
Module Type Controller SRZ
Temperature Control Module
[for Host Communication]
ll Rights Reserved, Copyright 2006, RKC INSTRUMENT INC.
Z-TIO
Host Communication
Quick Instruction
Manual
IMS01T02-E3
Thank you for purchasing this RKC product. In order to achieve maximum performance and
ensure proper operation of your new instrument, carefully read all the instructions in this
manual. Please place this manual in a convenient location for easy reference.
This manual describes the host communication, module address setting of the Z-TIO
module. For the address setting of any other module, refer to the Instruction Manual for the
respective module. For detailed handling procedures and various function settings, please
refer to separate SRZ Instruction Manual (IMS01T04 -E).
The above manuals can be downloaded from our website:
URL: http://www.rkcinst.com/english/manual_load.htm
1. COMMUNICATION SETTING
Set communication setting before mounting and wiring of the Z-TIO.
CAUTION
Do not separate the module mainframe from the base with the power turned on. If so,
instrument failure may result.
1.1 Module Address Setting
Set an address for the module using a small blade screwdriver.
Address setting switch
Setting range: 0 to F [0 to 15: Decimal]
• For Modbus, the value obtained by adding “1” to the set address
corresponds to the address used for the actual program.
• To avoid problems or malfunction, do not duplicate an address on the
same communication line.
1.2 Protocol Selections and Communication Speed Setting
Use the DIP switch on the right side of module to select communication speed, data bit
configuration and protocol. The data changes become valid when the power is turned on
again or when changed to RUN/STOP.
Right side view
(The above figure is for the terminal type. Howe ver, the switch positions are the same for the connector type.)
1 2 Communication speed
OFF OFF 4800 bps
ON OFF 9600 bps
OFF ON 19200 bps
ON ON 38400 bps
Factory set value: 19200 bps
3 4 5 Data bit configuration
OFF OFF OFF Data 7-bit, without parity, Stop 1-bit *
ON OFF OFF Don't set this one
OFF ON OFF Data 7-bit, Even parity, Stop 1-bit *
ON ON OFF Data 7-bit, Odd parity, Stop 1-bit *
OFF OFF ON Data 8-bit, without parity, Stop 1-bit
ON OFF ON Don't set this one
OFF ON ON Data 8-bit, Even parity, Stop 1-bit
ON ON ON Data 8-bit, Odd parity, Stop 1-bit
* When the Modbus communication protocol is selected, this setting becomes invalid.
Factory set value: Data 8-bit, without parity, Stop 1-bit
6 Protocol
OFF RKC communication
ON Modbus
Factory set value: RKC communication
• Switch No. 7 and 8 must be always OFF. Do not set to ON.
• When two or more modules are connected on the same communication
line, the DIP switch settings of all modules must be the same.
Factory set value: 0
Module
mainframe
DIP switch
1 234567
8
ON OFF
ON
2. CONNECTION TO HOST COMPUTER
To prevent electric shock or instrument failure, turn off the
power before connecting or disconnecting the instrument and
peripheral equipment.
Connect a termination resistor between the communication terminals (No.3
and No. 4) of the module at the end of the communication line from the host
computer.
The cable must be provided by the customer.
The Z-TIO has RS-485 communication terminals for RKC communication or Modbus/RTU
communication protocol. Communication terminals are on the base side.
Connection to the RS-485 port of the host computer (master)
Up to 16 Z-TIO modules can be connected.
The maximum number of SRZ modules (including other function modules ) on the same communication line is 31.
Connection to the RS-232C port of the host computer (master)
Up to 16 Z-TIO modules can be connected.
The maximum number of SRZ modules (including other function modules) on the same communication line is 31.
Connection to the USB of the host computer (master)
Up to 16 Z-TIO modules can be connected.
The maximum number of SRZ modules (including other function modules) on the same communication line is 31.
(Base)
34 5
Module type controller SRZ
(−)
(+)
(−)
(+)
Module type controller SRZ
(−)
(+)
(−)
(+)
Module type controller SRZ
(−)
(+)
(−)
(+)
Z-TIO module
(Slave)
T/R (A)
T/R (B)
SG
Z-TIO module
(Slave)
T/R (A)
T/R (B)
SG
Z-TIO module
(Slave)
T/R (A) 3
T/R (B)
SG
Z-TIO module
(Slave)
T/R (A) 3
T/R (B)
SG
Z-TIO module
(Slave)
T/R (A)
T/R (B)
SG 5
Z-TIO module
(Slave)
T/R (A)
T/R (B)
SG 5
3
4
5
3
4
5
4
5
4
5
3
4
3
4
WARNING
!
Communication terminals (RS-485)
Terminal No.
3
4
5
RS-485
Connected by
the internal
communication line
R
R: Termination resistor (Example: 120 Ω 1/2 W)
RS-485
Shielded twisted
pair wire
Connected by
the internal
communication line
R
R: Termination resistor
(Example: 120 Ω 1/2 W)
RS-485
Shielded twisted
pair wire
Connected by
the internal
communication line
R
R: Termination resistor
(Example: 120 Ω 1/2 W)
Signal name
Send data/Receive data
Send data/Receive data
Signal ground
Pair wire
Shielded twisted
Pair wire
Pair wire
Host computer (Master)
T/R (A)
T/R (B)
R
SG
pair wire
Host computer (Master)
R
RS-232C/RS-485 converter *
* When the host computer (master) uses
Windows95/98/Me/NT/2000/XP, use a
RS-232C/RS-485 conver ter with an
automatic send/receive transfer function.
Recommended RS-2 32C/RS-485 converter:
CD485, CD485/Vmanufactured by Data Link,
Inc. or equivalent
Host computer (Master)
1
SG
T/R (A)
2
T/R(B)
3
4
5
USB communication
converter COM-K *
* The terminati on resistor is built-in t o
the COM-K.
RS-232C
T/R (A)
T/R (B)
SG
Connected to USB port
of a personal com puter
Unused
Symbol
T/R (A)
T/R (B)
SG
(−)
(+)
USB cable
(COM-K
accessory)
Connected to
USB connector
3. COMMUNICATION REQUIREMENTS
Processing times during data send/receive
When the host computer is using either the polling or selecting procedure for communication,
the following processing times are required for controller to send data:
- Response wait time after controller sends BCC in polling procedure
- Response wait time after controller sends ACK or NAK in selecting procedure
RKC communication (Polling procedure)
Response send time after controller receives ENQ 50 ms max.
Response send time after controller receives ACK 50 ms max.
Response send time after controller receives NAK 50 ms max.
Response send time after controller sends BCC 2 ms max.
RKC communication (Selecting procedure)
Response send time after controller receives BCC 50 ms max.
Response wait time after controller sends ACK 2 ms max.
Response wait time after controller sends NAK 2 ms max.
Modbus
Read holding registers [03H]
Response send time after the slave receives the query message
Preset single register [06H]
Response send time after the slave receives the query message
Diagnostics (loopback test) [08H]
Response send time after the slave receives the query message
Preset multiple registers [10H]
Response send time after the slave receives the query message
RS-485 (2-wire system) send/receive timing
RS-485 communication is conducted through two wires, therefore the transmission and
reception of data requires precise timing.
Polling procedure
Host
computer
SRZ
a: Response send time after the controller receives [ENQ] + Interval time
b: Response send time after the controller sends BCC
c: Response send time after the controller receives [ACK] + Interval time or
Response send time after the controller receives [NAK] + Interval time
Send data
(Possible/Impossible)
Sending status
Send data
(Possible/Impossible)
Sending status
Selecting procedure
Host
computer
SRZ
a: Response send time after the controller receives BCC + Interval time
b: Response wait time after the controller sends ACK or Response wait time after the controller sends NAK
Send data
(Possible/Impossible)
Sending status
Send data
(Possible/Impossible)
Sending status
To switch the host computer from transmission to reception, send data must be on
line.
The following processing times are requires for the controller to process data.
- In Polling procedure, Response wait time after the controller sends BCC
- In Selecting procedure, Response wait time after the controller sends ACK or NAK
Fail-safe
A transmission error may occur with the transmission line disconnected, shorted or set to the
high-impedance state. In order to prevent the above error, it is recommended that the
fail-safe function be provided on the receiver side of the host computer. The fail-safe function
can prevent a framing error from its occurrence by making the receiver output stable to the
MARK (1) when the transmission line is in the high-impedance state.
Modbus data processing precautions
• Data with decimal point is treated as data without decimal point on the Modbus protocol.
• With Modbus protocol, the maximum number of channels per slave address is 4.
• Do not write data to any address which is not described in a list of data maps.
• If data range or address error occurs during data writing, the data written before error is in
effect.
• When communication data is sent to the controller that does not correctly match the
connected module or selected functions on the modules, the data will be invalid. If the
data is within a setting range, no error message is sent from the controller. The read data
is “0”.
• Send the next command message at time intervals of 24 bits after the master receives the
response message.
Procedure details Time
Procedure details Time
Procedure details Time
Possible
Impossible
Possible
Impossible
Possible
Impossible
Possible
Impossible
E
E
- - - - -
N
O
Q
T
S
- - - - -
T
X
S
B
T
C
- - - - -
X
C
a
b
N
A
or
A
C
K
K
50 ms max.
30 ms max.
30 ms max.
100 ms max.
b
B
C
C
4. HOST COMMUNICATION DATA MAP
Explanation of items shown in the communication data maps are as follows.
• Modbus register address (HEX: Hexadecimal DEC: Decimal)
Communication data (RKC communication/Modbus)
N
A
or
A
C
K
K
c a
Model code ♦ ID
ROM version ♦ VR
Measured value
(PV)
♠
Comprehensive
event state
♠
Operation mode
state monitor
♠
Error code
♦
For a 4CH type, follow the chart exactly. For the 2CH type, the register
addresses for Channel 3 and 4 are unused. For communication parameters for
heat/cool control, the register addresses for Channel 2 and 4 are unused.
Example: The register addresses of 0092 (HEX) to 0095 (HEX)
Address
CH#
・
・
・
CH1 0092
CH2 0093 (This address is unused with heat/cool control.)
CH3 0094 (This address is unused with 2CH type.)
CH4 0095 (This address is unused with heat/cool control or 2CH type.)
・
・
• Digits
The number of communication data digits in RKC communication
・
• Attribute
RO: Read only data (Host computer The controller)
R/W: Read and Write data (Host computer The controller)
• Data
RKC communication
ASCII code data (Example: 7 digits)
Modbus
16-bit data
Most significant
digit
……
Least significant
digit
…………….……………………
b15
Symbols used in MAP
♣: Parameters only used for heat/cool control or position proportioning control,
therefore data for CH2 and CH4 are unused.
: Parameters which can be used in multi-memory area function.
♦: Data for each module ♠: Data for each channel
For details on the data, see the SRZ Instruction Manual (IMS01T04-E).
Modbus
Name
RKC
register address
Identifier
HEX DEC
M1 0000
AJ 0004
L0 0008
ER 000C 12
0
・
・
・
・
・
・
0003
3
4
・
・
・
・
・
・
0007
7
8
・
・
・
・
・
・
000B
11
Attri-
Digits
bute
32 RO
8 RO
7 RO Input scale low to
7 RO RKC communication
Modbus
7 RO RKC communication
Modbus
7 RO RKC communication
Data range
Model code (character)
ROM version
Input scale high
Least significant digit to 4th digit:
Event 1 state
to Event 4 state
5th digit: Heater break alarm
state
6th digit: Temperature rise
completion
7th digit: Burnout
Data 0: OFF 1: ON
b0 to b3: Event 1 state
to Event 4 state
b4: Heater break alarm
state
b5: Temperature rise
completion
b6: Burnout
b7 to b15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 127]
Least significant digit:
Control STOP
2nd digit: Control RUN
3rd digit: Manual mode
4th digit: Remote mode
5th digit to Most significant digit:
Unused
Data 0: OFF 1: ON
b0: Control STOP
b1: Control RUN
b2: Manual mode
b3: Remote mode
b4 to b15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 15]
1: Adjustment data error
2: Data back-up error
4: A/D conversion error
32: Logic output data error
Modbus
b0: Adjustment data error
b1: Data back-up error
b2: A/D conversion error
b3: Unused
b4: Unused
b5: Logic output data error
b6 to b15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 63]
(Continued on the next page )
b0
Factory
set value

Name
Manipulated
output value
(MV) monitor
[heat-side] ♣
Manipulated
output value
(MV) monitor
[cool-side] ♣
Current
transformer (CT)
input value
monitor ♠
Set value (SV)
monitor ♠
Remote setting
(RS) input value
monitor ♠
Burnout state
monitor ♠
Event 1 state
monitor ♠
Event 2 state
monitor ♠
Event 3 state
monitor ♠
Event 4 state
monitor ♠
Heater break
alarm (HBA)
state monitor ♠
Output state
monitor
♦
Memory area
soak time
monitor ♠
Integrated
operating time
monitor ♦
Holding peak
value ambient
temperature
monitor ♠
Backup memory
state monitor ♦
Logic output
monitor 1
♦
Logic output
monitor 2
♦
Logic output
monitor
♦
Unused
PID/AT transfer
♠
Auto/Manual
♠
transfer
Remote/Local
transfer ♠
RUN/STOP
transfer ♦
Memory area
transfer ♠
Interlock release
♠
Event 1 set value
♠
(EV1)
Event 2 set value
(EV2) ♠
Event 3 set value
(EV3) ♠
Event 4 set value
♠
(EV4)
Modbus
RKC
register address
Identifier
HEX DEC
000D
O1
・
・
・
0010
0011
O2
・
・
・
0014
0015
M3
・
・
・
0018
0019
MS
・
・
・
001C
001D
S2
・
・
・
0020
0021
B1
・
・
・
0024
0025
AA
・
・
・
0028
0029
AB
・
・
・
002C
002D
AC
・
・
・
0030
0031
AD
・
・
・
0034
0035
AE
・
・
・
0038
0039 57 7
Q1
003A
TR
・
・
・
003D
003E 62
UT
003F
Hp
・
・
・
0042
0043 67
EM
ED
EE
0044 68
0045
・
・
・
0060
0061
G1
・
・
・
0064
0065
J1
・
・
・
0068
0069
C1
・
・
・
006C
006D 109
SR
006E
ZA
・
・
・
0071
0072
AR
・
・
・
0075
A1 0076
・
・
・
0079
A2 007A
・
・
・
007D
A3 007E
・
・
・
0081
A4 0082
・
・
・
0085
Attri-
Digits
bute
13
7
・
・
・
16
17
・
・
・
20
21
・
・
・
24
25
・
・
・
28
29
・
・
・
32
33
・
・
・
36
37
・
・
・
40
41
・
・
・
44
45
・
・
・
48
49
・
・
・
52
53
・
・
・
56
RO
7 RO
7 RO
7 RO
7 RO
1 RO
1 RO
1 RO
1 RO
1 RO
1 RO
RO
58
7 RO
・
・
・
61
7 RO
63
7 RO
・
・
・
66
1 RO
7 RO
7 RO
RO
69
・
・
・
96
97
1 R/W
・
・
・
100
101
1 R/W
・
・
・
104
105
1 R/W
・
・
・
108
1 R/W
110
7 R/W
・
・
・
113
114
7 R/W
・
・
・
117
118
7 R/W 50
・
・
・
121
122
7 R/W 50
・
・
・
125
126
7 R/W 50
・
・
・
129
130
7 R/W
・
・
・
133
Data range
PID control or heat/cool PID
control: −5.0 to +105.0 %
Position proportioning control
(FBR input): 0.0 to 100.0 %
−5.0 to +105.0 %
CTL-6-P-N: 0.0 to 30.0 A
CTL-12-S56-10L-N:
0.0 to 100.0 A
Setting limiter (low) to
Setting limiter (high)
Setting limiter (low) to
Setting limiter (high)
0: OFF
1: ON
0: OFF
1: ON
0: OFF
1: ON
RKC communication
Least significant digit to 4th digit:
OUT1 to OUT4
5th digit to Most significant digit:
Unused
Data 0: OFF 1: ON
Modbus
b0 to b3: OUT1 to OUT4
b4 to b15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 15]
0 minutes 00 seconds to
199 minutes 59 seconds:
RKC communication:
0:00 to 199:59 (min:sec)
Modbus: 0 to 11999 seconds
0 hours 00 minutes to
99 hours 59 minutes:
RKC communication:
0:00 to 99:59 (hrs:min)
Modbus: 0 to 5999 minutes
0 to 19999 hours
−10.0 to +100.0 °C or
14 to 212 °F
0: The content of the backup
memory does not coincide with
that of the RAM.
1: The content of the backup
memory coincides with that of
the RAM.
RKC communication
Least significant digit to 4th digit:
Logic output 1 to 4
5th digit to Most significant digit:
Unused
Data 0: OFF 1: ON
RKC communication
Least significant digit to 4th digit:
Logic output 5 to 8
5th digit to Most significant digit:
Unused
Data 0: OFF 1: ON
Modbus
b0 to b7: Logic output 1 to 8
b8 to b15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 255]
0: PID control
1: Autotuning (AT)
0: Auto mode
1: Manual mode
0: Local mode
1: Remote mode
0: STOP (Control stop)
1: RUN (Control start)
1 to 8
0: Normal state
1: Interlock release execution
Deviation action, Deviation action
between channels, Temperature
rise completion range*:
−Input span to +Input span
Process action, SV action:
Input scale low to
Input scale high
MV action:
−5.0 to +105.0 %
*When temperature r ise completion is
selected at Event 3 action type.
60
60
0.0
0.0
0.0
Name
Output
distribution
bias ♠
Output
distribution
ratio ♠
Proportional
cycle time
♠
Minimum
ON/OFF time of
proportioning
cycle ♠
Manual
manipulated
output value
♣ ♠
Area soak time
stop function
♠
EDS mode
(for disturbance 1)
♠
EDS mode
(for disturbance 2)
♠
EDS value 1
(for disturbance 1)
0
0
0
♠
EDS value 1
(for disturbance 2)
♠
EDS value 2
(for disturbance 1)
♠
EDS value 2
(for disturbance 2)
♠
EDS transfer time
(for disturbance 1)
♠
EDS transfer time
(for disturbance 2)
:
♠
EDS action time
(for disturbance 1)
♠
EDS action time
(for disturbance 2)
♠
EDS action wait
time ♠
(for disturbance 1)
EDS action wait
time ♠
(for disturbance 2)
EDS value
learning times
♠
EDS start signal♠ NU 013E
Operation mode♠ EI 0142
Startup tuning
(ST) ♠
Automatic
temperature rise
learning ♠
Communication
switch (for logic)
♦
0
Unused
For communication data (Engineering setting), refer to the S RZ Instruction Manual (IMS01T04-E).
Modbus
RKC
register address
Identifier
HEX DEC
DW
00F2
・
・
・
00F5
DQ
00F6
・
・
・
00F9
T0
00FA
・
・
・
00FD
VI
00FE
・
・
・
0101
ON
0102
・
・
・
0105
RV
0106
・
・
・
0109
NG
010A
・
・
・
010D
NX
010E
・
・
・
0111
NI
0112
・
・
・
0115
NJ
0116
・
・
・
0119
NK
011A
・
・
・
011D
NM
011E
・
・
・
0121
NN 0122
・
・
・
0125
NO 0126
・
・
・
0129
NQ 012A
・
・
・
012D
NL 012E
・
・
・
0131
NR 0132
・
・
・
0135
NY 0136
・
・
・
0139
NT 013A
・
・
・
013D
・
・
・
0141
・
・
・
0145
ST 0146
・
・
・
0149
Y8 014A
・
・
・
014D
EF 014E 334 7 R/W
014F
・
・
・
0175
Digits
7 R/W −100.0 to +100.0 % 0.0
242
・
・
・
245
7 R/W −9.999 to +9.999 1.000
246
・
・
・
249
7 R/W 0.1 to 100.0 seconds
250
・
・
・
253
7 R/W 0 to 1000 ms 0
254
・
・
・
257
7 R/W
258
・
・
・
261
1 R/W 0: No function 3: Event 3
262
・
・
・
265
1 R/W 0
266
・
・
・
269
1 R/W
270
・
・
・
273
7 R/W −100.0 to +100.0 % 0.0
274
・
・
・
277
7 R/W 0.0
278
・
・
・
281
7 R/W 0.0
282
・
・
・
285
7 R/W 0.0
286
・
・
・
289
290
7 R/W 0 to 3600 seconds or
・
・
・
293
294
7 R/W 0
・
・
・
297
298
7 R/W 1 to 3600 seconds 600
・
・
・
301
302
7 R/W 600
・
・
・
305
306
7 R/W 0.0 to 600.0 seconds 0.0
・
・
・
309
310
7 R/W 0.0
・
・
・
313
314
7 R/W 0 to 10 times
・
・
・
317
318
1 R/W
・
・
・
321
322
1 R/W
・
・
・
325
326
1 R/W
・
・
・
329
330
1 R/W 0: Unused
・
・
・
333
335
・
・
・
373
Attribute
Data range
M: Relay contact output
V: Voltage pulse output
T: Triac output
D: Open collector output
PID control:
Output limiter (low) to
Output limiter (high)
Heat/cool PID control:
−Cool-side output limiter (high) to
+Heat-side output limiter (high)
Position proportioning control
(with FBR input):
Output limiter (low) to
Output limiter (high)
Position proportioning control
(without FBR input):
0: Close-side output OFF,
Open-side output OFF
1: Close-side output ON,
Open-side output OFF
2: Close-side output OFF,
Open-side output ON
1: Event 1 4: Event 4
2: Event 2
0: No function
1: EDS function mode
2: Learning mode
3: Tuning mode
EDS function: External disturbance
suppression function
0.0 to 1999.9 seconds
(0: No learning mode)
0: EDS start signal OFF
1: EDS start signal ON
(for disturbance 1)
2: EDS start signal ON
(for disturbance 2)
0: Unused
1: Monitor
2: Monitor + Event function
3: Control
0: ST unused
1: Execute once
2: Execute always
1: Learning
RKC communication
Least significant digit to 4th digit:
Communication switch
1 to 4
5th digit to Most significant digit:
Unused
Data 0: OFF 1: ON
Modbus
b0 to b3: Communication switch
1 to 4
b4 to b15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 15]
Factory
set value
M output:
20.0
V, T, D
output: 2.0
0.0
0
0
0
1
0
3
0
0
0
0
Communication data for multi-memory area data
(only for Modbus)
Use the register addresses of 0500H to 0553H to confirm or change set values of
parameters in multi-memory areas which are not selected. For example, when memory area
1 is selected, set values of parameters in memory-area 2 to 7 can be changed by these
register addresses. [For RKC communication, communication parameter is used to do the
same operation. Refer to SRZ Instruction Manual (IMS01T04-E).]
Name
Setting memory area
number
Event 1 set value (EV1) 0504
Event 2 set value (EV2) 0508
Event 3 set value (EV3) 050C
Event 4 set value (EV4) 0510
Control loop break alarm
(LBA) time
LBA deadband 0518
Set value (SV) 051C
Proportional band
[heat-side]
Integral time [heat-side] 0524
Derivative time [heat-side] 0528
Control response
parameter
Proportional band
[cool-side]
Integral time [cool-side] 0534
Derivative time [cool-side] 0538
Overlap/Deadband 053C
Manual reset 0540
Setting change rate limiter
(up)
Setting change rate limiter
(down)
Area soak time 054C
Link area number 0550
For the Modbus data mapping function, see the SRZ Instruction Manual
(IMS01T04--E).
Modbus is a registered tradema rk of Schneider Electric.
Company names and product names used i n this manual are the trademarks or registered
trademarks of the respective companies.
HEADQUARTERS: 16-6, KUGAHARA 5-CHOME, OHTA-KU TOKYO 146-8515 J APAN
PHONE: 03-3751-9799 (+81 3 3751 9799) E-mail: info@rkcinst.co.jp
FAX: 03-3751-8585 (+81 3 3751 8585) SEP. 2007
Modbus
register address
HEX DEC
0500
・
・
・
0503
・
・
・
0507
・
・
・
050B
・
・
・
050F
・
・
・
0513
0514
・
・
・
0517
・
・
・
051B
・
・
・
051F
0520
・
・
・
0523
Attribute
1280
1283
1284
1287
1288
1291
1292
1295
1296
1299
1300
1303
1304
1307
1308
1311
1312
1315
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
1 to 8 1
R/W
R/W
Deviation action,
Deviation action between channels,
Temperature rise completion range:
R/W
−Input span to +Input span
Process action, SV action:
Input scale low to Input scale high
R/W
MV action:
−5.0 to +105.0 %
R/W
R/W 0 to 7200 seconds
(0: Unused)
R/W 0 (0.0) to Input span
R/W Setting limiter (low) to
Setting limiter (high)
R/W TC/RTD inputs:
0 (0.0) to Input span (Unit: °C [°F])
Voltage (V)/current (I) inputs:
0.0 to 1000.0 % of Input span
0 (0.0): ON/OFF action
1316
・
・
・
0527
・
・
・
052B
052C
・
・
・
052F
0530
・
・
・
0533
・
・
・
0537
・
・
・
053B
・
・
・
053F
・
・
・
0543
0544
・
・
・
0547
0548
・
・
・
054B
・
・
・
054F
・
・
・
0553
RKC INSTRUMENT INC.
®
R/W PID control or heat/cool PID control:
・
1319
1320
1323
1324
1327
1328
1331
1332
1335
1336
1339
1340
1343
1344
1347
1348
1351
1352
1355
1356
1359
1360
1363
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
・
0 to 3600 seconds or
0.0 to 1999.9 seconds
(0, 0.0: PD action)
Position proportioning control:
1 to 3600 seconds or
0.1 to 1999.9 seconds
R/W 0 to 3600 seconds or
0.0 to 1999.9 seconds
(0, 0.0: PI action)
R/W 0: Slow
1: Medium
2: Fast
When the P or PD action is selected,
this setting becomes invalid.
R/W TC/RTD inputs:
1 (0.1) to Input span (Unit: °C [°F])
Voltage (V)/current (I) inputs:
0.1 to 1000.0 % of Input span
R/W 0 to 3600 seconds or
0.0 to 1999.9 seconds
(0, 0.0: PD action)
R/W 0 to 3600 seconds or
0.0 to 1999.9 seconds
(0, 0.0: PI action)
R/W TC/RTD inputs:
−Input span to +Input span
(Unit:°C [°F])
Voltage (V)/current (I) inputs:
−100.0 to +100.0 % of Input span
R/W −100.0 to +100.0 % 0.0
R/W 0 (0.0) to Input span/unit time
0 (0.0): Unused
R/W Unit time: 60 seconds
(factory set value)
R/W 0 to 11999 seconds or 0 to 5999
minutes
R/W 0 to 8
(0: No link)
Data range
Factory
set value
50
50
50
50
480
0 (0.0)
TC/RTD: 0
V/I: 0.0
TC/RTD:
30 (30.0)
V/I: 30.0
240
60
PID control,
Position
proportioning
control: 0
Heat/cool
PID control:
2
TC/RTD:
30 (30.0)
V/I: 30.0
240
60
0
0 (0.0)
0 (0.0)
0
0
The first edition: MAR. 2006 [IMQ00]
The third edition: SEP. 2007 [IMQ00]
Factory
set value
Name
Control loop
break alarm
(LBA) time ♠
LBA deadband
♠
Set value (SV)
♠
Proportional
band [heat-side]
♣ ♠
Integral time
[heat-side]
♣ ♠
Derivative time
[heat-side]
♣ ♠
Control response
parameter
♣ ♠
Proportional
band [cool-side]
♣ ♠
Integral time
[cool-side]
♣ ♠
Derivative time
[cool-side]
♣ ♠
Overlap/
Deadband
♣ ♠
Manual reset
♠
Setting change
rate limiter (up)
♠
Setting change
rate limiter
(down) ♠
Area soak time
♠
Link area number
0
0
0
0
1
0
♠
Heater break
alarm (HBA) set
value ♠
Heater break
determination
point ♠
Heater melting
determination
point ♠
PV bias
♠
PV digital filter
♠
PV ratio
♠
PV low input
cut-off
♠
RS bias *
♠
RS digital filter *♠ F2
RS ratio *
♠
Output
distribution
selection
♠
50
* Data on RS bias, RS ratio and RS digital filter is that in cascade contr ol or ratio setting.
RKC
Identifier
A5
N1
S1
P1
I1
D1
CA
P2
I2
D2
V1
MR
HH
HL
TM
LP
A7
NE
NF
PB
F1
PR
DP
RB
RR
DV
Modbus
register address
HEX DEC
0086
134
・
・
・
・
・
・
0089
137
008A
138
・
・
・
・
・
・
008D
141
008E
142
・
・
・
・
・
・
0091
145
0092
146
・
・
・
・
・
・
0095
149
0096
150
・
・
・
・
・
・
0099
153
009A
154
・
・
・
・
・
・
009D
157
009E
158
・
・
・
・
・
・
00A1
161
00A2
162
・
・
・
・
・
・
00A5
165
00A6
166
・
・
・
・
・
・
00A9
169
00AA
170
・
・
・
・
・
・
00AD
173
00AE
174
・
・
・
・
・
・
00B1
177
00B2
178
・
・
・
・
・
・
00B5
181
00B6
182
・
・
・
・
・
・
00B9
185
00BA
186
・
・
・
・
・
・
00BD
189
00BE
190
・
・
・
・
・
・
00C1
193
00C2
194
・
・
・
・
・
・
00C5
197
00C6
198
・
・
・
・
・
・
00C9
201
00CA
202
・
・
・
・
・
・
00CD
205
206
00CE
・
・
・
・
・
・
00D1
209
210
00D2
・
・
・
・
・
・
00D5
213
00D6
214
・
・
・
・
・
・
00D9
217
00DA
218
・
・
・
・
・
・
00DD
221
222
00DE
・
・
・
・
・
・
00E1
225
00E2
226
・
・
・
・
・
・
00E5
229
00E6
230
・
・
・
・
・
・
00E9
233
234
00EA
・
・
・
・
・
・
00ED
237
00EE
238
・
・
・
・
・
・
00F1
241
Attri-
Digits
bute
7 R/W 0 to 7200 seconds
Data range
(0: Unused)
Factory
set value
7 R/W 0 (0.0) to Input span 0 (0.0)
7 R/W Setting limiter (low) to
Setting limiter (high)
TC/RTD inputs:
7 R/W
0 (0.0) to Input span
(Unit: °C [°F])
Voltage (V)/current (I) inputs:
0.0 to 1000.0 % of Input span
0 (0.0): ON/OFF action
PID control or heat/cool PID
7 R/W
control:
0 to 3600 seconds or 0.0 to
1999.9 seconds
(0, 0.0: PD action)
Position proportioning control:
1 to 3600 seconds or 0.1 to
1999.9 seconds
0 to 3600 seconds or 0.0 to
7 R/W
1999.9 seconds
(0, 0.0: PI action)
1 R/W 0: Slow
1: Medium
2: Fast
When the P or PD action is
selected, this setting becomes
invalid.
TC/RTD inputs:
7 R/W
1 (0.1) to Input span
(Unit: °C [°F])
Voltage (V)/current (I) inputs:
0.1 to 1000.0 % of Input span
0 to 3600 seconds or
7 R/W
0.0 to 1999.9 seconds
(0, 0.0: PD action)
0 to 3600 seconds or
7 R/W
0.0 to 1999.9 seconds
(0, 0.0: PI action)
TC/RTD inputs:
7 R/W
−Input span to +Input span
(Unit:°C [°F])
Voltage (V)/current (I) inputs:
−100.0 to +100.0 % of Input span
TC/RTD: 0
V/I: 0.0
TC/RTD:
30 (30.0)
V/I: 30.0
PID control,
Position
proportioning
control: 0
Heat/cool
PID control:
2
TC/RTD:
30 (30.0)
V/I: 30.0
7 R/W −100.0 to +100.0 % 0.0
7 R/W 0 (0.0) to Input span/unit time
0 (0.0): Unused
7 R/W Unit time: 60 seconds
(factory set value)
0 minutes 00 seconds to
7 R/W
199 minutes 59 seconds:
RKC communication:
0:00 to 199:59 (min:sec)
Modbus: 0 to 11999 seconds
0 hours 00 minutes to
99 hours 59 minutes:
RKC communication:
0:00 to 99:59 (hrs:min)
Modbus: 0 to 5999 minutes
7 R/W 0 to 8
(0: No link)
When CT is CTL-6-P-N:
7 R/W
0.0 to 30.0 A (0.0: Not used)
When CT is CTL-12-S56-10L -N:
0.0 to 100.0 A (0.0: Not used)
7 R/W 0.0 to 100.0 % of HBA set value
(0.0: Heater break determination
is invalid)
7 R/W 0.0 to 100.0 % of HBA set value
(0.0: Heater melting
determination is invalid)
communication
Modbus:
7 R/W −Input span to +Input span 0
7 R/W 0.0 to 100.0 seconds
(0.0: Unused)
7 R/W 0.500 to 1.500 1.000
7 R/W 0.00 to 25.00 % of input span 0.00
7 R/W −Input span to +Input span 0
7 R/W 0.0 to 100.0 seconds
(0.0: Unused)
7 R/W 0.001 to 9.999 1.000
1 R/W 0: Control output
1: Distribution output
480
240
240
0 (0.0)
0 (0.0)
RKC
0:00
30.0
30.0