed between 0 to 399 °C (0 to 751 °F).
2
Accuracy is not guaranteed between −199.9 to −100.0 °C (199.9 to −148 °F).
0 to 800 °C K 04 0 to 1000 °C K 05 0 to 1200 °C K 06
0 to 1372 °C K 07 0 to 100 °C K 13 0 to 300 °C K 14
0 to 450 °C K 17 0 to 500 °C K 20 0 to 800 °F K A1 0 to 1600 °F K A2 0 to 2502 °F K A3 20 to 70 °F K A9
J 0 to 200 °C J 01 0 to 400 °C J 02 0 to 600 °C J 03
0 to 800 °C J 04 0 to 1000 °C J 05 0 to 1200 °C J 06
0 to 450 °C J 10 0 to 800 °F J A1 0 to 1600 °F J A2 0 to 2192 °F J A3 0 to 4 00 °F J A6 0 to 300 °F J A7
1
0 to 1600 °C R 01 0 to 1769 °C R 02 0 to 1350 °C R 04
R
0 to 3200 °F R A1 0 to 3216 °F R A2 ⎯ ⎯
1
0 to 1 600 °C S 01 0 to 1769 °C S 02 0 to 3200 °F S A1
S
0 to 3216 °F S A2 ⎯ ⎯ ⎯ ⎯
1
400 to 1800 °C B 01 0 to 1820 °C B 02 800 to 3200 °F B A1
B
0 to 3308 °F B A2 ⎯ ⎯ ⎯ ⎯
E 0 to 800 °C E 01 0 to 1 000 °C E 02 0 to 1600 °F E A1
0 to 1832 °F E A2 ⎯ ⎯ ⎯ ⎯
N 0 to 1200 °C N 01 0 to 1300 °C N 02 0 to 2300 °F N A1
0 to 2372 °F N A2 ⎯ ⎯ ⎯ ⎯
2
199.9 to +400.0 °C T 01 199.9 to +100.0 °C T 02 100.0 to +200.0 °CT03
T
0.0 to 350.0 °C T 04 199.9 to +752.0 °F T A1 100.0 to +200.0 °FTA2
100.0 to +400.0 °F T A3 0.0 to 450.0 °F T A4 0.0 to 752.0 °FTA5
0 to 2000 °C W 01 0 to 2320 °C W 02 0 to 4000 °F W A1
0 to 1300 °C A 01 0 to 1 390 °C A 02 0 to 1200 °C A 03
PLII
0 to 2400 °F A A1 0 to 2534 °F A A2 ⎯ ⎯
2
199.9 to +600.0 °C U 01 199.9 to +100.0 °C U 02 0.0 to 400.0 °CU03
U
199.9 to +999.9 °FUA1 −100.0 to +200.0 °F U A2 0.0 to 999.9 °FUA3
L 0 to 400 °C L 01 0 to 800 °C L 02 0 to 800 °F L A1
0 to 1600 °F L A2 ⎯ ⎯ ⎯ ⎯
Pt100 199.9 to +649.0 °C D 01 199.9 to +200.0 °C D 02 −100.0 to +50.0 °CD03
100.0 to +100.0 °C D 04 100.0 to +200.0 °C D 05 0.0 to 50. 0 °C D 06
0.0 to 100.0 °C D 07 0.0 to 200.0 °C D 08 0.0 to 300.0 °CD09
0.0 to 500.0 °C D 10 −199.9 to +999.9 °F D A1 −199.9 to +400.0 °FDA2
199.9 to +200.0 °FDA3 −100.0 to +100.0 °F D A4 −100.0 to +300.0 °FDA5
0.0 to 100.0 °F D A6 0.0 to 200.0 °F D A7 0.0 to 400.0 °FDA8
0.0 to 500.0 °FDA9 ⎯ ⎯ ⎯ ⎯
199.9 to +649.0 °C P 01 199.9 to +200.0 °C P 02 − 100.0 to +50.0 °CP03
JPt100
100.0 to +100.0 °C P 04 100.0 to +200.0 °C P 05 0.0 to 50.0 °C P 06
0.0 to 100.0 °C P 07 0.0 to 200.0 °C P 08 0.0 to 300.0 °CP09
0.0 to 500.0 °C P 10 ⎯ ⎯ ⎯ ⎯
zVoltage/current inputs
Type Range Code Type Range Code
0 to 5 V DC 0.0 to 100.0 % 4 01 0 to 20 mA DC 0.0 to 100.0 % 7 01
0 to 10 V DC 1 0.0 to 100.0 % 5 01 4 to 20 mA DC 0.0 to 100.0 % 8 01
1 to 5 V DC 0.0 to 100.0 % 6 01 ⎯ ⎯
1
Z-1010 specification.

10. REMOVING THE INTERNAL ASSEMBLY

Change Settings
Example: Change the Decimal point position from “One decimal place (0001)” to “No decimal place (0000)”
1. Press the SET key two times at SLH until PGdP is displayed.
2. Press the UP key to
change the number to 0.
PV
SV
PV
STEP
SV
STEP
3. Press the SET key to store the new set value. The display goes to the next parameter.

8. ERROR DISPLAYS

Error display
Over-scale and Underscale
Measured value (PV)
[Flashing]
[Fashing]
[Fashing]
RAM failure (Incorrect set data write, etc.)
PV is outside of input range.
Over-scale: PV is above the high input display range limit.
Underscale: PV is below the low input display range limit.
Turn off the power at once. If an error occurs after the power is turned on again, please contact RKC sales office or the agent.
Check Input type, Input range and connecting state of sensor. Confirm that the sensor or wire is not broken.
WARNING
!
To prevent electric shock, always turn off the power before replacing the sens or.
Usually, this instrument is not necessary to remove the internal assembly from the case. When removing the internal assembly without disconnecting the external wiring, take the following steps.
z To prevent electric shock or instrument failure, only qualified
personnel should be allowed to pull out the internal assembly.
z To prevent electric shock or instrument failure, always turn off the
power before pulling out the internal assembly.
z To prevent injury or instrument failure, do not touch the internal
printed wiring board.
Lock (upper)
Recommended tool: Blade screwdriver
Lock (lower)
Unlock using such a blade screwdriver. Gently press down on handle for the upper lock and lift up for the lower lock.
Apply pressure very carefully when removing internal assembly to avoid damage to the frame.
To conform to IEC61010-1 requirements for protection from electric shock, the internal assembly of this instrument can only be removed with an appropriate tool.
(Blade width: 6 mm or less)
WARNING
Unlocking points (marked with “{”) depend on the model as follows:
The first edition: The seventh edition: NOV. 2009 [IMQ00]
CB403
CB103
APR. 1999 [IMQ00]
CB903
RKC INSTRUMENT INC.
®
IMCB11-E7 NOV. 2009
HEADQUARTERS: 16-6, KUGAHARA 5-CHOME, OHTA-KU TOKYO 146-8515 JAPAN
PHONE: 03-3751-9799 (+81 3 3751 9799) E-mail: info@rkcinst.co.jp
FAX: 03-3751-8585 (+81 3 3751 8585)
Loading...