Rittal SK 3378.200, SK 3378.280 Assembly And Operating Instructions Manual

Air/water heat exchangers
SK 3378.200
SK 3378.280
Assembly and operating instructions
Download options
Download options
Hinweis: Die Montage-, Installations- und Bedie­nungsanleitung ist auch als Download unter www.rittal.de verfügbar.
Note: The assembly and operating instructions are
available for downloading from www.rittal.com.
Remarque : La notice de montage, d'installation et d'em­ploi peut être téléchargée depuis le site www.rittal.fr.
Opmerking: De montage-, installatie- en gebruikshandlei-
ding is ook te downloaden via www.rittal.nl.
Obs: Montage-, installations- och bruksanvisning­en kan även laddas ner på www.rittal.se.
Nota: Las instrucciones de montaje, instalación y
puesta en marcha también están disponibles para su descarga en www.rittal.es.
Nota: Le istruzioni di montaggio, installazione e uso possono anche essere scaricate dal sito www.rittal.it.
注記: この取扱説明書 ( 組立・設置および運用マ
ニュアル ) は、www.rittal.co.jp からもダウ ンロードできます。
2 Rittal air/water heat exchanger
Safety instructions and warnings
Safety instructions and warnings
Warn- und Sicherheitshinweise
Warnung!
Bitte beachten Sie die maximal zulässi­gen Hebegewichte für Personen. Ggf. ist eine Hebevorrichtung zu verwenden.
Arbeiten an elektrischen Anlagen oder Betriebsmitteln dürfen nur von einer Elektrofachkraft oder von unterwiese­nem Personal unter Leitung und Auf­sicht einer Elektrofachkraft den elektrotechnischen Regeln entspre­chend vorgenommen werden. Der Luft/Wasser-Wärmetauscher darf erst nach Lesen dieser Informationen von den o. g. Personen angeschlossen werden!
Es darf nur spannungsisoliertes Werk­zeug benutzt werden.
Die Anschlussvorschriften des zuständi­gen Stromversorgungsunternehmens sind zu beachten. Der Luft/Wasser-Wärmetauscher muss über eine allpolige Trennvorrichtung nach Überspannungskategorie III (IEC 61 058-1) an das Netz angeschlossen werden.
Consignes de sécurité
Avertissement !
Veuillez tenir compte du poids de levage maximal autorisé pour les personnes et le cas échéant utilisez un appareil de le­vage.
Seuls les électriciens spécialisés ou les personnes dûment instruites opérant sous la direction et la surveillance d'un électricien spécialisé, sont autorisés à pratiquer des interventions sur les instal­lations ou appareils électriques, confor­mément aux règles de l'électrotech­nique. Les personnes mentionnées ci-dessus ne sont autorisées à raccorder l'échan­geur thermique air/eau qu'après avoir lu ces informations !
Utiliser exclusivement des outils isolés. Respecter les directives de raccorde-
ment du fournisseur d'électricité com­pétent. L'échangeur thermique air/eau doit être raccordé au réseau par l'intermédiaire d'un dispositif de coupure monophasé de catégorie III de surtension (CEI 61 058-1).
DE
Der Luft/Wasser-Wärmetauscher ist erst nach Trennung von allen Span­nungsquellen spannungsfrei!
Schalten Sie den Luft/Wasser-Wärme­tauscher vor dem Öffnen der Elektro­Anschlussbox und vor Arbeiten am Wasserkreislauf spannungsfrei und si­chern Sie ihn gegen versehentliches Wiedereinschalten. Die Spannungszuschaltung darf erst er­folgen, wenn das Abdeckblech der Elektro-Anschlussbox ordnungsgemäß verschraubt ist.
Vorsicht!
Verwenden Sie niemals brennbare Flüs­sigkeiten zur Reinigung des Luft/Was­ser-Wärmetauschers.
An nicht vollständig entgrateten Boh­rungen und Ausschnitten besteht Schnittgefahr, insbesondere bei der Montage des Luft/Wasser-Wärmetau­schers.
FR
L'échangeur thermique air/eau est hors tension uniquement après avoir débran­ché toutes les sources de tension !
Mettre l'échangeur thermique air/eau hors tension avant d'ouvrir le boîtier de raccordement électrique ou de travailler sur le circuit d'eau et prévenir toute re­mise en circuit inopinée. La mise sous tension doit avoir lieu uni­quement lorsque la face avant en tôle du boîtier de raccordement électrique est correctement vissée.
Prudence !
Ne jamais utiliser de liquides inflam­mables pour le nettoyage de l'échan­geur thermique air/eau.
Il y a risque de coupures au niveau des perçages et découpes qui ne sont pas complètement ébavurés, en particulier lors du montage de l'échangeur ther­mique air/eau.
Safety instructions and warnings
Warning!
Please note the maximum weights that may be lifted by individuals. It may be necessary to use lifting gear.
Work on electrical systems or equip­ment may only be carried out by an electrician or by trained personnel under the guidance and supervision of an electrician. All work must be carried out in accordance with electrical engineer­ing regulations. The air/water heat exchanger may only be connected after the above-men­tioned personnel have read this informa­tion!
Use only insulated tools. Follow the connection regulations of the
appropriate electrical supply company. The air/water heat exchanger must be connected to the mains via an all-pin isolating device to overvoltage catego­ryIII (IEC 61 058-1).
EN
The air/water heat exchanger is not de­energised until all of the voltage sources have been disconnected!
Switch off the power supply to the air/ water heat exchanger before opening the electrical connection box and before working on the water circuit, and take suitable precautions against it being ac­cidentally switched on again. The power supply must not be switched back on until the cover plate of the elec­trical connection box has been properly screw-fastened into position.
Caution!
Never use flammable liquids for cleaning the air/water heat exchanger.
There is a risk of cutting injury around all drill holes and cut-outs which have not been fully deburred, especially during mounting of the air/water heat exchang­er.
Rittal air/water heat exchanger 3
Contents
EN
Contents
Download options.......................................2
Safety instructions and warnings.................3
1 Notes on documentation .................. 5
1.1 CE label ....................................................... 5
1.2 Storing the documents................................. 5
1.3 Symbols used in these operating
instructions .................................................. 5
1.4 Other applicable documents ........................ 5
2 Safety instructions ............................ 5
3 Device description ............................ 6
3.1 Overview...................................................... 6
3.2 Functional description .................................. 6
3.2.1 How it works ......................................................... 6
3.2.2 Control .................................................................. 7
3.2.3 Bus mode ............................................................. 7
3.2.4 Safety equipment .................................................. 7
3.2.5 Condensation ....................................................... 7
3.2.6 Leak detection ...................................................... 7
3.2.7 Door limit switch ................................................... 7
3.2.8 Additional interface X3 .......................................... 7
3.3 Proper use ................................................... 7
3.4 Scope of supply........................................... 7
7 Inspection and maintenance .......... 20
7.1 General ...................................................... 20
7.2 Fan replacement ........................................ 21
8 Draining, storage and disposal ....... 21
9 Technical specifications ................. 22
10 List of spare parts .......................... 23
11 Hydrological data ........................... 24
12 Application example ....................... 25
13 Appendix ....................................... 26
13.1 Characteristic curves.................................. 26
13.1.1 Water resistance ................................................. 26
13.2 Drawings.................................................... 27
13.3 Circuit diagram........................................... 30
14 Declaration of conformity ............... 31
4 Installation ........................................ 8
4.1 Safety instructions........................................ 8
4.2 Siting location requirements ......................... 8
4.3 Assembly procedure .................................... 8
4.3.1 Assembly instructions ........................................... 8
4.3.2 Mounting options .................................................. 9
4.3.3 Connecting the condensate discharge ................ 10
4.4 Connecting the water connection............... 10
4.4.1 Notes on water quality ........................................ 11
4.4.2 Preparation and maintenance of the water in
recooling systems ............................................... 11
4.5 Routing busbars ........................................ 11
4.6 Electrical connection .................................. 12
4.6.1 Notes on electrical installation ............................. 12
4.6.2 Install the power supply ....................................... 13
5 Commissioning ............................... 13
6 Operation ....................................... 14
6.1 Properties .................................................. 14
6.2 Launching test mode ................................. 14
6.3 General programming information .............. 14
6.4 Eco-mode.................................................. 15
6.5 Editable parameters ................................... 16
6.6 Bus connection.......................................... 16
6.7 Programming overview of e-Comfort
controller .................................................... 18
6.8 Defining system messages for evaluation ... 19
6.9 Setting the master-slave identifier............... 19
6.10 Evaluating system messages ..................... 20
4 Rittal air/water heat exchanger
1 Notes on documentation
1 Notes on documentation
1.1 CE label
Rittal GmbH & Co. KG confirms the conformity of the air/ water heat exchanger with the European Union's Ma­chinery Directive 2006/42/EC and EMC Directive 2004/ 108/EC. A corresponding declaration of conformity has been issued and enclosed with the unit.
1.2 Storing the documents
The assembly and operating instructions as well as all other applicable documents are an integral part of the product. They must be issued to everyone who works with the air/water heat exchanger and must always be available and on hand for operating and maintenance personnel.
1.3 Symbols used in these operating in­structions
The following symbols are used in this documentation:
Warning! Hazardous situation which may lead to
death or serious injury if the instructions are not followed.
2 Safety instructions
Please observe the following general safety notes when assembling and operating the unit: – Assembly, installation and servicing may only be per-
formed by properly trained specialists.
– Only use the air/water heat exchanger within the pre-
scribed water inlet and operating temperature range.
– Use antifreeze agents only with the manufacturer's
consent.
– Do not obstruct the air inlet and air outlet of the air/wa-
ter heat exchanger inside the enclosure (see sec­tion4.3.2 "Mounting options").
– The heat loss of the components installed in the enclo-
sure must not exceed the specific useful cooling out­put of the air/water heat exchanger.
– The air/water heat exchanger must always be trans-
ported in a vertical position. – Use only original spare parts and accessories. – Do not make any changes to the air/water heat ex-
changer other than those described in these instruc-
tions or associated instructions. – The air/water heat exchanger must only be connected
to the mains with the system de-energised. Connect
the prefuse specified on the rating plate. – Always disconnect the air/water heat exchanger from
the supply voltage before servicing or maintenance
work.
EN
Caution! Hazardous situation which may lead to (minor) injuries if the instructions are not followed.
Note: Important notices and indication of situations
which may result in material damage.
This symbol indicates an "Action Point" and shows that you should perform an operation/procedure.
1.4 Other applicable documents
Assembly and operating instructions exist as paper doc­uments for the air/water heat exchanger described here and are enclosed with the equipment.
We cannot accept any liability for damage associated with failure to observe these instructions. Where applica­ble, the instructions for any accessories used also apply.
Rittal air/water heat exchanger 5
3 Device description
,
EN
3 Device description
3.1 Overview
Depending on the model chosen, your air/water heat ex­changer may vary in appearance from the illustrations contained in these instructions. However, the functions are identical in principle.
1 2
3
14
13
12
11
4 5 6
6
parable units, such as air/air heat exchangers, enclosure cooling units or fan-and-filter units, cannot be used for system reasons to effectively and economically dissipate heat loss.
The air/water heat exchanger is integrated into a TS 8 frame and can be incorporated flexibly into a TS 8 baying system (to either side or between two TS 8 enclosures, see section 4.3.2 "Mounting options").
3.2.1 How it works
The air/water heat exchanger comprises three main components (see fig.2):
– Heat exchanger package (item 2), – fan (item 3) and – magnetic valve (item 5), connected with each other using pipes
13
14
12
11
15
10
9
Fig. 1: Device description
Key
1 Water inlet, top 2 Water outlet, top 3 Gland for cables and busbars, top 4Magnetic valve 5Non-return valve 6Fan 7 Gland for cables and busbars, bottom (PE and N) 8 Water inlet, bottom
Water outlet
9 Condensate overflow
Water inlet,
10 Water outlet, bottom 11 Condensate water discharge 12 Drain cock 13 Cable entry 14 Display 15 Assembly and operating instructions
7
158
3.2 Functional description
Air/water heat exchangers are designed and built to dis­sipate heat from enclosures by cooling the air inside the enclosure and so protect the temperature-sensitive components.
Air/water heat exchangers are particularly appropriate for the temperature range of +5°C to +70°C where com-
17 16
Fig. 2: Air/water heat exchanger
Key
1Non-return valve
2 Heat exchanger
3Fan 4 Temperature control 5Magnetic valve 6 Cooling water inlet 7 Cooling water return
The heat loss of the enclosure is dissipated in a mem­brane heat exchanger to the water coolant. A fan (item 3) blows the internal enclosure air over the heat ex­changer (item 2); except for the inlet and outlet water and the condensed water discharge, the unit is closed to the environment.
The magnetic valve (item 5) controls the cooling output by changing the water flow volume depending on the re­quired target temperature and the water inlet tempera­ture.
6 Rittal air/water heat exchanger
3 Device description
3.2.2 Control
Rittal air/water heat exchangers are fitted with an e-Comfort controller for setting the functions of the heat exchanger.
3.2.3 Bus mode
The serial interface X2 allows you to create a bus con­nection with up to ten air/water heat exchangers using the master-slave cable (shielded, four-wire cable, Model No. 3124.100).
This allows you to implement the following functions: – Parallel unit control (the air/water heat exchangers in
the network can be switched on and off simultaneous-
ly) – Parallel door status message ("door open") – Parallel collective fault message Data is exchanged via the master-slave connection.
During commissioning, assign an address to each unit that also includes the identifier "master” or "slave” (see section 6.9 "Setting the master-slave identifier").
3.2.4 Safety equipment
– The EC fan is protected against overcurrent and over-
temperature by the integral electronics. – The device has two integral floating contacts on the
terminal block 3 – 5, via which system messages from
the heat exchanger may be polled e.g. via a PLC (2 x
normally-open contacts). – The air/water heat exchanger has a leak and conden-
sate warning. The device also has an overflow via its
base.
3.2.5 Condensation
At high levels of humidity and low cooling water temper­atures inside the enclosure, condensation may form on the heat exchanger.
Any condensation that forms on the heat exchanger (with high humidity and low water temperatures) is rout­ed to the front out of the unit via a drain opening in the heat exchanger tray. For this purpose, a hose must be connected to the condensate nozzle (see section 4.3.3 "Connecting the condensate discharge"). The conden­sate must be able to run off freely. The hose used for draining off condensate must be laid free from kinks and checked for correct drainage. Condensate hoses are available as accessories (refer also to the accessories section in the Rittal Catalogue).
3.2.6 Leak detection
If a leakage or pipe breakage occurs in the water circuit of the air/water heat exchanger, a magnetic valve imme­diately stops the cooling water supply, the floating change-over contact activated and the fan switched off. The warning "A08" appears on the display.
3.2.7 Door limit switch
The air/water heat exchanger may be operated with a door limit switch connected. The door limit switch is not
included with the supply (available as an accessory, Model No. 4127.010).
The door limit switch function causes the fan and the magnetic valve in the air/water heat exchanger to be switched off after approximately 15 seconds when the enclosure door is opened (contacts 1 and 2 closed). This prevents the formation of condensation inside the enclo­sure while the enclosure door is open.
The fan will start up after about 15 seconds on closure of the door. The connection is made at terminals 1 and
2. The extra-low voltage is supplied by the internal pow­er pack; the current is approx. 30 mA DC.
Note: The door limit switches must only be con-
nected free from potential. No external volt­ages!
3.2.8 Additional interface X3
Note: The electrical signals at the interface are of an extra-low voltage (not extra-low safety volt­ages to EN 60 335).
An additional interface board may be connected to the 9-pole SUB-D connector X3 in order to incorporate the air/water heat exchanger into higher-level monitoring systems (available as an accessory, interface board Model No. 3124.200).
3.3 Proper use
Rittal enclosure air/water heat exchangers were devel­oped and designed in accordance with the state of the art and the recognised rules governing technical safety. Nevertheless, if used improperly, they may pose a threat to life and limb or cause damage to property. The unit is only intended for cooling enclosures. Any other use is deemed improper. The manufacturer will not be liable for any damages caused as a result of improper use, or for incorrect assembly, installation or use. All risk is borne solely by the user. Proper usage also in­cludes the observation of all valid documents and com­pliance with the inspection and servicing conditions.
3.4 Scope of supply
The unit is supplied in a packaging unit in a fully assembled state.
Please check the delivery for completeness:
Qty. Description
1 Air/water heat exchanger
1 Dispatch bag:
1 – Assembly and operating instructions
Tab. 1: Scope of supply
EN
Rittal air/water heat exchanger 7
4 Installation
EN
4 Installation
4.1 Safety instructions
Warning! Please note the maximum weights that may be lifted by individuals. It may be necessary to use lifting gear.
Warning! Work on electrical systems or equip-
ment may only be carried out by an elec­trician or by trained personnel under the guidance and supervision of an electri­cian.
The air/water heat exchanger may only be connected after the aforementioned personnel have read this information!
Use only insulated tools.
Follow the connection regulations of the appropriate electrical supply company.
4.3 Assembly procedure
4.3.1 Assembly instructions
Check the packaging carefully for signs of damage. Packaging damage may be the cause of a subsequent functional failure.
– The enclosure must be sealed on all sides (IP 54). In-
creased condensation will occur if the enclosure is not airtight.
– The air inlet and outlet must not be obstructed on the
inside of the enclosure.
When arranging the components inside the enclosure, please ensure that the cold airflow from the air/water heat exchanger is not directed at active components.
The air/water heat exchanger must be connected to the mains via an all-pin isolating device to overvoltage catego­ryIII (IEC 61 058-1).
The air/water heat exchanger is not de­energised until all of the voltage sources have been disconnected!
4.2 Siting location requirements
When choosing the installation site for the enclosure, please observe the following:
– The air/water heat exchanger must be installed and
operated in a vertical position. – The ambient temperature must not exceed +70°C. – It must be possible to fit a condensate discharge (see
section4.3.3 "Connecting the condensate dis-
charge"). – It must be possible to fit a cooling water supply and re-
turn (see section 4.4 "Connecting the water connec-
tion"). – The mains connection data as stated on the rating
plate of the unit must be guaranteed. – Clearance of at least 1 m must be left in front of the
door to guarantee convenient access in case of servic-
ing.
Fig. 3: Never direct the cold airflow at active components
Please also ensure that the cold airflow is not directed at the warm exhaust airflow from active components such as converters. This may lead to an air short-circuit and therefore pre­vent adequate climate control, or may even cause the air/water heat exchanger's internal safety devices to cease cooling operation.
Exercise particular caution with the airflow from the blowers of built-in electronic components (fig. 3).
Never site the air/water heat exchanger directly adja­cent to the mounting plate. If such installation is unavoidable, appropriate meas­ures must be taken to optimise the air routing.
It is important to ensure even air circulation inside the enclosure.
Under no circumstances should air inlet and outlet openings be obstructed, otherwise the cooling perfor­mance of the unit will be reduced.
Ensure a suitable distance from electronic compo­nents and other installed enclosures so that the re­quired air circulation is not obstructed and prevented.
8 Rittal air/water heat exchanger
4 Installation
20˚ C
200
Fig. 4: Targeted air routing inside the enclosure
4.3.2 Mounting options
The air/water heat exchanger enclosure can be placed either within or to the right or left of an existing TS 8 en­closure suite (observe TS 8 dimensions!).
If the air/water heat exchanger is bayed on the left or right, the left side or right side of the air/water heat ex­changer (as appropriate) must be sealed with a side panel for TS 8 enclosure systems (Model No. 8106.235 for SK 3378.200 or 8108.235 for SK 3378.280).
Baying in the middle of an enclosure suite
20˚ C
Fig. 6: Baying in the middle of an enclosure suite
In case of installation within an enclosure suite, it is not necessary to seal the air/water heat exchanger to the left or right.
Baying between two TS 8 enclosures
EN
Note: Use the assembly parts included with the
Rittal system accessories to ensure secure baying.
Baying on the left or right
20˚ C
Fig. 5: Baying on the left or right
Fig. 7: Baying between two TS 8 enclosures
If the air/water heat exchanger is placed between two TS 8 enclosures, but cooling is only required on one side, the air inlet opening can be closed with an optional metal cover.
Note: The enclosure must be sealed on all sides. In
particular, in the area of the cable inlet open­ings and the enclosure base.
Rittal air/water heat exchanger 9
4 Installation
1
EN
Note: The air/water heat exchanger may be fitted on a base/plinth system (refer also to Acces­sories in the Rittal Catalogue).
4.3.3 Connecting the condensate discharge
A flexible condensate hose, dia. 12 mm (½"), can be fit­ted to the air/water heat exchanger to drain any conden­sate into a collecting bottle.
The condensate discharge – must be laid with a suitable and constant gradient (no
siphoning), – must be laid without kinks and – must not have a reduced cross-section if extended. The condensate hose (3301.612), condensate collect­ing bottle (3301.600) and external condensate evapora­tor (3301.500 or 3301.505) are available as accessories (see also Accessories in the Rittal Catalogue).
1 2
3
Fig. 9: Removing the sealing caps at the top
Key
1 Water inlet, top 2 Open-jawed spanner 3 Water outlet, top
Fig. 8: Connecting the condensate discharge
Key
1 Connecting the condensate discharge
Connect a suitable hose to the condensate nozzle (at
the bottom of the door) and secure it with a hose clip
(with 2 Nm torque).
Lay the condensate hose, e.g. into a drain.
4.4 Connecting the water connection
The water hoses may optionally be connected to the top or bottom of the device (¾" internal thread).
First, remove the sealing caps using an SW 22 open-
jawed spanner.
1
2
Fig. 10: Removing the sealing caps at the bottom
Key
1 Water inlet, bottom
Water outlet,
2 Water outlet, bottom
Water inlet,
The cooling water hose – must be laid without kinks – must not have a reduced cross-section if extended
and
– if necessary, must be insulated.
Warning! Switch off the power supply to the air/
water heat exchanger before opening the electrical connection box and before working on the water circuit, and take suitable precautions against it being ac­cidentally switched on again.
Note: The water inlet temperature should be select­ed to prevent the formation of critical con­densation in the enclosure being cooled.
10 Rittal air/water heat exchanger
Loading...
+ 22 hidden pages