RKC Z-TIO Instruction Manual

Module Type Controller SRZ
A
Temperature Control Module [for Host Communication]
ll Rights Reserved, Copyright 2006, RKC INSTRUMENT INC.
Z-TIO
Host Communication Quick Instruction Manual
IMS01T02-E3
Thank you for purchasing this RKC product. In order to achieve maximum performance and ensure proper operation of your new instrument, carefully read all the instructions in this manual. Please place this manual in a convenient location for easy reference.
The above manuals can be downloaded from our website: URL: http://www.rkcinst.com/english/manual_load.htm
1. COMMUNICATION SETTING
Set communication setting before mounting and wiring of the Z-TIO.
CAUTION
Do not separate the module mainframe from the base with the power turned on. If so, instrument failure may result.
1.1 Module Address Setting
Set an address for the module using a small blade screwdriver.
Address setting switch
Setting range: 0 to F [0 to 15: Decimal]
For Modbus, the value obtained by adding “1” to the set address corresponds to the address used for the actual program.
To avoid problems or malfunction, do not duplicate an address on the same communication line.
1.2 Protocol Selections and Communication Speed Setting
Use the DIP switch on the right side of module to select communication speed, data bit configuration and protocol. The data changes become valid when the power is turned on again or when changed to RUN/STOP.
Right side view
(The above figure is for the terminal type. Howe ver, the switch positions are the same for the connector type.)
1 2 Communication speed
OFF OFF 4800 bps
ON OFF 9600 bps
OFF ON 19200 bps
ON ON 38400 bps
Factory set value: 19200 bps
3 4 5 Data bit configuration
OFF OFF OFF Data 7-bit, without parity, Stop 1-bit *
ON OFF OFF Don't set this one
OFF ON OFF Data 7-bit, Even parity, Stop 1-bit *
ON ON OFF Data 7-bit, Odd parity, Stop 1-bit *
OFF OFF ON Data 8-bit, without parity, Stop 1-bit
ON OFF ON Don't set this one
OFF ON ON Data 8-bit, Even parity, Stop 1-bit
ON ON ON Data 8-bit, Odd parity, Stop 1-bit
* When the Modbus communication protocol is selected, this setting becomes invalid.
Factory set value: Data 8-bit, without parity, Stop 1-bit
6 Protocol
OFF RKC communication
ON Modbus
Factory set value: RKC communication
Switch No. 7 and 8 must be always OFF. Do not set to ON.
When two or more modules are connected on the same communication
line, the DIP switch settings of all modules must be the same.
Factory set value: 0
Module mainframe
DIP switch
1 234567
8
ON OFF
ON
2. CONNECTION TO HOST COMPUTER
To prevent electric shock or instrument failure, turn off the power before connecting or disconnecting the instrument and peripheral equipment.
Connect a termination resistor between the communication terminals (No.3 and No. 4) of the module at the end of the communication line from the host computer.
The cable must be provided by the customer.
The Z-TIO has RS-485 communication terminals for RKC communication or Modbus/RTU communication protocol. Communication terminals are on the base side.
Connection to the RS-485 port of the host computer (master)
Up to 16 Z-TIO modules can be connected. The maximum number of SRZ modules (including other function modules ) on the same communication line is 31.
Connection to the RS-232C port of the host computer (master)
Up to 16 Z-TIO modules can be connected. The maximum number of SRZ modules (including other function modules) on the same communication line is 31.
Connection to the USB of the host computer (master)
Up to 16 Z-TIO modules can be connected. The maximum number of SRZ modules (including other function modules) on the same communication line is 31.
(Base)
34 5
Module type controller SRZ
(−)
(+)
  
(−)
(+)
Module type controller SRZ
(−)
(+)
  
(−)
(+)
Module type controller SRZ
(−)
(+)
  
(−)
(+)
Z-TIO module
(Slave)
T/R (A)
T/R (B)
SG
Z-TIO module
(Slave)
T/R (A)
T/R (B)
SG
Z-TIO module
(Slave)
T/R (A) 3
T/R (B)
SG
Z-TIO module
(Slave)
T/R (A) 3
T/R (B)
SG
Z-TIO module
(Slave)
T/R (A)
T/R (B)
SG 5
Z-TIO module
(Slave)
T/R (A)
T/R (B)
SG 5
3
4
5
3
4
5
4
5
4
5
3
4
3
4
WARNING
!
Communication terminals (RS-485)
Terminal No.
3
4
5
RS-485
Connected by the internal communication line
R
R: Termination resistor (Example: 120 1/2 W)
RS-485
Shielded twisted
pair wire
Connected by the internal communication line
R
R: Termination resistor (Example: 120 Ω 1/2 W)
RS-485
Shielded twisted
pair wire
Connected by the internal communication line
R
R: Termination resistor (Example: 120 Ω 1/2 W)
Signal name
Send data/Receive data
Send data/Receive data
Signal ground
Pair wire
Shielded twisted
Pair wire
Pair wire
Host computer (Master)
T/R (A)
T/R (B)
R
SG
pair wire
Host computer (Master)
R
RS-232C/RS-485 converter *
* When the host computer (master) uses
Windows95/98/Me/NT/2000/XP, use a RS-232C/RS-485 conver ter with an automatic send/receive transfer function.
Recommended RS-2 32C/RS-485 converter: CD485, CD485/Vmanufactured by Data Link, Inc. or equivalent
Host computer (Master)
1
SG
T/R (A)
2
T/R(B)
3
4
5
USB communication
converter COM-K *
* The terminati on resistor is built-in t o
the COM-K.
RS-232C
T/R (A)
T/R (B)
SG
Connected to USB port of a personal com puter
Unused
Symbol
T/R (A)
T/R (B)
SG
(−)
(+)
USB cable (COM-K accessory)
Connected to USB connector
3. COMMUNICATION REQUIREMENTS
Processing times during data send/receive
When the host computer is using either the polling or selecting procedure for communication, the following processing times are required for controller to send data:
- Response wait time after controller sends BCC in polling procedure
- Response wait time after controller sends ACK or NAK in selecting procedure
RKC communication (Polling procedure)
Response send time after controller receives ENQ 50 ms max. Response send time after controller receives ACK 50 ms max. Response send time after controller receives NAK 50 ms max. Response send time after controller sends BCC 2 ms max.
RKC communication (Selecting procedure)
Response send time after controller receives BCC 50 ms max. Response wait time after controller sends ACK 2 ms max. Response wait time after controller sends NAK 2 ms max.
Modbus
Read holding registers [03H] Response send time after the slave receives the query message
Preset single register [06H] Response send time after the slave receives the query message
Diagnostics (loopback test) [08H] Response send time after the slave receives the query message
Preset multiple registers [10H] Response send time after the slave receives the query message
RS-485 (2-wire system) send/receive timing
RS-485 communication is conducted through two wires, therefore the transmission and reception of data requires precise timing.
Polling procedure
Host
computer
SRZ
a: Response send time after the controller receives [ENQ] + Interval time b: Response send time after the controller sends BCC c: Response send time after the controller receives [ACK] + Interval time or Response send time after the controller receives [NAK] + Interval time
Send data
(Possible/Impossible)
Sending status
Send data
(Possible/Impossible)
Sending status
Selecting procedure
Host
computer
SRZ
a: Response send time after the controller receives BCC + Interval time b: Response wait time after the controller sends ACK or Response wait time after the controller sends NAK
Send data
(Possible/Impossible)
Sending status
Send data
(Possible/Impossible)
Sending status
To switch the host computer from transmission to reception, send data must be on line.
The following processing times are requires for the controller to process data.
- In Polling procedure, Response wait time after the controller sends BCC
- In Selecting procedure, Response wait time after the controller sends ACK or NAK
Fail-safe
A transmission error may occur with the transmission line disconnected, shorted or set to the high-impedance state. In order to prevent the above error, it is recommended that the fail-safe function be provided on the receiver side of the host computer. The fail-safe function can prevent a framing error from its occurrence by making the receiver output stable to the MARK (1) when the transmission line is in the high-impedance state.
Modbus data processing precautions
Data with decimal point is treated as data without decimal point on the Modbus protocol.
With Modbus protocol, the maximum number of channels per slave address is 4.
Do not write data to any address which is not described in a list of data maps.
If data range or address error occurs during data writing, the data written before error is in
effect.
When communication data is sent to the controller that does not correctly match the connected module or selected functions on the modules, the data will be invalid. If the data is within a setting range, no error message is sent from the controller. The read data is “0”.
Send the next command message at time intervals of 24 bits after the master receives the response message.
Procedure details Time
Procedure details Time
Procedure details Time
Possible
Impossible
Possible
Impossible
Possible
Impossible
Possible
Impossible
E
E
- - - - -
N
O
Q
T
S
- - - - -
T X
S
B
T
C
- - - - -
X
C
a
b
N
A
or
A
C
K
K
50 ms max.
30 ms max.
30 ms max.
100 ms max.
b
B C C
4. HOST COMMUNICATION DATA MAP
Explanation of items shown in the communication data maps are as follows.
Modbus register address (HEX: Hexadecimal DEC: Decimal)
Communication data (RKC communication/Modbus)
N
A
or
A
C
K
K
c a
Model code ID
ROM version VR
Measured value (PV)
Comprehensive event state
Operation mode state monitor
Error code
For a 4CH type, follow the chart exactly. For the 2CH type, the register addresses for Channel 3 and 4 are unused. For communication parameters for heat/cool control, the register addresses for Channel 2 and 4 are unused.
Example: The register addresses of 0092 (HEX) to 0095 (HEX)
Address
CH#
・ ・ ・
CH1 0092 CH2 0093 (This address is unused with heat/cool control.) CH3 0094 (This address is unused with 2CH type.) CH4 0095 (This address is unused with heat/cool control or 2CH type.)
・ ・
Digits The number of communication data digits in RKC communication
Attribute RO: Read only data (Host computer The controller) R/W: Read and Write data (Host computer The controller)
Data
RKC communication ASCII code data (Example: 7 digits)
Modbus 16-bit data
Most significant digit
……
Least significant digit
…………….……………………
b15
Symbols used in MAP
: Parameters only used for heat/cool control or position proportioning control, therefore data for CH2 and CH4 are unused. : Parameters which can be used in multi-memory area function. : Data for each module : Data for each channel
For details on the data, see the SRZ Instruction Manual (IMS01T04-E).
Modbus
Name
RKC
register address
Iden­tifier
HEX DEC
M1 0000
AJ 0004
L0 0008
ER 000C 12
0
0003
3
4
0007
7
8
000B
11
Attri-
Digits
bute
32 RO
8 RO
7 RO Input scale low to
7 RO RKC communication
Modbus
7 RO RKC communication
Modbus
7 RO RKC communication
Data range
Model code (character)
ROM version
Input scale high
Least significant digit to 4th digit: Event 1 state to Event 4 state 5th digit: Heater break alarm state 6th digit: Temperature rise completion 7th digit: Burnout Data 0: OFF 1: ON
b0 to b3: Event 1 state to Event 4 state b4: Heater break alarm state b5: Temperature rise completion b6: Burnout b7 to b15: Unused Data 0: OFF 1: ON [Decimal number: 0 to 127]
Least significant digit: Control STOP 2nd digit: Control RUN 3rd digit: Manual mode 4th digit: Remote mode 5th digit to Most significant digit: Unused Data 0: OFF 1: ON
b0: Control STOP b1: Control RUN b2: Manual mode b3: Remote mode b4 to b15: Unused Data 0: OFF 1: ON [Decimal number: 0 to 15]
1: Adjustment data error 2: Data back-up error 4: A/D conversion error 32: Logic output data error
Modbus b0: Adjustment data error b1: Data back-up error b2: A/D conversion error b3: Unused b4: Unused b5: Logic output data error b6 to b15: Unused Data 0: OFF 1: ON [Decimal number: 0 to 63]
(Continued on the next page )
b0
Factory
set value
Name
Manipulated output value (MV) monitor [heat-side] Manipulated output value (MV) monitor [cool-side]
Current transformer (CT) input value monitor Set value (SV) monitor
Remote setting (RS) input value monitor Burnout state monitor
Event 1 state monitor
Event 2 state monitor
Event 3 state monitor
Event 4 state monitor
Heater break alarm (HBA) state monitor Output state monitor
Memory area soak time monitor
Integrated operating time monitor Holding peak value ambient temperature monitor Backup memory state monitor
Logic output monitor 1
Logic output monitor 2
Logic output monitor
Unused
PID/AT transfer
Auto/Manual
transfer
Remote/Local transfer
RUN/STOP transfer Memory area transfer
Interlock release
Event 1 set value
(EV1)
Event 2 set value (EV2)
Event 3 set value (EV3)
Event 4 set value
(EV4)
Modbus
RKC
register address
Iden­tifier
HEX DEC
000D
O1
・ ・ ・
0010
0011
O2
・ ・ ・
0014
0015
M3
・ ・ ・
0018
0019
MS
・ ・ ・
001C 001D
S2
・ ・ ・
0020 0021
B1
・ ・ ・
0024 0025
AA
・ ・ ・
0028 0029
AB
・ ・ ・
002C 002D
AC
・ ・ ・
0030 0031
AD
・ ・ ・
0034 0035
AE
・ ・ ・
0038 0039 57 7
Q1
003A
TR
・ ・ ・
003D
003E 62
UT
003F
Hp
・ ・ ・
0042
0043 67
EM
ED
EE
0044 68
0045
・ ・ ・
0060 0061
G1
・ ・ ・
0064 0065
J1
・ ・ ・
0068 0069
C1
・ ・ ・
006C 006D 109
SR
006E
ZA
・ ・ ・
0071 0072
AR
・ ・ ・
0075
A1 0076
・ ・ ・
0079
A2 007A
・ ・ ・
007D
A3 007E
・ ・ ・
0081
A4 0082
・ ・ ・
0085
Attri-
Digits
bute
13
7
・ ・ ・
16
17
・ ・ ・
20
21
・ ・ ・
24
25
・ ・ ・
28 29
・ ・ ・
32 33
・ ・ ・
36 37
・ ・ ・
40 41
・ ・ ・
44 45
・ ・ ・
48 49
・ ・ ・
52 53
・ ・ ・
56
RO
7 RO
7 RO
7 RO
7 RO
1 RO
1 RO
1 RO
1 RO
1 RO
1 RO
RO
58
7 RO
・ ・ ・
61
7 RO
63
7 RO
・ ・ ・
66
1 RO
7 RO
7 RO
RO
69
・ ・ ・
96 97
1 R/W
・ ・ ・
100 101
1 R/W
・ ・ ・
104 105
1 R/W
・ ・ ・
108
1 R/W
110
7 R/W
・ ・ ・
113 114
7 R/W
・ ・ ・
117 118
7 R/W 50
・ ・ ・
121 122
7 R/W 50
・ ・ ・
125 126
7 R/W 50
・ ・ ・
129 130
7 R/W
・ ・ ・
133
Data range
PID control or heat/cool PID control: 5.0 to +105.0 % Position proportioning control (FBR input): 0.0 to 100.0 %
5.0 to +105.0 %
CTL-6-P-N: 0.0 to 30.0 A CTL-12-S56-10L-N:
0.0 to 100.0 A
Setting limiter (low) to Setting limiter (high)
Setting limiter (low) to Setting limiter (high)
0: OFF 1: ON
0: OFF 1: ON
0: OFF 1: ON
RKC communication Least significant digit to 4th digit: OUT1 to OUT4 5th digit to Most significant digit: Unused Data 0: OFF 1: ON Modbus b0 to b3: OUT1 to OUT4 b4 to b15: Unused Data 0: OFF 1: ON [Decimal number: 0 to 15] 0 minutes 00 seconds to 199 minutes 59 seconds:
RKC communication: 0:00 to 199:59 (min:sec)
Modbus: 0 to 11999 seconds 0 hours 00 minutes to 99 hours 59 minutes:
RKC communication:
0:00 to 99:59 (hrs:min)
Modbus: 0 to 5999 minutes 0 to 19999 hours
10.0 to +100.0 °C or 14 to 212 °F
0: The content of the backup
memory does not coincide with that of the RAM.
1: The content of the backup
memory coincides with that of
the RAM. RKC communication Least significant digit to 4th digit: Logic output 1 to 4 5th digit to Most significant digit: Unused Data 0: OFF 1: ON RKC communication Least significant digit to 4th digit: Logic output 5 to 8 5th digit to Most significant digit: Unused Data 0: OFF 1: ON Modbus b0 to b7: Logic output 1 to 8 b8 to b15: Unused Data 0: OFF 1: ON [Decimal number: 0 to 255]
0: PID control 1: Autotuning (AT)
0: Auto mode 1: Manual mode
0: Local mode 1: Remote mode
0: STOP (Control stop) 1: RUN (Control start) 1 to 8
0: Normal state 1: Interlock release execution
Deviation action, Deviation action between channels, Temperature rise completion range*:
Input span to +Input span
Process action, SV action: Input scale low to Input scale high
MV action:
5.0 to +105.0 %
*When temperature r ise completion is selected at Event 3 action type.
60
60
0.0
0.0
0.0
Name
Output distribution bias Output distribution ratio Proportional cycle time
Minimum ON/OFF time of proportioning cycle Manual manipulated output value
Area soak time stop function
EDS mode (for disturbance 1)
EDS mode (for disturbance 2)
EDS value 1 (for disturbance 1)
0
0
0
EDS value 1 (for disturbance 2)
EDS value 2 (for disturbance 1)
EDS value 2 (for disturbance 2)
EDS transfer time (for disturbance 1)
EDS transfer time (for disturbance 2)
:
EDS action time (for disturbance 1)
EDS action time (for disturbance 2)
EDS action wait time (for disturbance 1) EDS action wait time (for disturbance 2) EDS value learning times
EDS start signal♠ NU 013E
Operation mode♠ EI 0142
Startup tuning (ST)
Automatic temperature rise learning
Communication switch (for logic)
0
Unused
For communication data (Engineering setting), refer to the S RZ Instruction Manual (IMS01T04-E).
Modbus
RKC
register address
Iden­tifier
HEX DEC
DW
00F2
・ ・ ・
00F5
DQ
00F6
・ ・ ・
00F9
T0
00FA
・ ・ ・
00FD
VI
00FE
・ ・ ・
0101
ON
0102
・ ・ ・
0105
RV
0106
・ ・ ・
0109
NG
010A
・ ・ ・
010D
NX
010E
・ ・ ・
0111
NI
0112
・ ・ ・
0115
NJ
0116
・ ・ ・
0119
NK
011A
・ ・ ・
011D
NM
011E
・ ・ ・
0121
NN 0122
・ ・ ・
0125
NO 0126
・ ・ ・
0129
NQ 012A
・ ・ ・
012D
NL 012E
・ ・ ・
0131
NR 0132
・ ・ ・
0135
NY 0136
・ ・ ・
0139
NT 013A
・ ・ ・
013D
・ ・ ・
0141
・ ・ ・
0145
ST 0146
・ ・ ・
0149
Y8 014A
・ ・ ・
014D
EF 014E 334 7 R/W
014F
・ ・ ・
0175
Digits
7 R/W 100.0 to +100.0 % 0.0
242
・ ・ ・
245
7 R/W 9.999 to +9.999 1.000
246
・ ・ ・
249
7 R/W 0.1 to 100.0 seconds
250
・ ・ ・
253
7 R/W 0 to 1000 ms 0
254
・ ・ ・
257
7 R/W
258
・ ・ ・
261
1 R/W 0: No function 3: Event 3
262
・ ・ ・
265
1 R/W 0
266
・ ・ ・
269
1 R/W
270
・ ・ ・
273
7 R/W 100.0 to +100.0 % 0.0
274
・ ・ ・
277
7 R/W 0.0
278
・ ・ ・
281
7 R/W 0.0
282
・ ・ ・
285
7 R/W 0.0
286
・ ・ ・
289 290
7 R/W 0 to 3600 seconds or
・ ・ ・
293 294
7 R/W 0
・ ・ ・
297 298
7 R/W 1 to 3600 seconds 600
・ ・ ・
301 302
7 R/W 600
・ ・ ・
305 306
7 R/W 0.0 to 600.0 seconds 0.0
・ ・ ・
309 310
7 R/W 0.0
・ ・ ・
313 314
7 R/W 0 to 10 times
・ ・ ・
317 318
1 R/W
・ ・ ・
321
322
1 R/W
・ ・ ・
325
326
1 R/W
・ ・ ・
329 330
1 R/W 0: Unused
・ ・ ・
333
335
・ ・ ・
373
Attri­bute
Data range
M: Relay contact output V: Voltage pulse output T: Triac output D: Open collector output
PID control: Output limiter (low) to Output limiter (high) Heat/cool PID control:
Cool-side output limiter (high) to +Heat-side output limiter (high) Position proportioning control (with FBR input): Output limiter (low) to Output limiter (high) Position proportioning control (without FBR input): 0: Close-side output OFF, Open-side output OFF 1: Close-side output ON, Open-side output OFF 2: Close-side output OFF, Open-side output ON
1: Event 1 4: Event 4 2: Event 2
0: No function 1: EDS function mode 2: Learning mode 3: Tuning mode
EDS function: External disturbance
suppression function
0.0 to 1999.9 seconds
(0: No learning mode)
0: EDS start signal OFF 1: EDS start signal ON (for disturbance 1) 2: EDS start signal ON (for disturbance 2) 0: Unused 1: Monitor 2: Monitor + Event function 3: Control 0: ST unused 1: Execute once 2: Execute always
1: Learning
RKC communication Least significant digit to 4th digit: Communication switch 1 to 4 5th digit to Most significant digit: Unused Data 0: OFF 1: ON Modbus b0 to b3: Communication switch 1 to 4 b4 to b15: Unused Data 0: OFF 1: ON [Decimal number: 0 to 15]
Factory
set value
M output:
20.0
V, T, D
output: 2.0
0.0
0
0
0
1
0
3
0
0
0
0
Communication data for multi-memory area data
(only for Modbus)
Use the register addresses of 0500H to 0553H to confirm or change set values of parameters in multi-memory areas which are not selected. For example, when memory area 1 is selected, set values of parameters in memory-area 2 to 7 can be changed by these register addresses. [For RKC communication, communication parameter is used to do the same operation. Refer to SRZ Instruction Manual (IMS01T04-E).]
Name
Setting memory area number
Event 1 set value (EV1) 0504
Event 2 set value (EV2) 0508
Event 3 set value (EV3) 050C
Event 4 set value (EV4) 0510
Control loop break alarm (LBA) time
LBA deadband 0518
Set value (SV) 051C
Proportional band [heat-side]
Integral time [heat-side] 0524
Derivative time [heat-side] 0528
Control response parameter
Proportional band [cool-side]
Integral time [cool-side] 0534
Derivative time [cool-side] 0538
Overlap/Deadband 053C
Manual reset 0540
Setting change rate limiter (up)
Setting change rate limiter (down)
Area soak time 054C
Link area number 0550
For the Modbus data mapping function, see the SRZ Instruction Manual (IMS01T04--E).
Modbus is a registered tradema rk of Schneider Electric. Company names and product names used i n this manual are the trademarks or registered trademarks of the respective companies.
HEADQUARTERS: 16-6, KUGAHARA 5-CHOME, OHTA-KU TOKYO 146-8515 J APAN
PHONE: 03-3751-9799 (+81 3 3751 9799) E-mail: info@rkcinst.co.jp FAX: 03-3751-8585 (+81 3 3751 8585) SEP. 2007
Modbus
register address
HEX DEC
0500
・ ・ ・
0503
・ ・ ・
0507
・ ・ ・
050B
・ ・ ・
050F
・ ・ ・
0513 0514
・ ・ ・
0517
・ ・ ・
051B
・ ・ ・
051F 0520
・ ・ ・
0523
Attri­bute
1280
1283 1284
1287 1288
1291 1292
1295 1296
1299 1300
1303 1304
1307 1308
1311 1312
1315
・ ・ ・
・ ・ ・
・ ・ ・
・ ・ ・
・ ・ ・
・ ・ ・
・ ・ ・
・ ・ ・
・ ・ ・
1 to 8 1
R/W
R/W
Deviation action, Deviation action between channels, Temperature rise completion range:
R/W
Input span to +Input span
Process action, SV action: Input scale low to Input scale high
R/W
MV action:
5.0 to +105.0 %
R/W
R/W 0 to 7200 seconds
(0: Unused)
R/W 0 (0.0) to Input span
R/W Setting limiter (low) to
Setting limiter (high)
R/W TC/RTD inputs:
0 (0.0) to Input span (Unit: °C [°F])
Voltage (V)/current (I) inputs:
0.0 to 1000.0 % of Input span
0 (0.0): ON/OFF action
1316
・ ・ ・
0527
・ ・ ・
052B
052C
・ ・ ・
052F
0530
・ ・ ・
0533
・ ・ ・
0537
・ ・ ・
053B
・ ・ ・
053F
・ ・ ・
0543 0544
・ ・ ・
0547 0548
・ ・ ・
054B
・ ・ ・
054F
・ ・ ・
0553
RKC INSTRUMENT INC.
®
R/W PID control or heat/cool PID control:
1319
1320
1323
1324
1327
1328
1331
1332
1335
1336
1339
1340
1343
1344
1347 1348
1351 1352
1355 1356
1359 1360
1363
・ ・
・ ・ ・
・ ・ ・
・ ・ ・
・ ・ ・
・ ・ ・
・ ・ ・
・ ・ ・
・ ・ ・
・ ・ ・
・ ・ ・
・ ・ ・
0 to 3600 seconds or
0.0 to 1999.9 seconds (0, 0.0: PD action)
Position proportioning control: 1 to 3600 seconds or
0.1 to 1999.9 seconds
R/W 0 to 3600 seconds or
0.0 to 1999.9 seconds (0, 0.0: PI action)
R/W 0: Slow
1: Medium 2: Fast
When the P or PD action is selected, this setting becomes invalid.
R/W TC/RTD inputs:
1 (0.1) to Input span (Unit: °C [°F])
Voltage (V)/current (I) inputs:
0.1 to 1000.0 % of Input span
R/W 0 to 3600 seconds or
0.0 to 1999.9 seconds (0, 0.0: PD action)
R/W 0 to 3600 seconds or
0.0 to 1999.9 seconds (0, 0.0: PI action)
R/W TC/RTD inputs:
Input span to +Input span (Unit:°C [°F])
Voltage (V)/current (I) inputs:
100.0 to +100.0 % of Input span
R/W 100.0 to +100.0 % 0.0
R/W 0 (0.0) to Input span/unit time
0 (0.0): Unused
R/W Unit time: 60 seconds
(factory set value)
R/W 0 to 11999 seconds or 0 to 5999
minutes
R/W 0 to 8
(0: No link)
Data range
Factory
set value
50
50
50
50
480
0 (0.0)
TC/RTD: 0 V/I: 0.0
TC/RTD: 30 (30.0) V/I: 30.0
240
60
PID control, Position proportioning control: 0 Heat/cool PID control: 2 TC/RTD: 30 (30.0) V/I: 30.0
240
60
0
0 (0.0)
0 (0.0)
0
0
The first edition: MAR. 2006 [IMQ00] The third edition: SEP. 2007 [IMQ00]
Factory
set value
Name
Control loop break alarm (LBA) time LBA deadband
Set value (SV)
Proportional band [heat-side]
Integral time
[heat-side]
Derivative time
[heat-side]
Control response parameter
Proportional band [cool-side]
Integral time [cool-side]
Derivative time [cool-side]
Overlap/ Deadband
Manual reset
Setting change rate limiter (up)
Setting change rate limiter (down) Area soak time
Link area number
0
0
0
0
1
0
Heater break alarm (HBA) set value
Heater break determination point
Heater melting determination point
PV bias
PV digital filter
PV ratio
PV low input cut-off
RS bias *
RS digital filter *♠ F2
RS ratio *
Output distribution selection
50
* Data on RS bias, RS ratio and RS digital filter is that in cascade contr ol or ratio setting.
RKC Iden­tifier
A5
N1
S1
P1
I1
D1
CA
P2
I2
D2
V1
MR
HH
HL
TM
LP
A7
NE
NF
PB
F1
PR
DP
RB
RR
DV
Modbus
register address
HEX DEC
0086
134
0089
137
008A
138
008D
141
008E
142
0091
145
0092
146
0095
149
0096
150
0099
153
009A
154
009D
157
009E
158
00A1
161
00A2
162
00A5
165
00A6
166
00A9
169
00AA
170
00AD
173
00AE
174
00B1
177
00B2
178
00B5
181
00B6
182
00B9
185
00BA
186
00BD
189
00BE
190
00C1
193
00C2
194
00C5
197
00C6
198
00C9
201
00CA
202
00CD
205 206
00CE
00D1
209 210
00D2
00D5
213
00D6
214
00D9
217
00DA
218
00DD
221 222
00DE
00E1
225
00E2
226
00E5
229
00E6
230
00E9
233 234
00EA
00ED
237
00EE
238
00F1
241
Attri-
Digits
bute
7 R/W 0 to 7200 seconds
Data range
(0: Unused)
Factory
set value
7 R/W 0 (0.0) to Input span 0 (0.0)
7 R/W Setting limiter (low) to
Setting limiter (high)
TC/RTD inputs:
7 R/W
0 (0.0) to Input span (Unit: °C [°F])
Voltage (V)/current (I) inputs:
0.0 to 1000.0 % of Input span 0 (0.0): ON/OFF action PID control or heat/cool PID
7 R/W
control: 0 to 3600 seconds or 0.0 to
1999.9 seconds (0, 0.0: PD action)
Position proportioning control: 1 to 3600 seconds or 0.1 to
1999.9 seconds 0 to 3600 seconds or 0.0 to
7 R/W
1999.9 seconds (0, 0.0: PI action)
1 R/W 0: Slow
1: Medium 2: Fast
When the P or PD action is selected, this setting becomes invalid. TC/RTD inputs:
7 R/W
1 (0.1) to Input span (Unit: °C [°F])
Voltage (V)/current (I) inputs:
0.1 to 1000.0 % of Input span 0 to 3600 seconds or
7 R/W
0.0 to 1999.9 seconds (0, 0.0: PD action)
0 to 3600 seconds or
7 R/W
0.0 to 1999.9 seconds (0, 0.0: PI action)
TC/RTD inputs:
7 R/W
Input span to +Input span (Unit:°C [°F])
Voltage (V)/current (I) inputs:
100.0 to +100.0 % of Input span
TC/RTD: 0 V/I: 0.0
TC/RTD: 30 (30.0) V/I: 30.0
PID control, Position proportioning control: 0 Heat/cool PID control: 2
TC/RTD: 30 (30.0) V/I: 30.0
7 R/W −100.0 to +100.0 % 0.0
7 R/W 0 (0.0) to Input span/unit time
0 (0.0): Unused
7 R/W Unit time: 60 seconds
(factory set value)
0 minutes 00 seconds to
7 R/W
199 minutes 59 seconds: RKC communication: 0:00 to 199:59 (min:sec) Modbus: 0 to 11999 seconds
0 hours 00 minutes to 99 hours 59 minutes: RKC communication: 0:00 to 99:59 (hrs:min) Modbus: 0 to 5999 minutes
7 R/W 0 to 8
(0: No link)
When CT is CTL-6-P-N:
7 R/W
0.0 to 30.0 A (0.0: Not used) When CT is CTL-12-S56-10L -N:
0.0 to 100.0 A (0.0: Not used)
7 R/W 0.0 to 100.0 % of HBA set value
(0.0: Heater break determination is invalid)
7 R/W 0.0 to 100.0 % of HBA set value
(0.0: Heater melting determination is invalid)
communication
Modbus:
7 R/W −Input span to +Input span 0
7 R/W 0.0 to 100.0 seconds
(0.0: Unused)
7 R/W 0.500 to 1.500 1.000
7 R/W 0.00 to 25.00 % of input span 0.00
7 R/W −Input span to +Input span 0
7 R/W 0.0 to 100.0 seconds
(0.0: Unused)
7 R/W 0.001 to 9.999 1.000
1 R/W 0: Control output
1: Distribution output
480
240
240
0 (0.0)
0 (0.0)
RKC
0:00
30.0
30.0
Loading...