Abb./Fig./Fig. 11: Bedien- und Anzeigeelemente sowie Anschlüsse PDU metered/switched/managed / Ope-
Abb./Fig./Fig. 12: Bedien- und Anzeigeelemente sowie Anschlüsse Slave PDU managed / Operating and dis-
PDU international) / Blocage des câbles (la représentation montre le PDU international)
rating and display elements as well as connectors for PDU metered/switched/managed /
Organes de commande et de signalisation ainsi que raccordements pour PDU metered/
switched/managed
play elements as well as connectors for Slave PDU managed / Organes de commande et
de signalisation ainsi que raccordements pour Slave PDU managed
Rittal PDU international/PDU UK5
Abbildungen / Figures / Figures
Abb./Fig./Fig. 13: Website Netzwerkeinstellungen / Network settings web site / Interface WEB pour les
réglages réseau PDU metered/switched/managed
6Rittal PDU international/PDU UK
DE
Hinweise zur Dokumentation, Sicherheitshinweise, Produktbeschreibung
1Hinweise zur Dokumentation
Diese Installations- und Kurz-Bedienungsanleitung richtet sich an versiertes Fachpersonal und enthält
nur die wichtigsten Informationen zur Montage, Installation und Funktion der Stromverteilung
PDU international/PDU UK (nachfolgend PDU genannt).
1.1Mitgeltende Unterlagen
– Montage-, Installations- und Bedienungsanleitung Stromverteilung PDU international/PDU UK.
Sie ist unter www.rittal.de verfügbar und enthält die vollständigen anwendungsrelevanten Informationen
und technischen Daten zur PDU in Hinblick auf:
– Details zum elektrischen Anschluss
– Funktionen und Services
– Konfigurationsmöglichkeiten
– Detaillierte Bedienungsanweisungen
– Fehlerbehebung
Des Weiteren sind dort die Montage-, Installations- und Bedienungsanleitungen zu den Sensoren des
CMC III Systems verfügbar, die an der PDU angeschlossen werden können.
– Temperatursensor (7030.110)
– Temperatur-/Feuchtesensor (7030.111)
– Infrarot-Zugangssensor (7030.120)
– Vandalismussensor (7030.130)
2Sicherheitshinweise
– Montage und Installation des Geräts dürfen nur durch versiertes Fachpersonal erfolgen.
– Das Gehäuse der PDU darf nicht geöffnet werden.
– Die PDU darf nicht in Kontakt mit Wasser, aggressiven oder entzündbaren Gasen und Dämpfen kom-
men.
– Die PDU darf nur innerhalb der spezifizierten Umgebungsbedingungen betrieben werden (vgl.
Abschnitt 3.3).
DE
3Produktbeschreibung
3.1Funktionsbeschreibung
Die PDU ist eine Stromverteilung zum Einsatz in IT-Racks. Es gibt vier Ausführungsvarianten, die sich
folgendermaßen unterscheiden:
– PDU metered: Energiemessung an der Einspeisung je Phase, d. h. Leistungsbedarf eines gesamten
IT-Racks; ohne Schaltfunktion; mit Display und Netzwerkschnittstelle.
– PDU switched: Energiemessung an der Einspeisung je Phase, d. h. Leistungsbedarf eines gesamten
IT-Racks; mit Schaltfunktion je einzelnem Ausgangssteckplatz, Display und Netzwerkschnittstelle.
– PDU managed: Energiemessung und Schaltfunktion je einzelnem Ausgangssteckplatz; mit Display
und Netzwerkschnittstelle.
– Slave PDU managed: Energiemessung und Schaltfunktion je einzelnem Ausgangssteckplatz (analog
PDU managed); jedoch ohne Display und Netzwerkschnittstelle, mit CAN-Bus zum Anschluss an eine
CMC III Processing Unit (7030.000/.010 ab Softwareversion 3.13) oder PDU metered/switched/managed (ab Softwareversion 2).
3.2Bestimmungsgemäße Verwendung
Die PDU dient insbesondere zur Stromverteilung in IT-Racks.
Rittal Stromverteilung PDU international/PDU UK7
DE
Montagehinweise, Installation und Bedienung PDU metered/switched/managed
3.3Betriebsbedingungen
Die PDU darf nur unter folgenden Betriebsbedingungen betrieben werden:
Temperatur-Einsatzbereich:+0°C…+45°C
Feuchtigkeits-Einsatzbereich:10 %…95 % relative Feuchte, nicht kondensierend
Schutzart:IP 20 nach IEC 60 529
4Montagehinweise
Die Montage der PDU erfolgt mit Hilfe der im Zubehör beigelegten Halter. Die Montage kann generell
gleichermaßen vorne wie hinten und links wie rechts im IT-Rack erfolgen.
Hinweis:
Fa. Rittal empfiehlt, immer zunächst die Halter an der PDU und diese dann gemeinsam
im Schrank anzubringen, außer bei der verdeckten Montage (Abb. 8), bei der dies nicht
möglich ist. Hierdurch sind die Abstände zwischen den Haltern und somit die Befestigungspunkte im Schrank vorgegeben und Sie erkennen frühzeitig eine mögliche Kollisionsgefahr der PDU im Schrank.
Hinweis:
Wählen Sie den Befestigungspunkt (Position und Abstand) der beiden Universalhalter im
Schrank so, dass keine Kollisionsgefahr mit den Clips auf der Rückseite der PDU besteht.
5Installation und Bedienung PDU metered/switched/managed
5.1Bedien- und Anzeigeelemente
Die Bedien- und Anzeigeelemente sind in Abb. 11 dargestellt. Hierbei richtet sich die Anzeigerichtung
des Displays sowie die Belegung der vier Tasten seitlich neben dem Display nach der Montagerichtung
der PDU. In der Legende zu Abb. 11 ist die Tastenbelegung für den Montagefall dargestellt, dass der
elektrische Anschluss der PDU unten liegt. Wird die PDU so montiert, dass der elektrische Anschluss
oben liegt, wird die Belegung der Tasten 7 und 10 sowie 8 und 11 getauscht. Die aktuelle Belegung
der Tasten wird am Display entsprechend angezeigt.
Legende zu Abb. 11
1Reset-Taste zum Zurücksetzen des Controllers
2CAN-Bus-Anschluss (Daisy Chain) für CMC III Sensoren, 24 V,1 A
3USB-Anschluss zum Durchführen von Firmware-Updates
4Multi-LED zur Statusanzeige
5Ethernet-Schnittstelle RJ 45
6Grüne LED zur Anzeige der Spannungsversorgung
7„Abwärts“- bzw. „Weiter“-Taste
8„Return“-Taste
9Display
10„Esc“-Taste
11„Aufwärts“-Taste
8Rittal Stromverteilung PDU international/PDU UK
Einstellungen PDU metered/switched/managed
5.2Installation
Schließen Sie die PDU an ein TN-S- oder IT-Netz an. Beachten Sie hierbei die detaillierten Informa-
tionen in Abschnitt 8 „Technische Daten“.
Sehen Sie je nach Ausführung der PDU folgende Vorsicherung vor:
– PDU international: 3 x 16 A (3~/16 A-Ausführungen), 3 x 32 A (3~/32 A-Ausführungen), 1 x 16 A
(1~/16 A-Ausführungen) bzw. 1 x 32 A (1~/32 A-Ausführungen)
– PDUUK: 1x16A (16A-Ausführungen) bzw. 1x32A (32A-Ausführungen)
Führen Sie das Anschlusskabel der PDU aus dem IT-Rack und schließen Sie es am Stromnetz an.
Direkt nach dem Anschließen zeigt die grüne LED zur Anzeige der Spannungsversorgung grünes
Dauerlicht (Abb. 11, Pos. 6). Etwa 10 Sekunden später zeigt auch die grüne Multi-LED zur Statusanzeige grünes Dauerlicht (Abb. 11, Pos. 4). Nach weiteren 15 Sekunden erscheint auf dem Display zunächst das Rittal Logo, nochmal 15 Sekunden später das Menü Main menu. Die LEDs des CANBus-Anschlusses (Abb. 11, Pos. 2) sowie der Ethernet-Schnittstelle (Abb. 11, Pos. 5) blinken grün
bzw. gelb.
Der gesamte Startvorgang ist nach ca. 40 Sekunden abgeschlossen, wenn auf dem Display die gemessenen Leistungswerte angezeigt werden.
Schließen Sie ein Anschlusskabel aus dem Rittal Zubehör an einem freien Steckplatz der PDU und
dem Verbraucher an.
Hinweis:
Beachten Sie beim Anschluss der Verbraucher die maximale Belastung pro Steckplatz
der PDU (C13: 10 A, C19: 16 A, UK-Version: 13 A).
Je nach Ausführung der PDU können Sie nicht benötigte Steckplätze mit den C13-/C19-Abdeckun-
gen aus dem Zubehör verschließen (Abb. 9).
Bei nicht erfolgreicher Installation: siehe Abschnitt 1.1.
DE
6Einstellungen PDU metered/switched/managed
Standardmäßig ist für die PDU der automatische Bezug einer IPv4-Adresse von einem DHCP-Server
im Netzwerk aktiviert. Wenn kein DHCP-Server verfügbar ist, ist folgende Grundkonfiguration voreingestellt:
Falls die PDU mit diesen Einstellungen nicht in das Netzwerk eingebunden werden kann, können die
Einstellungen über das Display oder die Website der PDU geändert werden.
6.1Einstellung über das Display
Wenn das Display ausgeschaltet ist: Drücken Sie eine beliebige Taste. Das Menü Main menu er-
scheint.
Drücken Sie die „Esc“-Taste (Abb. 11, Pos. 10). Das Menü Pin Input erscheint.
Drücken Sie so oft die „Aufwärts“-Taste (Abb. 11, Pos. 11), bis die gewünschte Ziffer an der ersten
Stelle der PIN angezeigt wird.
Drücken Sie die „Weiter“-Taste (Abb. 11, Pos. 7), um zur zweiten Stelle der PIN zu wechseln.
Drücken Sie wiederum so oft die „Aufwärts“-Taste, bis die gewünschte Ziffer an der zweiten Stelle
der PIN angezeigt wird.
Wechseln Sie zur dritten und vierten Stelle der PIN und stellen Sie diese analog ein.
Rittal Stromverteilung PDU international/PDU UK9
Einstellungen PDU metered/switched/managed
DE
Hinweis:
Um Zugriff auf das Konfigurationsmenü zu erhalten, ist die PIN „1221“ voreingestellt.
Drücken Sie abschließend die „Return“-Taste (Abb. 11, Pos. 8). Das Menü Config erscheint.
Wählen Sie mit der „Abwärts“- oder der „Aufwärts“-Taste den Eintrag „IP v4“ an.
Bestätigen Sie die Auswahl mit der „Return“-Taste. Das Menü DHCP erscheint.
Wählen Sie mit der „Abwärts“- oder der „Aufwärts“-Taste den Eintrag „Nein“ an. Dieser ist dann rot
hinterlegt.
Bestätigen Sie die Auswahl mit der „Return“-Taste. Das Menü IP v4 erscheint.
Geben Sie analog wie bei der PIN-Eingabe eine im Netzwerk erlaubte IPv4-Adresse für den Eintrag
„Adresse“ein.
Stellen Sie ggf. die Subnetzmaske und das Gateway korrekt ein.
Bestätigen Sie Ihre Eingaben mit der „Return“-Taste. Das Menü Config erscheint.
Drücken Sie abschließend die „Esc“-Taste. Das Menü Main menu erscheint.
Verbinden Sie die PDU mit einem Netzwerkkabel mit Ihrem Ethernet-LAN (Abb. 11, Pos. 5).
6.2Einstellungen über die Website der PDU
Schließen Sie das Gerät mit einem Netzwerkkabel über die Ethernet-Schnittstelle an Ihren Computer
an (Abb. 11, Pos. 5).
Hinweis:
Eventuell müssen Sie hierfür ein Crossoverkabel nutzen.
Ändern Sie die IP-Adresse Ihres Computers auf eine beliebige Adresse im Bereich 192.168.0.xxx,
z. B. 192.168.0.191. Nicht zulässig ist die voreingestellte Adresse 192.168.0.200 des Geräts.
Stellen Sie die Subnetzmaske auf den Wert 255.255.255.0.
Schalten Sie ggf. den Proxyserver im Browser ab, um eine direkte Verbindung zum Gerät zu ermög-
lichen.
Geben Sie im Browser die Adresse http://192.168.0.200 ein (Abb. 13, Pos. 1). Es wird der Anmel-
dedialog zur Anmeldung am Gerät angezeigt.
Melden Sie sich als Benutzer admin mit dem Kennwort admin an (Abb. 13, Pos. 2).
Klicken Sie im linken Teilbereich des Übersichtsfensters (Navigationsbereich) auf den Eintrag Pro-
cessing Unit (Abb. 13, Pos. 3) und im rechten Teilbereich (Konfigurationsbereich) auf die Registerkarte Configuration (Abb. 13, Pos. 4).
Klicken Sie im Gruppenrahmen Network auf die Schaltfläche TCP/IP (Abb. 13, Pos. 5).
Hinweis:
Im Folgenden wird die Einstellung für das IPv4-Protokoll detailliert beschrieben. Weiterführende Hinweise zur TCP/IP-Konfiguration: vgl. Abschnitt 1.1.
Ändern Sie im Fenster TCP/IP Configuration im Gruppenrahmen IPv4 Configuration die IP-
Adresse des Geräts auf eine im Netzwerk erlaubte Adresse ab (Abb. 13, Pos. 6).
Stellen Sie ggf. die Subnetzmaske und das Gateway korrekt ein.
Wählen Sie alternativ die Einstellung „DHCPv4“ statt „Manual“ für eine automatische IP-Vergabe.
Klicken Sie auf die Schaltfläche Save, um die Einstellungen zu speichern.
10Rittal Stromverteilung PDU international/PDU UK
Einstellungen PDU metered/switched/managed
Ändern Sie die Netzwerkeinstellungen Ihres Computers auf die ursprünglichen Werte der IP-Adresse
sowie der Subnetzmaske ab.
Trennen Sie das Netzwerkkabel zu Ihrem Computer.
Verbinden Sie die PDU mit einem Netzwerkkabel mit Ihrem Ethernet-LAN.
Eventuell notwendige Softwareupdates: siehe www.rittal.de oder Anfrage bei Rittal Service (vgl.
Abschnitt 9).
6.3Anschluss von Sensoren
An der PDU können bis zu insgesamt vier der folgenden CMC III Sensoren angeschlossen werden:
– Temperatursensor (7030.110)
– Temperatur-/Feuchtesensor (7030.111)
– Infrarot-Zugangssensor (7030.120)
– Vandalismussensor (7030.130)
Verbinden Sie einen der o. g. Sensoren aus dem Zubehörprogamm über ein CAN-Bus-Verbindungs-
kabel mit der CAN-Bus-Schnittstelle der PDU (Abb. 11, Pos. 2).
Anzeige der Statusänderung:
– Die beiden grünen sowie die beiden roten CAN-Bus LEDs am CAN-Bus-Anschluss des ange-
schlossenen Sensors blinken.
– Die Multi-LED der PDU blinkt dauerhaft in der Reihenfolge grün – orange – rot.
– Die Multi-LED des angeschlossenen Sensors blinkt dauerhaft blau.
Bestätigen Sie den neu angeschlossenen Sensor auf der Website der PDU.
Anzeige der Statusänderung an den CAN-Bus LEDs:
– Dauerlicht grüne LEDs: Status CAN-Bus „OK“.
– Dauerlicht rote LEDs: Status CAN-Bus fehlerhaft.
Anzeige der Statusänderung an der Multi-LED der PDU:
– Grünes Dauerlicht: Alle am CAN-Bus angeschlossenen Geräte haben den Status „OK“.
– Oranges Dauerlicht: Mindestens ein am CAN-Bus angeschlossenes Gerät hat den Status „War-
nung“.
– Rotes Dauerlicht: Mindestens ein am CAN-Bus angeschlossenes Gerät hat den Status „Alarm“.
Anzeige der Statusänderung an der Multi-LED des anschlossenen Sensors:
– Dauerhaft blaues Blinken: Kommunikation über den CAN-Bus.
– Grünes Blinken: bei Messwertänderung oder spätestens alle 5 Sekunden.
Der Anschluss weiterer Sensoren erfolgt als Daisy Chain.
Schließen Sie ggf. an der zweiten, freien CAN-Bus-Schnittstelle der ersten Komponente eine weitere
Komponente an (z. B. einen anderen Sensortyp).
Gehen Sie analog mit weiteren Komponenten vor (bis zu vier Stück insgesamt).
DE
Hinweis:
Weiterführende Hinweise zum Anschluss und zur Konfiguration von Sensoren finden Sie
in der jeweiligen Dokumentation des Zubehörteils.
Rittal Stromverteilung PDU international/PDU UK11
DE
Installation und Bedienung Slave PDU managed
7Installation und Bedienung Slave PDU managed
7.1Bedien- und Anzeigeelemente
Die Bedien- und Anzeigeelemente sind in Abb. 12 dargestellt.
Legende zu Abb. 12
1CAN-Bus-Anschluss (Daisy Chain) für CMC III Processing Unit bzw. CMC III Sensoren,
24 V
2Zweiter CAN-Bus-Anschluss, 24 V
3Multi-LED zur Statusanzeige
7.2Installation
Schließen Sie die PDU an ein TN-S- oder IT-Netz an. Beachten Sie hierbei die detaillierten Informa-
tionen in Abschnitt 8 „Technische Daten“.
Sehen Sie je nach Ausführung der PDU folgende Vorsicherung vor:
– PDU international: 3 x 16 A (3~/16 A-Ausführungen), 3 x 32 A (3~/32 A-Ausführungen), 1 x 16 A
(1~/16 A-Ausführungen) bzw. 1 x 32 A (1~/32 A-Ausführungen)
– PDU UK: 1 x 16 A (16 A-Ausführungen) bzw. 1 x 32 A (32 A-Ausführungen)
Führen Sie das Anschlusskabel der PDU aus dem IT-Rack und schließen Sie es am Stromnetz an.
Nach dem Anschließen zeigt die grüne Multi-LED zur Statusanzeige grünes Dauerlicht (Abb. 12,
Pos. 3). Die LEDs der CAN-Bus-Anschlüsse (Abb. 12, Pos. 1, 2) blinken grün bzw. gelb.
Schließen Sie ein Anschlusskabel aus dem Rittal Zubehör an einem freien Steckplatz der PDU und
dem Verbraucher an.
Hinweis:
Beachten Sie beim Anschluss der Verbraucher die maximale Belastung pro Steckplatz
der PDU (C13: 10 A, C19: 16 A, UK-Version: 13 A).
Je nach Ausführung der PDU können Sie nicht benötigte Steckplätze mit den C13-/C19-Abdeckun-
gen aus dem Zubehör verschließen (Abb. 9).
7.3Anschluss an eine CMC III Processing Unit
Verbinden Sie die PDU über ein CAN-Bus-Verbindungskabel mit der CMC III PU bzw. den benach-
barten Elementen im CAN-Bus (Abb. 12, Pos. 1, 2).
Anzeige der Statusänderung:
– Die beiden grünen sowie die beiden roten CAN-Bus LEDs am CAN-Bus-Anschluss der PDU blin-
ken.
– Die Multi-LED der Processing Unit blinkt dauerhaft in der Reihenfolge grün – orange – rot.
– Die Multi-LED der PDU blinkt dauerhaft blau.
Drücken Sie die „C“-Taste an der CMC III PU (ein erster Signalton ertönt) und halten Sie sie für ca.
3 Sekunden gedrückt, bis ein zweiter Signalton ertönt.
Anzeige der Statusänderung an den CAN-Bus LEDs:
– Dauerlicht grüne LEDs: Status CAN-Bus „OK“.
– Dauerlicht rote LEDs: Status CAN-Bus fehlerhaft.
Anzeige der Statusänderung an der Multi-LED der Processing Unit:
– Grünes Dauerlicht: Alle am CAN-Bus angeschlossenen Geräte haben den Status „OK“.
– Oranges Dauerlicht: Mindestens ein am CAN-Bus angeschlossenes Gerät hat den Status „War-
nung“.
– Rotes Dauerlicht: Mindestens ein am CAN-Bus angeschlossenes Gerät hat den Status „Alarm“.
12Rittal Stromverteilung PDU international/PDU UK
Technische Daten
Anzeige der Statusänderung an der Multi-LED der PDU:
– Dauerhaft blaues Blinken: Kommunikation über den CAN-Bus.
– Grünes Blinken: bei Messwertänderung oder spätestens alle 5 Sekunden.
– Dauerhaft oranges Blinken: Die PDU hat den Status „Warnung“. Schnelles Blinken: oberer Grenz-
und v6, DHCP, DNS, NTP, Syslog, SNMP v1, v2c
und v3, FTP/SFTP (Update/Filetransfer), E-Mail-Versand (SMTP)
Zugangssensor, Vandalismussensor
chen Typs (nicht bei Slave PDU managed)
14Rittal Stromverteilung PDU international/PDU UK
Technische Daten
Technische Daten
NormenSicherheitEN 60 950-1
EMVEN 55 022/B, EN 61 000-4-2, EN 61 000-4-3,
Sicherheitsrichtlinie2006/95/EG
EMV Richtlinie2004/108/EG
MTBF (bei 40°C)70.000 Stunden
SchutzartIP 20 (IEC 60 529)
Schutzklasse3
Verschmutzungsgrad2
ÜberspannungsklasseII
UmwelteigenschaftenRoHS
Lagertemperatur-25°C…+70°C
Umgebungstemperaturen0°C…+45°C
Umgebungsfeuchte 10…95 % rF, nicht kondensierend
Stecker Verriegelung C13 und C191 x (weitere optional 7955.020), nicht bei UK-Versi-
Abdeckungen C13 im Lieferumfang8 x (weitere optional 7955.010), nicht bei UK-Versi-
Abdeckungen C19 im Lieferumfang3 x (weitere optional 7955.015), nicht bei UK-Versi-
Gewährleistung24 Monate
EN 61 000-6-2, EN 61 000-6-3
onen
onen
onen
DE
Hinweis:
Alle in der Tabelle mit einem „*“ gekennzeichneten Funktionen sind in Vorbereitung und
werden als Softwareupdate erhältlich sein. Dieses Softwareupdate kann von der im
Abschnitt 9 „Service“ angegebenen Internetseite geladen werden.
Rittal Stromverteilung PDU international/PDU UK15
DE
Technische Daten
8.2Zuordnung der Sicherungen, Phasen und Steckplätze
Best.-Nr.
DK
7955.X01230 V/1~/16 A–12–
7955.X10230 V/1~/16 A–244
7955.X11230 V/1~/32 A2 x244
7955.X31400 V/3~/16 A–183
7955.X32400 V/3~/16 A–246
7955.X33400 V/3~/32 A6 x246
7955.X34400 V/3~/32 A6 x366
7955.X35400 V/3~/16 A–42–
7955.X36400 V/3~/32 A6 x48–
Einspeisung
PDU
Sicherung
(Typ C16 A)
Tab 1:Zuordnung der Sicherungen – Ausführungen PDU international
Steckplätze total
C13C19
Best.-Nr.
DK
7955.X0112 x C13–––––
7955.X10
7955.X11
7955.X31
7955.X32
7955.X338 x C132 x C198 x C132 x C198 x C132 x C19
7955.X34
7955.X3514 x C13–14 x C13–14 x C13–
7955.X368 x C138 x C138 x C138 x C138 x C138 x C13
Tab 2:Zuordnung der Phasen und Steckplätze – Ausführungen PDU international
16Rittal Stromverteilung PDU international/PDU UK
Service
Best.-Nr.
DK
7955.520
7955.530
7955.540
7955.940
7955.521230 V/1~/16 A–204
7955.531
7955.541
7955.941
7955.522230 V/1~/32 A2 x204
7955.532
7955.542
7955.942
Einspeisung
PDU
230 V/1~/13 A–16–16–
230 V/1~/16 A–164
230 V/1~/32 A2 x164
Sicherung
(Typ C16 A)
Steckplätze totalPhase 1
UK-PlugC19Strang 1 (F1)Strang 1 (F2)
20 x UK +
4 x C19
16 x UK +
4 x C19
10 x UK +
2 x C19
8 x UK +
2 x C19
Tab 3:Zuordnung der Sicherungen, Phasen und Steckplätze – Ausführungen PDU UK
9Service
Zu technischen Fragen wenden Sie sich bitte an:
Tel.: +49(0)2772 505-9052
E-Mail: info@rittal.de
Homepage: www.rittal.de
Bei Reklamationen oder Servicebedarf wenden Sie sich bitte an:
Tel.: +49(0)2772 505-1855
E-Mail: service@rittal.de
–
–
10 x UK +
2 x C19
8 x UK +
2 x C19
DE
Rittal Stromverteilung PDU international/PDU UK17
EN
Notes on documentation, Safety instructions, Product description
1Notes on documentation
EN
This Installation and Short User's Guide is intended for experienced, trained specialists and contains
only the most important information concerning the assembly, installation and function of the PDU international/PDU UK power distribution unit (subsequently referred to as the PDU).
1.1Other applicable documents
– Assembly, installation and operating instructions for the PDU international/PDU UK power distribution
unit.
These are available at www.rittal.com and contain comprehensive application-relevant information and
technical data for the PDU with regard to:
– Details concerning the electrical connection
– Functions and services
– Configuration options
– Detailed operating instructions
– Troubleshooting
The assembly, installation and operating instructions for the sensors in the CMC III system, which may
be connected to the PDU, are also available on this website.
– Temperature sensor (7030.110)
– Temperature/humidity sensor (7030.111)
– Infrared access sensor (7030.120)
– Vandalism sensor (7030.130)
2Safety instructions
– Assembly and installation of the device may only be performed by experienced, trained specialists.
– The PDU housing must not be opened.
– The PDU must not come into contact with water, aggressive or inflammable gases or vapours.
– The PDU may only be operated within the specified environmental conditions (see section 3.3).
3Product description
3.1Functional description
The PDU is a power distribution unit for use in IT racks. There are four design variants, with the following
distinguishing features:
– PDU metered: Energy measurement at the infeed per phase, i.e. output requirement of an entire
IT rack; no switching function; with display and network interface.
– PDU switched: Energy measurement at the infeed per phase, i.e. output requirement of an entire
IT rack; with switching function per individual output slot, display and network interface.
– PDU managed: Energy measurement and switching function per individual output slot; with display
and network interface.
– Slave PDU managed: Energy measurement and switching function per individual output slot (analo-
gous to PDU managed); but without display and network interface, with CAN bus for connecting to
CMC III Processing Unit (7030.000/.010 from software version 3.13) or PDU metered/switched/man-
aged (from software version 2).
3.2Proper use
The PDU is used for distributing power in IT racks.
18Rittal PDU international/PDU UK power distribution unit
Assembly notes, Installation and operation of the PDU metered/switched/managed
3.3Operating conditions
The PDU may only be operated under the following operating conditions:
Operating temperature range:+0°C…+45°C
Humidity range:10%...95% relative humidity, non-condensing
Protection category:IP 20 to IEC 60 529
4Assembly notes
The PDU is assembled using the brackets supplied loose as accessories. As a general rule, assembly
may be carried out either from the front or back, or from the left or right of the IT rack.
Note:
Rittal recommends always attaching the brackets to the PDU first, and then securing the
assembled unit to the inside of the enclosure, except with concealed assembly (fig. 8),
where this is not possible. This means that the distances between the brackets and hence
the mounting points inside the enclosure are pre-defined, allowing you to promptly identify any potential collisions of the PDU inside the enclosure.
Note:
Select the mounting point (position and spacing) for the two universal brackets inside the
enclosure so that they cannot collide with the clips on the rear of the PDU.
5Installation and operation of the PDU metered/switched/managed
5.1Operating and display elements
The operating and display elements are shown in fig. 11. The display direction and the assignment of
the four keys at the side next to the display depends on the installation direction of the PDU. The key
to fig. 11 shows the key assignment for the installation case with electrical connection of the PDU at
the bottom. If the PDU is installed with the electrical connection at the top, the assignment of keys 7
and 10 as well as 8 and 11 is reversed. The actual assignment of the keys is shown correctly on the
display.
Key to fig. 11
1Reset button for resetting the controller
2CAN bus connection (daisy chain) for CMC III sensors, 24 V,1 A
3USB connection for implementing firmware updates
4Multi-LED for status display
5Ethernet interface RJ 45
6Green LED to indicate the power supply
7"Down" or "Next" key
8"Return" key
9Display
10"Esc" key
11"Up" key
EN
Rittal PDU international/PDU UK power distribution unit19
EN
Settings of the PDU metered/switched/managed
5.2Installation
Connect the PDU to a TN-S or IT network. Please note the detailed information in section 8 "Tech-
nical specifications".
Depending on the PDU version, provide the following pre-fuse:
– PDU international: 3 x 16 A (3~/16 A versions), 3 x 32 A (3~/32 A versions), 1 x 16 A (1~/16 A ver-
sions) or 1 x 32 A (1~/32 A versions)
– PDU UK: 1 x 16 A (16 A versions) or 1 x 32 A (32 A versions)
Route the PDU connection cable out of the IT rack and connect it to the mains supply.
Immediately after connection, the green LED to indicate the power supply illuminates continually
(fig. 11, item 6). Around 10 seconds later, the green multi-LED for the status display illuminates con-
tinually (fig. 11, item 4). After a further 15 seconds, the Rittal logo will appear first on the display, fol-
lowed a further 15 seconds later by the Main menu. The LEDs of the CAN bus connection (fig. 11,
item 2) and the Ethernet interface (fig. 11, item 5) are flashing green or yellow.
The entire start process will be complete after around 40 seconds when the measured power values
are shown on the display.
Connect one connection cable from the Rittal accessories to a free slot on the PDU and the equip-
ment.
Note:
When connecting the equipment, please note the maximum load per PDU slot (C13:
10 A, C19: 16 A, UK version: 13 A).
Depending on the PDU version, unused slots can be closed using the C13/C19 covers from the ac-
cessories (fig. 9).
If installation was unsuccessful: see section 1.1.
6Settings of the PDU metered/switched/managed
The PDU is activated as standard to automatically obtain an IPv4 address from a DHCP server in the
network. If there is no DHCP server available, the following basic configuration is preset:
IP address:192.168.0.200
Netmask:255.255.255.0
Gateway:0.0.0.0
If the PDU cannot be incorporated into the network with these settings, the settings can be amended
via the display or the PDU website.
6.1Settings via the display
If the display is switched off: Press any key. The Main menu appears.
Press the "Esc" key (fig. 11, item 10). The Pin input menu appears.
Keep pressing the "Up" key (rig. 11, item 11), until the required digit is displayed in the first position
of the PIN.
Press the "Next" key (fig. 11, item 7) to move to the second position of the PIN.
Once again, keep pressing the "Up" key until the required digit is displayed in the second position of
the PIN.
Move to the third and fourth positions of the PIN and set them in the same way.
20Rittal PDU international/PDU UK power distribution unit
Settings of the PDU metered/switched/managed
Note:
"1221" is the preset PIN for accessing the configuration menu.
Finally, press the "Return" key (fig. 11, item 8). The Config menu will appear.
Use the "Down" key or the "Up" key to select the "IP v4" entry.
Click the "Return" key to confirm your selection. The DHCP menu will appear.
Use the "Down" key or the "Up" key to select the "No" entry. This will now appear on a red back-
ground.
Click the "Return" key to confirm your selection. The IP v4 menu will appear.
In the same way as you entered the PIN, enter an IPv4 address permitted in the network for the "Ad-
dress" entry.
If necessary, correct the settings for the subnet mask and the gateway.
Click the "Return" key to confirm your entries. The Config menu will appear.
Finally, press the "Esc" key. The Main menu appears.
Connect the PDU to your Ethernet LAN with a network cable (fig. 11, item 5).
6.2Settings via the PDU website
Using a network cable, connect the device to your computer via the Ethernet interface (fig. 11,
item 5).
Note:
You may need to use a cross-over cable for this purpose.
Change your computer's IP address to any address within the range 192.168.0.xxx, e.g.
192.168.0.191. The default address 192.168.0.200 of the device must not be used.
Set the subnet mask to the value 255.255.255.0.
If applicable, switch off the proxy server in the browser to facilitate a direct connection to the device.
In the browser, enter the address http://192.168.0.200 (fig. 13, item 1). The login dialog for logging
in to the device will be displayed.
Log in with the username admin and the password admin (fig. 13, item 2).
In the left-hand section of the overview window (navigation area), click the Processing Unit entry
(fig. 13, item 3), and in the right-hand section (configuration area), click the Configuration tab
(fig. 13, item 4).
In the Network group box, click on the TCP/IP button (fig. 13, item 5).
EN
Note:
The following sections describe in detail how to make the setting for the IPv4 protocol.
Further notes regarding the TCP/IP configuration can be found in section 1.1.
In the TCP/IP Configuration window, change the device's IP address in the IPv4 Configuration
group box to an address permitted in the network (fig. 13, item 6).
If necessary, correct the settings for the subnet mask and the gateway.
Alternatively, select the "DHCPv4" setting instead of "Manual" for automatic IP allocation.
Click on the Save button to change your settings.
Change the network settings of your computer to its original values for the IP address and the subnet
mask.
Rittal PDU international/PDU UK power distribution unit21
EN
Settings of the PDU metered/switched/managed
Disconnect the network cable from your computer.
Connect the PDU to your Ethernet LAN with a network cable.
For any required software updates, please visit www.rittal.com or contact Rittal Service (see section 9).
6.3Connection of sensors
Up to four of the following CMC sensors may be connected to the PDU:
– Temperature sensor (7030.110)
– Temperature/humidity sensor (7030.111)
– Infrared access sensor (7030.120)
– Vandalism sensor (7030.130)
Connect one of the above sensors from the accessories range to the CAN bus interface of the PDU
using a CAN bus connection cable (fig. 11, item 2).
Status change display:
– The two green and the two red CAN bus LEDs on the CAN bus connection of the connected sen-
sor will start to flash.
– The multi-LED of the PDU flashes continually in the sequence green – orange – red.
– The multi-LED of the connected sensor flashes blue continuously.
Confirm the newly connected sensor on the PDU website.
Status change display on the CAN bus LEDs:
– Continuous green LEDs: CAN bus status "OK".
– Continuous red LEDs: CAN bus status faulty.
Status change display on the multi-LED of the PDU:
– Continuous green light: All devices connected to the CAN bus have the status "OK".
– Continuous orange light: At least one device connected to the CAN bus has the status "Warning".
– Continuous red light: At least one device connected to the CAN bus has the status "Alarm".
Status change display on the multi-LED of the connected sensor.
– Continuous blue flashing: Communication via the CAN bus.
– Green flashing: When the measured value changes or, at the latest, every 5 seconds.
Further sensors are connected as daisy chain.
If necessary, connect another component (e.g. another sensor type) to the second, free CAN bus
interface of the first component.
Proceed in the same way for further components (up to four units in total).
Note:
Further information concerning the connection and configuration of sensors can be found
in the associated documentation of the accessory part.
22Rittal PDU international/PDU UK power distribution unit
Installation and operation of the slave PDU managed
7Installation and operation of the slave PDU managed
7.1Operating and display elements
The operating and display elements are shown in fig. 12.
Key to fig. 12
1CAN bus connection (daisy chain) for CMC III processing unit and CMC III sensors, 24 V
2Second CAN bus connection, 24 V
3Multi-LED for status display
7.2Installation
Connect the PDU to a TN-S or IT network. Please note the detailed information in section 8 "Tech-
nical specifications".
Depending on the PDU version, provide the following pre-fuse:
– PDU international: 3 x 16 A (3~/16 A versions), 3 x 32 A (3~/32 A versions), 1 x 16 A (1~/16 A ver-
sions) or 1 x 32 A (1~/32 A versions)
– PDUUK: 1x16A (16A versions) or 1x32A (32A versions)
Route the PDU connection cable out of the IT rack and connect it to the mains supply.
Once connected, the green multi-LED for the status display illuminates continually (fig. 12, item 3).
The LEDs of the CAN bus connections (fig. 12, items 1, 2) are flashing green or yellow.
Connect a connection cable from the Rittal accessories to a free slot on the PDU and the equipment.
Note:
When connecting the equipment, please note the maximum load per PDU slot (C13:
10 A, C19: 16 A, UK version: 13 A).
Depending on the PDU version, unused slots can be closed using the C13/C19 covers from the ac-
cessories (fig. 9).
EN
7.3Connection to a CMC III processing unit
Connect the PDU to the CMC III PU or to the adjacent components in the CAN bus using a CAN bus
connection cable (fig. 12, items 1, 2).
Status change display:
– The two green and the two red CAN bus LEDs on the CAN bus connection of the PDU will start
to flash.
– The multi-LED of the processing unit flashes continually in the sequence green – orange – red.
– The multi-LED of the PDU flashes blue continuously.
Press the "C" key on the CMC III PU (an initial audio signal will sound) and keep it pressed for approx.
3 seconds until a second audio signal is heard.
Status change display on the CAN bus LEDs:
– Continuous green LEDs: CAN bus status "OK".
– Continuous red LEDs: CAN bus status faulty.
Status change display on the multi-LED of the processing unit.
– Continuous green light: All devices connected to the CAN bus have the status "OK".
– Continuous orange light: At least one device connected to the CAN bus has the status "Warning".
– Continuous red light: At least one device connected to the CAN bus has the status "Alarm".
Status change display on the multi-LED of the PDU:
– Continuous blue flashing: Communication via the CAN bus.
– Green flashing: When the measured value changes or, at the latest, every 5 seconds.
Rittal PDU international/PDU UK power distribution unit23
EN
Technical specifications
– Continuous orange flashing: The PDU has "warning" status. Fast flashing: upper limit value over-
shot. Slow flashing: lower limit value undershot.
– Continuous red flashing: The PDU has "alarm" status. Fast flashing: upper limit value overshot.
Slow flashing: lower limit value undershot.
– Continuous red light: Invalid measured value.
Note:
Connection cables in various lengths can be purchased from Rittal.
If installation was unsuccessful: see section 1.1.
8Technical specifications
8.1General technical specifications
Technical specifications
Input voltage range (L – N)90 V…260 (400) V AC, 50…60 Hz
Input current16A/32A/63A (depending on variant)
No. of phases1 or 3 depending on PDU variant
PDU inherent supplyIntegral long-range SMPS, error-tolerant from all
PDU power consumptionapprox. 15 W
Redundant power supply via PoEYes (for PDU switched, PDU managed)
User administration including rights managementYes
LDAP(S)/Radius/Active Directory connectionYes*
USB port for firmware update and data logging functionsYes*
CAN bus interfaceRJ 45, for connecting sensors
CAN sensor typesTemperature, temperature/humidity (combined), in-
Max. number of sensors per PDU 4, sensor configuration freely selectable, including 4
Plug & play drivers in the Rittal RiZone DCIM softwareYes
ConformityCE
StandardsSafetyEN 60 950-1
Current measurement range0…16/32/63 A (depending on PDU variant)
Current resolution0.1 A
Current accuracy2%
Frequency accuracy2%
Active power (kW) accuracy2%
Apparent power (VA) accuracy2%
Active energy (kWh) accuracy1%
Power factor accuracy2%
Freely settable limit values for
warning/alarm
EMCEN 55 022/B, EN 61 000-4-2, EN 61 000-4-3,
(kW), active energy (kWh), apparent power (VA),
power factor, neutral-conductor measurement /
load imbalance detection, fuse monitoring (for 32 A/
63 A versions)
Yes
switched, PDU managed)
aged)
and v6, DHCP, DNS, NTP, Syslog, SNMP v1, v2c
and v3, FTP/SFTP (update/file transfer), e-mail forwarding (SMTP)
frared access sensor, vandalism sensor
of the same type (not for slave PDU managed)
EN 61 000-6-2, EN 61 000-6-3
EN
Rittal PDU international/PDU UK power distribution unit25
Connector latch C13 and C191 x (further optional DK 7955.020), not for UK ver-
C13 covers included with supply8 x (further optional DK 7955.010), not for UK ver-
C19 covers included with supply3 x (further optional DK 7955.015), not for UK ver-
Warranty24 months
sions
sions
sions
Note:
All functions in the table marked with an "*" are currently under preparation and will be
available as software updates. These software updates can be downloaded from the
website specified in chapter 9 "Service".
26Rittal PDU international/PDU UK power distribution unit
8.2Allocation of fuses, phases and slots
Model No.
DK
7955.X01230 V/1~/16 A–12–
7955.X10230 V/1~/16 A–244
7955.X11230 V/1~/32 A2 x244
7955.X31400 V/3~/16 A–183
7955.X32400 V/3~/16 A–246
7955.X33400 V/3~/32 A6 x246
7955.X34400 V/3~/32 A6 x366
7955.X35400 V/3~/16 A–42–
7955.X36400 V/3~/32 A6 x48–
PDU infeed
Fuse
(type C16 A)
Tab 1:Allocation of fuses – PDU international versions
Total slots
C13C19
Technical specifications
EN
Model No.
DK
7955.X0112 x C13–––––
7955.X10
7955.X11
7955.X31
7955.X32
7955.X338 x C132 x C198 x C132 x C198 x C132 x C19
7955.X34
7955.X3514 x C13–14 x C13–14 x C13–
7955.X368 x C138 x C138 x C138 x C138 x C138 x C13
For complaints or service requests, please contact:
Tel.: +49(0)2772 505-1855
E-mail: service@rittal.de
20 x UK +
4 x C19
16 x UK +
4 x C19
10 x UK +
2 x C19
8 x UK +
2 x C19
–
–
10 x UK +
2 x C19
8 x UK +
2 x C19
28Rittal PDU international/PDU UK power distribution unit
FR
Remarques relatives à la documentation, Consignes de sécurité, Description du produit
1Remarques relatives à la documentation
Cette notice d’installation et d’utilisation succincte s’adresse à du personnel qualifié et chevronné et
contient uniquement les informations essentielles pour le montage, l’installation et le fonctionnement du
rail de distribution de courant PDU international / PDU UK (nommée PDU par la suite).
1.1Autres documents applicables
– Notice de montage, d’installation et d’utilisation du rail de distribution de courant PDU international /
PDU UK.
Elle est disponible sous www.rittal.fr et contient les informations complètes relatives à la mise en œuvre
ainsi que les caractéristiques techniques du PDU dans les domaines suivants :
– Détails des raccordements électriques
– Fonctionnement et services
– Possibilités de configuration
– Instructions d’utilisation détaillées
– Suppression des défauts
Des notices de montage, d’installation et d’utilisation des capteurs du système de supervision CMC III,
qui peuvent être raccordés au PDU, y figurent également.
– Sonde de température (7030.110)
– Sonde de température / détecteur d’humidité (7030.111)
– Détecteur d’accès infrarouge (7030.120)
– Détecteur de vandalisme (7030.130)
2Consignes de sécurité
– Le montage et l’installation de l’appareil doivent être réalisés uniquement par du personnel qualifié et
chevronné.
– Le boîtier du PDU ne doit pas être ouvert.
– Le PDU ne doit pas se trouver au contact de l’eau, de gaz et de vapeurs agressifs ou inflammables.
– Le PDU doit être mis en œuvre uniquement dans les conditions ambiantes spécifiées (cf. paragraphe
3.3).
FR
3Description du produit
3.1Principe de fonctionnement
Le PDU est un rail de distribution de courant à utiliser dans les baies. Il existe quatre versions qui se
différencient de la manière suivante :
– PDU metered : Mesure de puissance par phase de l’alimentation ; sans fonction de commutation ;
avec écran et interface réseau.
– PDU switched : Mesure de puissance par phase de l’alimentation ; avec fonction de commutation de
chaque prise, écran et interface réseau.
– PDU managed : Mesure de puissance et commutation de chaque prise ; avec écran et interface ré-
seau.
– PDU managed esclave : Mesure de puissance et commutation de chaque prise (analogue au PDU
managed) ; néanmoins sans écran ni interface réseau, avec CAN-Bus pour le raccordement d’une
Unité Centrale CMC III (7030.000/.010 à compter de la version de logiciel 3.13) ou d’un PDU metered
/ switched / managed (à compter de la version de logiciel 2).
3.2Utilisation conforme au règlement
Le PDU sert en particulier à la distribution de courant dans les baies serveurs et réseaux.
Rail de distribution de courant PDU international / PDU UK Rittal29
FR
Installation et utilisation des PDU metered / switched / managed
3.3Conditions de fonctionnement
Le PDU doit être mis en œuvre uniquement dans les conditions de fonctionnement suivantes :
Plage de température tolérée :+0°C…+45°C
Plage d’humidité tolérée :10 %...95 % d’humidité relative, sans condensation
Indice de protection :IP 20 selon CEI 60 529
4Remarques relatives au montage
Le montage du PDU est réalisé à l’aide des supports qui figurent dans les accessoires. Le montage
peut se faire aussi bien à l’avant, à l’arrière, à gauche ou à droite de la baie IT.
Remarque :
La société Rittal conseille de monter tout d’abord les supports sur le PDU et d’installer
ensuite ceux-ci simultanément dans la baie, hormis pour le montage masqué (fig. 8) pour
lequel cela n’est pas possible. Cela permet de définir les écartements entre les supports
et ainsi les points de fixation dans la baie, ce qui vous permet de détecter rapidement un
possible risque de collision du PDU dans la baie.
Remarque :
Choisissez le point de fixation (position et écartement) des deux supports universels dans
la baie de manière à éviter tout risque de collision avec les clips à l’arrière du PDU.
5Installation et utilisation des PDU metered / switched / managed
5.1Organes de commande et de signalisation
Les organes de commande et de signalisation sont présentés à la fig. 11. La direction d’affichage à
l’écran ainsi que l’attribution des quatre touches à côté de l’écran s’orientent ici en fonction de la direction de montage du PDU. Dans la légende de la fig. 11, l’attribution des touches est représentée pour
un montage avec le raccordement électrique en bas du PDU. Si le PDU est monté de manière telle que
le raccordement électrique se trouve en haut, l’attribution des touches 7 et 10 ainsi que 8 et 11 est
inversée. L’attribution effective des touches est affichée en conséquence à l’écran.
Légende pour la fig. 11
1Touche Reset pour l’initialisation du contrôleur
2Raccordement de CAN-Bus (Daisy Chain) pour capteurs CMC III, 24 V,1 A
3Raccordement USB pour effectuer des mises à jour du logiciel
4LED multiple pour l’affichage d’état
5Interface Ethernet RJ 45
6LED verte pour l’affichage de l’alimentation électrique
7Touche « Descente » ou « Suivant »
8Touche « Retour »
9Ecran
10Touche « Esc »
11Touche « Montée »
30Rail de distribution de courant PDU international / PDU UK Rittal
Réglages des PDU metered / switched / managed
5.2Installation
Raccorder le PDU à un réseau TN-S ou IT. Respecter ici les informations détaillées du paragraphe 8
« Caractéristiques techniques ».
Prévoir le dispositif de sécurité suivant en fonction du modèle de PDU :
– PDU international : 3 x 16 A (modèles 3~/16 A), 3 x 32 A (modèles 3~/32 A), 1 x 16 A (modèles
1~/16 A) ou 1 x 32 A (modèles 1~/32 A)
– PDU UK : 1 x 16 A (modèles 16 A) ou 1 x 32 A (modèles 32 A)
Faire sortir le câble de raccordement du PDU de la baie et le raccorder au réseau électrique.
Juste après le raccordement, la LED verte pour l’affichage de l’alimentation électrique est allumée en
vert en permanence (fig. 11, pos. 6). Environ 10 secondes plus tard, la LED multiple pour l’affichage
d’état est également allumée en vert en permanence (fig. 11, pos. 4). Le logo Rittal apparaît tout
d’abord à l’écran après 15 secondes supplémentaires puis, à nouveau 15 secondes plus tard, le
menu Main menu. Les LED de connexion CAN-Bus (fig. 11, pos. 2) ainsi que de l’interface Ethernet
(fig. 11, pos. 5) clignotent en vert ou en jaune.
Le processus de démarrage complet est terminé après env. 40 secondes, lorsque les valeurs de
puissance mesurées sont affichées à l’écran.
Brancher un câble de raccordement qui figure dans les accessoires Rittal à une prise libre du PDU
et à l’équipement.
Remarque :
Lors du raccordement des équipements, respecter la charge maximale par prise du PDU
(C13 : 10 A, C19 : 16 A, version UK : 13 A).
Selon le modèle de PDU, vous pouvez obturer les emplacements non occupés avec des couvercles
C13 / C19 qui figurent dans les accessoires (fig. 9).
En cas d’échec de l’installation : voir le paragraphe 1.1.
FR
6Réglages des PDU metered / switched / managed
L’attribution automatique d’une adresse IPv4 depuis un serveur DHCP dans le réseau est activée sur
le PDU, par défaut. La configuration de base suivante est préréglée si aucun serveur DHCP n’est
disponible :
Adresse IP :192.168.0.200
Masque réseau :255.255.255.0
Liaison :0.0.0.0
Les réglages peuvent être modifiés via l’écran ou l’interface web du PDU, s’il n’est pas possible d’identifier le PDU dans le réseau à l’aide de ces réglages.
6.1Réglage via l’écran
Lorsque l’écran est hors fonction : Actionner n’importe quelle touche. Le menu Main menu s’affi-
che.
Actionner la touche « Esc » (fig. 11, pos. 10). Le menu Pin Input s’affiche.
Actionner la touche « Montée » (fig. 11, pos. 11) autant que cela est nécessaire pour afficher le chiffre
souhaité pour le premier chiffre du code PIN.
Actionner la touche « Suivant » (fig. 11, pos. 7) pour aller au deuxième chiffre du code PIN.
Actionner à nouveau la touche « Montée » autant que cela est nécessaire pour afficher le chiffre sou-
haité pour le deuxième chiffre du code PIN.
Aller au troisième et au quatrième chiffre du code PIN et régler celui-ci de manière analogue.
Rail de distribution de courant PDU international / PDU UK Rittal31
Réglages des PDU metered / switched / managed
FR
Remarque :
Le code PIN « 1221 » est préréglé pour accéder au menu de configuration.
Actionner en dernier la touche « Retour » (fig. 11, pos. 8). Le menu Config s’affiche.
Sélectionner la valeur « IP v4 » en actionnant la touche « Descente » ou « Montée ».
Valider la sélection à l’aide de la touche « Retour ». Le menu DHCP s’affiche.
Sélectionner la valeur « Non » en actionnant la touche « Descente » ou « Montée ». Celle-ci est alors
affichée sur fond rouge.
Valider la sélection à l’aide de la touche « Retour ». Le menu IP v4 s’affiche.
Saisir une adresse IPv4 autorisée sur le réseau dans la valeur « Adresse » de manière analogue à la
saisie du code PIN.
Saisir si nécessaire correctement le masque réseau et la liaison.
Valider vos saisies à l’aide de la touche « Retour ». Le menu Config s’affiche.
Actionner en dernier la touche « Esc ». Le menu Main menu s’affiche.
Raccorder le PDU à votre Ethernet LAN via un câble réseau (fig. 11, pos. 5).
6.2Réglages via le site Internet du PDU
Raccorder l’appareil à votre ordinateur à l’aide d’un câble réseau via l’interface Ethernet (fig. 11,
pos.5).
Remarque :
Il faut éventuellement utiliser un câble croisé pour cela.
Modifier l’adresse IP de votre ordinateur à une adresse quelconque de la plage 192.168.0.xxx, p. ex.
192.168.0.191. L’adresse présélectionnée 192.168.0.200 de l’appareil n’est pas autorisée.
Régler le masque réseau sur la valeur 255.255.255.0.
Déconnecter éventuellement le serveur Proxy dans le navigateur pour avoir une liaison directe avec
l’appareil.
Saisir l’adresse http://192.168.0.200 dans le navigateur (fig. 13, pos. 1). Le dialogue pour l’identifi-
cation est affiché sur l’appareil.
S’identifier comme utilisateur admin avec le mot de passe admin (fig. 13, pos. 2).
Da ns l a pa rtie gau che de l a fenêtr e (zone de navigation), cliquer sur Processing Unit (fig. 13, pos. 3)
et dans la partie droite (zone de configuration), sur l’onglet Configuration (fig. 13, pos. 4).
Dans le cadre Network, cliquer sur la fonction TCP/IP (fig. 13, pos. 5).
Remarque :
Le réglage pour le protocole IPv4 est décrit de manière détaillée dans ce qui suit. Autres
remarques pour la configuration TCP/IP : cf. paragraphe 1.1.
A l’écran TCP/IP Configuration, dans le cadre IPv4 Configuration, modifier l’adresse IP de l’ap-
pareil à une adresse autorisée sur le réseau (fig. 13, pos. 6).
Saisir si nécessaire correctement le masque réseau et la liaison.
Une alternative consiste à sélectionner le réglage « DHCPv4 » au lieu de « Manuel » pour une attribu-
tion automatique de l’adresse IP.
Cliquer sur la fonction Save pour mémoriser les réglages.
32Rail de distribution de courant PDU international / PDU UK Rittal
Réglages des PDU metered / switched / managed
Modifier les réglages réseau de votre ordinateur aux valeurs d’origine de l’adresse IP et du masque
réseau.
Débrancher le câble réseau de votre ordinateur.
Raccorder le PDU à votre Ethernet LAN via un câble réseau.
Si des mises à jour de logiciel sont éventuellement nécessaires : voir www.rittal.fr ou sur demande au
service après-vente Rittal (cf. paragraphe 9).
6.3Raccordement des capteurs
Vous pouvez raccorder jusqu’à un total de quatre des capteurs CMC III suivants au PDU :
– Sonde de température (7030.110)
– Sonde de température / détecteur d’humidité (7030.111)
– Détecteur d’accès infrarouge (7030.120)
– Détecteur de vandalisme (7030.130)
Raccorder un des capteurs ci-dessus, qui figurent dans les accessoires, à l’interface CAN-Bus du
PDU via un câble de raccordement CAN-Bus (fig. 11, pos. 2).
Affichage de la modification d’état :
– Les deux LED vertes et les deux LED rouges CAN-Bus de connexion CAN-Bus sur le capteur rac-
cordé clignotent.
– La LED multiple du PDU clignote de manière continue dans l’ordre vert – orange – rouge.
– La LED multiple du capteur raccordé clignote en bleu de manière continue.
Valider le capteur qui vient d’être raccordé sur le site Internet du PDU.
Affichage de la modification d’état sur la LED du CAN-Bus :
– Les LED vertes sont allumées en continu : état du CAN-Bus « OK ».
– Les LED rouges sont allumées en continu : état défectueux du CAN-Bus.
Affichage de la modification d’état sur la LED multiple du PDU :
– Lumière verte en continu : tous les appareils raccordés au CAN-Bus sont dans l’état « OK ».
– Lumière orange en continu : au moins un appareil raccordé au CAN-Bus est dans l’état
« Avertissement ».
– Lumière rouge en continu : au moins un appareil raccordé au CAN-Bus est dans l’état « Alarme ».
Affichage de la modification d’état sur la LED multiple du capteur raccordé :
– Clignotement bleu continu : communication via le CAN-Bus.
– Clignotement vert : lors d’une modification de la valeur de mesure ou au plus tard toutes les 5 se-
condes.
Le raccordement d’autres capteurs se fait sous forme de Daisy Chain.
Raccorder si nécessaire un autre composant à la deuxième interface de CAN-Bus libre du premier
composant (p. ex. un autre type de capteur).
Procéder de manière analogue pour les autres composants (jusqu’à quatre au total).
FR
Remarque :
D’autres remarques pour le raccordement et la configuration des capteurs figurent dans
la documentation correspondante de l’accessoire.
Rail de distribution de courant PDU international / PDU UK Rittal33
FR
Installation et utilisation du PDU managed esclave
7Installation et utilisation du PDU managed esclave
7.1Organes de commande et de signalisation
Les organes de commande et de signalisation sont présentés à la fig. 12.
Légende pour la fig. 12
1Connexion CAN-Bus (Daisy Chain) pour Unité Centrale CMC III ou capteurs CMC III, 24 V
2Deuxième connexion CAN-Bus, 24 V
3LED multiple pour l’affichage d’état
7.2Installation
Raccorder le PDU à un réseau TN-S ou IT. Respecter ici les informations détaillées du paragraphe 8
« Caractéristiques techniques ».
Prévoir le dispositif de sécurité suivant en fonction du modèle de PDU :
– PDU international : 3 x 16 A (modèles 3~/16 A), 3 x 32 A (modèles 3~/32 A), 1 x 16 A (modèles
1~/16 A) ou 1 x 32 A (modèles 1~/32 A)
– PDU UK : 1 x 16 A (modèles 16 A) ou 1 x 32 A (modèles 32 A)
Faire sortir le câble de raccordement du PDU de la baie et le raccorder au réseau électrique.
Après le raccordement, la LED multiple verte pour l’affichage d’état est allumée en vert en continu
(fig. 12, pos. 3). Les LED des connexions CAN-Bus (fig. 12, pos. 1, 2) clignotent en vert ou en jaune.
Brancher un câble de raccordement qui figure dans les accessoires Rittal à une prise libre du PDU
et à l’équipement.
Remarque :
Lors du raccordement des équipements, respecter la charge maximale par prise du PDU
(C13 : 10 A, C19 : 16 A, version UK : 13 A).
Selon le modèle de PDU, vous pouvez obturer les emplacements non occupés avec des couvercles
C13 / C19 qui figurent dans les accessoires (fig. 9).
7.3Raccordement à une Unité Centrale CMC III
Raccorder le PDU à l’UC CMC III ou aux éléments voisins au sein du CAN-Bus via un câble de rac-
cordement CAN-Bus (fig. 12, pos. 1, 2).
Affichage de la modification d’état :
– Les deux LED vertes et les deux LED rouges CAN-Bus de connexion CAN-Bus sur le PDU cligno-
tent.
– La LED multiple de l’Unité Centrale clignote de manière continue dans l’ordre vert – orange – rou-
ge.
– La LED multiple du PDU clignote en bleu de manière continue.
Appuyer sur la touche « C » de l’UC CMC III (un premier signal sonore retentit) et la maintenir appuyée
pendant env. 3 secondes jusqu’à ce qu’un deuxième signal sonore retentisse.
Affichage de la modification d’état sur les LED du CAN-Bus :
– Les LED vertes sont allumées en continu : état du CAN-Bus « OK ».
– Les LED rouges sont allumées en continu : état défectueux du CAN-Bus.
Affichage de la modification d’état sur la LED multiple de l’Unité Centrale :
– Lumière verte en continu : tous les appareils raccordés au CAN-Bus sont dans l’état « OK ».
– Lumière orange en continu : au moins un appareil raccordé au CAN-Bus est dans l’état
« Avertissement ».
– Lumière rouge en continu : au moins un appareil raccordé au CAN-Bus est dans l’état « Alarme ».
34Rail de distribution de courant PDU international / PDU UK Rittal
Caractéristiques techniques
Affichage de la modification d’état sur la LED multiple du PDU :
– Clignotement bleu continu : communication via le CAN-Bus.
– Clignotement vert : lors d’une modification de la valeur de mesure ou au plus tard toutes les 5 se-
condes.
– Clignotement orange continu : le PDU est dans l’état « Avertissement ». Clignotement rapide : va-
leur limite supérieure dépassée. Clignotement lent : valeur limite inférieure dépassée.
– Clignotement rouge continu : le PDU est dans l’état « Alarme ». Clignotement rapide : valeur limite
Plage de mesure du courant0…16 / 32 / 63 A (selon la variante de PDU)
Fonctions de mesure
(entrée / phase ou prise)
Compteur d’heures de fonctionnementOui
Ecran / AffichageOLED, RGB 128 x 128 Pixel, LED par prise (pour
Interface réseauRJ 45, serveur Internet intégré (par
Protocoles gérésHTTP, HTTPS, SSL, SSH, NTP, Telnet, TCP/IP v4 et
Gestion des utilisateurs, y compris gestion des droitsOui
Liaison LDAP(S) / Radius / Active DirectoryOui*
Port USB pour la mise à jour de logiciel et l’enregistrement
de données
Interface de CAN-BusRJ 45, pour le raccordement des capteurs
Types de capteurs CANTempérature, température / humidité (combiné), dé-
Résolution du courant0,1 A
Précision du courant2 %
Précision de la fréquence2 %
Précision de la puissance active
(kW)
Précision de la puissance apparente (VA)
Précision du travail actif (kWh)1 %
Précision du facteur de puissance 2 %
Valeurs limites à réglage libre pour
l’avertissement / l’alarme
active (kW), travail actif (kWh), puissance apparente
(VA), facteur de puissance, mesure du neutre / détection de déséquilibre, contrôle de sécurité (sur les
versions 32 A / 63 A)
2%
2%
Oui
PDU switched, PDU managed)
pour PDU managed esclave)
v6, DHCP, DNS, NTP, Syslog, SNMP v1, v2c et v3,
FTP/SFTP (mise à jour / transfert de fichiers), émission d’e-mails (SMTP)
Oui*
tecteur d’accès infrarouge, détecteur de vandalisme
36Rail de distribution de courant PDU international / PDU UK Rittal
Caractéristiques techniques
Caractéristiques techniques
Nombre max. de capteurs par PDU 4, configuration libre des capteurs, également 4 x le
Pilote plug & play dans le logiciel Rittal RiZone DCIMOui
ConformitéCE
NormesSécuritéEN 60 950-1
CEMEN 55 022/B, EN 61 000-4-2, EN 61 000-4-3,
Directive de sécurité2006/95/CE
Directive CEM2004/108/CE
MTBF (à 40°C)70 000 heures
Indice de protectionIP 20 (CEI 60 529)
Classe de protection3
Taux d’encrassement2
Classe de surtensionII
Caractéristiques environnementalesRoHS
Température de stockage-25°C…+70°C
Températures ambiantes0°C…+45°C
Humidité ambiante 10…95 % d’humidité relative, sans condensation
Verrouillage de la prise C13 et C191 x (autres en option 7955.020), sauf pour les ver-
Couvercles C13 compris dans la fourniture8 x (autres en option 7955.010), sauf pour les ver-
Couvercles C19 compris dans la fourniture3 x (autres en option 7955.015), sauf pour les ver-
Garantie24 mois
même type (sauf pour PDU managed esclave)
EN 61 000-6-2, EN 61 000-6-3
sions UK
sions UK
sions UK
FR
Remarque :
Toutes les fonctions identifiées dans le tableau par un « * » sont en préparation et seront
disponibles avec la mise à jour du logiciel. Cette mise à jour du logiciel peut être téléchargée depuis le site Internet indiqué dans le paragraphe 9 « Service après-vente ».
Rail de distribution de courant PDU international / PDU UK Rittal37
FR
Caractéristiques techniques
8.2Attribution des fusibles, phases et prises
Référence
DK
7955.X01230 V/1~/16 A–12–
7955.X10230 V/1~/16 A–244
7955.X11230 V/1~/32 A2 x244
7955.X31400 V/3~/16 A–183
7955.X32400 V/3~/16 A–246
7955.X33400 V/3~/32 A6 x246
7955.X34400 V/3~/32 A6 x366
7955.X35400 V/3~/16 A–42–
7955.X36400 V/3~/32 A6 x48–
Alimentation
PDU
Fusible
(type C16 A)
Tab 1 :Attribution des fusibles – Modèles PDU international
Nombre total de prises
C13C19
Référence
DK
7955.X0112 x C13–––––
7955.X10
7955.X11
7955.X31
7955.X32
7955.X338 x C132 x C198 x C132 x C198 x C132 x C19
7955.X34
7955.X3514 x C13–14 x C13–14 x C13–
7955.X368 x C138 x C138 x C138 x C138 x C138 x C13