Rittal SK 3201.200 Installation and Operating Guide

Montage-, Installations- und Bedienungsanleitung
Assembly and operating instructions
Manuel d’installation et de maintenance
R
RITTAL TOP THERM
Rittal Thermoelectric Cooler
SK 3201.200 SK 3201.300
Montage- en bedieningshandleiding
Montage- och hanteringsanvisning
Istruzioni di montaggio e funzionamento
Instrucciones de montaje
Schaltschrank­Kühlgerät
Cooling unit
Climatiseur
Koelaggregaat
Kylaggregat
Condizionatore per armadi
Refrigerador para armarios
2 Rittal Thermoelectric Cooler assembly and operating instructions
GB
Before installation of the cooling unit,
please read this manual completely and carefully.
The manual is a permanent part of the supplied system
and must be retained until the device is decommissioned.
We thank you for deciding to purchase a Rittal product!
The Rittal Thermoelectric Cooler is a high-perfor­mance thermoelectric light-weight cooling unit with the highest efficiency (COP > 1) of its class!
The cooling unit is particularly suitable for the climate control of operating housings and small enclosures!
Before using the cooling unit, read this manual care­fully in order to make full use of the excellent per­formance characteristics of the product.
Rittal GmbH & Co. KG products are continually adapted to the requirements and needs of our cus­tomers. This means the information concerning the product characteristics and functions contained in this manual can be changed without notice in the case of product improvements.
Rittal Thermoelectric Cooler assembly and operating instructions 3
GB
Contents
1 Unpacking and checking. . . . . . . . . . 4
2 Notes on documentation. . . . . . . . . . 4
2.1 Retention of the manual . . . . . . . . . . . . . . . . 4
3 Safety notes . . . . . . . . . . . . . . . . . . . . 5
3.1 Proper usage . . . . . . . . . . . . . . . . . . . . . . . . . 5
3.2 Standards, guidelines. . . . . . . . . . . . . . . . . . 5
4 How it works. . . . . . . . . . . . . . . . . . . . 6
5 Control . . . . . . . . . . . . . . . . . . . . . . . . 7
6 Device description . . . . . . . . . . . . . . . 8
7 Device mounting . . . . . . . . . . . . . . . . 9
7.1 External mounting. . . . . . . . . . . . . . . . . . . . 10
7.2 Internal mounting . . . . . . . . . . . . . . . . . . . . 10
8 Filter mounting. . . . . . . . . . . . . . . . . 11
9 Mounting of the
condensate discharge . . . . . . . . . . . 11
10 Electrical connection. . . . . . . . . . . . 12
10.1 Connection data . . . . . . . . . . . . . . . . . . . . . 12
11 Interfaces . . . . . . . . . . . . . . . . . . . . . 13
11.1 Interface X1 –
power supply and alarm output. . . . . . . . . 13
11.2 Interface X2 –
device programming. . . . . . . . . . . . . . . . . . 13
11.3 Interface X3 – integration in a higher-level
monitoring system . . . . . . . . . . . . . . . . . . . 13
12 Earth connection . . . . . . . . . . . . . . . 13
13 Commissioning . . . . . . . . . . . . . . . . 14
14 Status and function displays . . . . . 14
15 Technical specifications . . . . . . . . . 15
16 Maintenance and cleaning . . . . . . . 16
16.1 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . 16
16.2 Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
17 Fault correction . . . . . . . . . . . . . . . . 17
18 Disposal . . . . . . . . . . . . . . . . . . . . . . 18
19 Guarantee . . . . . . . . . . . . . . . . . . . . . 18
4 Rittal Thermoelectric Cooler assembly and operating instructions
1 Unpacking and checking
GB
1 Unpacking and checking
The Rittal Thermoelectric Cooler is delivered in trans­port packaging.
The supplied system consists of: 1 x cooling unit 1 x assembly and operating instructions 1 x accessories bag
Shipping bag content: 1 x assembly and operating instructions 1 x self-adhesive sealing tape 1 x filter mat 1 x drilling template 1 x connector plug (power supply and alarm output) Assembly parts
Check that the delivered system is complete and un­damaged. Any obvious transport damage must be reported without delay to the responsible transport company. The latest version of the “General conditions for deliveries and services” of the ZVEI (Central Asso­ciation of the German Electrotechnical Industry) applies.
Prior to disposal, check the packaging material for any loose function parts!
2 Notes on documentation
Assembly and operating instructions are available in printed form (provided with the supplied system) and as a PDF file for the
Rittal Thermoelectric Cooler.
A PDF file is available as free download from www.rittal.com. ACROBAT READER® is required to view the file. The accompanying documentation must be ob­served for the assembly, installation and operation of the cooling unit. Rittal cannot accept any liability for damage associated with the failure to observe these instructions. The information and safety notes in this manual follow the following structure:
Safety and other instructions:
2.1 Retention of the manual
The operating company is responsible for retaining the manual.
No part of the manual may be reproduced or processed, copied or distributed using electronic systems in any form (printed, microfilm or any other form) without the written approval of Rittal GmbH & Co. KG. No liability can be assumed for any damage resulting from the non-observance of the information contained in this manual.
Danger! Warning of a potential danger source. Danger to life and health in case of non-observance!
Danger! Warning of a dangerous electrical voltage. Danger to life and health in case of non-observance!
Danger! Warning of slippery surface. Danger to life and health in case of non-observance!
Note:
Useful information and special features.
3 Safety notes
Rittal Thermoelectric Cooler assembly and operating instructions 5
GB
3 Safety notes
The following general safety notes must be observed for the assembly, installation and operation of the cooling unit: – The assembly, installation and servicing of the
cooling unit may only be performed by properly trained specialists.
– The mains connector of the cooling unit must only
be connected and disconnected with the system de-energised. The device must be protected with
a pre-fuse. – No changes may be made to the cooling unit. – Only the customer service or authorised personnel
may open the device. The opening of the device by
the user or unauthorised persons is not permitted
and will void any warranty claim. – The cooling unit is intended only for the climate
control of enclosures and housings. Any other use
shall be deemed improper. The manufacturer is
not liable for any resulting damage! Proper usage
also includes the observance of all valid docu-
ments and compliance with the inspection and
servicing conditions. – The air inlet and outlet openings on the cooling unit
must not be covered. – Use only original spare parts and accessories
expressly approved for the Rittal Thermoelectric
Cooler. Otherwise malfunctions or damage can
occur. Warranty claims cannot be accepted for
such damage.
3.1 Proper usage
The Rittal Thermoelectric Cooler conforms to the current state-of-the-art. The cooling unit is intended only for cooling enclo­sures and operating housings. Any other use shall be deemed improper. Proper usage is possible only when all associated documents, and the device-specific assembly and operating instructions are observed. The manufacturer is not liable for any damage result­ing from improper use.
3.2 Standards, guidelines
The Rittal Thermoelectric Cooler meets the require­ments of the following guidelines and standards: – DIN 3168 Section 4.5 (enclosure cooling units) – Machine directive 98/37/EC – Low-voltage directive 2006/95/EC – Electromagnetic compatibility 2004/108/EC – EN 378-1 to -4 (cooling systems and heat pumps) – EN ISO 12100-1 and -2 (machine safety) – EN 294 (safety distances for contact) – EN 60 204-1 (machine electrical equipment) – EN 60 529 (degrees of protection provided by the
housing IP rating)
– EN 60 335-1 and -2-40
(safety of electrical devices) – EN 55 011 Kl B (radio disturbances) – EN 61 000-3-11 (electromagnetic compatibility) – ISO 9001/14001 – RoHs COMPLIANT 2002/95/EC
6 Rittal Thermoelectric Cooler assembly and operating instructions
4 How it works
GB
4 How it works
The Rittal Thermoelectric Cooler uses the Peltier ef­fect for cooling. This effect is based on the principle that an electric direct-current flowing through a cir­cuit consisting of two different metals causes the cooling of one contact point and the heating of the other contact points. An appropriate layout for the cooling production is designated as Peltier element. When the Peltier effect is used for enclosure climate control, an air flow is fed over the upper and lower connection point. The heat energy is released or accepted from the air flow to the Peltier element.
The air flow that releases the heat energy to the ele­ment is introduced as cooling air flow in the enclo­sure or the operating housing. After
the heating of the
cooling air flow by the active installed equipemt
, it is returned to the cooling unit and fed for renewed cool­ing over the “cold” side of the Peltier element. This produces an air circulation that causes the cooling of the enclosure or the operating housing. The air flow that accepts the heat energy from the “warm” side of the Peltier element is released as warm air flow to the external air circuit of the cooling unit. This means the heat produced by the compo­nents in the enclosure is dissipated to the ambient air surrounding the cooling unit.
Fig. 1: Peltier element Fig. 2: Peltier cooling unit
n-doped
n-doped
p-doped
p-doped
Warm area
Cold area
+ –
Divider panel
Environment
Enclosure/operating housing
Warm area
Cold area
5 Control
Rittal Thermoelectric Cooler assembly and operating instructions 7
GB
5 Control
The Rittal Thermoelectric Cooler controls the cooling capacity of the Peltier elements and the air through­put of the integrated fans so that the required internal temperature of the enclosure or the operating hous­ing is set with high accuracy. For this purpose, the device permanently monitors the air entry tempera­ture at the warm air entry (internal circulation). If this temperature exceeds a parameterised temperature value (factory setting: 35°C), the device starts cool­ing operation. To do this, the trigger voltages of the Peltier elements and fans are corrected by a PID control so that the cooling capacity required for the cooling is always available and the cooling operation is provided with the least possible power. The redun­dant fans in the external air circuit of the Rittal Ther­moelectric Cooler have variable air delivery rates (and consequently variable speeds) appropriate for the required cooling capacity. If only limited or in­deed no cooling capacity is required, this control be­haviour can lead to a temporary inactivity of the fans in the external air circuit. This does not constitute a malfunction of the device, but rather an extreme power-saving operating state that also increases the service life of the used fans.
Note:
The fan speed in the external air circuit of the cooling unit is matched to the current cooling capacity requirement. Consequently, a stoppage of the fans – interrupted by periodic, short-term fan starts – is not a malfunction of the device, but rather represents an extreme power­saving operating state!
Fig. 3: Control behaviour of the fans in the external air circuit
max.
Cooling capacity requirement
Fan speed in the external air circuit
Fan off
min.
8 Rittal Thermoelectric Cooler assembly and operating instructions
6 Device description
GB
6 Device description
Fig. 4: Device front Fig. 5: Device rear
1 2 3
4
5
7
6
1098
11
12
13
14
16
15
Legend
1 Status display 2 Function display 3 Housing 4 Louvred grille 5 Warm air outlet opening – external air circuit 6 Cold air inlet opening with filter element
(optional) – external air circuit 7 Condensate discharge 8 Interface X1: supply voltage and alarm output 9 Interface X2: USB 2.0, type B 10 Interface X3: RJ 45 11 Connection diagram 12 Warm air inlet opening – air internal circuit 13 Earth connection 14 Cold air outlet opening – air internal circuit 15 Blind nut 16 Rating plate (on the device lower side)
7 Device mounting
Rittal Thermoelectric Cooler assembly and operating instructions 9
GB
7 Device mounting
The following principles must be observed for deter­mining the mounting position on the enclosure or op­erating housing:
The Rittal Thermoelectric Cooler is mounted as exter­nal or full internal mounting. The supplied drilling template must be used to fasten the cooling unit on the enclosure or the operating housing. The drilling template provides dimension lines for the various installation options of the cooling unit. Identify appropriate lines and dimensions on the drilling template for the required mounting type (external or full internal mounting) using figures 6 and 7.
Drill the required holes for fastening the cooling unit and then cut the required cut-out, including the line width, in accordance with the drilling template.
The direct incidence of cold air on tem­perature-sensitive components must be avoided!
Components with integrated fans determine the cooling air routing in the enclosure or operating housing.
The mounting position of the cooling unit must be chosen so that the cooling air flow supports the heat dissipation of these com­ponents.
A free space of at least 100 mm is required in front of the air inlet and outlet openings of the cooling unit in the internal and external circuit.
The cooling unit must be positioned on the enclosure so that the condensate dis­charge opening is located at the lowest point of the cooling unit.
Risk of injury! Wear protective gear (safety glasses, protective gloves) when cutting the mounting cut-out and drilling the fastening holes. Carefully deburr all drilled holes and cut-outs to prevent injuries caused by sharp edges.
Fig. 6: Mounting cut-out and hole sizes
for external mounting
Fig. 7: Mounting cut-out and hole sizes
for internal mounting (full internal mounting)
377
366
400
25
25
11.5
15
Ø 6.5
10012.5
8.5
108
125
Climate control unit external contour
386
400
25
15
100
15
25
40
377
25
18
Ø 6.5 Ø 12
10
7
11.5
85
11
12.5
8.5
108
125
12
Climate control unit external contour
10 Rittal Thermoelectric Cooler assembly and operating instructions
7 Device mounting
GB
7.1 External mounting
When the cooling unit is mounted as externally­mounted variant, the supplied self-adhesive sealing tape must be fastened on the device rear wall of the cooling unit so that no gaps result at the joint edges. Then screw the supplied studs into the blind nuts at the rear of the unit. Secure the cooling unit using the supplied washers and nuts.
Fig. 8: Position of the sealing tape
Fig. 9: Fastening the cooling unit
Fig. 10: External and internal mounting
Fig. 11: Permissible mounting positions
7.2 Internal mounting
For the full internal mounting of the cooling unit, the louvred grille must be carefully removed from the de­vice. The self-adhesive sealing tape supplied must be placed on the front of the cooling unit (the device face from which the louvred grille has been re­moved) so that no gaps result at the joints. Then screw the supplied studs into the blind nuts at the front of the unit. Secure the cooling unit using the supplied washers and nuts. To complete the mount­ing, the louvred grille must be re-attached.
Fig. 12: Position of the sealing tape
Fig. 13: Fastening the cooling unit
125
400
400
155
55100
10055
Internal mountingExternal mounting
External mounting, vertical
External mounting, horizontal
Internal mounting, horizontal
Internal mounting, vertical
max. 45°
max. 45°
max. 45°
max. 45°
8 Filter mounting
Rittal Thermoelectric Cooler assembly and operating instructions 11
GB
8 Filter mounting
The Rittal Thermoelectric Cooler can be equipped with a device filter (supplied). An appropriate filter unit is recommended when the cooling unit is used in ambient air subject to dust.
When a filter is installed, the lower louvred grille in the air inlet of the cooling unit must be removed. To do this, raise the louvred grille with a light tug at the marked position (see Figure 14) and withdraw it at the front. Then place the filter mat in the filter holder of the device. The colour-marked side of the filter mat must face the device. Then re-mount the louvred grille and snap it into position by applying light pres­sure.
Fig. 14: Removable louvred grille
9 Mounting the
condensate discharge
The Rittal Thermoelectric Cooler is equipped with a condensate discharge.
Fig. 15: Condensate discharge
The controlled condensate discharge requires a condensate discharge hose be connected to the cooling unit’s condensate discharge supports. The condensate hose is available as accessory.
The installation of the condensate hose requires that it – is laid with a gradient (no siphon formation), – does not have any kinks, – must not have a reduced cross-section if extended.
Note:
When a filter unit is used, it must be cleaned regularly or, if necessary, replaced.
Risk of injury! The operation of the cooling unit without controlled condensate discharge can cause liquid to accumulate below the device.
Condensate discharge
12 Rittal Thermoelectric Cooler assembly and operating instructions
10 Electrical connection
GB
10 Electrical connection
10.1 Connection data
– The mains voltage and frequency must corres-
pond to the values stated on the rating plate.
– An all-range fuse specified on the rating plate must
be connected upstream as line and device pro­tection.
– No additional temperature control is allowed to be
connected upstream of the cooling unit on the supply side.
– An isolating device that ensures a contact opening
of at least 3 mm in switched-off state must be connected upstream of the cooling unit.
– The mains connection must ensure low-noise
potential equalisation.
Fig. 16: Rating plate
The Rittal Thermoelectric Cooler is available as version with integrated multi-range power pack (100 – 240 V) and as 24 V variant (without integrated power pack).
Fig. 17: SK 3201.200 connection diagram,
with integrated power pack
Fig. 18: SK 3201.300 connection diagram,
without integrated power pack
Legend
A1 Power PCB A2 Power pack B1 Temperature sensor, internal temperature B2 Ambient temperature sensor B3 Temperature sensor, power pack H1/H2 Status and function display M2.1 Condenser fan 1 M2.2 Condenser fan 2 M4 Evaporator fan TE Thermoelectric elements X1 Terminal strip X2 USB connection X3 Optional interface
Danger! Warning of a dangerous electrical voltage. Danger to life and health in case of non-observance!
M M M
M4
MS1
3
2
1
213
Ser ial
A1
TE
1
2
Power
PE
+
M2.2
1
3
2
M4
3
2
1
X1
1PE2
3
M2.2
4
M2.1
1
3
2
M2.1
4 4
L1
N
PE
TE
~
A2
PE
Mains
X2
X3
Alarm
NTC_O YELLOW
NTC_I RED
2
B2
2
B1
2
B3
NTC_N WHITE
H1 H2
M4
NTC_O YELLOW
NTC_I RED
MS1
3
2
1
2
1
3
Ser ial
A1
TE
1
2
Power
PE
+
M2.2
1
3
2
M4
3
2
1
PE
X1
Mains
1PE23
X2
X3
2
B2
2
B1
M2.2
4
M2.1
1
3
2
M2.1
M
4
M M
4
+ –
PE
TE
Alarm
H1 H2
11 Interfaces
Rittal Thermoelectric Cooler assembly and operating instructions 13
GB
11 Interfaces
Fig. 19: Designations of the device interfaces
11.1 Interface X1 – power supply and alarm output
– Power supply
SK 3201.200: AC: 100 – 240 V, 50/60 Hz SK 3201.300: DC: 24 V (SELV)
– Change-over contact/alarm output (floating
connection) Switching load: AC: 250 V/2 A, DC: 6...30 V/2 A The signal relay releases for overtemperature, sensor break and fan failures.
Fig. 20: Change-over contact assignment
11.2 Interface X2 – device programming
– USB 2.0
11.3 Interface X3 – integration in a higher-level monitoring system
– RJ 45
The interface X3 permits the connection of the cool­ing unit in higher-level monitoring systems.
12 Earth connection
The Rittal Thermoelectric Cooler is equipped with a potential equalisation connection point. A conductor with a nominal cross-section of at least 6 mm2 must be connected to this connection point and included in the provided potential equalisation.
Fig. 21: Contact point for potential equalisation
X2X1 X3
PE
1+
23
24 V DC
0322231
X2X1 X3
PEL1
L2
N
123
0322416
Connection terminal designation SK 3201.300
Connection terminal designation SK 3201.200
Interface X3Interface X2Interface X1
Interface X3Interface X2Interface X1
Pin 1 Pin 2 Pin 3
Note:
The electrical signals at the interface X3 are extra-low voltages (not extra-low safety voltages in accordance with EN 60 335).
Note:
According to the standard, the PE conduc­tor in the mains connection cable is not classified as an equipotential bonding con­ductor.
X2X1 X3
PE
123
24 V DC
0322231
Contact point for the potential equalisation
14 Rittal Thermoelectric Cooler assembly and operating instructions
13 Commissioning
GB
13 Commissioning
The Rittal Thermoelectric Cooler is operational im­mediately after connection of the power supply. If the factory setting is unchanged, the temperature con­trol of the enclosure or operating housing uses the following parameters:
Set enclosure interior temperature: +35°C Start temperature for cooling operation: +35°C Overtemperature alarm message: +45°C
Under normal operating conditions, device opera­tion with unchanged factory setting should ensure a problem-free enclosure climate control. If it would appear to be useful to change the predefined pa­rameters for special climate control requirements, this can be realised with programming software. In this case, please contact the device manufacturer.
14 Status and function displays
The Rittal Thermoelectric Cooler is equipped with a status and function display. Two coloured LEDs show the status, alarm and error messages that indi­cate the operating state of the cooling unit.
Fig. 22: Status and function displays on the cooling unit
Tab. 1: Function display
Tab. 2: Status display
Function LED
Description
Off Unit OFF or Cooling OFF
Green Cooling operation ON
Red Error – unit
Status LED
Description
Off Unit OFF
Green Unit OK
Orange Warning (temperature alarm,
temperature > alarm value)
Red Error (sensor defective, fan
defective, thermoelectric module defective)
Function display
Status display
15 Technical specifications
Rittal Thermoelectric Cooler assembly and operating instructions 15
GB
15 Technical specifications
Tab. 3: Technical specifications
Tab. 4: Setting ranges
Fig. 23:
Cooling output characteristic curve for full internal moun­ting and an enclosure internal temperature T
i
of 35°C
Model No. SK
3201.200 3201.300
Dimensions in mm
W H D
125 400 155
Operating voltage in volts, Hz 100 – 240 V AC, 50/60 Hz 24 V DC
Useful cooling output
Q
k
in accordance with DIN 3168
L 35 L 35
100 W
Power consumption P
el
in accordance with DIN 3168
L 35 L 35
Max. 100 W
Refrigeration factor (max.)/COP
L 35 L 35
1.0 1.2
Power pack Integral
Housing colour RAL 7024/anodised aluminium
Protection category according to EN 60 529
Internal circuit External circuit
IP 54 IP 34
Weight 3.0 kg 2.4 kg
Noise level Max. 63 dB(A)
Operating temperature +5°C to +55°C
Storage temperature –20°C to +70°C
Installation position Horizontal or vertical
Air throughput, unimpeded air flow
Internal circuit External circuit
132 m
3
/h
132 m
3
/h
Temperature setting range +20°C to +55°C
Cooling activation temperature +35°C (factory setting)
Type of connection Plug-in terminal strip
Pre-fuse gG 2 A 10 A
Floating change-over contact; contact loading
DC: 6...30 V / 0.1...2 A AC: 250 V / 2 A
Technical modifications reserved.
.
Variable Range Default value EEPROM
Temperature conversion °C/°F 0...1 0 (°C) Yes
Cooling setpoint +20 to +55°C 35°C Yes
Overtemperature alarm message (0)2...15 K (0 = off) 10 K Yes
Internal fan deactivation (during cooling pauses) 0...1 0 (no deactivation) Yes
2520 30 35 40 45
0
140
160
120
100
80
60
40
20
Cooling output in W
T
i
Ambient temperature in °C
Ti = Enclosure internal temperature (°C)
Room temperature
16 Rittal Thermoelectric Cooler assembly and operating instructions
16 Maintenance and cleaning
GB
16 Maintenance and cleaning
16.1 Maintenance
The Rittal Thermoelectric Cooler is low-maintenance.
16.2 Cleaning
If the Rittal Thermoelectric Cooler is used in ambient air subject to dust, dust can accumulate in the area of the air inlet and outlet openings and on the heat transferring surfaces of the Peltier element. This can cause a reduction of the air flow in the device and thus a gradually reducing cooling capacity. To re­move the dust, withdraw the louvred grille at the de­vice front side. Blow compressed air through the air inlet and outlet openings of the cooling unit.
If the Peltier cooling unit is equipped with a device filter, it must be cleaned or replaced regularly. The filter mat can be cleaned by washing, dusting or blowing with compressed air. The high-quality filter material used for the mat means the cleaning does not impair the filter-technical properties and the form stability. The fire class remains unchanged!
Danger! Prior to any cleaning or maintenance work, the power to the cooling unit must be disconnected!
Note:
When the filter is replaced, use only filter materials approved for the Rittal Thermo­electric Cooler. The dust collecting efficiency and dust storage capacity of the filter equipment chosen is matched to the rated flow speed of the cooling unit in the external air circuit and so guarantees an excellent dust filtering for a high useful cooling output.
17 Fault correction
Rittal Thermoelectric Cooler assembly and operating instructions 17
GB
17 Fault correction
Tab. 5: Fault correction
Fault description Possible cause Correction
The unit does not switch on. No power supply. Check the mains connection and the
pre-fuse.
The unit does not cool adequately. The air circulation in the enclosure is
impaired.
Check the air circulation inside the enclosure. Check, in particular, those components equipped with a fan. Check the free spaces above and below the main heat dissipation sources.
Ambient temperature too high. Reduce the ambient temperature.
Protect the unit from radiation heat caused by direct sunshine and hot surfaces.
Filter equipment contaminated. Check the filter and, if necessary,
clean or replace.
Internal fan defective.
Replace (Rittal Service).
External fan defective. Replace (Rittal Service).
The heat produced in the enclosure exceeds the cooling capacity of the Peltier cooling unit.
Reduce the heat loss.
Condensation. Enclosure leakages. Check the enclosure for leaks (IP 54).
Check, in particular, the cable entry points for leaks.
Internal temperature of enclosure set too low.
Check the set enclosure internal temperature (factory setting: +35°C).
18 Rittal Thermoelectric Cooler assembly and operating instructions
18 Disposal
GB
18 Disposal
To ensure the material reuse of the recyclable pack­aging materials, they must be delivered to the local collection sites. The cooling unit must be delivered to a waste man­agement service provider that ensures the correct reuse of the recyclable parts and the proper disposal of the rest.
19 Guarantee
Provided the unit is used correctly (refer to the operating instructions), Rittal gives its customers a 24-month “Rittal manufacturer’s guarantee” starting with date of manufacture.
If, within the guarantee period, during the 24 months after manufacture, a malfunction occurs on the prod­uct that substantially adversely affects its functional­ity, Rittal will, within a reasonable period of time, rec­tify the malfunction by telephone service or, if neces­sary, by replacement, repair or other measures, at its option. If this is inappropriate for the customer, Rittal also has the possibility to provide the customer with the replacement parts required to correct the mal­function. Within the scope of its guarantee, Rittal will bear all costs concerning the dispatching, deployment and accommodation of its staff and with replacing or re­pairing any parts, provided the malfunction occurred during the proper usage of the products and provid­ed the costs are not increased by the movement of the products to a place other than that where they were originally delivered. In addition, Rittal will bear the necessary costs for procuring and delivering the replacement parts to the place where the products were originally delivered. Any parts delivered for or in replacement will be new or in mint condition and in a fully functional state free of faults; the replaced parts will become Rittal’s property; the customer warrants that no rights of any third parties will obstruct that exchange and transfer of title. Any claims based on this guarantee are to be sub­mitted to Rittal in writing within one month after the occurrence of the malfunction. Any further claims, in particular claims for damages
, are not covered by the guarantee. The statutory lia­bility for defects is not affected by the guarantee.
Switch to perfection
R
Power Distribution
Stromverteilung
Distribution de courant Stroomverdeling Strömfördelning Distribuzione di corrente Distribución de corriente
IT Solutions
IT-Solutions
Solutions IT IT-Solutions IT-lösningar Soluzioni per IT Soluciones TI
System-Klimatisierung System Climate Control Climatisation Systeemklimatisering Systemklimatisering Soluzioni di climatizzazione Climatización de sistemas
Schaltschrank-Systeme Industrial Enclosures Coffrets et armoires électriques Kastsystemen Apparatskåpssystem Armadi per quadri di comando Sistemas de armarios
Elektronik-Aufbau-Systeme Electronic Packaging Electronique Electronic Packaging Systems Electronic Packaging Contenitori per elettronica Sistemas de montaje para la electrónica
Communication Systems Communication Systems Armoires outdoor Outdoor-behuizingen Communication Systems Soluzioni outdoor Sistemas de comunicación
Rittal GmbH & Co. KG · Postfach 1662 · D-35726 Herborn Tel.: +49 (0) 2772 505-0 · Fax: +49 (0) 2772 505-2319 · eMail: info@rittal.de · www.rittal.com
322 194
Loading...