Rittal SK 3382.xxx, SK 3359.xxx, SK 3383.xxx, SK 3384.xxx, SK 3385.xxx Assembly Instructions Manual

...
Schaltschrank­Kühlgerät
Cooling unit Climatiseur Koelaggregaat Kylaggregat Condizionatore
para armarios
Montageanleitung Assembly instructions Notice de montage Montage-instructie Montageanvisning Istruzioni di montaggio Instrucciones de montaje
Umschalten auf Perfektion
SK 3382.xxx SK 3359.xxx SK 3383.xxx
SK 3384.xxx SK 3385.xxx
SK 3386.xxx SK 3387.xxx
00_Umsch_Ti_SK3382.fm Seite 1 Freitag, 5. März 2004 4:24 16
2
375
415
326
170
597
415
365
Ø 80
30
Abb. 3.1
Montageausschnitte
Fig. 3.1
Mounting cutouts
Fig. 3.1
Découpes de montage
Afb. 3.1
Montage-uitsparingen
Bild 3.1
Håltagning
Fig. 3.1
Dime di foratura
Fig. 3.1
Recorte del montaje
Montageausschnitt
SK 3359.... / SK 3382....
Montageausschnitt
SK 3383.... / SK 3384.... / SK 3385....
Montageausschnitt
SK 3386.... / SK 3387....
475
260
326
375
597
475
415
420
280
597
415
380
Ø 100
27
490
597
420
390
475
580
520
392
796 692
470
796
538
Ø 150
38.5
580
238
Ø 150
01_SK3382_2_3.fm Seite 2 Freitag, 5. März 2004 4:27 16
Tab. 2.1
Tec hnische Daten
Tab. 2.1
Tec hnical data
Tab. 2.1
Données techniques
Tab. 2.1
Tec hnische gegevens
Tab. 2.1
Tekniska data
Tab. 2.1
Caratteristiche tecniche
Tab. 2.1
Datos técnicos
Farbton RAL 7035
Edelstahlhaube
1.4301
Bemessungs­spannung
Bemes­sungs­strom
Anlauf­strom
Vor­siche­rung T
Einschalt­dauer
Bemessungs­leistung
Nutzkühlleistung Kältemittel zul.
Druck PS
Temperatur­bereich
Geräusch­pegel
Schutzart Innenkreislauf Außenkreislauf
Abmessungen (B x H x T) mm
Gewicht
Colour RAL 7035
Stainless steel cover
1.4301
Operating voltage
Rated current
Starting current
Pre-fuse TDuty cycle Nom.
refrigeration
Useful cooling output
Refrigerant Permis-
sible pressure
Temperature range
Noise level
Protection categ. Internal circuit External circuit
Dimensions (W x H x D) mm
Weight
Coloris RAL 7035
Capot en acier inoxydable
1.4301
Tension nominale
Courant nominal
Courant de démarrage
Dispositif de sécurité T
Durée de mise en circuit
Puissance nominale
Puissance frigorifique de régime
Fluide frigori­gène
Pression de régime autor.
Plage de température
Niveau sonore
Degré de protect. Circuit intérieur Circuit extérieur
Dimensions (L x H x P) mm
Poids
Kleur RAL 7035
RVS mantel
1.4301
Bedrijfs­spanning
Nominale stroom
Aanloop­stroom
Primaire zekering T
Inschakel­duur
Nominaal vermogen
Nuttig koelvermogen
Koel­middel
p. max. Temperatuur-
bereik
Geluids­nivo
Beschermklasse Inwendig circuit Uitwend. circuit
Afmetingen (B x H x D) mm
Gewicht
Färgton RAL 7035
Huv i rostfritt stål 1.4301
Anslutnings­spänning
Märk­ström
Startström För-
säkring gL
Inkopp­lingstid
Märkeffekt Effektiv
kyleffekt
Kylmedel Tillåtet
drifts­övertryck
Temperatur­område
Ljudnivå Kapslingsklass
Inre kretslopp Yttre kretslopp
Mått (B x H x D) mm
Vikt
Colore RAL 7035
Cover in acciaio inox 1.4301
Tensione nominale
Corrente nominale
Corrente di spunto
Fusibili T Ciclo d’in-
serzione
Potenza nominale
Potenza frigorifera utile
Fluido frigorigeno
Pressione max.
Campo di temperatura
Livello di rumore
Grado di protez. Circuito interno Circuito esterno
Dimensioni (L x A x P) mm
Peso
Color RAL 7035
Cubierta de acero inoxidable
1.4301
Tensión de servicio
Intensidad nominal
Intensidad de arranque
Fusible T Duración
de conexión
Potencia nominal
Potencia frigorífica útil
Fluido frigorífico
Presión máxima admis.
Campo de temperaturas
Nivel de ruido
Protección Circuito interior Circuito exterior
Dimensiones (anch. x alt. x prof.) mm
Peso
RAL 7035
1.4301
L35 L 35 L35 L 50
DIN 3168/EN 814 L35 L 35 L35 L 50
EN 60529
SK 3382.100 SK 3382.500
SK 3382.200 SK 3382.600
230 V, 50/ 60 Hz
2.7 A/
2.9 A
9.2 A/
10.2 A
10.0 A/
10.0 A
100 %
360 W/410 W 410 W/450 W
500 W/510 W 270 W/370 W
R134a, 250 g
25 bar
+20 – +55°C
<64dB(A)
IP 54 IP 34
597 x 415 x 375
30 kg
SK 3382.110 SK 3382.510
SK 3382.210 SK 3382.610
115 V,
50/ 60 Hz
5.5 A/
6.0 A
18.4 A/
18.4 A
10.0 A/
10.0 A
100 %
370 W/420 W 420 W/470 W
R134a, 250 g
+20 – +55°C
<64dB(A)
IP 54 IP 34
35 kg
SK 3359.100 SK 3359.500
SK 3359.200 SK 3359.600
230 V, 50/ 60 Hz
3.0 A/
3.9 A
10.0 A/
10.7 A
10.0 A/
10.0 A
100 %
410 W/520 W 490 W/600 W
750 W/810 W 545 W/590 W
R134a, 300 g
25 bar
+20 – +55°C
<64dB(A)
IP 54 IP 34
596 x 415 x 375
32 kg
SK 3359.110 SK 3359.510
SK 3359.210 SK 3359.610
115 V,
50/ 60 Hz
6.0 A/
7.8 A
20.0 A/
21.4 A
16.0 A/
16.0 A
100 %
420 W/535 W 500 W/615 W
R134a, 300 g
+20 – +55°C
<64dB(A)
IP 54 IP 44
34 kg
SK 3359.140 SK 3359.540
SK 3359.240 SK 3359.640
400 V, 2 ~, 50/60 Hz
1.7 A/
2.2 A
5.8 A/
6.2 A
10.0 A/
10.0 A
100 %
R134a, 300 g
+20 – +55°C
<64dB(A)
IP 54 IP 34
34 kg
SK 3383.100 SK 3383.500
SK 3383.200 SK 3383.600
230 V, 50/ 60 Hz
4.3 A/
4.5 A
15.5 A/
15.5 A
10.0 A/
10.0 A
100 %
550 W/650 W 660 W/750 W
1000 W/1080 W
760 W/ 820 W
R134a, 500 g
25 bar
+20 – +55°C
<64dB(A)
IP 54 IP 34
597 x 415 x 475
40 kg
SK 3383.110 SK 3383.510
SK 3383.210 SK 3383.610
115 V, 50/ 60 Hz
8.3 A/
8.7 A
25.3 A/
24.3 A
16.0 A/
16.0 A
100 %
580 W/660 W 670 W/755 W
R134a, 500 g
+20 – +55°C
<64dB(A)
IP 54 IP 44
46 kg
SK 3383.140 SK 3383.540
SK 3383.240 SK 3383.640
400 V, 2 ~, 50/60 Hz
2.4 A/
2.4 A
8.0 A/
8.8 A
10.0 A/
10.0 A
100%
R134a, 500 g
+20 – +55°C
<64dB(A)
IP 54 IP 34
46 kg
SK 3384.100 SK 3384.500
SK 3384.200 SK 3384.600
230 V, 50/ 60 Hz
5.7 A/
6.8 A
16.6 A/
17.1 A
10.0 A/
10.0 A
100%
815 W/ 930 W 950 W/1090 W
1500 W/1520 W 1100 W/1210 W
R134a, 500 g
25 bar
+20 – +55°C
<64dB(A)
IP 54 IP 34
41 kg
SK 3384.110 SK 3384.510
SK 3384.210 SK 3384.610
115 V, 50/ 60 Hz
12.5 A/
14.1 A
30.7 A/
29.1 A
20.0 A/
20.0 A
100%
850 W/ 950 W
1000 W/1150 W
R134a, 500 g
+20 – +55°C
<64dB(A)
IP 54 IP 34
47 kg
SK 3384.140 SK 3384.540
SK 3384.240 SK 3384.640
400 V, 2 ~, 50/60 Hz
3.4 A/
4.0 A
9.8 A/
9.6 A
10.0 A/
10.0 A
100%
R134a, 500 g
+20 – +55°C
<64dB(A)
IP 54 IP 34
47 kg
SK 3385.100 SK 3385.500
SK 3385.200 SK 3385.600
230 V, 50/ 60 Hz
5.7 A/
6.6 A
16.8 A/
18.4 A
10.0 A/
10.0 A
100 %
1000 W/1175 W 1100 W/1310 W
2000 W/2130 W 1570 W/1670 W
R134a, 950 g
25 bar
+20 – +55°C
<64dB(A)
IP 54 IP 34
42 kg
SK 3385.110 SK 3385.510
SK 3385.210 SK 3385.610
115 V, 50/ 60 Hz
13.0 A/
14.2 A
36.0 A/
32.0 A
20.0 A/
20.0 A
100 %
1050 W/1250 W 1160 W/1380 W
R134a, 950 g
+20 – +55°C
<64dB(A)
IP 54 IP 34
48 kg
SK 3385.140 SK 3385.540
SK 3385.240 SK 3385.640
400 V, 2 ~, 50/60 Hz
3.3 A/
3.8 A
10.0 A/
12.0 A
10.0 A/
10.0 A
100%
R134a, 950 g
+20 – +55°C
<64dB(A)
IP 54 IP 34
48 kg
SK 3386.140 SK 3386.540
SK 3386.240 SK 3386.640
400 V, 3 ~, 50 Hz, 460 V, 3 ~, 60 Hz
3.0 A/
3.1 A
8.0 A/
9.0 A
10.0 A*/
10.0 A*
100%
1180 W/1490 W 1430 W/1770 W
3000 W/3300 W 2460 W/2750 W
R134a, 1600 g
25 bar
+20 – +55°C
<67dB(A)
IP 54 IP 34
796 x 470 x 580
70 kg
SK 3387.140 SK 3387.540
SK 3387.240 SK 3387.640
400 V, 3 ~, 50 Hz 460 V, 3 ~, 60 Hz
3.5 A/
3.6 A
17.0 A/
19.0 A
100%
1620 W/2060 W 1870 W/2340 W
4000 W/4200 W 3250 W/3490 W
R134a, 1800 g
25 bar
+20 – +55°C
<67dB(A)
IP 54 IP 34
77 kg
Technische Änderungen vorbehalten. Technical modifications reserved. Sous réserve de modifications techniques. Technische wijzigingen voorbehouden. Tekniska ändringar förbehålles. Rittal si riserva di apportare eventuali modifiche tecniche. Se reserva el derecho a realizar cambios técnicos. * Motorschutzschalter, motor circuit breaker, disjoncteur-protecteur, motorbeveiligingsschakelaar, motorskyddsbrytare, salvamotore, guardamotor.
D
GB
F
NL
S
I
E
J
3
01_SK3382_2_3.fm Seite 3 Freitag, 5. März 2004 4:27 16
8
Contents
1. Application
2. Technical data
3. Assembly of roof-mounted units
4. Safety notices
5. Electrical connection
6. Commencing operation and control behaviour
7. Supplementary functions
8. BUS system
9. Technical information
10. Handling Instructions
11. Scope of supply and guarantee
12. Display screen and system analysis
13. Comfort control programming
1. Application
Enclosure cooling units are designed and built to dissipate heat from enclosures by cooling the air inside the enclosure and protecting tempera­ture-sensitive components. Enclosure cooling units are particularly suitable for a temperature range of +40°C to +55°C.
2. Technical data
(see table 2.1)
3. Assembly of roof-mounted units
The roof-mounted unit can be assembled as standard. Make the cutout at the mounting place as shown in Fig. 3.1. Attach the enclosed sealing plate under the plastic base of the cooling unit and the enclosed sealing frame to the cut out roof plate. After the assembly of the unit, screw double-threaded bolts in the holes of the plastic base at the bottom side of the unit. After this, insert the sliding part, slide it over the cutout and fasten it by means of washers and nuts.
4. Safety notices
The following safety notices are to be observed in their entirety for the correct use of the equipment: Prior to mounting, ensure that:
the site for the enclosure, and hence the arrangement of the cooling unit, is selected so as to ensure good ventilation;
the location is free from excessive dirt and moisture;
the cutout for air extraction is located in the upper area of the enclosure;
the mains connection ratings, as stated on the rating plate, are available;
the ambient temperature does not exceed +55°C;
the packaging shows no signs of damage. Traces of oil on damaged packaging are an indication of refrigerant loss and of leakage in the unit system. Any damage to the packaging may be the cause of subsequent mal­functions;
the enclosure is sealed on all sides (IP 54). Condensation will occur if the enclosure is leaky;
the distance of the units from the wall should not be less than 200 mm;
air inlet and outlet are not obstructed on the inside of the enclosure;
units are only fitted horizontally in the speci­fied position. Max. deviation from the true horizontal: 2°;
condensate drainage is provided (see 9.3);
electrical connection and repair are carried out only by authorised personnel. Use only original replacement parts!
to avoid an increase in condensation, a door­operated switch (e.g. PS 4127.000) should be used which will switch the cooling unit off when the enclosure door is opened (see 7.3);
losses from the components installed in the enclosure must not exceed the specific refrigeration capacity of the cooling unit itself;
the customer must not modify the cooling unit in any way.
Important note:
In order to achieve a permanent seal between cooling unit and enclosure, the mounting surface should be reinforced or supported where neces­sary (see example fig. 3.2), especially in case of larger roof surfaces. Observe assembly instruc­tion under heading 3.
Fig. 3.2
Roof plate reinforcement with TS 8 enclosure
Accessory for roof plate reinforcement with TS: Mounting rail Sliding nut Mounting bracket Threaded block (see Accessories in the Rittal Catalogue)
Transportation by means of a crane: Remove blanking plug in the cover and screw in eyebolt M12.
5. Electrical connection
The connected voltage and frequency must correspond to the values stated on the rating plate. During commissioning, the data on the rating plate of the device shall apply. The cooling unit must be connected to the mains via an all-pin isolating device, which ensures at least 3 mm contact opening when switched off. The unit must not have any additional temperature control connected up-stream at the supply end. The fans and compressors built into single and three­phase devices are intrinsically safe (thermal winding protection).
This also applies to SK 3382...., SK 3359....,
SK 3383...., SK 3384...., SK 3385....
transformer types, and to specially rated units which are also fitted with a transformer. Line protection should be provided by means of the pre-fuse specified on the rating plate. Only one automatic cutout should be connected bet­ween the cooling unit and the power supply. A time-lag backup-fuse as specified on the rating plate (safety cutout K-characteristic or time-lag lead fuse) is mandatory.
The three phase supplies for the SK 3386.... /
SK 3387.... must be connected via a motor
safety switch to a TN grid with grounded star point. Summation current as specified on the rating plate. Specially rated three-phase units must be protected by means of transformer safety switches (category AC-6A) specified on the rating plate. For units designed for three phase 400/460 V, the rotary field or the absence of a phase is also monitored. If the rotary field is incorrect or a phase is absent, the unit will not run. Observe the relevant regulations during installation!
6.Commencing operation and control behaviour
Following the completion of mounting and a waiting period of approximately 30 minutes (to allow oil to collect in the compressor in order to ensure lubrication and cooling).
6.1 Basic control system
Version .....100 / .110 / .140
The cooling unit operates automatically, i.e. after electrical connection, the evaporator fan will run continuously to circulate the air inside the enclo­sure. The installed basic controller (setting the desired internal temperature; factory setting +35°C) provides automatic control switch-off of the cooling unit by the set value of the fixed switching difference of 5 K.
English
6.1.1 Temperature setting at the basic controller
First of all, the louvred grille with the incorporated display is to be removed from the unit. The display lock is then to be slackened and this is to be pushed forward off the louvred grille. Finally, the display screen (1) is carefully removed, e.g. with a screwdriver. The desired nominal temperature can be set on the potentiometer (2) which is now accessible. After the temperature has been set, the display of all screens in the louvred grille is to be locked once more. The louvred grille is to be fastened to the unit again.
Fig. 6.1
Basic controller
6.1.2 Operation of the basic controller
The basic controller monitors and controls the cooling unit. After the supply voltage has been connected, the green LED (3) lights to indicate readiness for operation. The green LED is connected in series with a door limit switch, and flashes if the enclosure door is opened. The red LED (4) signals too high a temperature inside the enclosure; at 5 K above the set value, the red LED comes on permanently. In addition, the excess temperature message can still be queried via an integrated potential-free contact in the cooling unit connection terminal. K1 fault signal relay with changeover contact Te rminal 3: NC (normally closed) Te rminal 4: C (connection between voltage
supply and fault signal relay) Te rminal 5: NO (normally open) The definitions NC and NO refer to the de­energised state. As soon as voltage is applied to the cooling unit, the fault signal relay picks up. As a result, the relay contacts change their state (contact 3 – 4 open; contact 4 – 5 closed), representing the normal operating status of the cooling unit. As soon as a system message occurs or the voltage supply is interrupted, the relay drops out. (see circuit diagrams on page 37). The high pressure alarm in the cooling circuit is indicated by the red LED flashing. In this case, the unit is to be reset manually, by pressing the rubberized potentiometer display (5) for 3 seconds (see 6.1.1).
6.2 Comfort controller control
Version .....500 / .510 / .540
Fig. 6.2
Comfort controller
34
1
2
5
H2 = Button
H4 = Button
/set
°C
H3 = Button
°F
H1 = Display terminal
After electrical connection the internal fan turns on and circulates the enclosure air. This helps assure even temperature distribution within the enclosure. The condenser fan and compressor are controlled by the Comfort controller. The minimum break time is 3 min. The switching difference is 5 K, but can be set in the range 2 – 10 K. To avoid short switching cycles and hence the danger of inadequate or only partial cooling in some sections of the enclosure, the switching difference should be set to be only as low as necessary. For economic reasons (energy saving), the nominal value of the internal enclosure temperature T as low as necessary.
6.2.1 Operation of the Comfort controller
The display terminal H1 consists of a 3 position 7-segment display which indicates the enclosure internal temperature in °C or °F (changeable) as well as any fault codes. The actual enclosure internal temperature is constantly displayed on H1. When a system message is generated, this alternates in the display with the current internal enclosure temperature. While programming the unit, the programming level and prescribed value are also displayed.
Test mode
By simultaneously holding down keys H2
°C key) and H4 ( /set key) for 5 seconds, the
( cooling unit will commence cooling operation, irrespective of the setpoint. The door limit switch function is disregarded in such cases. After approximately 5 minutes or upon reaching 15°C, the device deactivates cooling operation once again.
6.2.2
In the EEPROM of the Comfort controller various parameters are stored which can be changed by using the buttons H2, H3 and H4. 24 changeable parameters can be set via 24 programme levels in the stated ranges (max. and min. values). To this end, input code “22” is required (see diagram 13.1). The H2, H3 and H4 keys are multiple occupancy. To access programming mode, set 5 sec is to be pressed and held down. Primary occupancy (only diode displays): H2: °C, H3: °F, H4: Alarm Secondary occupancy (for programming): H2: Arrow upwards, H3: Arrow downwards, H4: set Programming via diagnostic software (order no. SK 3159.100) is also an option. The programming cable interface is the connecting cable plug, located on the rear of the Comfort controller. To do this, the louvred grille also is to be removed if necessary.
6.2.3 System messaging equipment
All system messages at the cooling unit are recorded and displayed as an error number by H1. System messages alternate in the display with the current internal enclosure temperature. (see 12. Comfort control fault display and error analysis).
6.2.3.1 System message contacts
Both relays are normally closed. All system messages assigned to an individual relay result in it opening. If the control voltage fails, this also results in the relay opening and can hence be captured and documented in the log file. According to individual weighting, all system messages can be assigned to both relays or suppressed. Terminal strip X3 provides the connection. See the wiring diagram for contact data and occupancy. K1/K2 fault signal relay (normally open contact): Te rminal 3: Fault signal relay 1 Te rminal 4: Voltage supply connection for both
Te rminal 5: Fault signal relay 2 (see the circuit diagrams on page 37).
should also be set to be only
i
(see diagram 13.1 Programming)
Programming (see 13.1 Comfort controller programming)
(K1 and K2; potential free)
fault signal relays
7. Supplementary functions
7.1 Filter mat use and changing
The PU foam filter mat available as an accessory is coarse and filters large dust particles or fluff from the air. Metallic filter mats are used to trap oil condensate. These are also available as an accessory. Subject to the suction of the blower being high enough, fine dust is blown through the filter mat and the external circuit of the unit. This does not affect the unit's operation.
Fig.7.1
Filter mat replacement
2.
1.
7.2 Filter mat monitoring
Function of the filter mat monitor: The filter mat is monitored for soiling by measur­ing the temperature difference in the external cir­culation of the cooling unit (see diagram 13.1: Programming on page 45). In the event of any filter mat soiling, the temperature difference will increase. The nominal value of the temperature difference in the external circuit is matched to the relevant operating points in the characteristic fields. Hence there is no requirement to adjust the nominal value for different unit operating points.
7.3 Door limit switch S1 (supplied by customer)
Where a door limit switch is used and the enclo­sure door is open (contact is closed when door is open), the cooling unit (fans and condenser) will switch off after approx. 15 s. This only applies to devices with a Comfort controller and devices with a three-phase connection to the basic con­troller. For devices with a basic controller (115 V, 230 V and 400 V, 2~), the internal fan is not switched off when using a door limit switch. Thereby avoiding an increase in condensation while the door is open. To avoid cyclic operation, switch-on of condenser and external fan is delayed by about 3 minutes after the cooling unit has been switched off. The internal fan will start up after about 15 s on closure of the door. Connection is made at the terminals 1 and 2. The extra low voltage is supplied by the internal power pack, current is approx. 30 mA DC. Each door limit switch must only be assigned to one cooling unit. Several door limit switches may be operated on one cooling unit (parallel connection). The minimum cross­section of the connection cable is 0.3 mm cable length of 2 m. The resistance of the door limit switch contact must not exceed a maximum of 50Ω.
Only connect the door limit switch to the cooling unit’s own DC supply!
7.4 Interface X3 (option)
(Connector X3)
Note!
The electrical signals at the interface are of an extra-low voltage (not extra-low safety voltages to EN 60 335).
The 9-pin SUB-D socket X3 can be used to connect additional interface cards for integrating cooling units with higher level monitoring systems. These cards are also available as an accessory. (Interface card: Model No. SK 3124.200).
2
for a
8. BUS system
(Model No.: Master-slave cable SK 3124.100)
8.1 General
The BUS system allows a maximum of 10 cool­ing units to be interconnected. As a result, the following functions are available to the operator:
Parallel unit control (the cooling units in the network can be simultaneously switched on and off)
Parallel door status messages (“door open”)
Parallel collective fault message
The data exchange is carried out using master­slave cables (shielded, two-wire leads). All units are assigned an address. This address also includes the ID for “master” or “slave”.
8.2 Installation notices for the X2 interface (Jack X2)
Note!
The electrical signals at the interface are of an extra-low voltage (not extra-low safety voltages to EN 60 335). Always heed the following notes!
De-energise the cooling units to be connected.
Ensure proper electrical insulation.
Make sure the cables are not laid in parallel to power lines.
Make sure that the lines are short.
8.3 Programming the cooling unit
See diagram 13.1 for details on programming.
ID’s:
Master cooling unit Slave cooling unit
00 Basic state 00 Basic state
Master
01
with 1 slave
Master
02
with 2 slaves
Master
03
with 3 slaves
Master
04
with 4 slaves
Master
05
with 5 slaves
Master
06
with 6 slaves
Master
07
with 7 slaves
Master
08
with 8 slaves
Master
09
with 9 slaves
Note
Only one unit may be configured as master; the address ID must match the number of slave units. The individual slave units must have different addresses; the addresses must be in ascending order (without gaps in between).
Example: 1 master cooling unit with 2 slave cooling units
Master
02
(see wiring example of master/slave and door limit function, page 42/43).
Slave
11
11
12
13
14
15
16
17
18
19
Slave
with address 1
Slave
with address 2
Slave
with address 3
Slave
with address 4
Slave
with address 5
Slave
with address 6
Slave
with address 7
Slave
with address 8
Slave
with address 9
Slave
12
9
Fig. 9.3
Condensate discharge
English
9.Technical information
The cooling unit (compressor refrigeration unit) consists of four main components: the coolant compressor, evaporator, condenser, and the control or expansion valve, which are connected by suitable pipework. This circuit is filled with a readily boiling substance, the refrigerant. The R134a (CH rine. It has an ozone destroying potential (ODP) of 0 and is therefore environmentally friendly. A filter dryer which is integrated in the hermetically sealed cooling circuit, provides effective protec­tion against moisture, acid, dirt particles, and foreign bodies within the cooling circuit.
9.1 Operation of the cooling unit
Fig. 9.1
Compressor
External circuit Internal circuit
The compressor takes the gaseous refrigerant from the evaporator and compresses it to a higher pressure in the condenser. During this process the temperature of the refrigerant rises above the ambient temperature and heat can be dissipated to the environment via the surface of the condenser. Then the refrigerant is liquefied and, by means of a thermostatically controlled expansion valve, returned to the evaporator, where it evaporates at low pressure. The heat required for complete evaporation is drawn from the enclosure interior causing it to cool down. The cooling cycle is thus completed, the afore­mentioned process of the heat transfer starts afresh.
9.2 Safety equipment
The cooling circuit of the cooling unit has a component-tested, high-pressure monitor to EN 12 263, which is set to maximum PS (allowed pressure) and operates via an automatic reset device in case of recurring pressure drop. Tem­perature monitoring will prevent the evaporator from icing up. If there is a risk of icing up, the compressor is switched off and automatically switched on again at higher temperatures. The refrigerant compressor and the fans are equipped with thermal winding protection switches against excess current and excess temperatures.
9.3 Condensate discharge
A cast gutter in the evaporator tray ensures that any condesate which may form on the evapora­tor (at high air humidity, low temperatures inside the enclosure), is drained away to the right or rear of the unit. For this purpose, a length of hose should be fitted to one of the two conden­sate pipe connection pieces (see fig. 9.3). The other drain that is not used has to be sealed accordingly. The condensate must be able to run off freely. If the condensate is to be drained off over a greater distance, then care must be taken that the hose is free from kinks and a check for correct drainage made. Units with a comfort controller have an additional conden­sate alarm.
FCF3) refrigerant is free from chlo-
2
Operation of the cooling unit
H
PSA
monitor
Fan 2
Evaporator
Fan 1
Liquefier
Filter dryer
Thermostat
Expansion valve
1
′′
/
2
10. Handling Instructions
Storage, maintenance, transport and disposal
As a maintenance-free, hermetically sealed system, the cooling circuit has been filled in the factory with the required amount of refrigerant, and tested for leaks and subjected to a function trial run. The installed maintenance-free fans use ball bearings, they are protected against moisture and dust, and are fitted with a temperature monitor. The life expectancy is at least 30,000 operating hours. The cooling unit is thus largely mainte­nance free. All that may be required from time to time is that the components of the external air circuit are cleaned by compressed air. The use of a filter mat is recommended only if large particles of lint are present in the air, so that blockage of the condenser is prevented. (Filter mat replacement, fig. 7.1). Note: Prior to any maintenance work, the power to the cooling unit must be disconnected.
Storage temperature: The cooling units must not be exposed to temperatures above +70°C. Transport position: The cooling units must always be transported upright. Waste disposal: The closed cooling circuit contains refrigerant and oil which must be correctly disposed of for the protection of the environment. Disposal can be carried out at Rittal. We reserve the right to make technical modifications.
11. Scope of supply and guarantee
1 cooling unit, ready for connection 1 drilling template 1 sealing plate 1 sealing frame 1 set of mounting and operating instructions 1 plug-in terminal strip
Guarantee: This unit is covered by a 1-year guarantee from the date of supply, subject to correct usage (see also Safety notices under heading 4.). Within this period, the returned unit will be repaired in the factory or replaced free of charge. The cooling unit is to be used for the cooling of enclosures only. If it is con­nected or handled improperly the manufacturer’s guarantee does not apply and in this case we are not liable for any damage caused.
10
Loading...
+ 13 hidden pages