Rittal SK 3186930, SK 3187930, SK 3188940, SK 3189940 Assembly instructions

Enclosure cooling unit
SK 3186930 SK 3187930 SK 3188940 SK 3189940
Assembly and operating instructions
EN
Preface
Preface
Dear Customer!
Yours Rittal GmbH & Co. KG
Rittal GmbH & Co. KG Auf dem Stützelberg
35745 Herborn Germany
Phone: +49(0)2772 505-0 Fax: +49(0)2772 505-2319
E-mail: info@rittal.com www.rittal.com www.rittal.de
We are always happy to answer any technical questions regarding our entire range of products.
2 Rittal enclosure cooling unit
Contents
Contents
1 Notes on documentation .................. 4
1.1 CE labelling................................................... 4
1.2 Storing the documents.................................. 4
1.3 Symbols used in these operating instructions 4
1.4 Other applicable documents ......................... 4
2 Safety notes ..................................... 5
2.1 General safety instructions ............................ 5
2.2 Operating and technical staff......................... 5
2.3 Other dangers when using the cooling unit ... 5
3 Product description .......................... 6
3.1 Functional description and components........ 6
3.1.1 Function ............................................................... 6
3.1.2 Components ........................................................ 7
3.1.3 Control ................................................................. 7
3.1.4 Safety devices ...................................................... 7
3.1.5 Condensation ....................................................... 7
3.1.6 Filter mats ............................................................ 7
3.1.7 Door limit switch ................................................... 8
3.2 Proper use, foreseeable misuse .................... 8
3.3 Supply includes............................................. 8
4 Transport and handling .................... 9
4.1 Delivery ......................................................... 9
4.2 Unpacking .................................................... 9
4.3 Transport ...................................................... 9
5 Installation ...................................... 10
5.1 Safety instructions....................................... 10
5.2 Siting location requirements ........................ 10
5.3 Assembly procedure ................................... 10
5.3.1 Assembly instructions ......................................... 10
5.3.2 Mounting options ............................................... 11
5.3.3 Make a mounting cut-out in the enclosure .......... 12
5.3.4 External mounting of the cooling unit .................. 12
5.3.5 Mounting the cooling unit externally on a 500 mm
deep enclosure ................................................... 14
5.3.6 Partial internal mounting of the cooling unit ......... 14
5.3.7 Full internal mounting of the cooling unit ............. 18
5.3.8 Connect the condensate water discharge .......... 19
5.4 Electrical connection ................................... 20
5.4.1 Notes on electrical installation ............................. 20
5.4.2 Install the power supply ...................................... 21
5.4.3 Connect the alarm relays .................................... 22
5.4.4 Interfaces ........................................................... 22
7.4 Configuration menu.................................... 26
7.4.1 Temperature ....................................................... 26
7.4.2 Alarm relays ....................................................... 27
7.4.3 Language settings .............................................. 27
7.4.4 Self-test .............................................................. 27
7.5 System messages...................................... 28
7.5.1 Occurrence of a malfunction ............................... 28
7.5.2 Display in case of errors ..................................... 28
7.6 List of system messages ............................ 29
8 Inspection and maintenance ........... 32
8.1 Safety instructions for maintenance work ... 32
8.2 Notes on the refrigerant circuit ................... 32
8.3 Maintenance work on the cooling unit ........ 32
8.4 Compressed air cleaning............................ 32
8.4.1 Dismantling a unit with full internal mounting ....... 32
8.4.2 Dismantling the unit ............................................ 32
8.4.3 Cleaning the components with compressed air .. 35
8.4.4 Re-assembling the cooling unit ........................... 35
9 Storage and disposal ...................... 36
10 Technical specifications .................. 37
11 List of spare parts ........................... 39
12 Drawings ........................................ 40
12.1 Representation of mounting cut-outs ......... 40
12.2 Dimensions and installation depths ............ 41
13 Accessories .................................... 43
14 Customer service addresses .......... 44
15 Compact service information .......... 48
EN
6 Commissioning .............................. 23
7 Operation ....................................... 24
7.1 General....................................................... 24
7.2 Layout of the display ................................... 24
7.2.1 Start screen ........................................................ 24
7.2.2 Changing a parameter value ............................... 24
7.3 Information menu ........................................ 25
7.3.1 Temperature information .................................... 25
7.3.2 Device information .............................................. 25
7.3.3 Efficiency information .......................................... 26
Rittal enclosure cooling unit 3
EN

1 Notes on documentation

1 Notes on documentation

1.1 CE labelling

Rittal GmbH & Co. KG confirms the conformity of the cooling unit with the European Union's Machinery Di­rective 2006/42/EC and EMC Directive 2004/108/EC. A corresponding declaration of conformity has been is­sued and enclosed with the unit.

1.2 Storing the documents

The assembly and operating instructions as well as all other applicable documents are an integral part of the product. They must be issued to everyone who works with the unit and must always be available and on hand for operating and maintenance personnel.
1.3 Symbols used in these operating in­structions
The following symbols are used in this documentation:
Danger! A dangerous situation in which failure to
comply with the instructions will result in death or severe injury.
Warning! A dangerous situation which may cause death or serious injury if the instructions are not followed.
Caution! A dangerous situation which may lead to
(minor) injuries if the instructions are not followed.
Note: Important notices and indication of situations
which may result in material damage.
This symbol indicates an "action point" and shows that you should perform an operation or procedure.

1.4 Other applicable documents

Assembly and operating instructions exist as paper doc­uments and/or digital data carriers for the unit types de­scribed here and are enclosed with the equipment.
We cannot accept any liability for damage associated with failure to observe these instructions. Where applica­ble, the instructions for any accessories used also apply.
4 Rittal enclosure cooling unit
2 Safety notes

2.1 General safety instructions

Please observe the following general safety instructions for the installation and operation of the system:
– Please be sure to observe the applicable regulations
governing electrical installations of the country in which the device is installed and operated as well as national regulations for accident prevention. Please also observe any internal company regulations, such as work, operating and safety regulations.
– Use only original Rittal products or products recom-
mended by Rittal in conjunction with the cooling unit.
– Please do not make any changes to the cooling unit
that are not described in these operating instructions or other applicable assembly and operating instruc­tions.
– The operational safety of the cooling unit is only war-
ranted if used as intended. The technical specifica­tions and limit values stated must not be exceeded un­der any circumstances. In particular, this applies to the specified ambient temperature range and IP protec­tion category.
– Operating the cooling unit in direct contact with water,
aggressive materials or inflammable gases and va­pours is prohibited.
– Other than these general safety instructions, it is also
vital to observe the specific safety instructions when carrying out the tasks described in the following chap­ters.
– Please note the maximum weights that may be lifted
by individuals. It may be necessary to use lifting gear.

2 Safety notes

Where applicable, use suitable components to divert the air.
Please observe the prescribed minimum distances at the installation site as outlined in section 5.3.1 "As­sembly instructions".
EN

2.2 Operating and technical staff

– The assembly, installation, commissioning, mainte-
nance and repair of this cooling unit may only be per­formed by qualified, trained personnel.
– Only properly instructed personnel may operate a
cooling unit with the system operational.
– Children and persons with limited cognitive/coordina-
tive abilities must not operate, maintain or clean the unit or be allowed to use it as a toy.

2.3 Other dangers when using the cooling unit

Particularly when the cooling unit is externally mounted (see section 5 "Installation"), there is a risk that the en­closure could become unbalanced and tip over.
In such cases, the enclosure should be bolted to the floor as a precaution.
If the air inlet or outlet of the cooling unit is obstructed, there is a risk of air short-circuits, resulting in inadequate climate control.
Please ensure that the electronic assemblies in the en­closure are installed in accordance with section 5.3.1 "Assembly instructions".
Rittal enclosure cooling unit 5

3 Product description

EN
3 Product description

3.1 Functional description and components

3.1.1 Function

There are two separate cooling circuits installed in the cooling unit.
– One conventional refrigerant circuit (compression sys-
tem), and
– One heat pipe integrated into the condenser and
evaporator coil.
Refrigerant circuit with compression system
The refrigerant circuit with compression system is com­prised of the following four main components:
1. Evaporator coil
2. Compressor
3. Condenser
4. Expansion valve
The evaporator coil fan draws hot air from the enclosure in the internal circuit of the cooling unit and passes it over the evaporator coil. After the evaporator coil, the cooled air is fed back into the enclosure via the outlet opening.
The air is cooled down by evaporating the refrigerant in the evaporator coil. The refrigerant vapour is transported by the compressor in the external circuit of the cooling unit to the condenser. There, the refrigerant condenses and becomes a liquid. The heat produced is dissipated by the condenser fan. The downstream electronic ex­pansion valve reduces the high pressure of the refriger­ant, and the refrigerant is then fed back into the evapo­rator coil.
Both the compressor and the two fans in the cooling unit are activated via an inverter. This makes it possible to control these components, so that the fan and compres­sor may be activated for a longer time but at a lower out­put and improved efficiency.
Fig. 1: Cooling circuit
Key
1 Compressor 2 Condenser (dual version) with fan 3Expansion valve 4 Evaporator coil (dual version) with fan 5 Refrigerant circuit with heat pipe 6 Refrigerant circuit with compression system 7 Internal circuit 8 External circuit 9 Dryer/collector 10 Internal fan 11 External fan 12 PSA
H
pressure monitor
In both cooling circuits, the individual components are connected with pipes in which the refrigerant R134a is circulating. This refrigerant is very environmentally friend­ly, thanks to the following properties: –Chlorine-free
– Does not deplete the ozone layer (ozone destruction
potential ODP = 0)
Refrigerant circuit with heat pipe
The additional second refrigerant circuit operates with­out a compressor, expansion valve or other control ele­ments, and is integrated into the evaporator coil and condenser as a heat pipe. The refrigerant inside the heat pipe (R134a) absorbs thermal energy from the intake of enclosure air and evaporates. The gaseous refrigerant then rises through the pipeline until it reaches the condenser. The refriger­ant is cooled down again in the condenser (provided Tu < Ti), and the heat released is emitted into the environ­ment. Gravity then causes the liquid refrigerant to flow back down the pipelines. The whole cycle begins again.
6 Rittal enclosure cooling unit
3 Product description

3.1.2 Components

Fig. 2: Main components of cooling unit
Key
1Cover 2 Chassis 3 Connection box 4Evaporator fan 5Handle 6 Air outlet opening 7 Lower louvred grille for air inlet 8Display 9 Infill panel 10 Upper louvred grille for air outlet 11 Thread for eyebolt

3.1.3 Control

Rittal enclosure cooling units are fitted with a controller for setting the functions of the cooling unit.
Operation using this controller is described in section 7 "Operation".

3.1.4 Safety devices

– In the refrigerant circuit, the cooling units have a type-
tested pressure monitor (to EN 12263) which switches off the cooling unit if the maximum admissible pres­sure is exceeded. Once the pressure drops back be­low the admissible pressure, the unit will automatically resume operation.
– Temperature monitoring prevents the evaporator coil
from icing over. If there is a risk of icing, the compres­sor switches itself off and automatically switches itself back on again at higher temperatures.
– The compressor is monitored and protected by the in-
verter to prevent overloading.
– The fans have a built-in overload protection with auto-
matic reset.
– In order to allow a reduction of pressure inside the
compressor and hence a safe restart, once it has been switched off (e.g. upon reaching the set temperature via the door limit switch function or via de-energising), the device will switch back on with a delay of 180 sec­onds.
– The device has floating contacts on the connection
pins on terminals 1 and 3 of the signal connector (X2), via which system messages from the device may be polled, e.g. using a PLC (2 x normally closed or nor­mally open contacts).

3.1.5 Condensation

At high levels of humidity and low temperatures inside the enclosure, condensate water may form on the evap­orator coil.
The cooling units have an automatic electrical conden­sate water evaporator. The thermal component used for this purpose is based on self-regulating PTC technolo­gy. Condensate water arising on the evaporator coil is collected in a tank in the external circuit of the cooling unit, and partially evaporated via the airflow. When the water level rises, the water enters the PTC thermal com­ponent and is evaporated (through-flow heater princi­ple). The water vapour streams out of the cooling unit with the airflow from the external fan. The PTC thermal component is activated automatically when the compressor is running, and continues to run for around 15 minutes after the compressor has been switched off. During the after-run phase, the condenser fan will likewise continue to run at low speed.
In the event of a short-circuit in the PTC component or if there is a risk of inverter overload (possible at high ambi­ent temperatures), the PTC component will be deacti­vated. This means that any condensate water arising can be discharged via the safety overflow.
If the fuse has tripped, any condensate water is drained off via the safety overflow. The condensation is routed downwards out of the unit via a drain pipe on the evap­orator coil divider panel. For this purpose, a hose may be connected to the condensate water nozzle (see section
5.3.8 "Connect the condensate water discharge").

3.1.6 Filter mats

The entire cooling unit condenser is covered with a dirt­repelling, easy-to-clean RiNano coating. In many appli­cations, therefore, the use of filter media is unnecessary, particularly with dry dusts. For dry, coarse dust and lint in the ambient air, we rec­ommend installing an additional PU foam filter mat (avail­able as an accessory) in the cooling unit. Depending on the incidence of dust, you will need to replace the filter mat from time to time (see section 8 "Inspection and maintenance").
For oily ambient air, we recommend the use of metal fil­ters (also available as an accessory). These may be cleaned with suitable detergents and reused.
EN
Rittal enclosure cooling unit 7
3 Product description
EN

3.1.7 Door limit switch

The cooling unit may be operated with a floating door limit switch connected. The door limit switch is available as accessory from Rittal.
The door limit switch function causes the fans and the compressor in the cooling unit to gradually slow down and then switch off after approximately 15 seconds when the enclosure door is opened (contacts 1 and 2 closed). This prevents the formation of condensate wa­ter inside the enclosure while the enclosure door is open. In order to prevent damage to the unit, it is equipped with an ON delay: The evaporator fan will cut in again after a delay of a few seconds on closure of the door.
Please note that no external voltage may be applied to the door contacts (terminals 1 and 2)

3.2 Proper use, foreseeable misuse

The cooling unit is only intended for cooling connected enclosures. Any other use is not permitted.
– The unit must not be installed and operated in loca-
tions which are accessible to the general public (see
DIN EN 60335-2-40, paragraph 3.119). – The unit is designed solely for stationary use. – The manufacturer's consent must be obtained in ad-
vance for mobile applications, e.g. on cranes.
The cooling unit is state of the art and built according to recognised safety regulations. Nevertheless, improper use can pose a threat to the life and limb of the user or third parties, or result in possible damage to the system and other property.

3.3 Supply includes

Qty. Description
1 Enclosure cooling unit
1 Shipping bag with
1 – Declaration of conformity
1 – Assembly and installation instructions
1 – Assembly, installation and operating in-
structions on digital data carrier
1 – Warning and safety notes
6 – Grub screws M8 x 40 mm
6 – Nut-and-washer assembly M8
1 – Sealing tape 10 x 10 mm, L = 4.1 m
1 – Signal connector X2
1–Connector X1
1 – Cover for connection unit
1 – Membrane entry grommet
1 – Clip
1 – Wedge element
6 – Fixing clamps
4 – Corner bracket for internal/external
mounting
2 – L-shaped brackets
Consequently, the cooling unit must only be used prop­erly and in a technically sound condition! Any malfunc­tions which impair safety should be rectified immediate­ly.
Proper use also includes the observance of the docu­mentation provided, and compliance with the inspection and maintenance conditions.
Rittal GmbH & Co. KG is not liable for any damage which may result from failure to comply with the documenta­tion provided. The same applies to failure to comply with the valid documentation for any accessories used.
Inappropriate use may be dangerous. Examples of inap­propriate include: – Use of the cooling unit over long periods with the en-
closure open. – Use of impermissible tools. – Improper operation. – Improper rectification of malfunctions. – Use of accessories not approved by Rittal GmbH &
Co. KG.
1–Earth clamp 4 NS
1–Earth clamp 5 NS
1 – Washer for attaching the earth clamp
1 – Contact washer for attaching the earth
clamp
1 – M4 nut for attaching the earth clamp
1 – Cable gland M20 x 1.5 mm
1 – EMC cable gland M20 x 1.5 mm
1 – Strain relief
Tab. 1: Supply includes
8 Rittal enclosure cooling unit
4 Transport and handling

4.1 Delivery

The cooling unit is supplied in one packaging unit.
Check the packaging carefully for signs of damage. Traces of oil on damaged packaging indicate a loss of refrigerant and/or a leak in the cooling unit. Any pack­aging damage may be the cause of a subsequent functional failure.

4.2 Unpacking

Remove the packaging materials from the cooling unit.
Note: After unpacking, the packaging materials
must be disposed of in an environmentally friendly way.
Check the cooling unit for any damage that may have occurred during transport.
Note: Damage and other faults, e.g. incomplete de­livery, should be reported immediately, in writing, to the shipping company and to Rittal GmbH & Co. KG.

4 Transport and handling

Fig. 3: Thread and eyebolt on top of the chassis
Key
1Eyebolt 2 M12 thread
Before transporting by crane, please ensure that the
lifting gear and crane have sufficient load capacity to transport the cooling unit safely.
Never allow anyone to stand beneath a suspended load, even for a short time, during transportation by crane.
Protect the lifting gear on the crane hook from load de­flection, because the load's centre of gravity may be off-centre.
First position the cooling unit close to the installation site and protect from accidentally being knocked over.
EN
Check the supply contents for completeness (see sec­tion 3.3 "Supply includes").

4.3 Transport

Depending on the chosen version, the cooling unit may weigh up to 85 kg. The components in the cooling unit chassis account for the bulk of the weight.
Warning! Please note the maximum weights that may be lifted by individuals. It may be necessary to use lifting gear.
At the rear of the cooling unit is a handle which can be used to briefly lift the cooling unit when inserting into the mounting cut-out.
There is also an M12 thread at the top of the chassis, into which a Rittal eyebolt (e.g. belonging to an enclo­sure) may be screw-fastened. The cooling unit is readily transported with the aid of lifting gear and an indoor crane.
Note: An eyebolt with M12 thread may be ordered
as an accessory from Rittal (see section 13 "Accessories").
Rittal enclosure cooling unit 9

5 Installation

EN
5 Installation

5.1 Safety instructions

Warning! Please note the maximum weights that
may be lifted by individuals. It may be necessary to use lifting gear.
Warning! Work on electrical systems or equip­ment may only be carried out by an elec­trician or by trained personnel under the guidance and supervision of an electri­cian. All work must be carried out in ac­cordance with electrical engineering regulations.
The cooling unit may only be connected after the aforementioned personnel have read this information!
Use only insulated tools.
Follow the connection regulations of the appropriate electrical supply company.
The cooling unit must be connected to the mains via an all-pin isolating device to overvoltage category III (IEC 61058).
The cooling unit is not de-energised until all of the voltage sources have been dis­connected!
– The installation site must be free from excessive dirt,
aggressive ambient conditions and moisture. – The ambient temperature must not exceed 60°C. – It must be possible to fit a condensate water discharge
(see section 5.3.8 "Connect the condensate water
discharge"). – The mains connection data as stated on the rating
plate of the cooling unit must be guaranteed.
Size of installation room
Units SK 3186930 and SK 3187930 must not be in-
stalled in rooms of less than 6 m³. – Units SK 3188940 and SK 3189940 must not be in-
stalled in rooms of less than 12 m³.
Electromagnetic interference (EMI)
– Interfering electrical installations (high frequency) must
be avoided.

5.3 Assembly procedure

5.3.1 Assembly instructions

Before assembling, please ensure that the enclosure
is sealed on all sides (IP 54). Increased condensation
will occur later during operation if the enclosure is not
airtight.
If applicable, additionally fit a door limit switch (such as
4127.010) to the enclosure which switches off the
cooling unit when the enclosure door is opened to pre-
vent excessive condensation (see section 3.1.7 "Door
limit switch").
Please ensure that the electronic assemblies in the en-
closure allow the even circulation of air.
Please be sure to observe the applicable regulations governing electrical installations of the country in which the device is installed and operated, as well as national regulations for accident prevention. Please also observe any internal company regulations, such as work, operating and safety regulations.
The technical specifications and limit values stated must not be exceeded under any circumstances. In particular, this applies to the specified ambient tem­perature range and IP protection category.

5.2 Siting location requirements

When choosing the installation site for the enclosure, please observe the following:
– The site for the enclosure, and hence the positioning
of the cooling unit, must be carefully selected so as to ensure good ventilation (clearance between cooling units and clearance between a cooling unit and the wall must be at least 200 mm in each case).
– The cooling unit must be installed and operated with a
maximum deviation of 2° from the vertical.
10 Rittal enclosure cooling unit
Fig. 4: Never direct the cold airflow at active components
Under no circumstances should the air inlet and outlet openings of the cooling unit be obstructed. Only in this way is it possible to ensure that the maximum cooling output is available.
Please ensure that the cold airflow from the cooling unit is not directed at active components.
Fig. 5: Never direct the cold airflow at active components
If appropriate, install components to divert the air.
When installing in a dismantled door or side panel, please ensure that it cannot fall over when installing the cooling unit in the mounting cut-out.
Note: The pictures in this chapter illustrate the in-
stallation of the cooling unit in an enclosure door. Installation in a side panel is carried out in the same way.

5.3.2 Mounting options

In principle, there are three different options for installing the cooling unit on an enclosure door or side panel.
5 Installation
EN
Fig. 6: Mounting options
Key
1 External mounting 2 Partial internal mounting 3 Full internal mounting
– External mounting: All of the cooling unit is outside the
enclosure.
– Partial internal mounting The cooling unit chassis is in-
side the enclosure, while the cover and the louvred grilles are outside.
– Full internal mounting: All of the cooling unit is inside
the enclosure. Only the louvred grilles project on the outside.
Note: – Full installation of the 6 kW cooling unit is
not possible.
– On an enclosure with 500 mm depth, the
unit may only be externally mounted on the side panel.
Your chosen installation option will ultimately depend on how much space you require inside and outside of the enclosure. The various mounting options have no influ­ence on the cooling output of the cooling unit, which re­mains the same in all cases. – If there are a large number of components installed in-
side the enclosure, external mounting or partial in­ternal mounting of the cooling unit may be appropri­ate. In such cases, the space inside the enclosure may be insufficient for full internal mounting, or it may not be possible to guarantee adequate cooling of all com­ponents inside the enclosure.
– If the space surrounding the enclosure is limited,
full internal mounting may be suitable, so as to keep essential escape routes clear.
Rittal enclosure cooling unit 11
EN
5 Installation

5.3.3 Make a mounting cut-out in the enclosure

In order to mount the cooling unit on the enclosure, a suitable mounting cut-out must be made in the door or side panel of the enclosure. In principle, the mounting cut-out is identical for all three mounting options. A spe­cial mounting cut-out is only required for external mount­ing on the side panel of a 500 mm deep enclosure.
Note: The dimensions of the mounting cut-outs
can be found in section 12.1 "Representation of mounting cut-outs".
Using the diagrams in section 12.1 "Representation of mounting cut-outs", calculate the required dimensions for your mounting cut-out .
Drill all the required holes and make the mounting cut­out.
Carefully deburr all drilled holes and the cut-out to pre­vent injuries caused by sharp edges.
Caution! Drilled holes and cut-outs that have not
been fully deburred may cause cut inju­ries, particularly when assembling the cooling unit.

5.3.4 External mounting of the cooling unit

Note: The description in this section does not ap-
ply to external mounting of the cooling unit on the side panel of a 500 mm deep enclosure. This is described in section 5.3.5 "Mounting the cooling unit externally on a 500 mm deep enclosure".
Fig. 7: Threaded bolts at the rear of the cooling unit
Key
1 Rear of cooling unit 2 Lower threaded bolt 3 Joint of sealing tape 4Cover
Push the clip included with the supply into the relevant
hole at the top edge of the cooling unit at the rear.
This clip will prevent the cooling unit from falling out of
the mounting cut-out later on if it is not yet adequately
secured with the threaded bolt.
Cut the sealing tape in the dispatch bag to the re­quired length so that it can be placed all the way round the rear of the cooling unit once.
Start by positioning the sealing tape on the bottom edge, so that the joint between the two ends of the sealing tape is likewise on the lower edge of the unit.
Carefully stick the sealing tape as close to the edge as possible on the rear of the cooling unit.
Screw the four threaded bolts into the blind nuts in the corners at the rear of the cooling unit.
Fig. 8: Clip at the rear of the cooling unit
Key
1 Clip 2 Rear of cooling unit
12 Rittal enclosure cooling unit
Lift up the cooling unit, preferably from a lifting eye us­ing suitable lifting gear, and initially set the cooling unit down with the two bottom threaded bolts on the door or side panel of the enclosure.
If transportation by crane is not possible, lift the cool­ing unit into the mounting cut-out in the same way us­ing the handle.
Fig. 9: Threaded bolt in door cut-out
Key
1 Inside of enclosure door 2 Threaded bolts at bottom (2x) 3 Cooling unit on the outside of the enclosure door
5 Installation
Fig. 11: Corner brackets on the threaded bolts
Key
1Corner bracket 2 Threaded bolt
Next, attach the two corner brackets to the threaded
bolts at the bottom and secure with the corresponding nuts.
EN
Slide the cooling unit into the mounting cut-out at the
top until the clip behind the cut-out latches home.
Fig. 10: Clip in mounting cut-out
Key
1 Inside of enclosure door 2 Clip
Attach the two corner brackets to the threaded bolts
at the top and secure with the corresponding nuts.
Fig. 12: Threaded bolts at rear
Key
1 Threaded bolts (4x) 2 Fastening clamps (6x) 3 Rear of cooling unit 4 Cooling unit in front of enclosure door
Insert the six fastening clamps into the rear of the cool-
ing unit.
Rittal enclosure cooling unit 13
5 Installation
EN
These fastening clamps ensure that the cooling unit is directly in contact with the mounting cut-out of the en­closure door over the entire height.
If applicable, re-attach the door or side panel including cooling unit to the enclosure, if not mounted directly on the enclosure.

5.3.5 Mounting the cooling unit externally on a 500 mm deep enclosure

Note: The description in this section applies to ex-
ternal mounting of the cooling unit on the side panel of a 500 mm deep enclosure. Ex­ternal mounting on deeper enclosures is also possible with this type of installation.
In principle, external mounting on the side panel is car­ried out in the same way as described in section 5.3.4 "External mounting of the cooling unit". However, please note the following differences: – Six threaded bolts are required for installation, rather
than four.

5.3.6 Partial internal mounting of the cooling unit

At the front of the cooling unit, pull the top louvred grille away from the mounting clips on the cover, and place or lay it down somewhere safe.
Fig. 13: Threaded bolts at rear
Key
1 Threaded bolts (6x) 2 Rear of cooling unit
Fig. 14: Remove the top louvred grille
Key
1Mounting clip 2Cover 3 Top louvred grille 4 Infill panel on cooling unit
Flip open the bottom louvred grille below the infill pan-
el.
Release the two stays in the hinge mechanism at the top from the brackets attached to the cover of the cooling unit.
– The unit with the threaded bolts is lowered into the rel-
evant holes, rather than on the mounting cut-out.
– No fastening clamps are fitted into the rear of the unit.
14 Rittal enclosure cooling unit
Fig. 15: Attachments on hinge mechanism
Key
1Cover 2 Stays in hinge mechanism 3 Bracket 4 Bottom louvred grille
5 Installation
Fig. 17: Remove the infill panel
Key
1 Mounting clips 2Cover 3 Infill panel
On the rear of the display, disconnect both of the con-
nectors (PE conductor and connection) and remove the infill panel completely from the cooling unit.
EN
Pull the bottom louvred grille forwards out of its hold-
ers, and place or lay it down somewhere safe.
Fig. 16: Bottom holders of louvred grille
Key
1 Bottom louvred grille 2Holders
Gently pull the infill panel including display forwards to release it from the mounting clips on the cover.
Fig. 18: Connection point on the rear of the cooling unit
Key
1 Connection point
Place the infill panel somewhere safe.
 
Carefully push the connector including connection ca­ble inwards through the cable gland in the cover.
Fig. 19: Cable gland in the cover
Key
1Cover 2 Cable gland
Rittal enclosure cooling unit 15
5 Installation
EN
Caution! The cooling unit will only be stable as long as the cover and chassis are con­nected. For this reason, be sure to brace the chassis, in particular, to prevent it from falling over before removing the cover.
Loosen the four threaded bolts in the corners of the cover which connect the cover to the chassis.
Carefully pull the cover forwards (approx. 5 cm) from the chassis. The PE conductor connection between the cover and the chassis is located on the right-hand side, approx­imately halfway up.
Fig. 21: Clip on the top edge of the chassis
Key
1Chassis 2 Clip in chassis 3 Seal
Lift up the chassis, preferably with a lifting eye using
suitable lifting gear, and insert it into the mounting cut­out in the door or side panel of the enclosure from the inside with the edge fold at the bottom of the chassis.
If transportation by crane is not possible, lift the chas­sis into the mounting cut-out in the same way using the handle.
Fig. 20: PE conductor connection (viewed from behind)
Key
1 PE conductor connection, cover 2 PE conductor connection, chassis
Pull the flat-pin connector of the PE conductor off in-
wards, preferable on the chassis.
Remove the cover completely from the chassis, and place or lay it down somewhere safe. There is a clip prefitted to the top edge of the chassis on the front. This clip will later prevent the chassis from falling out of the mounting cut-out before it is properly secured with the threaded bolt.
Fig. 22: Edge fold at bottom of chassis
Key
1 Edge fold on chassis (towards cover) 2 Outside of enclosure door
Push the chassis into the mounting cut-out at the top until the clip behind the cut-out latches home.
16 Rittal enclosure cooling unit
Fig. 23: Clip on the top edge of the chassis
Key
1 Outside of enclosure door 2 Clip in chassis
Make sure that the clip behind the cut-out is fully
snapped in towards the top.
5 Installation
Slide the flat-pin connector of the PE conductor into place, and ensure that the cover and chassis are con­nected.
Warning! The PE conductor which connects the
cover and the chassis must be connect­ed to both connectors in all cases. Oth­erwise, there is a risk of injury from electric shock if the unit connection was faulty or defective.
Place the cover fully over the chassis, and connect the cover and the chassis using the four threaded bolts in the corners of the cover.
EN
Fig. 24: Mounting of the wedge element
Key
1 Outside of enclosure door 2 Clip in chassis 3 Wedge element
Please also insert the wedge element from the exterior
up to the stop in order to fasten the clip in the upper position.
Fig. 25: Fully inserted wedge element
Set the cover down at the front near the chassis, and thread the connection cable of the display outwards through the cable gland in the cover.
Fig. 26: Cover on the chassis
Key
1 Threaded bolts (4x) 2 Outside of enclosure door 3Chassis 4Cover
Connect the display to the connector and insert the
entire infill panel on the cooling unit.
Place the bottom louvred grille onto the holders and secure the two stays at the top of the hinge mecha­nism into the brackets attached to the cover of the cooling unit.
Finally, replace the top louvred grille onto the cover.
If applicable, re-attach the door or side panel including cooling unit to the enclosure, if not assembled directly on the enclosure.
Rittal enclosure cooling unit 17
EN
5 Installation

5.3.7 Full internal mounting of the cooling unit

First, dismantle the top and bottom louvred grilles as well as the infill panel and the display in the same way as for partial internal mounting (see section 5.3.6 "Par­tial internal mounting of the cooling unit").
Cut the sealing tape in the dispatch bag to the re­quired length so that it can be placed all the way round the cover once.
Start sticking the sealing tape at the bottom edge, so that the joint between the two ends of the sealing tape is likewise on the bottom edge of the unit.
Carefully stick the sealing tape as close as possible to the edge of the cover.
On the front top edge of the cover, push the clip in­cluded with the supply into the relevant hole. This clip will prevent the cooling unit from falling out of the mounting cut-out later on before it is properly se­cured with the threaded bolt.
Fig. 28: Bracket at the bottom of the cover
Key
1 Bracket in mounting cut-out 2 Outside of door
Push the cooling unit into the mounting cut-out at the
top until the clip behind the cut-out latches home.
Fig. 27: Clip at top edge of cover
Key
1Cover 2 Clip on the cover
Lift up the cooling unit, preferably with a lifting eye us-
ing suitable lifting gear, and insert it into the mounting cut-out in the door or side panel of the enclosure with the two brackets at the bottom of the cover.
If transportation by crane is not possible, lift the cool­ing unit into the mounting cut-out in the same way us­ing the handle.
Fig. 29: Clip at top edge of cooling unit
Key
1 Outside of enclosure door 2 Clip in mounting cut-out
Mount the corner brackets onto the top two threaded
bolts from the outside.
18 Rittal enclosure cooling unit
Fig. 30: Corner brackets on top threaded bolts
Key
1 Threaded bolt 2Corner bracket
Mount the L-shaped brackets onto the bottom two threaded bolts from the outside.
5 Installation
EN
Fig. 31: L-shaped brackets on bottom threaded bolts
Key
1 L-shaped bracket 2 Threaded bolt
Next, working from the outside of the enclosure, se-
cure the four threaded bolts in the corners of the cover using the corresponding nuts from the dispatch bag.
Fig. 32: Mounting points on cooling unit
Key
1 Threaded bolts with nuts (4x) 2 Fastening clamps 3 Cooling unit behind enclosure door 4 Front of cooling unit (without louvred grille)
Insert the six fastening clamps into the cover of the
cooling unit. These fastening clamps ensure that the cooling unit is
directly in contact with the mounting cut-out of the en­closure door over the entire height.
Connect the display to the connector and fit the entire infill panel to the cooling unit.
Place the bottom louvred grilles onto the holders and secure the two stays of the top hinge mechanism into the brackets attached to the cooling unit cover.
Finally, replace the top louvred grille onto the cover.
If applicable, re-attach the door or side panel including cooling unit to the enclosure if not mounting directly on the enclosure.

5.3.8 Connect the condensate water discharge

There is a condensate water evaporator fitted in the ex­ternal circuit of the cooling unit. With an enclosure con­nected, this condensate water evaporator may typically evaporate condensate water volumes of up to 100 ml/h.
If larger quantities of condensate water are produced, a condensate water discharge hose may additionally be fitted. This hose allows condensate water to be routed out of the cooling unit pressurelessly. A suitable hose is available as an accessory from Rittal (see section 13 "Accessories").
Please follow the instructions given below:
Rittal enclosure cooling unit 19
5 Installation
EN
– The hose must be laid with an adequate and constant
gradient to prevent siphoning. – The hose must be laid without any kinks. – If extended, the cross-section of the hose must not be
reduced. – The hose should be routed to a drain or external con-
densate water evaporator by the customer.
Fig. 33: Connection for condensate water discharge hose
Key
1 Connection point 2 Hole in enclosure for hose
rated values may be taken from section 10 "Technical specifications" below.
– Low-noise potential equalisation must be guaranteed
with the mains connection.
– In order to prevent EMC interference, the unit should
be incorporated into the existing potential equalisation system with a larger cable cross-section (10 mm²).
Overvoltage protection and supply line load
– The unit does not have its own overvoltage protection.
Measures must be taken at the supply end by the switchgear manufacturer or operator to ensure effec­tive protection against lightning and overvoltage. The limits specified in standard UL/IEC/EN 60335-2-40 must be observed.
– The units are classified as overvoltage category III. The
mains voltage must not deviate by more than the tol­erance specified in section 10 "Technical specifica-
tions". – The discharge current may exceed 3.5 mA. – The units are high-voltage tested ex works. An addi-
tional high voltage test must only be carried out with a
DC voltage supply source (1500 VDC max.).
Connect a suitable hose to the condensate water dis­charge nozzle and secure using a hose clip.
Lay the hose as per the instructions above.

5.4 Electrical connection

5.4.1 Notes on electrical installation

When carrying out the electrical installation, it is impor­tant to observe all valid national and regional regula­tions as well as the provisions of the responsible power supply company.
– Electrical installation must only be carried out by a
qualified electrician who is responsible for compliance with the existing standards and regulations.
– The mains infeed and the signal cable must be of a
shielded design. The shielding can be connected to the earth lug provided in the connection area of the mains connector.
– All cables routed into the wiring compartment have to
be insulated for the maximum voltage of the power supply.
Connection data
– The connected voltage and frequency must corre-
spond to the ranges stated on the rating plate. The units support multiple voltages.
– The cooling unit must be connected to the mains via
an all-pole disconnect to overvoltage category III (IEC 61058-1).
– No additional temperature control may be connected
upstream of the unit at the supply end
– Install a pre-fuse to match the supply voltage used and
the specific electrical output of the cooling unit. The
Three-phase devices
– There is no need to observe a counterclockwise or
clockwise phase rotation when making the electrical
connection for inverter devices in the three-phase ver-
sion. The electronics incorporated into the devices au-
tomatically create the required phase rotation. – In three-phase devices, the absence of a phase is de-
tected, and the device is switched off. – Outgoing equipment is monitored by the inverter, and
deactivated in the event of a malfunction in the elec-
tricity supply.
Door limit switch
– Each door limit switch can only be assigned to one
cooling unit. – Several door limit switches may be operated in parallel
with one cooling unit. – The minimum cross-section for the connection cable
is 0.3 mm² for a cable length of 2 m. – The line resistance to the door limit switch must not
exceed a maximum of 50 Ω. – The maximum admissible line length is 10 m. – The door limit switch only supports a floating connec-
tion; no external voltages. – The contact of the door limit switch must be closed
when the door is open. – The safety extra-low voltage for the door limit switch is
provided by the internal power pack: Current approx.
5mA DC.
Connect the door limit switch to terminals 5 and 6 of
the signal connector.
20 Rittal enclosure cooling unit
Fig. 34: Connections at rear
Key
1 Connection for communication module (X3) 2 Connection for signal connector (X2) 3 Connection for mains connector (X1) 4 Bolt (here with fitted earth clamp)
Potential equalisation
If the unit is to be integrated into the customer's existing potential equalisation system for EMC reasons, a con­ductor with a larger nominal cross-section of at least 10 mm² can be connected to the potential equalisation connection point (attachment points) on wall-mounted cooling units. The connection point is labelled with the required switch symbol.
5 Installation
Fig. 36: Potential equalisation arrangement
Key
1 Ring terminal with PE conductor 2 Contact washer 3Washer 4 Screw
Note: According to the standard, the PE conductor
in the mains connection cable is not classed as an equipotential bonding conductor.

5.4.2 Install the power supply

Note: – The mains supply must be of a shielded
design with preferred EMC types in order to achieve the values required by the standard.
– The earth clamp may be used to contact
the cable shielding with the enclosure in­side the connection box (fig. 34, item 4).
Remove the mains connector from the dispatch bag and connect to the mains as shown on the connection diagram (fig. 37 or fig. 38).
EN
Fig. 37: Circuit diagram SK 3186930 and SK 3187930
Fig. 35: Connection point for potential equalisation
Key
1 Connection point
Attach the potential equalisation to the unit's connec-
tion point using the screw, washer and contact wash­er.
Rittal enclosure cooling unit 21
EN
5 Installation
Fig. 38: Circuit diagram SK 3188940 and SK 3189940
There is also a cover for the connection box included in the dispatch bag.
Insert the EMC cable gland included with the supply into the openings in the cover to ensure adequate strain relief for the connection cable.
Close the connection box with the cover.
Cover any unused openings in the cover with sealing bungs.
When connecting the cooling unit in accordance with NFPA 70 (NEC):
Use a conduit fitting instead of the cable gland.
Use copper conductors only to connect the supply ca­ble to the mains connector.
Micro-USB interface
A micro-USB interface is located on the front, to the right of the display. A tablet or laptop may be connected here for easy configuration of the unit.
Connect a tablet or laptop with installed RiDiag soft-
ware to the micro-USB interface. No other USB devices will be detected on this connec-
tion.
RS 485 interface
An RS 485 interface is located on the rear of the connec­tion box. The communication module with which you can connect the cooling unit to a monitoring system (Rittal CMC), may be connected here.
Connect the communication module (available as an
accessory) to the RS 485 interface.
Note: A direct connection to the cooling unit via the
RS 485 interface is not possible.
NFC interface
The cooling unit may be accessed with a smartphone app via the integral NFC interface. Access is only possi­ble with the app supplied by Rittal.

5.4.3 Connect the alarm relays

System messages from the cooling unit may be output to an external signal source via two floating relay out­puts.
Note: The factory setting of the relay outputs in their
de-energised state is NO (Normally Open).
Connect a suitable connection cable to the connec­tion terminals 1 (Alarm K1) and/or 3 (Alarm K2) of the signal connector (X2).
Configure the alarm relays you wish to use to output error messages (see section 7.4.2 "Alarm relays").
AC cos φ = 1
I max. = 2 A U max. = 250 V
Tab. 2: Contact data

5.4.4 Interfaces

The cooling unit has the following interfaces for commu­nicating with external systems:
– Micro-USB interface on the front – RS 485 interface on the rear –NFC interface
22 Rittal enclosure cooling unit
6 Commissioning
Note: The oil must collect in the compressor in or-
der to ensure adequate lubrication and cool­ing. For this reason, do not operate the cooling unit for at least 30 minutes after as­sembling the equipment.
Observe the aforementioned waiting period of at least 30 minutes before commissioning the unit after as­sembly.
Next, switch on the voltage supply to the cooling unit.
The Rittal logo will initially appear on the display, fol­lowed a short time later by the start screen.
You can now make your individual settings on the unit, e.g. set the temperature or assign the network identi­fier, etc. (refer to chapter 7 "Operation").
Note: It is not necessary to carry out leak or pres­sure tests on the cooling unit prior to com­missioning. Rittal has already done this in the factory.

6 Commissioning

EN
Rittal enclosure cooling unit 23

7 Operation

EN
7Operation

7.1 General

The cooling unit is equipped with a touch function dis­play for making basic settings and displaying error mes­sages. This is an industrial-grade touch display which is pressure-sensitive and may therefore be operated with gloves.
As well as operating directly on the cooling unit itself, there is also a smartphone app available. This offers al­most the same functions as the actual display, and ad­ditionally provides extended explanations of error mes­sages, as well as the option of contacting the Rittal Ser­vice team directly.

7.2 Layout of the display

The display is divided into a top section on a dark back­ground, and a bottom section with the menu bar. This layout is always identical, but the content of the two sec­tions will vary according to the menu selected.

7.2.1 Start screen

The start screen is always displayed while the cooling unit is in normal operation, provided there are no error messages.
Item Description Possible icons
5 USB connection (if
connected)
6 Self-test (if initiated)
7 NFC connection (max.
120 seconds after con­necting)
8 Type of cooling
9 Control based on ...
10 External sensor
11 Information menu
12 System messages
(where applicable)
13 Service icon (if re-
quired)
Fig. 39: Layout of the start screen
Key
Item Description Possible icons
1 Internal temperature
display (2-digit °C/3­digit °F)
2 EER scale: Range
0...20 / current average EER value of the last 24 hours
3 Ti scale: Range 20 ...60
/ value: Average enclo­sure internal tempera­ture of the last 24 hours
4 Display temperature
unit
Numbers from 0-9
14 Configuration
Tab. 3: List of all icons with descriptions
Type of cooling
The current form of cooling is indicated by one of the fol­lowing four icons.
Symbol Parameters
Cooling in compressor mode without support from the heat pipe
Cooling in compressor mode with support from the heat pipe
Cooling via the heat pipe only
No cooling
Tab. 4: Possible icons for the current type of cooling

7.2.2 Changing a parameter value

If a parameter value is changed, the display including the menu bar will also change.
Tab. 3: List of all icons with descriptions
24 Rittal enclosure cooling unit
Fig. 40: Screen for changing a parameter value
Key
1Main screen 2Control bar
The currently selected parameter value is displayed in the centre of the main screen. To change this value, you always proceed in the same way, as described below with the example of adjusting the set temperature:
On the start screen, click on the "Configuration" but­ton.
Enter the PIN to gain access to the lower-level screen pages of the "Configuration" zone.
"22" is the default PIN.
Click on the "Temperature" symbol.
Click on the "Control mode" symbol.
Select your preferred control mode from the display.
Change the setting to the required temperature using the "Up" and "Down" arrows.
Alternatively, you can also select the one of the dis­played higher or lower values directly.
Finally, confirm the set value with "OK".
Exit this screen page with the "Back" button.

7.3 Information menu

Click on the "Information" symbol to display a list of lower-level screen pages.
Symbol Parameters
7 Operation

7.3.1 Temperature information

Click on the "Temperature information" symbol. The ambient temperature and internal temperature are
displayed, in each case as an average for the last 24 hours of operation.
Symbol Parameter
Ambient temperature Average ambient temperature (external tem­perature) over the last 24 hours of operation.
Internal temperature Average internal temperature over the last 24 hours of operation.
Tab. 6: "Temperature information" zone

7.3.2 Device information

Click on the "Device information" symbol. A list of general information about the device will be
displayed.
Page through the list using the "Up" and "Down" ar­rows.
Symbol Parameter
Serial number
Production date YYYY-MM-DD
Hardware Release x.xx.xx
Firmware Release x.xx.xx
Software Release x.xx.xx
EN
Temperature information
Device information
Efficiency information
Tab. 5: "Information" zone
Tab. 7: "Device information" zone
Rittal enclosure cooling unit 25
Last updated YYYY-MM-DD
Last serviced YYYY-MM-DD
Customer device name Name assigned to the cooling unit by the cus­tomer. This title can be assigned using the RiDiag software or the Blue e+ app to distin­guish between individual units.
Current control mode
7 Operation
EN
Symbol Parameter
If the unit is configured as a "slave": Slave num­ber.
Tab. 7: "Device information" zone

7.3.3 Efficiency information

Click on the "Efficiency information" symbol. The average energy efficiency ratio (EER) for the last
24 hours of operation will be displayed. The energy ef­ficiency ratio is the ratio of the cooling output generat­ed to the electrical power used.
Symbol Parameter
Efficiency information Average energy efficiency ratio (EER) of the last 24 hours of operation.
Tab. 8: "Efficiency information" zone

7.4 Configuration menu

Click on the "Configuration" symbol. A screen page will appear asking you to enter the PIN
in order to access the lower-level screen pages.

7.4.1 Temperature

Click on the "Temperature" symbol to display a list of
lower-level screen pages.
Symbol Parameter
Change unit Set the unit "°C" or "°F"
Control mode
Alarm limit Temperature limit which will trigger an alarm message if exceeded.
Tab. 10: "Temperature" zone
Unit
All temperature values for the unit may be displayed ei­ther in degrees Celsius "°C" or degrees Fahrenheit "°F".
Click on the "Change unit" symbol.
Change the required unit ("°C" or "°F") using the "Up"
or "Down" arrows.
Confirm your entry with "OK".
Note: "22" is preset in the factory as the default
PIN.
For the first digit, page through the digits "0" to "9" us­ing the "Up" and "Down" arrows until the required digit appears in the box.
Confirm your selection with "OK".
For the second digit, once again page through the dig­its "0" to "9" using the "Up" and "Down" arrows until the required digit appears in the box.
Confirm your selection with "OK".
A list of lower-level screen pages will be displayed.
Symbol Parameter
Temperature Settings for set temperature and control mode
Alarm relay Settings for the alarm relays.
Display language Choice of language for display texts.
Self-test Perform a self-test.
Tab. 9: "Configuration" zone
Control mode
The cooling unit is able to control cooling output accord­ing to one of the following two temperature values: – Internal temperature: The temperature at which air
is drawn out of the enclosure into the cooling unit. – External sensor: The temperature measured with an
external temperature sensor at a so-called hot spot in
the enclosure.
Click on the "Control mode" symbol.
The setpoint for the currently set control mode is dis-
played.
Choose your preferred control mode by selecting it
from the display:
Symbol Parameter
Internal temperature
External sensor
Tab. 11: "Control mode" zone
The corresponding symbol for the chosen control mode is likewise displayed on the overview page.
Note: The external temperature sensor is available
as accessory from Rittal.
26 Rittal enclosure cooling unit
Change the setpoint using the "Up" and "Down" ar­rows or select the required temperature directly.
Setting range: 20°C (68°F)…50°C (122°F) Factory setting: 35°C (95°F)
Confirm your entry with "OK".
Symbol Parameters
Normally Open Switch the alarm relay as a normally open con­tact.
7 Operation
EN
Alarm limit
This limit is used for an alarm message. The set value must therefore be at least 3 K and up to a maximum of 15 K above the actual setpoint to which the cooling unit is set. For example:
– Setpoint: 35°C (95°F) – Alarm limit min.: 38°C (100°F) – Alarm limit max.: 50°C (122°F) The setpoint must likewise be modified accordingly if the
control mode is changed.
Click on the "Alarm limit" symbol.
Change the setpoint using the "Up" and "Down" ar­rows or select the required temperature directly (Fac­tory setting: 38°C (100°F)).
Confirm your entry with "OK".

7.4.2 Alarm relays

There are two floating relay outputs in the connection box on the rear of the unit, which may be used to output system messages from the cooling unit to an external signal source (see section 5.4.3 "Connect the alarm re­lays"). The relay outputs may be configured here.
Click on the "Alarm relay" symbol to display a list of lower-level screen pages.
Symbol Parameter
Normally Closed Switch the alarm relay as a normally closed contact.
Tab. 13: Switch logic of the alarm relay
Note: The factory setting of the relay outputs in their
de-energised state is NO (Normally Open).
List of functions
This is where you specify which error messages should lead to switching of the respective relay output.
Click on the "Relay 1" or "Relay 2" symbol, and select the alarm relay to which you wish to assign a function.
From the list of errors, select the function which should cause the previously selected relay output to switch.
If applicable, assign further functions to the relay out­put, and the output will then be switch if at least one of the assigned functions leads to an error message.
Confirm your entry with "OK".
If applicable, configure the other relay output with oth­er functions.
Symbol Parameter
Assign relay 1
Change NO/NC Switch the alarm relay as a normally closed or normally open contact.
List of functions Allocation of a function to the respective alarm relay.
Tab. 12: "Alarm relay" zone
Note: For the factory setting of alarm relay alloca-
tion see section 7.6 "List of system messag­es" (Tab. 15).
Change NO/NC
The switch logic of the relay output, i.e. whether it is to be used as a normally closed or normally open contact, may be set here.
Click on the "Change NO/NC" symbol.
Choose your preferred switch logic by selecting it from the display.
Confirm your entry with "OK".
Assign relay 2
Tab. 14: List of functions

7.4.3 Language settings

All the unit's displays may be shown in different languag­es. The languages "English" and "German" are available as standard on the unit. Other languages may be in­stalled using the RiDiag software or with the aid of an on­line tool available on the Rittal website.
Click on the "Display language" symbol.
Page through to the required language using the "Up" and "Down" arrows.
Confirm the chosen language with "OK".
The language will change over immediately, and all menu displays will appear in the chosen language.

7.4.4 Self-test

In the event of a malfunction in the unit which fails to pro­duce an error message, it may be useful to check the key functions of all components with a self-test. You
Rittal enclosure cooling unit 27
7 Operation
EN
may continue to operate the unit as normal while the self-test is being carried out.
Click on the "Self-test" symbol.
Confirm the start of the self-test with "OK".
While the self-test is being carried out, a progress indi­cator will appear on the display. Once the test is com­plete, either the message "Unit OK" or "Check error" will be displayed.
If applicable, use the error list to determine which mal­function applies.

7.5 System messages

We distinguish between three different types of system messages on the unit:
– Malfunctions –Errors – Servicing If a corresponding message applies, the "System mes­sages" symbol is displayed in the menu bar (fig. 39, item 13). A list of all possible system messages may be found in section 7.6 "List of system messages".
Click on the "System messages" symbol.
A list of all active system messages will be displayed. The individual messages are arranged in ascending or­der as they occur according to the above three catego­ries.
If an error message can only be resolved by the Rittal Service team, the "Service" symbol will additionally appear after the error message.
In such cases, please contact Rittal Service (see sec­tion 14 "Customer service addresses").

7.5.1 Occurrence of a malfunction

In the event of a malfunction, the start screen will be su­perimposed with an error message.
If the malfunctions cannot be resolved by the operator himself, the Service symbol will additionally be displayed (Fig. 39, item 14).
Contact the Rittal Service team if you are unable to re-
solve the malfunction yourself (see section 14 "Cus-
tomer service addresses").

7.5.2 Display in case of errors

If errors have occurred or servicing is required, the "Sys­tem messages" symbol will appear in the menu bar (see section 7.5 "System messages").
Most system messages are reset automatically once the fault has been resolved.
Fig. 42: Screen showing error messages
Key
1 "Errors" menu 2 Error message
If an error message applies that cannot be resolved by the operator himself and which is not reset automatical­ly, the "Service" symbol will appear after the error mes­sage and in the control bar next to the symbol for system messages (fig. 43, item 2).
Fig. 43: Screen showing error messages
Fig. 41: Screen in the event of a malfunction
Key
1Superimposed 2 Menu bar in red
The start screen is superimposed with a message in the following three cases:
1. There is a malfunction on the unit itself.
Key
1 "Errors" menu 2 Error message 3 "Return" button
Contact Rittal Service (see section 14 "Customer ser-
vice addresses").
Acknowledge the error message by pressing the "Re-
turn" button.
2. There is a malfunction on one of the units in the mas­ter-slave combination.
3. The enclosure door is open and a connected door contact is emitting a corresponding message.
28 Rittal enclosure cooling unit
7 Operation

7.6 List of system messages

The applicable error messages are displayed with the
Contact details for the Rittal Service team can be found in section 14 "Customer service addresses".
corresponding symbol in the Errors list (see section 7.5 "System messages"). Extended information for resolv­ing individual faults may be found in this section.
System message Alarm relay output
(factory setting)
Door open Please close the enclosure door and check the door contact switch.
Interior temperature too high
Change filter The filter mat in your cooling unit is dirty. Please replace or clean the filter
Clean condenser The condenser in your cooling unit is dirty. Please remove the top lou-
The measured interior temperature exceeds the set alarm limit for your
Troubleshooting measures/solutions
The error message will terminate automatically approximately 30 sec­onds after it has been resolved.
cooling unit. Please check any maintenance and error messages, and check the rat­ing of your cooling unit. For any further questions, please contact Rittal Service directly.
mat and confirm this by pressing reset in the list of system messages on the cooling unit display.
vred grille and clean the heat exchanger, e.g. using compressed air. The error message will terminate automatically approximately 30 sec­onds after it has been resolved.
EN
Air routing EC 1 The air inlet or outlet in the external circuit is blocked. Please remove the
blockage and ensure that minimum distances from the air inlet or outlet are observed.
Air routing IC The air inlet or outlet in the internal circuit is blocked. Please remove the
blockage and ensure that minimum distances from the air inlet or outlet to components inside the enclosure are observed.
EEV defective A malfunction has been detected in the electronic expansion valve.
Please contact your Rittal Service.
External temperature too high
Refrigerant shortage 2 Your cooling unit is reporting a lack of cooling in the active refrigerant cy-
Condensate warning 1 Please check whether the condensate water drain of your cooling unit is
Your cooling unit is being operated outside of the admissible ambient
temperature. Please ensure that the ambient temperature does not ex­ceed the admissible range (-20°C…+60°C).
cle. Please contact the Rittal Service team immediately. The system mes­sage will need to be acknowledged manually once the cause has been rectified.
blocked, and remove the blockage. If you are unable to resolve the fault, please contact your Rittal Service team.
Tab. 15: Error messages
Rittal enclosure cooling unit 29
7 Operation
EN
System message Alarm relay output
(factory setting)
Internal fan Alarm 1 1 The fan in the internal circuit of your cooling unit is blocked. Please check
Internal fan Alarm 2 1 The fan in the internal circuit of your cooling unit is defective. Please re-
External fan Alarm 1 1 The fan in the external circuit of your cooling unit is blocked. Please check
External fan Alarm 2 1 The fan in the external circuit of your cooling unit is defective. Please re-
Inverter cooler The cooling body of the inverter in your cooling unit is dirty. Please re-
Troubleshooting measures/solutions
if you can see a blockage and remove it. If no blockage is visible, please replace the fan in the internal circuit. The required spare part may be or­dered directly from Rittal using the Blue e+ app. Please use the contact form "Generate service order".
place the fan in the internal circuit. The required spare part may be or­dered directly from Rittal using the Blue e+ app. Please use the contact form "Generate malfunction report".
if you can see a blockage and remove it. If no blockage is visible, please replace the fan in the external circuit. The required spare part may be or­dered directly from Rittal using the Blue e+ app. Please use the contact form "Generate service order".
place the fan in the external circuit. The required spare part may be or­dered directly from Rittal using the Blue e+ app. Please use the contact form "Prepare malfunction report".
move the filter grille and the cover at the front and clean the cooling body, e.g. using compressed air. The error message will terminate automatically approximately 30 sec­onds after it has been resolved.
Compressor defective 2 The compressor in your cooling unit is reporting a malfunction. Please
contact the Rittal Service team immediately.
Sensor xx defective 1 Sensor xx in your cooling unit is reporting a sensor failure. Please contact
the Rittal Service team.
Ext. sensor missing 1 The external sensor is not connected or has a malfunction. Please check
the connection or select another control mode.
Check voltage 1 You are operating your cooling unit outside of the admissible voltage
ranges. Please check the power supply to the cooling unit and observe the specifications on the rating plate. With a three-phase infeed, please also check that all three phases are correctly connected.
Electronic fault 2 The electronics in your cooling unit are reporting an electronic fault.
Please contact the Rittal Service team.
Check parameters Due to an error, the cooling unit has been reset to the factory defaults.
Please check the current messages or contact your Rittal Service team.
Inverter fault 2 The inverter in your cooling unit is reporting a malfunction. Please contact
the Rittal Service team.
Tab. 15: Error messages
30 Rittal enclosure cooling unit
7 Operation
System message Alarm relay output
(factory setting)
Emergency operation ac­tive
Compressor phase 2 The compressor in your cooling unit is reporting a malfunction. Please
Overload 1 Please check the rating of your cooling unit. For any further questions,
Alarm active cooling The active cooling function of your unit is defective. Please contact the
Tab. 15: Error messages
Due to a previous error your cooling unit is only operating with a perfor-
Troubleshooting measures/solutions
mance of 50%. Please remedy this error and/or contact your Rittal Ser­vice team.
contact your Rittal Service team.
please contact your Rittal Service team directly.
Rittal Service team immediately, and/or check the rating of your cooling unit.
EN
Rittal enclosure cooling unit 31
EN

8 Inspection and maintenance

8 Inspection and maintenance
8.1 Safety instructions for maintenance
work
The unit must be opened in order to carry out mainte­nance work. There is a risk of injury from electric shock.
Switch off the power supply before carrying out main­tenance work.
Secure the power supply to prevent it being switched back on accidentally.
Disconnect the electrical connection cable of the cool­ing unit from the power supply at the connection box.
Wait at least five minutes before handling the unit. Only then will the capacitors built into the unit have dis­charged themselves.
When handling the enclosure, be aware of any ex­posed power sources, where applicable.
If possible, disconnect the entire enclosure from the
power. There is also a risk of injury from sharp edges, such as the louvres of the heat exchanger.
Wear cut-resistant gloves for all maintenance work. After removing the cover, there is a risk of burn injuries
from hot surfaces on the components inside the unit.
Before carrying out any work on the interior of the unit,
allow it to cool down for at least ten minutes.

8.2 Notes on the refrigerant circuit

The cooling unit is filled with the amount of refrigerant re­quired at the factory, checked for leaks, and subjected to a functional test run. The refrigerant circuit is designed in the form of a maintenance-free, hermetically sealed system. For this reason, the operator should not carry out any maintenance work on the refrigerant circuit.
Caution! Maintenance tasks on the refrigerant
circuit must only be undertaken by a qualified refrigeration specialist.
Any stubborn, oily stains may additionally be removed using a non-flammable detergent, such as degreaser.
Caution! Never use flammable liquids for cleaning
the unit.
The installed maintenance-free fans are mounted on ball bearings, protected against moisture and dust, and fit­ted with a temperature monitor.
Rittal recommends that the cooling unit fans should be checked e.g. for unusual running noises after around 40,000 operating hours.

8.4 Compressed air cleaning

8.4.1 Dismantling a unit with full internal mount­ing
Cooling units with full internal mounting in the enclosure must first be completely removed from the mounting cut-out before cleaning with compressed air.
Remove the cooling unit from the rack mount in the re­verse order as for installation (see section 5.3.7 "Full internal mounting of the cooling unit")
Hold the threaded bolts in place with a screwdriver in order to loosen the nuts.
Then dismantle the unit as described in section 8.4.2 "Dismantling the unit".

8.4.2 Dismantling the unit

Note: In principle, the unit is dismantled in the re-
verse order from assembly.
At the front of the cooling unit, pull the top louvred grille away from the mounting clips on the cover, and place or lay it down somewhere safe.

8.3 Maintenance work on the cooling unit

If there is visible dirt present, the components in the out­er air circuit should be cleaned using a vacuum cleaner or compressed air.
Note: The maintenance intervals given below de-
pend to a large extent on the level of contam­ination in the ambient air. For heavily contaminated air, the maintenance intervals will be reduced accordingly.
Clean the cooling unit inside and out at least every 5,000-8,000 operating hours as described in section
8.4 "Compressed air cleaning".
32 Rittal enclosure cooling unit
Fig. 44: Remove the top louvred grille
Key
1 Mounting clip 2Cover 3 Top louvred grille 4 Infill panel on cooling unit
Flip open the bottom louvred grille below the infill pan-
el.
Release the two stays in the top hinge mechanism from the brackets attached to the cover of the cooling unit.
8 Inspection and maintenance
Fig. 45: Attachments on hinge mechanism
Key
1Cover 2 Stays in hinge mechanism 3Bracket 4 Bottom louvred grille
Pull the bottom louvred grille forwards out of its hold-
ers, and place or lay it down somewhere safe.
EN
Fig. 46: Bottom holders of louvred grille
Key
1 Bottom louvred grille 2Holders
Gently pull the infill panel, including display, forwards to release it from the mounting clips on the cover.
Rittal enclosure cooling unit 33
8 Inspection and maintenance
EN
Fig. 47: Remove the infill panel
Key
1 Mounting clips 2Cover 3 Infill panel
On the rear of the display, disconnect both of the con-
nectors (PE conductor and connection) and remove the infill panel completely from the cooling unit.
Caution! The cooling unit will only be stable as long as the cover and chassis are con­nected. For this reason, be sure to brace the chassis, in particular, to stop it falling over before removing the cover.
Loosen the six fixing clamps used to connect the cool-
ing unit and enclosure door or side panel. You may wish to use a screwdriver to press the stays
back and remove the fixing clamps.
Fig. 48: Connection point on rear of cooling unit
Key
1 Connection point
Place the infill panel somewhere safe.
 
Carefully push the connector including connection ca­ble inwards through the cable gland in the cover.
Fig. 50: Loosen the fixing clamps
Key
1 Enclosure door or side panel 2 Opening for screwdriver in cooling unit 3Stays 4 Fixing clamps
Caution! After removing the cover, there is a risk
of burn injuries from hot component sur­faces inside the unit.
Allow the unit to cool down for at least ten minutes be-
fore removing the cover. This should allow hot surfaces inside the unit to cool
down sufficiently.
Loosen the four threaded bolts in the corners of the cover which connect the cover to the chassis.
Carefully pull the cover forwards (approx. 5 cm) from the chassis. The PE conductor connection between the cover and the chassis is located o the right-hand side, around half-way up.
Fig. 49: Cable gland in cover
Key
1Cover 2 Cable gland
34 Rittal enclosure cooling unit
Fig. 51: PE conductor connection (viewed from behind)
Key
1 PE conductor connection, cover 2 PE conductor connection, chassis
Disconnect the PE conductor's flat-pin connector from the inside, preferably on the chassis.
Remove the cover completely from the chassis, and place or lay it down somewhere safe.
Dismantling of the unit is now complete.
8 Inspection and maintenance
EN
8.4.3 Cleaning the components with com­pressed air
After removing the cover from the unit, you will be able to access the components in the outer circuit, particu­larly the condenser, the condenser fan and the com­pressor chamber.
Wear cut-resistant gloves when cleaning with com­pressed air, so as to avoid injuries caused by sharp edges inside the unit.
When cleaning the components with compressed air, blow dirt sideways out of the cooling unit.
Alternatively, use a suitable vacuum cleaner to clean all components.

8.4.4 Re-assembling the cooling unit

Once the cleaning work is complete, the cooling unit must be sealed and, in the case of full internal mounting, fitted back into the mounting cut-out.
First, completely re-assemble the cooling unit. It is assembled in the reverse order from dismantling
(see section 8.4.2 "Dismantling the unit"), in the same way as for the initial assembly (see section 5.3 "As­sembly procedure").
For full internal mounting of the cooling unit, re-insert it into the mounting cut-out.
Make the electrical connection for the cooling unit.
Rittal enclosure cooling unit 35
EN

9 Storage and disposal

9 Storage and disposal
Note: When storing the cooling unit, please ob-
serve the temperature range given in the technical specifications.
Store the cooling unit in the appropriate position for transport.
The closed refrigerant circuit contains refrigerant and oil which must be properly disposed of for the sake of the environment. Facilities for disposal are available at the Rittal plant or a specialist company. Give us a call (see section 14 "Customer service addresses").
36 Rittal enclosure cooling unit

10 Technical specifications

10 Technical specifications
Technical specifications SK 3186930 SK 3187930 SK 3188940 SK 3189940
General specifications
Model number SK3186930 SK3187930 SK3188940 SK3189940
Dimensions (width x height x depth) [mm] 450 x 1600 x 294 450 x 1600 x 393
Cooling output
EN
Total cooling output Pc to EN 14511 [kW]
Sensible cooling capacity Pc to EN 14511 [kW]
Power consumption Pel to EN 14511 [kW]
Energy efficiency ratio (EER) L35 L35 3,5 2,63 3,46 2,64
Electrical specifications
Rated voltage [V, ~], tolerance
Rated frequency [Hz] 50…60
Rated insulation voltage Ui [V] 500
Rated output [kW] 0,73 1,05 1,30 2,20
Rating of overcurrent protective device [A] 15
Minimum circuit ampacity [A] 15
L35 L35 2,00 2,60 4,20 5,80
L35 L50 1,29 1,82 3,02 4,20
L35 L35 2,00 2,60 4,20 5,30
L35 L35 0,57 0,99 1,21 2,20
L35 L50 0,60 0,94 1,28 2,20
+10%/
-10%
+5%/
-15%
110…240, 1
380…480, 3
Input ampere range [A] 1,3@110 V –
7,3@380 V
Pre-fuse T [A] (Time delay fuse type: CCMR)
Overvoltage category III
Level of contamination III
Protection category to IEC 60 529
Internal circuit IP 55
External circuit IP 24
NEMA Type 12
Electromagnetic compatibility
Immunity to interference For industrial areas to EN 61000-6-2
Emitted interference
Tab. 16: Technical specifications Blue e+
For residential, business and commercial areas and small
11@110 V –
1,8@380 V
companies to EN 61000-6-3
2,3@380 V –
1,8@480 V
15
3,7@380 V –
2,94@480 V
Rittal enclosure cooling unit 37
10 Technical specifications
EN
Technical specifications SK 3186930 SK 3187930 SK 3188940 SK 3189940
Refrigerant circuit
Admissible pressure (PS) HP/LP [MPa] 2,4
Operating temperature range [°C] -20…+60
Heat pipe active mode [°C] 0…+60
Refrigerant cycle active mode [°C] +10…+60
Setting range set value [°C] +20…+50
Refrigerant identification R134a, Tetrafluorethane (CH2FCF3)
Refrigerant filling mass compression sys­tem/heat pipe system [g]
Other
Weight [kg] 55,2 72,4
Storage temperature range [°C] -40…+70
Noise pressure level Lp [dB(A)] <67 <70 <74
Further information
650/500 700/1050
Tab. 16: Technical specifications Blue e+
ü
38 Rittal enclosure cooling unit

11 List of spare parts

11 List of spare parts
Spare parts may be ordered directly from the Rittal web­site: – http://www.rittal.com/com_en/spare_parts
Select the item number of your unit.
Note: The components used are Rittal-specific components. We recommend using only original Rittal spare parts to ensure the guar­anteed unit properties (output).
EN
Fig. 52: Spare parts
Key
1 Compressor 5Condenser fan 10 Evaporator coil fan 15 Dispatch bag as accessories bag 20 Expansion valve 21 Coil for expansion valve 25 Filter dryer 30 PSA 40 I/O-board 41 Inverter 45 Louvred grille, top 46 Louvred grille, bottom 50 Infill panel 55 Display/controller 70 Temperature sensor kit 75 Cover 90 Evaporator coil 100 Condenser 101 Condensate water evaporator 102 Display cable
Rittal enclosure cooling unit 39
H
pressure-operated switch as pressostat
EN

12 Drawings

12 Drawings

12.1 Representation of mounting cut-outs

Fig. 53: Mounting cut-out Fig. 54: Mounting cut-out for 500 mm deep enclosure
40 Rittal enclosure cooling unit

12.2 Dimensions and installation depths

12 Drawings
EN
Fig. 55: Dimensions SK 3186930 and SK 3187930
Key
1 External mounting 2 Partial internal mounting 3 Full internal mounting
Rittal enclosure cooling unit 41
EN
12 Drawings
Fig. 56: Dimensions SK 3188940 and SK 3189940
Key
1 External mounting 2 Partial internal mounting
42 Rittal enclosure cooling unit
13 Accessories
As well as the components listed below, a detailed list of the entire range of accessories may be found on the website given in section 14 "Customer service address­es".
Item Model No.
Door limit switch SK 4127010
M12 eyebolt SK 4568000
Filter mats (polyurethane foam) SK 3285900
Metal filter SK 3285910
Condensate water hose SK 3301612
External temperature sensor SK 3124400
Tab. 17: List of accessories

13 Accessories

EN
Rittal enclosure cooling unit 43

14 Customer service addresses

EN
14 Customer service addresses
For technical queries, please contact: Phone: +49(0)2772 505-9052 E-mail: info@rittal.com Homepage: www.rittal.com
For complaints or service requests, please contact
your local Rittal organisation.
Argentina
Phone: +54 (11) 4760 6660 E-mail: service@rittal.com.ar
Australia
Phone: +61 (2) 95 25 27 66 E-mail: service@rittal.com.au
Austria
Phone: +43 (0) 599 40 -0 E-mail: service@rittal.at
Belarus
Please contact Lithuania. E-mail: service@rittal.lt
Belgium
Phone: +32 (9) 353 91 45 E-mail: service@rittal.be
Bosnia-Herzegovina
Please contact the headquarters in Germany. Phone: +49 (0) 2772 505 1855 E-mail: service@rittal.de
Brazil
Phone: +55 (11) 3622 2377 E-mail: service@rittal.com.br
Bulgaria
Phone: +359 (2) 8890055 E-mail: service@rittal.bg
Canada
Phone: +1 (905) 877 COOL 292 E-mail: service@rittal.ca
Chile
Phone: +56 2 9477 400 E-mail: info@rittal.cl
China
Phone: +86 800 820 0866 E-mail: service@rittal.cn
Columbia
Phone: +571 621 8200 E-mail: service@rittal.com.co
Costa Rica
Please contact Mexico.
E-mail: servicemx@rittal.com.mx
Croatia
Phone: +385 1 3455 256 E-mail: service@rittal.hr
Cyprus
Please contact the headquarters in Germany.
E-mail: service@rittal.de
Czech Republic
Phone: +420 234 099 068 E-mail: servis@rittal.cz
Denmark
Phone: +45 70 25 59 20 E-mail: info@rittal.dk
Dubai
Phone: +971 3416855 206 E-mail: service@rittal-middle-east.com
Ecuador
Please contact Brazil.
E-mail: service@rittal.com.br
El Salvador
Please contact Mexico.
E-mail: servicemx@rittal.com.mx
Estonia
Please contact Lithuania.
E-mail: service@rittal.lt
Finland
Phone: +358 9 413 444 50 E-mail: service@rittal.fi
France
Phone: +33 (1) 49836070 E-mail: service@rittal.fr
Germany
Phone: +49(0)2772 505-1855 E-mail: service@rittal.de
44 Rittal enclosure cooling unit
14 Customer service addresses
Greece
Phone: +30 210 271 79756 E-mail: service@rittal.gr
Guatemala
Please contact Mexico.
E-mail: servicemx@rittal.com.mx
Honduras
Please contact Mexico.
E-mail: servicemx@rittal.com.mx
Hong Kong
Please contact China.
E-mail: marvis.lun@rittal.com
Hungary
Phone: +36 1 399 800 E-mail: rittal@rittal.hu
Iceland
Please contact the headquarters in Germany.
E-mail: srj@sminor.is
Jordan
Please contact Dubai.
E-mail: service@rittal-middle-east.com
Kazakhstan
Please contact Lithuania.
E-mail: service@rittal.lt
Latvia
Please contact Lithuania.
E-mail: service@rittal.lt
Lebanon
Please contact Dubai.
E-mail: service@rittal-middle-east.com
Lithuania
Phone: +37 (0) 52105738 E-mail: service@rittal.lt
Luxembourg
Please contact the headquarters in Germany.
E-mail: services@dme.lu
EN
India
Phone: +91 (80) 33720783 E-mail: service@rittal-india.com
Indonesia
Please contact Singapore.
E-mail: service@rittal.com.sg
Iran
Please contact Dubai.
E-mail: service@rittal-middle-east.com
Ireland
Phone: +353 (59) 9 18 21 00 E-mail: sales@rittal.ie
Israel
Phone: +972 (4) 6275505 E-mail: service@rittal.co.il
Italy
Phone: +39 (02) 95 930 308 E-mail: service@rittal.it
Morocco
Please contact the headquarters in Germany.
E-mail: service@rittal.ma
Malaysia
Please contact Singapore.
E-mail: service@rittal.com.sg
Macedonia
Please contact Austria.
E-mail: siskon@mt.net.mk
Mexico
Phone: +52 (55) 59 5369 E-mail: servicemx@rittal.com.mx
Netherlands
Phone: +31 (316) 59 1692 E-mail: service@rittal.nl
New Zealand
Please contact Australia.
E-mail: service@rittal.com.au
Japan
Phone: +81 280 87 5130 E-mail: service@rittal.co.jp
Rittal enclosure cooling unit 45
Norway
Phone: +47 64 85 13 00 E-mail: service@rittal.no
14 Customer service addresses
EN
Oman
Please contact Dubai. E-mail: service@rittal-middle-east.com
Pakistan
Please contact Dubai. E-mail: service@rittal-middle-east.com
Peru
Please contact Brazil. E-mail: service@rittal.com.br
Philippines
Please contact Singapore. E-mail: service@rittal.com.sg
Poland
Phone: +48 (22) 724 2784 E-mail: service@rittal.pl
Portugal
Phone: +351 256780210 E-mail: service@rittal.pt
Slovenia
Phone: +386 1 5466370 E-mail: service@rittal.si
Spain
Phone: +34 902 504 678 E-mail: service@rittal.es
South Africa
Phone: +27 (11) 609 82 94 E-mail: service@rittal.co.za
South Korea
Phone: +82 2 577 6525 114 E-mail: service@rittal.co.kr
Sweden
Phone: +46 (431) 442600 E-mail: service@rittal.se
Switzerland
Phone: +41 56 416 0690 E-mail: service@rittal.ch
Qatar
Please contact Dubai. E-mail: service@rittal-middle-east.com
Romania
Phone: +40 351 76 47 E-mail: service@rittal.ro
Russia
Phone: +7 (495) 775 02 30 E-mail: service@rittal.ru
Saudi Arabia
Please contact Dubai. E-mail: service@rittal-middle-east.com
Serbia
Please contact the headquarters in Germany. E-mail: sloba@vesimpex.co.yu
Singapore
Phone: +65 6309 7327 E-mail: service@rittal.com.sg
Taiwan
Phone: +886 (3) 3971745 18 E-mail: sales.info@rittal.com.tw
Thailand
Phone: +66 (2) 369 2896 99 13 E-mail: service@rittal.co.th
Turkey
Phone: +90 (216) 383 74 44 E-mail: servis@rittal.com.tr
Turkmenistan
Please contact Lithuania.
E-mail: service@rittal.lt
UK
Phone: +44 8448 006 007 E-mail: service.desk@rittal.co.uk
Ukraine
Phone: +38 (44) 536 9944 E-mail: service@rittal.com.ua
Slovak Republic
Phone: +421 2 5363 0651 E-mail: service@rittal.sk
46 Rittal enclosure cooling unit
USA
Phone: +1 800-477-4000, option 3 E-mail: rittal@rittal.us
Uzbekistan
Phone: Please contact Lithuania.
E-mail: service@rittal.lt
Venezuela
Please contact Brazil.
E-mail: service@rittal.com.br
Vietnam
Please contact Singapore.
E-mail: service@rittal.com.sg
14 Customer service addresses
EN
Rittal enclosure cooling unit 47
EN

15 Compact service information

15 Compact service information
Step See OK/comment
Assembly and connection
– Installation site requirements taken into
account
Assembly instructions
– Observe the relevant assembly instructions Section 5.3.1
– Condensate water discharge connected Section 5.3.8
– Electrical installation (overvoltage protection,
door limit switch)
Commissioning
Check the assembly – All attachments checked, filter mat fitted
Commissioning – At least 30 minutes after assembly Section 6
– Download the Blue e+ app to support
commissioning and subsequent operation
– Commissioning check carried out via Blue e+
app
Operation
– Check the device status during operation
using the Blue e+ app
Section 5.2
Section 5.4
– Read maintenance instructions and warnings
or fault messages using the Blue e+ app
Tab. 18: Quick installation check
For all other service enquiries:
Original spare parts Maintenance, warranty extensions (up to 5 years), ser-
vice contracts
– Enquire directly via Blue e+ app – http://www.rittal.com
Other service contacts worldwide Rittal International Service HUBs (see section 14 "Customer service address­es")
Tab. 19: Service contacts worldwide
– Enquire directly via Blue e+ app – http://www.rittal.com – Enquire at the relevant national company – http://www.rittal.com/de_de/service_contact/index.asp
48 Rittal enclosure cooling unit
Enclosures
Power Distribution
Climate Control
IT Infrastructure
Software & Services
RITTAL GmbH & Co. KG Postfach 1662 · D-35726 Herborn Phone +49(0)2772 505-0 · Fax +49(0)2772 505-2319 E-mail: info@rittal.de · www.rittal.com
2nd edition 10.2015 / ID no. 335286 / Drawing no. A05999100SK
Loading...