Rittal SK 3302.100, SK 3302.110, SK 3303.100, SK 3303.110, SK 3302.200 Assembly And Operating Instructions Manual

...
Montage-, Installations- und Bedienungsanleitung Assembly and operating instructions Manuel d’installation et de maintenance Montage- en bedieningshandleiding Montage- och hanteringsanvisning Istruzioni di montaggio e funzionamento Instrucciones de montaje
R
Schaltschrank­Kühlgerät
Cooling unit Climatiseur Koelaggregaat Kylaggregat Condizionatori per
armadi di comando Refrigerador
para armarios
SK 3302.xxx SK 3302.3xx SK 3303.xxx SK 3304.xxx SK 3305.xxx SK 3328.xxx SK 3329.xxx
SK 3332.xxx SK 3361.xxx SK 3366.xxx SK 3377.xxx
RITTAL cooling unit assembly and operating instructions 3
EN
Contents
1 Notes on documentation. . . . . . . . . . 4
1.1 Associated documents. . . . . . . . . . . . . . . . . 4
1.2 CE labelling . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.3 Retention of documents. . . . . . . . . . . . . . . . 4
1.4 Symbols used . . . . . . . . . . . . . . . . . . . . . . . . 4
2 Safety instructions. . . . . . . . . . . . . . . 4
3 Device description. . . . . . . . . . . . . . . 5
3.1 Functional description . . . . . . . . . . . . . . . . . 5
3.1.1 How it works . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.1.2 Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.1.3 Bus mode (Comfort controller only) . . . . . . . . 5
3.1.4 Safety equipment . . . . . . . . . . . . . . . . . . . . . . 6
3.1.5 Condensation . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.1.6 Filter mats . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
3.1.7 Door limit switch . . . . . . . . . . . . . . . . . . . . . . . 6
3.1.8 Additional interface X3 . . . . . . . . . . . . . . . . . . 7
3.2 Proper usage . . . . . . . . . . . . . . . . . . . . . . . . . 7
3.3 Scope of supply . . . . . . . . . . . . . . . . . . . . . . 7
4 Assembly and connection . . . . . . . . 7
4.1 Choosing the installation site . . . . . . . . . . . 7
4.2 Assembly instructions . . . . . . . . . . . . . . . . . 7
4.2.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.2.2 Layout of the electronic components
in the enclosure. . . . . . . . . . . . . . . . . . . . . . . . 8
4.3 Fitting the cooling unit . . . . . . . . . . . . . . . . . 8
4.3.1 Cutting out the enclosure . . . . . . . . . . . . . . . . 9
4.3.2 External mounting of the cooling unit . . . . . . . 9
4.3.3 Partial internal mounting
of the cooling unit . . . . . . . . . . . . . . . . . . . . . . 9
4.3.4 Full internal mounting of the cooling unit . . . 11
4.4 Connecting the condensate discharge. . . 11
4.5 Notes on electrical installation . . . . . . . . . 12
4.5.1 Connection data . . . . . . . . . . . . . . . . . . . . . . 12
4.5.2
Overvoltage protection and supply line load
. . . . . . . . . . . . . . . . . . . 12
4.5.3 Three-phase devices . . . . . . . . . . . . . . . . . . 12
4.5.4 Door limit switch . . . . . . . . . . . . . . . . . . . . . . 12
4.5.5 Notes on the flicker standard . . . . . . . . . . . . 12
4.5.6 Potential equalisation . . . . . . . . . . . . . . . . . . 12
4.6 Carrying out the electrical installation . . . 13
4.6.1 Bus connection (only in conjunction with several units with
a Comfort controller) . . . . . . . . . . . . . . . . . . . 13
4.6.2 Connection X3 for serial interface. . . . . . . . . 13
4.6.3 Installing the power supply. . . . . . . . . . . . . . 14
4.7 Finalising assembly . . . . . . . . . . . . . . . . . . 22
4.7.1 Installing the filter media . . . . . . . . . . . . . . . 22
4.7.2 Fitting the cooling unit. . . . . . . . . . . . . . . . . . 22
4.7.3 Setting the filter mat monitor
(only with Comfort controller) . . . . . . . . . . . . 22
5 Commissioning . . . . . . . . . . . . . . . . 22
6 Operation . . . . . . . . . . . . . . . . . . . . . 23
6.1 Control using the Basic controller . . . . . . 23
6.1.1 Properties. . . . . . . . . . . . . . . . . . . . . . . . . . . .23
6.1.2 Operating and error display. . . . . . . . . . . . . .24
6.1.3 Test mode for the Basic controller . . . . . . . . .25
6.1.4 Setting the temperature . . . . . . . . . . . . . . . . .25
6.1.5 Resetting the Basic controller . . . . . . . . . . . .25
6.2 Control using the Comfort controller . . . . 26
6.2.1 Properties. . . . . . . . . . . . . . . . . . . . . . . . . . . .26
6.2.2 Launching test mode . . . . . . . . . . . . . . . . . . .26
6.2.3 General programming information. . . . . . . . .26
6.2.4 Editable parameters. . . . . . . . . . . . . . . . . . . .27
6.2.5 Programming overview . . . . . . . . . . . . . . . . .28
6.2.6 Defining system messages
for evaluation . . . . . . . . . . . . . . . . . . . . . . . . .29
6.2.7 Setting the master-slave identifier . . . . . . . . .30
6.2.8 Evaluating system messages. . . . . . . . . . . . .30
6.2.9 Resetting the Comfort controller . . . . . . . . . .32
7 Inspection and maintenance. . . . . . 32
7.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
7.1.1 Compressed air cleaning
SK 3304.xxx, SK 3305.xxx . . . . . . . . . . . . . . .32
7.1.2 Compressed air cleaning
SK 3328.xxx, SK 3329.xxx, SK 3332.xxx . . . .36
8 Storage and disposal. . . . . . . . . . . . 41
9 Technical specifications . . . . . . . . . 41
10 List of spare parts . . . . . . . . . . . . . . 45
11 Appendix:
Cut-out and hole sizes
. . . . . . . . . . . 49
11.1 Dimensions for external mounting . . . . . . 49
11.2 Dimensions for partial
internal mounting . . . . . . . . . . . . . . . . . . . . 50
11.3 Dimensions for full internal mounting . . . 51
4 RITTAL cooling unit assembly and operating instructions
1 Notes on documentation
EN
1 Notes on documentation
These assembly instructions are aimed at tradesper­sons who are familiar with assembly and installation of the cooling unit, and at trained specialists who are familiar with operation of the cooling unit.
1.1 Associated documents
There are two sets of instructions for the unit types described here: – Assembly and installation instructions enclosed
with the unit in the form of a paper document
– Assembly, installation and operating instructions
enclosed with the unit in the form of a PDF file
(Adobe Acrobat) on CD-ROM We cannot accept any liability for damage associat­ed with failure to observe these instructions. Where applicable, the instructions for any accessories used also apply.
1.2 CE labelling
The declaration of conformity is supplied with the unit as a separate document.
1.3 Retention of documents
These instructions and all associated documents constitute an integral part of the product. They must be given to the plant operator. The plant operator is responsible for storage of the documents so they are readily available when needed.
1.4 Symbols used
Please observe the following safety instructions and other notes in this guide:
Symbol for an instructed action:
• The bullet point indicates that you should perform
an action.
Safety and other instructions:
2 Safety instructions
Please observe the following general safety instruc­tions when assembling and operating the unit: – Assembly, installation and servicing may only be
performed by properly trained specialists.
– Screw the enclosure to the floor to prevent it from
tipping over when the cooling unit is installed.
– Do not obstruct the air inlet and air outlet of the
cooling unit inside and outside the enclosure (see also section 4.2.2).
– To ensure problem-free opening and closing of
the enclosure door, use a ride-up door roller (refer to the accessories in the RITTAL Catalogue). This raises the door slightly and balances out the weight of the cooling unit, to prevent buckling of the door and associated seal problems.
– The heat loss of the components installed in the
enclosure must not exceed the specific useful cooling output of the cooling unit.
– When transporting the enclosure with the cooling
unit externally mounted, always use an additional shipping brace to support the cooling unit.
– The cooling unit must always be transported in an
upright position. – Use only original spare parts and accessories. – Do not make any changes to the cooling unit other
than those described in these instructions or asso-
ciated instructions. – Risk of burn injuries! For cooling units with auto-
matic condensate evaporation, the surface of the
thermal element will get very hot during operation,
and will remain so for some time afterwards. – The mains connector of the cooling unit must only
be connected and disconnected with the system
de-energised. Connect the pre-fuse specified on
the rating plate.
Danger! Immediate danger to life and limb!
Caution! Potential threat to the product and its environment.
Note:
Useful information and special features.
3 Device description
RITTAL cooling unit assembly and operating instructions 5
EN
3 Device description
Depending on the model chosen, your cooling unit may vary in appearance from the illustrations con­tained in these instructions. However, the functions are identical in principle.
Fig. 1: Device description
Legend
1 Blind nut 2 Evaporator fan 3 Electrical wiring plan 4 X2 master-slave connection 5 X3 optional serial interface 6 X1 terminal strip 7 Air outlet hole 8 Front half of the enclosure 9 Rear half of the enclosure 10 Louvred grille for air outlet 11 Display 12 Infill panel 13 Louvred grille for air inlet 14 Rating plate 15 Condensate discharge 16 Dispatch bag
3.1 Functional description
Enclosure cooling units are designed to dissipate heat from enclosures by cooling the air inside the enclosure and so protect the temperature-sensitive components. They are built into the side or rear panel or into the door of the enclosure.
3.1.1 How it works
The cooling unit (compression refrigeration system) is comprised of four main components (cf. Fig. 2): the evaporator (1), the coolant compressor (2), the condenser (3), and the control or expansion valve (4), which are connected by suitable pipework. This circuit is filled with a readily boiling substance, the refrigerant. Coolant R134a (CH
2
FCF3) is chlorine­free. Its ozone destruction potential is 0, making it very eco-friendly. A filter dryer (5) which is integrated
into the hermetically sealed cooling circuit provides effective protection against moisture, acid, dirt particles, and foreign bodies within the cooling circuit.
Fig. 2: Cooling circuit
In the evaporator coil (1), the liquid coolant is con­verted to a gaseous state. The energy needed for this purpose is taken from the enclosure air in the form of heat, which has the effect of cooling the enclosure air. In the compressor (2), the coolant is heavily compressed, so that it achieves a higher temperature inside the condenser (3) than the ambi­ent air. This means that excess heat may be emitted to the ambient air via the surface of the condenser, as a result of which the temperature of the coolant drops and it is converted back into liquid. It is re­injected into the evaporator coil via a thermostatic expansion valve (4), which causes it to cool down further, and is then once again able to absorb the energy from the enclosure air in the evaporator coil. The whole cycle begins again.
3.1.2 Control
RITTAL enclosure cooling units are fitted with a con­troller for setting the functions of the cooling unit. Depending on the design, this is either a Basic con­troller (display of the operating status via LED) or a Comfort controller (display plus extended functions, see chapter “6 Operation”, page 23).
3.1.3 Bus mode (Comfort controller only)
The serial unit interface X2 allows you to create a bus connection with up to ten cooling units using the master-slave cable (shielded, four-wire cable, Model No. SK 3124.100). This allows you to implement the following functions: – Parallel unit control (the cooling units in the network
can be switched on and off simultaneously) – Parallel door status message (“door open”) – Parallel collective fault message Data is exchanged via the master-slave connection. During commissioning, assign an address to each unit that also includes the identifier “master” or “slave”.
10
9
8
11
13
12
16
15
14
1
2
4
5
6
7
3
PSA
H
pressure-
operated
switch
Condenser fan
Expansion valve (4)
Temperature control
Filter dryer (5)
Internal circuit
Compressor
(2)
External circuit
Evaporator fan
Evaporator coil (1)
Condenser (3)
6 RITTAL cooling unit assembly and operating instructions
3 Device description
EN
3.1.4 Safety equipment
– In the cooling cycle, the cooling unit has a tested
pressure-operated switch to EN 12 263 which is set to maximum PS (admissible pressure); this operates via an automatic reset device whenever the pressure drops again.
– Temperature monitoring prevents the evaporator
coil from icing over. If there is a risk of icing, the compressor switches itself off and automatically switches itself back on again at higher tempera­tures.
– The refrigerant compressor and the fans are
equipped with thermal winding shields to protect against excess current and excess temperatures.
– In order to allow a reduction of pressure inside the
compressor and hence a safe restart, once it has been switched off (e.g. upon reaching the set tem­perature via the door limit switch function or via de­energising), the device will switch back on with a delay of 180 seconds.
– The device has floating contacts on the connection
pins (terminals 3 – 5), via which system messages from the device may be polled, e.g. using a PLC (1x change-over contact Basic controller, 2 x nor­mally open contacts Comfort controller).
3.1.5 Condensation
At high levels of humidity and low temperatures in­side the enclosure, condensation may form on the evaporator coil. The cooling units (except SK 3302.xxx, SK 3303.xxx and SK 3361.xxx) have automatic, electric conden­sate evaporation. The thermal component used for this purpose is based on self-regulating PTC tech­nology. Condensate arising on the evaporator coil is collected in a tank in the external circuit of the cool­ing unit, and partially evaporated via the airflow. When the water level rises, the water enters the PTC thermal component and is evaporated (through-flow heater principle). The water vapour streams out of the cooling unit with the airflow from the external fan. The PTC thermal component is permanently con­nected and has no switchpoint. It is protected against short-circuits with miniature fuses (F1.1, F1.2). If the fuse has tripped, any condensation is drained off via the safety overflow. For unit types SK 3302.xxx, SK 3303.xxx and SK 3361.xxx, the condensation is routed downwards out of the unit via a drain pipe on the evaporator coil divider panel. For this purpose, a hose must be con­nected to the condensate nozzle (see “4.4 Connect­ing the condensate drain”, page 11). External con­densate evaporators are available as accessories for these unit types (refer also to the accessories in the RITTAL Catalogue).
3.1.6 Filter mats
The cooling unit condenser is finished all over with a dirt-repelling, easy-to-clean RiNano coating. In many cases, therefore, the use of filter media is unneces­sary, particularly in the case of dry dusts. For dry, coarse dust and lint in the ambient air, we recommend installing an additional PU foam filter mat (available as an accessory) in the cooling unit. Depending on the incidence of dust, you will need to replace the filter from time to time. For air containing oil condensation, we recommend the use of metal filters (also available as an accesso­ry). These may be cleaned with suitable detergents and reused. Function of the filter mat monitor: Dirt on the filter mat is automatically determined by measuring the temperature difference in the external circuit of the cooling unit. As the level of filter mat soil­ing rises, the temperature difference will increase. The nominal value of the temperature difference in the external circuit adapts automatically to the rele­vant operating points in the performance diagrams. Hence there is no need to readjust the nominal value for different operating points of the cooling unit.
3.1.7 Door limit switch
The cooling unit may be operated with a floating door limit switch connected. The door limit switch is not in­cluded with the supply (available as an accessory, Model No. PS 4127.000). The door limit switch function causes the fans and the compressor in the cooling unit to be switched off after approximately 15 seconds when the enclosure door is opened (contacts 1 and 2 closed). This pre­vents the formation of condensation inside the enclo­sure while the enclosure door is open. In order to prevent damage to the unit, it is equipped with an ON delay: The evaporator fan cuts back in with a de­lay of approximately 15 seconds after the door has been closed, while the condenser fan and compres­sor switch on after approximately 3 minutes.
Note:
– No external voltage must be applied to
the door contacts (terminals 1 and 2).
– For Basic controller cooling units with
230/115 V and 400 V/2-phase connec­tion, the evaporator fan remains opera­tional even with the door open.
4 Assembly and connection
RITTAL cooling unit assembly and operating instructions 7
EN
3.1.8 Additional interface X3
An additional interface card may be connected to the 9-pole SUB-D connector X3 in order to incor­porate the cooling unit into higher-level monitoring systems (available as an accessory, interface card Model No. SK 324.200).
3.2 Proper usage
RITTAL enclosure cooling units were developed and designed in accordance with the state-of-the-art and the recognised rules governing technical safety. Nevertheless, if used improperly, they may pose a threat to life and limb or cause damage to property. The unit is only intended for cooling enclosures. Any other use is deemed improper. The manufacturer will not be liable for any damages caused as a result of improper use, or for incorrect assembly, installation or use. All risk is borne solely by the user. Proper usage also includes the observation of all valid documents and compliance with the inspection and servicing conditions.
3.3 Scope of supply
The unit is supplied in a packaging unit in a fully assembled state. Please check the delivery for completeness:
Tab. 1: Scope of supply
4 Assembly and connection
4.1 Choosing the installation site
When choosing the installation site for the enclosure, please observe the following: – The site for the enclosure, and hence the arrange-
ment of the cooling unit, must be carefully selected
so as to ensure good ventilation (distances bet-
ween units and distances between the unit and the
wall must be at least 200 mm in each case). – The cooling unit must be installed and operated in
a vertical position (maximum deviation: 2°). – The site must be free from excessive dirt and
moisture. – The ambient temperature must not exceed 55°C. – It must be possible to fit a condensate discharge
(see “4.4 Connecting the condensate discharge”,
page 11). – The mains connection data as stated on the rating
plate of the unit must be guaranteed.
4.2 Assembly instructions
4.2.1 General
– Check the packaging carefully for signs of damage.
Traces of oil on damaged packaging are an indi-
cation of refrigerant loss and leakages. Packaging
damage may be the cause of a subsequent func-
tional failure. – The enclosure must be sealed on all sides (IP 54).
Increased condensation will occur if the enclosure
is not airtight. – In order to avoid excessive condensation inside
the enclosure, we recommend installing a door
limit switch (e.g. PS 4127.000) which deactivates
the cooling unit when the enclosure door is opened
(see “3.1.7 Door limit switch”, page 6).
Note:
The electrical signals at the interface are of an extra-low voltage (not extra-low safety voltages to EN 60 335).
Qty.
Description
1 Enclosure cooling unit 1
1 1
1 1 4 – 10 1
Dispatch bag: – Assembly and installation instructions
– Assembly, installation and operating
instructions on CD-ROM – Self-adhesive tape – Connector X1 – Threaded rods – Declaration of conformity – Nuts, washers
1 Drilling template
8 RITTAL cooling unit assembly and operating instructions
4 Assembly and connection
EN
4.2.2 Layout of the electronic components in the enclosure
Fig. 3: Never direct the cold airflow at active components
Air diversion components are available as accesso­ries – please refer to the RITTAL catalogue “System climate control”. It is important to ensure even air circulation inside the enclosure. Under no circumstances should air inlet and outlet openings be obstructed, otherwise the cooling performance of the unit will be reduced. Ensure the distance “x” (see Fig. 4) from electronic components and other installed enclosures so that the required air circulation is not obstructed and pre­vented.
Fig. 4: Air circulation inside the enclosure
4.3 Fitting the cooling unit
The enclosure cooling unit may optionally be exter­nally mounted on the enclosure (1), partially internal­ly mounted (2) or fully internally mounted (3):
Fig. 5: Installation method
To this end, cut the side panel or door of the enclo­sure as per the drilling template included with the supply, and drill the relevant holes.
Caution! Risk of condensation! When arranging the components inside the enclosure, please ensure that the cold airflow from the cooling unit is not directed at active components. Please also ensure that the cold airflow is not directed at the warm exhaust airflow from active components such as con­verters. This may lead to an air short­circuit and therefore prevent adequate climate control, or may even cause the cooling unit’s internal safety devices to cease cooling operation.
Note:
Units of type SK 3302.xxx can only be either externally mounted or fully internally moun­ted. Units of type SK 3332.xxx can only be either externally mounted or partially internally mounted. For mounting the units SK 3328.xxx, SK 3329.xxx and SK 3332.xxx in the TS side panel or rear panel, we recommend the use of enclosure panel fasteners TS 8800.071 (see RITTAL Catalogue).
x
1 2 3
4 Assembly and connection
RITTAL cooling unit assembly and operating instructions 9
EN
4.3.1 Cutting out the enclosure
• Stick the supplied drilling template onto the side panel or door of the enclosure using adhesive tape.
There are dimensioning lines on the drilling template to suit the various installation options for your cooling unit.
• Using the dimension drawings (see Appendix), identify the valid lines and dimensions for your installation type on the drilling template.
• Mark, drill and deburr the holes.
• Make the cut-outs including the line width as per the drilling template. Deburr the cut-outs.
4.3.2 External mounting of the cooling unit
• Cut the supplied sealing tape to the correct length and stick it carefully along the back of the unit so that no gaps are left at the joints.
Fig. 6: Attach the sealing tape
• Screw the supplied grub screws into the blind nuts on the rear of the unit.
• Secure the unit using the supplied washers and nuts.
Fig. 7: Secure the cooling unit
(all models except SK 3302.1xx)
Fig. 8: Secure the cooling unit
(SK 3302.1xx “external mounting” only)
Only for SK 3302.xxx:
• Before installing, remove the four screws as shown.
Fig. 9: Only for SK 3302.xxx: Remove the four screws
4.3.3 Partial internal mounting of the cooling unit
• Carefully remove the louvred grille and, where applicable, the infill panel, from the enclosure by pulling forwards.
• Carefully disconnect the connector from the rear of the display and gently push it inwards through the cable gland.
Fig. 10: Remove the louvred grille & disconnect the display
Risk of injury! Carefully deburr all drilled holes and cut-outs to prevent injuries caused by sharp edges.
4x
10 RITTAL cooling unit assembly and operating instructions
4 Assembly and connection
EN
• Loosen the four nuts on the front enclosure half and pull the enclosure forwards by approx. 5 cm.
• Loosen the flat-pin connectors of the PE conductor between the two enclosure halves.
• Disconnect the fan connection.
• Remove the front enclosure tray completely.
Fig. 11: Remove the cover
• Remove the four spacer bolts.
• Cut the supplied sealing tape to the correct length and stick it carefully along the inside of the rear enclosure half so that no gaps are left at the con­nection points.
Fig. 12: Attach the sealing tape
• Push the rear enclosure half into the mounting cut­out and secure it with the four spacer bolts.
• Push the display cable through the cable gland of the front enclosure half.
Fig. 13: Secure the cooling unit
• Connect the fan connector and PE conductor.
• Mount the front enclosure tray using the washers and nuts.
Fig. 14: Connect the display connector
• Carefully connect the display connector.
• Push the louvred grille and, where applicable, the infill panel, onto the enclosure.
Risk of damage! Stability of the cooling unit is only guaranteed in its assembled state. Brace the rear enclosure half to prevent it from falling over before removing the front enclosure half.
4 Assembly and connection
RITTAL cooling unit assembly and operating instructions 11
EN
4.3.4 Full internal mounting of the cooling unit
• Carefully remove the louvred grille and the infill panel from the enclosure by pulling forwards.
• Carefully disconnect the connector from the rear of the display.
Fig. 15: Remove the louvred grille and disconnect
the display
• Cut the supplied sealing tape to the correct length and stick it carefully along the front enclosure half so that no gaps are left at the connection points.
Fig. 16: Attach the sealing tape
• Loosen the four nuts and washers from the front enclosure half.
• Push the unit into the mounting cut-out from the inside of the enclosure, and secure it to the en­closure from the outside using the washers and nuts.
Fig. 17: Secure the cooling unit
• Where necessary, additionally secure the unit using the supplied mounting plates as shown in Fig. 17.
• Carefully connect the display connector.
• Push the louvred grille and, where applicable, the infill panel, onto the enclosure.
4.4 Connecting the condensate discharge
Unit types SK 3302.xxx, SK 3303.xxx and SK 3361.xxx support the installation of a condensate discharge hose (Ø 1/2˝). The condensate discharge – must be laid with a suitable and constant gradient
(no siphoning)
– must be laid without kinks – must not have a reduced cross-section if extended. The condensate hose is available as an accessory (refer also to Accessories in the RITTAL Catalogue).
Fig. 18: Connecting the condensate discharge
• Connect a suitable hose to the condensate nozzle and secure using a hose clip.
• Lay the condensate hose into a pay-off or into the external condensate evaporator (refer to accesso­ries in the RITTAL Catalogue).
12 RITTAL cooling unit assembly and operating instructions
4 Assembly and connection
EN
4.5 Notes on electrical installation
When performing the electrical installation, it is im­portant to observe all valid national and regional reg­ulations as well as the provisions of the responsible power supply company. Electrical installation must only be carried out by a qualified electrician who is re­sponsible for compliance with the existing standards and regulations.
4.5.1 Connection data
– The connected voltage and frequency must
correspond to the values stated on the rating plate.
– The cooling unit must be connected to the mains
via an all-pin isolating device, which ensures at least 3 mm contact opening when switched off.
– No additional temperature control may be connec-
ted upstream of the unit at the supply end.
– Install the pre-fuse specified on the rating plate
to protect the cable and equipment from short­circuits.
– The mains connection must ensure low-noise
potential equalisation.
4.5.2 Overvoltage protection and supply line load
– The unit does not have its own overvoltage pro-
tection. Measures must be taken by the operator at the supply end to ensure effective lightning and overvoltage protection. The mains voltage must not exceed a tolerance of ±10%.
– In accordance with IEC 61 000-3-11, the unit is
intended solely for use at sites with a continuous current-carrying capacity (incoming mains power supply) of more than 100 A per phase and with a supply voltage of 400/230 V. If necessary, the power supply company must be consulted to ensure that the continuous current-carrying capa­city at the point of connection to the public grid is sufficient for connection of such a unit.
– The fans and compressors in single- and three-
phase units are intrinsically safe (thermal winding protection). The same also applies to the transfor­mer versions of types SK 3304.110, SK 3304.510, SK 3305.110, SK 3305.510, SK 3328.110, SK 3328.510, SK 3329.110 and SK 3329.510 and to special-voltage units which are likewise equipped with a transformer.
– Install the slow pre-fuse specified on the rating
plate (miniature circuit-breaker with “K” charac­teristic, circuit-breaker for plant or transformer protection) to protect the cable and equipment from short-circuits. Select a suitable circuit-breaker in accordance with the information specified on the rating plate: Set it to the minimum specified value. This will achieve the best short-circuit protection for cables and equipment. Example: Specified setting range 6.3 – 10 A; set to 6.3 A.
4.5.3 Three-phase devices
– The three-phase version of models SK 3304.xxx,
SK 3305.xxx, SK 3328.xxx, SK 3329.xxx and SK 3332.xxx must be connected to a TN network with star earthing via a circuit-breaker for plant protection (current setting as per the rating plate). Three-phase units with special voltages must be protected with a circuit-breaker for transformer protection (category AC-3) as per the rating plate.
– Units designed for three phase 400/460 V feature
additional monitoring of the rotary field or the absence of a phase. If the rotary field is incorrect or a phase is absent, the unit will not run.
4.5.4 Door limit switch
– Each door limit switch must only be assigned to one
cooling unit.
– Several door limit switches may be connected in
parallel and operated on one cooling unit.
– The minimum cross-section for the connection
cable is 0.3 mm2 for a cable length of 2 m.
– The line resistance to the door limit switch must not
exceed a maximum of 50 Ω.
– The door limit switch only supports a floating
connection; no external voltages.
– The contact of the door limit switch must be closed
when the door is open.
The safety extra-low voltage for the door limit switch
is provided by the internal power pack: Current approx. 30 mA DC.
• Connect the door limit switch to terminals 1 and 2 of
the connector.
4.5.5 Notes on the flicker standard
The flicker limits specified in standard EN 61 000-3-3 or -3-11 are adhered to, provided the supply im­pedance is less than approx. 1.5 . Where necessary, the unit operator should measure the connected impedance or consult the responsible power supply company. If there is no way of influenc­ing the supply impedance and sensitive installed components (e.g. BUS) are subjected to interference, a line reactor or starting-current limiting device should be connected upstream of the cooling unit to restrict the startup current of the cooling unit.
4.5.6 Potential equalisation
RITTAL recommends connecting a conductor with a nominal cross-section of at least 6 mm
2
to the poten­tial equalisation connection point on wall-mounted cooling units, and incorporating it into the existing po­tential equalisation system. According to the standard, the PE conductor in the mains connection cable is not classified as an equi­potential bonding conductor.
4 Assembly and connection
RITTAL cooling unit assembly and operating instructions 13
EN
4.6 Carrying out the electrical installation
4.6.1 Bus connection (only in conjunction with several units with a Comfort controller)
When using several cooling units, the serial device interface X2 can be used to connect up to ten cool­ing units with the bus cable (Model No. SK 3124.100).
When interconnecting, please note the following: – De-energise the cooling units to be connected. – Ensure proper electrical insulation. – Make sure the cables are not laid in parallel to
power lines.
– Make sure that the lines are short.
4.6.2 Connection X3 for serial interface
The interface card (Model No. SK 3124.200) may be connected to X3. This is used to evaluate system messages in a PLC, for remotely setting parameters and monitoring, or for integration into the facility management system.
Note:
The electrical signals at the X2 interface are of an extra-low voltage (not extra-low safety voltages to EN 60 335-1).
Caution! Regarding the last slave unit in the group, do not, under any circumstances, connect the remaining socket of the Y cable SK 3124.100 into interface X3 of the cooling unit!
14 RITTAL cooling unit assembly and operating instructions
4 Assembly and connection
EN
Fig. 19: Connection example: Master-slave operation
Legend
1 Serial interface (Model No. SK 3124.200) 2 Serial interface cable 3 Master-slave bus cable (Model No. SK 3124.100) RTT RITTAL TopTherm cooling units X1 Supply connection/door limit switch/alarms
X2 Master-slave connection Sub-D, 9-pole X3 Serial interface Sub-D, 9-pole St. Sub-D connector, 9-pole Bu. Sub-D jack, 9-pole Adr. Address
Fig. 20: Connection example: Door limit switch and master-slave operation
Legend
1 Master cooling unit 2 Slave cooling units 3 2-door enclosure with two door limit switches 4 Enclosure with door limit switch
4.6.3 Installing the power supply
• Complete the electrical installation by following the wiring plan on the rear of the cooling unit (see Fig. 1 on page 5, for key see page 21).
• If you would like the system messages from the cooling unit to be evaluated via the system message relay, you should also connect a suitable low-voltage cable to connection clamps 3 – 5.
X2
CMC
I/O unit
RTT Master
Adr.: 09
X1
X2
X3
X1
X2
X3
X1
X2
X3
X1
X2
X3
X2
X3
X2
X2
X2
X2
X2
X2
St. St. St.
Bu.
St.
Bu.
X2
Adr.: 11 Adr.: 12RTT
Slave
RTT Slave
Adr.: 19RTT
Slave
St.
Bu.
St.
Bu.
3
2
1
X10
L1
L2 N
PE
1
2345
1
X10
X10 X10 X10 X10
X2 X2 X2 X2 X2 X2
X2
L1PE1
2345
L1
L2 N
PE
1
2345
L2 L3
L1PE1
2345
L2 L3
L1PE1
2345
L2 L3
L1PE1
2345
L2 L3
L1
L2
N
PE
1
23
4
5
X10
2
3
4
56
1
Adr.: 06 Adr.: 11 Adr.: 12 Adr.: 13 Adr.: 14 Adr.: 15
22 2 2 2
34432
Adr.: 16
4 Assembly and connection
RITTAL cooling unit assembly and operating instructions 15
EN
Fig. 21: Electrical wiring plan no. 1
Fig. 22: Electrical wiring plan no. 2
22 21
A1
M1
M2
X1
L1
L2
N
PE
1
2345
S1
Mains
L
123 1 2 3 2 1
N
PE
5
Power
S1
Kx
M1
123
M2
123
M4
123
2 1
F2
NTC I red
NTC E blue
Ter m
A2
L1
L2
R1
2 2
8
B1
B2
P
F2
M4
M
1~
M
1~
C2
C1
R
S
F3
C
C4
SK 3302.100/.110, SK 3303.100/.110, SK 3302.200/.210, SK 3303.200/.210, SK 3302.300/.310, SK 3361.100/.110, SK 3361.200/.210
M2
X1
L1
L2
N
PE
1
2345
L
123
12 321
N
PE
5
Power
M1
123
M2
123
M4
123
2 1
NTC I red
Serial
2 2
2
B1 B2
P
M4
M 1~
M
1~
C2
C1
R
S
F3
C
C4
S1
22
21
X2
X3
83
A2
NTC E blue
NTC C white
NTC A yellow
Level green
2 2
4
Ter m
F2
F2
B3 B4 B5
PE
S1
Kx
K2
K1
MS1
A1
PE
M1
SK 3303.500/.510, SK 3303.600/.610, SK 3361.500/.510, SK 3361.600/.610
Mains
16 RITTAL cooling unit assembly and operating instructions
4 Assembly and connection
EN
Fig. 23: Electrical wiring plan no. 3
Fig. 24: Electrical wiring plan no. 4
SK 3361.540/.640
L1
PE
1
2
345
L2
N
S1
22
21
PE
5
X1
M1
1
2
3
1
2
3
LN
Power
S1
1
2
3
12
Kx
NTC I red
A2
1
F2
2
P
2 2
2
A1
M2
1
2
3
M4
1
2
3
S
R
C
M1
F3
C2
C4
M2
1~
M
M4
1~
M
C1
X2 X3
38
PE
K2
K1
MS1
Serial
NTC E blue
NTC C white
NTC A yellow
Level green
Term
2
2
4
F2
B1 B2 B3 B4 B5
PE
L1 L2 PE
T1
400 V
230 V
2345
M2
L1
L2
PE
1
S1
PE
5
L
123
N
Power
Kx
M1
123
M2
123
M4
13
NTC I red
NTC E blue
Ter m
L1 L2
R1
P
M4
M
1~
M
1~
X1
A2
2
2
8
B1 B2
F2
2 1
F2
C4
S1
12321
A1
PE
C2
L2L1
L
N
T1
2
22 21
N
C1
F3
S
R
1
3
M1
C
SK 3304.100/.200
F11
E1
Mains
Loading...
+ 36 hidden pages