Modbus is a registered trademark of Schneider Electric.
Company names and product names used in this manual are the trademarks or registered trademarks of
the respective companies.
All Rights Reserved, Copyright 2007, RKC INSTRUMENT INC.
Thank you for purchasing this RKC instrument. In order to achieve maximum performance and ensure
proper operation of your new instrument, carefully read all the instructions in this manual. Please place this
manual in a convenient location for easy reference.
SYMBOLS
WARNING
CAUTION
!
: This mark indicates where additional information may be located.
An external protection device must be installed if failure of this instrument
could result in damage to the instrument, equipment or injury to personnel.
: This mark indicates precautions that must be taken if there is danger of electric
shock, fire, etc., which could result in loss of life or injury.
: This mark indicates that if these precautions and operating procedures are not taken,
damage to the instrument may result.
: This mark indicates that all precautions should be taken for safe usage.
: This mark indicates important information on installation, handling and operating
procedures.
: This mark indicates supplemental information on installation, handling and
operating procedures.
WARNING
!
All wiring must be completed before power is turned on to prevent electric
shock, fire or damage to instrument and equipment.
This instrument must be used in accordance with the specifications to
prevent fire or damage to instrument and equipment.
This instrument is not intended for use in locations subject to flammable or
explosive gases.
Do not touch high-voltage connections such as power supply terminals, etc.
to avoid electric shock.
RKC is not responsible if this instrument is repaired, modified or
disassembled by other than factory-approved personnel. Malfunction can
occur and warranty is void under these conditions.
IMS01T21-E2
i-1
CAUTION
This product is intended for use with industrial machines, test and measuring equipment.
(It is not designed for use with medical equipment and nuclear energy.)
This is a Class A instrument. In a domestic environment, this instrument may cause radio
interference, in which case the user may be required to take adequate measures.
This instrument is protected from electric shock by reinforced insulation. Provide reinforced
insulation between the wire for the input signal and the wires for instrument power supply,
source of power and loads.
Be sure to provide an appropriate surge control circuit respectively for the following:
- If input/output or signal lines within the building are longer than 30 meters.
- If input/output or signal lines leave the building, regardless the length.
This instrument is designed for installation in an enclosed instrumentation panel. All
high-voltage connections such as power supply terminals must be enclosed in the
instrumentation panel to avoid electric shock by operating personnel.
All precautions described in this manual should be taken to avoid damage to the instrument or
equipment.
All wiring must be in accordance with local codes and regulations.
All wiring must be completed before power is turned on to prevent electric shock, instrument
failure, or incorrect action.
The power must be turned off before repairing work for input break and output failure including
replacement of sensor, contactor or SSR, and all wiring must be completed before power is
turned on again.
To prevent instrument damage or failure, protect the power line and the input/output lines from
high currents with a protection device such as fuse, circuit breaker, etc.
Prevent metal fragments or lead wire scraps from falling inside instrument case to avoid
electric shock, fire or malfunction.
Tighten each terminal screw to the specified torque found in the manual to avoid electric shock,
fire or malfunction.
For proper operation of this instrument, provide adequate ventilation for heat dispensation.
Do not connect wires to unused terminals as this will interfere with proper operation of the
instrument.
Turn off the power supply before cleaning the instrument.
Do not use a volatile solvent such as paint thinner to clean the instrument. Deformation or
discoloration will occur. Use a soft, dry cloth to remove stains from the instrument.
To avoid damage to instrument display, do not rub with an abrasive material or push front
panel with a hard object.
Do not connect modular connectors to telephone line.
NOTICE
This manual assumes that the reader has a fundamental knowledge of the principles of electricity,
process control, computer technology and communications.
The figures, diagrams and numeric values used in this manual are only for purpose of illustration.
RKC is not responsible for any damage or injury that is caused as a result of using this instrument,
instrument failure or indirect damage.
RKC is not responsible for any damage and/or injury resulting from the use of instruments made by
imitating this instrument.
Periodic maintenance is required for safe and proper operation of this instrument. Some components
have a limited service life, or characteristics that change over time.
Every effort has been made to ensure accuracy of all information contained herein. RKC makes no
warranty expressed or implied, with respect to the accuracy of the information. The information in this
manual is subject to change without prior notice.
No portion of this document may be reprinted, modified, copied, transmitted, digitized, stored,
processed or retrieved through any mechanical, electronic, optical or other means without prior written
approval from RKC.
1.1 Features ...........................................................................................1-2
1.2 Checking the Product .......................................................................1-3
1.3 Model Code ......................................................................................1-4
1.4 Parts Description ..............................................................................1-5
1.5 Corresponding to the SRZ Modules
and Communication Protocol................................1-7
1.6 Application of Z-CT Module ..............................................................1-8
IMS01T21-E2 1-1
1. OUTLINE
1.1 Features
The module type controller has the following features:
The current transformer input module Z-CT (hereafter called Z-CT module) has 12 current transformer
(CT) inputs (hereafter called CT inputs), and is a functional module that is used exclusively for the module
type controller SRZ.Z-CT module interfaces with the host computer via Modbus or RKC communication
protocols. The Z-CT module sets all of the data items via communication (The communication interface
used for both protocols is RS-485). Therefore before operation, it is necessary to set value of each data item
via communication.
Heater break alarm (HBA) and heater overcurrent alarm are possible
A Z-TIO module or Z-DIO module can be connected to a Z-CT module to enable the use of heater break
alarm (HBA), heater melting alarm, and heater overcurrent alarm. (Time proportional output is supported.)
Both heater break alarm (HBA) and heater overcurrent alarm can be used with one CT input.
(Either alarm can also be used alone.)
• A Z-CT module can be connected to a Z-TIO module to enable heater break alarm (HBA) and heater
overcurrent alarm for three-phase loads.
• When the output distribution function is used with a Z-DIO module, a Z-CT module can be connected
to enable heater break alarm (HBA) and heater overcurrent alarm for distribution output.
Heater break alarm (HBA) and heater overcurrent can be set automatically
The heater break alarm (HBA) set value and heater overcurrent alarm set value can be automatically set
using the push button on the front of the Z-CT module or by communication.
CTs other than the specified CTs can also be used
CTs other than the specified CTs can be used by changing the CT type and CT ratio settings. There are
certain requirements for the CTs that can be used.
For details of CT condition, see on page 7-18.
Specified CTs
• CTL-6-P-Z (0.0 to 10.0 A)
• CTL-6-P-N (0.0 to 30.0 A)
• CTL-12-S56-10L-N (0.0 to 100.0 A)
12-point current measurement is possible with a single module
Up to 12 current transformers can be connected to one Z-CT module.
Up to 16 Z-CT modules can be connected, enabling 192-point current measurement.
When used for current measurement applications, a Z-CT module can be used by itself.
Some usage conditions may prevent the current transformer (CT) input value monitor
from showing the root mean squared current value. (See P. 7-4)
1-2 IMS01T21-E2
1.2 Checking the Product
Before using this product, check each of the following:
Model code
Check that there are no scratch or breakage in external appearance (case, front panel, or terminal, etc.)
Check that all of the items delivered are complete. (See below)
If any of the products are missing, damaged, or if your manual is incomplete, please contact RKC
sales office or the agent.
Package contents
1. OUTLINE
Name Q’TY
Z-CT module 1
Z-CT Instruction Manual (IMS01T16-E) 1 Enclosed with instrument
Joint connector cover KSRZ-517A 2 Enclosed with instrument
Power terminal cover KSRZ-518A 1 Enclosed with instrument
Remarks
Option (Sold separately)
Name Q’TY
End plate DEP-01 2
Connector SRZP-01 (front screw type) 2 For the connector type module
Connector SRZP-02 (side screw type) 2 For the connector type module
Terminal cover KSRZ-510A 1 For the terminal type module
Current transformer CTL-6-P-Z 1 0.0 to 10.0 A
Current transformer CTL-6-P-N 1 0.0 to 30.0 A
Current transformer CTL-12-S56-10L-N 1 0.0 to 100.0 A
Check whether the delivered product is as specified by referring to the following model code list. If the
product is not identical to the specifications, please contact RKC sales office or the agent.
Suffix code
Z-CT-A□/□-□□
(1) (2) (3) (4)
Suffix code Initial setting code
Specifications Hardware coding only Quick start code
(1) (2) (3) (4)
Wiring type
Quick start code
CT type
Communication
protocol
Terminal type T
Connector type
No quick start code (Configured as factory default)* N
Specify quick start code 1
No specify quick start code No code
CTL-6-P-N P
CTL-12-S56-10L-N S
CTL-6-P-Z
No specify quick start code No code
RKC communication (ANSI X3.28) 1
Modbus 2
C
Z
* Factory set value: CT type: P: CTL-6-P-N
Communication protocol: RKC communication (ANSI X3.28)
1-4 IMS01T21-E2
A
A
A
A
1.4 Parts Description
Module mainframe
<Terminal type>
Loader
communication
connector
utomatic
setting state
indication lamp
Current
transformer (CT)
input terminals
<Connector type>
Loader
communication
connector
utomatic
setting state
indication lamp
Current
transformer (CT)
input terminals
FAIL/ UNR
RX/TX
C
B
LOADER
A
9
8
7
6
5
SET
CT
FAIL/ UNR
RX/TX
C
B
A
LOADER
9
8
7
6
5
SET
CT
CN3
CN4
D
E
F
0
1
2
3
4
D
E
F
0
1
2
3
4
CN1
CN2
Indication lamps
ddress setting switch
Push button
Indication lamps
ddress setting switch
Push button
1. OUTLINE
(Right side)
DIP switch
Module
mainframe
Base
(Right side)
DIP switch
Module
mainframe
Base
Indication lamps
FAIL/RUN [Green or Red] When normal (RUN): A green lamp is on Self-diagnostic error (FAIL): A green lamp flashes Instrument abnormality (FAIL): A red lamp is on
RX/TX [Green] During data send and receive: A green lamp turns on
SET [Green] During automatic setting execution: A green lamp is on
(Automatic setting state indication lamp) Automatic setting failure: A green lamp flashes *
* Flashes if automatic setting fails for even one channel among the CT input channels for which automatic setting is being
executed.
Button
Push button
Use when the heater break alarm set value or heater overcurrent
alarm set value should be automatically set.
Switches
Address setting switch Sets the Z-CT module address. (See P. 5-2)
DIP switch
Sets the communication speed, data bit configuration, and
communication protocol. (See P. 5-3)
IMS01T21-E2 1-5
1. OUTLINE
f
Base
Mounting holes (M3 screw)
Holes for screws to fix the base to
a panel, etc.
Customer must provide the M3 screws.
Mounting bracket
Used to fix the module on DIN rails and
also to fix each module joined together.
(Front view)
Joint connector
Used to mechanically and electrically connect
each module.
Power supply terminals
Supply power to only one of the joined
modules, and all of the joined modules will
receive power.
(See 4.1 Wiring Cautions)
Communication terminals (RS-485)
Connect communication wires to only one o
the joined modules, and all of the joined
modules will communicate.
(Rear view)
1-6
IMS01T21-E2
1. OUTLINE
1.5 Corresponding to the SRZ Modules
and Communication Protocol
SRZ modules and communication protocols that can be connected to and used with the Z-CT module are shown
in the table below.
Can be used: ×Cannot be used: −
The connectable
SRZ module
Communication protocols
RKC communicationModbus PLC communication
Z-TIO-A/Z-TIO-B
Z-TIO-C/Z-TIO-D
Z-TIO-E/ Z-TIO-F
Z-DIO-A
Z-COM-A
× ×
× × −
× × −
× ×
− − −
IMS01T21-E2 1-7
1. OUTLINE
1.6 Application of Z-CT Module
For three-phase load alarm monitoring
For three-phase loads, two CT inputs are used for one control output.
When a Z-TIO module is connected to a three-phase load, the CT input (option) of the Z-TIO module does
not allow heater break alarms (HBA) and heater overcurrent alarms to be added to all control outputs.
A Z-CT module can be connected to the Z-TIO module to add heater break alarms (HBA) and heater
overcurrent alarms to the control outputs that could not be handled by the CT input (option) of the Z-TIO
module.
When the Z-TIO-B module (2-channel type) is used
CH1 control output
CH2
control
output
Power supply
24 V DC
SSR
R
U
S
V
T
W
CT input
SSR
R
S
T
U
V
W
CT input
CT input
Three-phase load
The heater break-alarm (HBA) and heater overcurrent alarm of the Z-CT module corresponds to
the time proportional output.
Z-CT module Z-TIO-B module
CT
RKC communication
Modbus
CT input
Three-phase load
Host
computer
RS-232C
RS-232C/RS-485
converter
RS-485
1-8 IMS01T21-E2
1. OUTLINE
For alarm monitoring of distribution output
When the output distribution function is used with a Z-DIO module, a Z-CT module can be connected to enable
detection of heater break and heater overcurrent in distribution output.
Z-DIO
module
CH1 control output
DIOCTTIO
TC
Power
supply
DC 24 V
Hot plate
Heater 1 Heater 2
Heater 3
CT input
CT input
CT input
SSR
SSR
SSR
The heater break-alarm (HBA) and heater overcurrent alarm of the Z-CT module corresponds to
the time proportional output.
For the output distribution function, see SRZ Instruction Manual (IMS01T04-E).
Z-CT module Z-TIO module
Distribution output
Host
computer
RS-232C
RS-232C/RS-485
converter
RS-485
RKC communication
Modbus
IMS01T21-E2
1-9
1. OUTLINE
For CT input value monitor
One Z-CT module is capable of monitoring 12 channels of current.
When only used for CT input value monitoring, the Z-CT module can be used by itself; connection to
another SRZ functional module (Z-TIO or Z-DIO module) is not necessary.
Some usage conditions may prevent the current transformer (CT) input value monitor
from showing the root mean squared current value. (See P. 7-4)
Load
SSR
CT input
Load
SSR
CT input
Load
SSR
CT input
Z-CT module
RKC communication
Power supply
24 V DC
You can confirm the current value by
the current transformer (CT) input
value monitor.
Before configuring settings, complete installation of the SRZ and host computer and make all connections.
Once installation and the connections are completed, follow the procedure below to configure settings
required for operation.
(1) When the Z-CT module is connected to a Z-TIO module or Z-DIO module
Processing of
the host computer side
Preparation of
communication program
Execute it after turning
on a power supply of the
host computer.
communication relation
Setting of
• Communication speed setting
• Data bit configuration
• Communication port setting
Power-OFF
Power-ON
Turn on the power of the host computer and SRZ.
Communication program start
Set the engineering setting
data of Z-TIO and Z-DIO
modules
Set the Input scale high/low limit, Input range decimal point position, Control type, Event type etc.
A
Processing of the SRZ side
Execute it after turning
off a power supply o
the SRZ unit.
Setting of
communication relation
Set the host computer
and SRZ in always
the same value.
Before setting operation data items, always set initial setting data items so as to
satisfy the specification used.
For the engineering setting data items of Z-TIO module and Z-DIO module, see SRZ
Instruction Manual (IMS01T04-E).
• Communication speed setting
• Data bit configuration
• Communication protocol selection
See 5.2 Protocol Selections
and Communication Speed
Setting (P. 5-3).
Module address setting
See 5.1 Module Address
Setting (P. 5-2).
2-2 IMS01T21-E2
2. HANDLING PROCEDURE TO OPERATION
A
Set the normal setting data
of Z-TIO and Z-DIO modules
Set parameters in Normal setting of data.
For the normal setting data of Z-TIO module and Z-DIO module, see SRZ Instruction Manual (IMS01T04-E).
Sets the data of
Z-CT module
Before starting automatic setting, always set the data of heater break alarm (HBA) or
heater overcurrent alarm.
Set the heater break/heater overcurrent alarm automatic setting selection, Module address
assignments for CT input, Module channel assignments for CT input, etc.
For the automatic setting, see 6.3 automatic setting example (P. 6-12).
Temperature rise start
Power on the load.
Set the SRZ unit to RUN (start control).
For the RUN/STOP transfer of SRZ unit, see SRZ instruction Manual (IMS01T04-E).
Automatic setting start
Start automatic setting of the heater break alarm (HBA) or heater overcurrent alarm using the push
button or communication.
For the procedure for starting automatic setting, see 6.3.4 Procedure for executing automatic setting (P. 6-21).
Operation start
IMS01T21-E2
2-3
2. HANDLING PROCEDURE TO OPERATION
f
(2) Using the Z-CT module by itself (using as a CT input monitor)
Some usage conditions may prevent the current transformer (CT) input value monitor
from showing the root mean squared current value. (See P. 7-4)
Communication program start
CT input value monitor start
Processing of
the host computer side
Preparation of
communication program
Execute it after turning
on a power supply of the
host computer.
Setting of
communication relation
• Communication speed setting
• Data bit configuration
• Communication port setting
Power-OFF
Power-ON
Turn on the power of the host computer and SRZ.
Operation start
Set the host computer
and SRZ in always
the same value.
Processing of the SRZ side
Setting of
communication relation
• Communication speed setting
• Data bit configuration
• Communication protocol selection
Module address setting
Execute it after turning
off a power supply o
the SRZ unit.
• If the ambient temperature rises above 50 °C, cool this instrument with a forced air fan, cooler, or the like.
However, do not allow cooled air to blow this instrument directly.
• In order to improve safety and the immunity to withstand noise, mount this instrument as far away as
possible from high voltage equipment, power lines, and rotating machinery.
− High voltage equipment: Do not mount within the same panel.
− Power lines: Separate at least 200 mm
− Rotating machinery: Separate as far as possible
(5) This instrument is Permanently connected to equipment, please take the following points.
• A switch or circuit-breaker shall be included in the building installation.
• It shall be in close proximity to the equipment and within easy reach of the operator.
• It shall be marked as the disconnecting device for the equipment.
3-2 IMS01T21-E2
3. MOUNTING
• Space required between each module vertically
When the module is mounted on the panel, allow a minimum of 50 mm at the top and bottom of the module
to attach the module to the mainframe.
50 mm or more
• Depth for connector mount type module (Connector type)
Space for connectors and cables must be considered when installing.
76.9 mmApprox. 50 mm
Connector
(Plug)
• Mounting the joint connector cover
It is recommended to use a plastic cover on the connector on both sides of the mounted modules for
protection of connectors.
Joint connector cover
Joint connector cover (Standard equipment)
Parts code Ordering code Q’ty
KSRZ-517A 00433384 2
• Installing direction of SRZ unit
Mount the SRZ unit in the direction specified as shown below.
IMR01W21-E2
Top
Bottom
3-3
3. MOUNTING
3.2 Dimensions
<Terminal type module>
100
85
(Unit: mm)
30 6.7
5
<Connector type module>
99
76.9 2.9
100
5
Connector type (sold separately):
SRZP-01 [Front-screw type]
89.7
76.92.9
100
5
Connector type (sold separately):
SRZP-02 [Side-screw type]
(Unit: mm)
30 6.7
3-4 IMS01T21-E2
3. MOUNTING
3.3 Joinable Number of Modules
The maximum number of functional modules (Z-TIO, Z-DIO or Z-CT module) that can be connected at a
time is indicated below.
When connecting only Z-CT modules: Up to 16 modules
When connecting only the Z-CT modules
Up to 16 modules
(
)
SRZ unit
When connecting two or more different types of functional modules: Up to 31 modules
(However, the number of connected function modules of the same type must not exceed the maximum)
4.3.2 Power supply terminals and communication terminals ..............................4-7
4.4 Connection to Host Computer ..........................................................4-8
4.5 Installation of Termination Resistor ................................................4-13
4.6 Connections for Loader Communication ........................................4-15
IMS01T21-E2 4-1
4. WIRING
4.1 Wiring Cautions
To prevent electric shock or instrument failure, do not turn on the power until all
the wiring is completed.
WARNING
!
• To avoid noise induction, keep input/output signal wires away from instrument power line, load lines and
power lines of other electric equipment.
• If there is electrical noise in the vicinity of the instrument that could affect operation, use a noise filter.
− Shorten the distance between the twisted power supply wire pitches to achieve the most effective noise
reduction.
− Always install the noise filter on a grounded panel. Minimize the wiring distance between the noise
filter output and the instrument power supply terminals to achieve the most effective noise reduction.
− Do not connect fuses or switches to the noise filter output wiring as this will reduce the effectiveness of
the noise filter.
• Power supply wiring must be twisted and have a low voltage drop.
• For an instrument with 24 V power supply, supply power from a SELV circuit.
• A suitable power supply should be considered in the end-use equipment. The power supply must be in
compliance with a limited-energy circuits (maximum available current of 8 A).
• Supply the power to only one of the joined modules. When power is supplied to any one of the joined
modules, all of the joined modules will receive power.
• Select the power capacity which is appropriate for the total power consumption of all joined modules and
the initial current surge when the power is turned on.
Z-CT module power consumption (at maximum load): 35 mA max. (at 24 V DC)
Rush current: 10 A or less
• For the power supply terminals and communication terminals, use the specified solderless terminals.
Only these specified solderless terminals can be used due to the insulation between the terminals.
0.4 N・m (4 kgf・cm)
Applicable wire: Solid/twisted wire of 0.25 to 1.65 mm
2
φ
5.5 MAX
φ
3.2 MIN
φ
3.2
Specified solderless terminals:
Manufactured by J.S.T MFG CO., LTD.
Circular terminal with isolationV1.25−MS3 (M3 screw, width 5.5 mm, hole diameter 3.2 mm)
5.6 mm
9.0 mm
Connecting solderless terminals to CT input terminals (terminal type module)
When using a non-specified CT, use solderless terminals that are the same size as the above.
A spade terminal (Y type) can also be used if it is the same size.
4-2 IMS01T21-E2
Loading...
+ 84 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.