Rittal Blue e+ Assembly And Operating Instructions Manual

Blue e+ chiller for cooling media
SK 3320200 SK 3334300 SK 3334400
Assembly and operating instructions
Contents
EN
Contents
1.1 General ........................................................ 4
1.2 CE conformity .............................................. 4
1.3 Storing the documents................................. 4
1.4 Symbols used in these operating instructions 4
1.5 Other applicable documents ........................ 4
2.1 General ........................................................ 4
2.2 Risks in case of failure to observe the safety
instructions .................................................. 4
2.3 Safety instructions for assembly, inspection
and maintenance work ................................. 4
2.4 Unauthorised operation................................ 5
2.5 Health risks due to the refrigerant R134a and
the cooling medium ..................................... 5
2.6 First aid measures........................................ 5
2.7 Fire-fighting measures.................................. 5
2.8 Safety measures and equipment.................. 5
2.9 Potential hazards and how to avoid them..... 6
3 Device description ............................ 7
3.1 General ........................................................ 7
3.2 General functional description ...................... 8
3.3 Control......................................................... 9
3.4 Characteristic curves.................................... 9
3.4.1 Characteristic curves of pump ............................... 9
3.4.2 Performance diagrams ........................................ 10
3.5 Safety devices............................................ 10
3.6 Options...................................................... 10
3.6.1 Inverter pump ..................................................... 10
3.6.2 Reinforced pump ................................................ 10
3.6.3 Outdoor .............................................................. 10
3.6.4 Oil/emulsion ........................................................ 10
3.6.5 Free Cooling ....................................................... 10
3.6.6 Water-cooled condenser ..................................... 10
3.6.7 Tank heating ....................................................... 10
3.7 Proper use, foreseeable misuse ................. 10
3.8 Supply includes.......................................... 11
4 Transport ....................................... 11
4.1 Delivery ...................................................... 11
4.2 Unpacking ................................................. 11
4.3 Transport ................................................... 11
6 Commissioning .............................. 18
6.1 Cooling medium water-glycol mixture......... 18
6.1.1 General remarks ................................................. 18
6.1.2 Cooling medium requirements ............................ 18
6.1.3 Preparation and care .......................................... 19
6.1.4 Recommended "Cooling medium for chillers" ..... 19
6.2 Filling the cooling medium .......................... 20
6.3 Bleeding the cooling medium pump ........... 20
6.4 Commissioning procedure ......................... 21
6.5 Adjusting the bypass valve ......................... 21
7 Operation ....................................... 21
7.1 General ...................................................... 21
7.2 Layout of the display .................................. 22
7.2.1 Start screen ........................................................ 22
7.2.2 Changing a parameter value ............................... 22
7.2.3 Help function ...................................................... 23
7.3 Info menu................................................... 23
7.3.1 Temperature info ................................................. 23
7.3.2 Device info .......................................................... 23
7.3.3 Efficiency info ...................................................... 24
7.3.4 Hydraulic info ...................................................... 24
7.4 Configuration menu.................................... 24
7.4.1 Control parameters ............................................. 25
7.4.2 Remote ............................................................... 28
7.4.3 Network .............................................................. 28
7.4.4 Alarm relays ........................................................ 29
7.4.5 Language settings .............................................. 29
7.4.6 Self-test .............................................................. 29
7.5 System messages...................................... 30
7.5.1 Occurrence of a malfunction ............................... 30
7.5.2 Display in case of errors ...................................... 30
8 Inspection and maintenance .......... 30
8.1 Maintaining the refrigerant circuit................ 31
8.2 Monitoring the cooling medium .................. 31
8.3 Cleaning the condenser ............................. 32
8.4 Cleaning the filter mat (accessories)............ 32
8.5 Draining the cooling medium tank .............. 32
9 Troubleshooting ............................. 33
9.1 List of system messages ............................ 34
10 Decommissioning and disposal ...... 36
10.1 Decommissioning....................................... 36
10.2 Disposal ..................................................... 36
5 Assembly and connection .............. 13
5.1 Dimensions ................................................ 13
5.2 Installation site requirements ...................... 13
5.3 Installing the chiller..................................... 14
5.4 Making the hydraulic connection................ 14
5.5 Connecting the cooling circuit (optional) ..... 15
5.6 Making electrical connection ...................... 15
5.6.1 Installing the power supply .................................. 16
5.6.2 Connecting the alarm relay query device ............. 16
5.6.3 External activation ............................................... 16
5.6.4 Room temperature sensor (accessories) ............. 16
5.7 Installing the filter mats (accessories).......... 16
2 Rittal Chiller Blue e+
11 Accessories ................................... 37
11.1 Connection set for air/water heat
exchangers ................................................ 37
11.2 Flow regulator valve.................................... 37
11.3 Textile filter mats ........................................ 37
11.4 Metal filter (aluminium filter)......................... 38
11.5 Cooling medium for chillers (ready-mix) ...... 38
11.6 Levelling feet .............................................. 38
11.7 Twin castors............................................... 38
11.8 Cross member ........................................... 38
11.9 External temperature sensor....................... 39
12 Appendix ....................................... 40
12.1 Block diagram............................................. 40
12.2 Spare parts................................................. 41
12.3 Technical specifications .............................. 42
12.4 Device drawings ......................................... 43
12.5 Operation of inverter pump ......................... 46
12.6 Declaration of Conformity............................ 47
Contents
EN
Rittal Chiller Blue e+ 3

1 Notes on documentation

EN
1 Notes on documentation

1.1 General

These instructions are aimed at installers and operators who are familiar with the installation and the operation of the chiller. It is very important to read and follow these assembly and operating instructions prior to commis­sioning. These are the original operating instructions.

1.2 CE conformity

Rittal GmbH & Co. KG confirms the conformity of the chiller with the European Union's Machinery Directive 2006/42/EC and EMC Directive 2004/108/EC. A corre­sponding declaration of conformity has been issued and enclosed with the unit.

1.3 Storing the documents

The assembly and operating instructions as well as all other applicable documents are an integral part of the product. They must be issued to everyone who works with the chiller and must always be available and on hand for operating and maintenance personnel.
1.4 Symbols used in these operating in­structions
The following symbols are used in this documentation:
Danger! A dangerous situation in which failure to comply with the instructions will result in death or severe injury.

1.5 Other applicable documents

Assembly and operating instructions exist as paper doc­uments and/or digital data carriers for the unit types de­scribed here and are enclosed with the equipment.
We cannot accept any liability for damage associated with failure to observe these instructions. Where applica­ble, the instructions for any accessories used also apply.

2 Safety notes

2.1 General

Please observe the following general safety notes when operating and installing the chiller:
Assembly, installation and maintenance must only be
carried out by qualified personnel.
Children and persons with limited cognitive/coordina-
tive abilities must not operate, maintain or clean the unit or be allowed to use it as a toy.
Only use original spare parts and accessories author-
ised by the manufacturer to ensure the protection and safety of the chiller. The usage of other parts will ren­der any liability void.
Do not make any changes to the chiller that have not
been agreed with and approved by the manufacturer.
It is also imperative that you observe the special safety
instructions for the individual activities in the individual chapters.

2.2 Risks in case of failure to observe the safety instructions

In case of failure to observe the safety notes, people, the environment and the chiller may be placed at risk. Failure to comply with the safety notes makes all claims for compensation void.
Warning! A dangerous situation which may cause
death or serious injury if the instructions are not followed.
Caution! A dangerous situation which may lead to
(minor) injuries if the instructions are not followed.
Note: Important notices and indication of situations which may result in material damage.
This symbol indicates an "action point" and shows that
you should perform an operation or procedure.
4 Rittal Chiller Blue e+
2.3 Safety instructions for assembly, in­spection and maintenance work
– The installation, commissioning and servicing of the
chiller must be carried out in strict compliance with the technical documentation for the chiller and in such a way that no potentially hazardous situations are al­lowed to occur.
– Cleaning and maintenance work on the chiller must
only be performed with the unit shut down. For this purpose, it is vital to ensure that the chiller is discon­nected from the power supply and is secured against switching back on. It is imperative that you observe the procedure for shutting down the chiller described in the assembly and operating instructions.
– All safety devices and protective equipment must be
reattached or put in a functional condition immediately
after the work is complete. – Modifications or changes to the chiller are not allowed. – Only appropriately qualified personnel as defined by
BGR500 chap. 2.35 / EN 378 are allowed to work on
the refrigerant circuit.
– Do not install the chiller without protection outside of
covered areas, or in an explosive or aggressive envi­ronment.
– Do not install the chiller on an unstable surface or a
surface that is not designed for the weight of the chill­er.
– Do not bypass any electrical safety devices to make it
possible to operate the chiller.

2.4 Unauthorised operation

The safety of the chiller supplied is only ensured if it is used properly (see section3.7 "Proper use, foreseeable misuse"). Under no circumstances should the limit val­ues specified in the technical data be exceeded. The chiller is not allowed to be used for the direct cooling of liquids that are used for foodstuffs (e.g. drinking wa­ter).
Any existing contact hazard protection for moving parts must not be removed from chillers while operational. Hazards due to electrical power, do not remove any switch box cover!
2 Safety notes
EN
Explosion hazard! The use of the chiller for cooling inflam-
mable or pyrophoric substances is pro­hibited.

2.5 Health risks due to the refrigerant R134a and the cooling medium

The refrigerant changes status during operation and be­comes pressurised. The R134a safety data sheet must be observed.
The cooling medium (additive) is a liquid. We suggest: "Cooling medium for chillers" (see section6.1 "Cooling medium water-glycol mixture"). The safety data sheet "Cooling medium for chillers" must be observed.

2.6 First aid measures

Please refer to safety data sheets R134a and "Cooling medium for chillers".
Note: Safety data sheets are available for down-
loading at www.rittal.com.

2.7 Fire-fighting measures

Suitable extinguishing agent
All known extinguishing agents can be used.

2.8 Safety measures and equipment

Ensure adequate ventilation.Hand protection: Safety gloves.Eye protection: Safety goggles.Body protection: Wear safety shoes when handling
pressurised gas bottles.
Rittal Chiller Blue e+ 5
EN
2 Safety notes

2.9 Potential hazards and how to avoid them

The following table provides an overview of other poten­tial sources of danger and how to avoid them.
Location Hazard Cause Precautionary measures
Device interior Severe personal
injury or damage to property
Device interior Personal injury or
damage to proper­ty
Device interior Inhalation of toxic
gases/materials
Device interior Risk for the prod-
uct
Device interior: Micro­channel condenser
Device interior: Hot or cold parts
Minor cuts Contact while cleaning the
Burns / frostbite Contact with parts with a
Hazard due to electrical equipment of the chiller
Electrical hazard while working on the chiller
Soldering work inside the chiller may release toxic gases due to the installed cooling circuit.
Liquid level after transport not in upright position
condenser (see sec­tion8.3 "Cleaning the condenser")
high or low surface tem­perature.
Recurrent testing of electrical equipment (Germany BGV A3)
The power to the chiller must be disconnect­ed via the main switch.
Maintenance may only be carried out by spe­cialist personnel. Before carrying out solder­ing work on the cooling circuit or in its immediate vicinity, the refrigerant should be drained from the chiller.
Only transport the chiller upright. Should the chiller be tilted during transportation, please wait some minutes before switching on again.
Wear safety gloves.
The chiller may only be opened by trained, qualified personnel.
Device interior: Cooling medium circuit
Device exterior Severe personal
Device exterior Personal injury or
Device exterior Cuts Contact with fan wheel Do not remove the protective cover around
Device exterior: Area around the chiller
Device exterior: Chiller with wheels
Tab. 1: Hazards and precautionary measures
Fungus and algae formation
injury or damage to property
damage to proper­ty
Major burns Fire caused by short-cir-
Personal injury or damage to proper­ty
Use of pure water as a cooling medium or refrig­erant.
The floor on which the chiller is installed is unsta­ble and unable to support its weight. The chiller tips over or the floor gives way.
Hazards when transport­ing or assembling the chill­er
cuiting or overheating of the electricity supply line to the chiller
The chiller starts to move due to unevenness of the floor surface.
Use a water-glycol mixture as your cooling medium. Rittal recommends the use of "Cooling medium for chillers" (ready-mix).
The weight of the chiller can be found in sec­tion12.3 "Technical specifications". Addi­tionally, please allow for the weight of the liquid in the tank (the capacity of the tank can likewise be found in section 12.3 "Technical specifications") and make sure that the floor is suitable for installation purposes.
Secure the chiller against any risk of tilting (eyebolts) when transporting or assembling.
the fan wheel.
Ensure that the cable cross-section and elec­tricity supply line comply with the valid regu­lations.
If the recooling system is equipped with wheels (option), they must be locked with brakes while operational.
6 Rittal Chiller Blue e+

3 Device description

5
4
2
3
1
16 15
14
13
11
12
10
9
6
7
8
Note: Specialist personnel are individuals who, by virtue of their training, education, experience and knowledge of the relevant provisions, regulations and measures for accident pre­vention and relating to the operating condi­tions, have been authorised by the owner or responsible individual to ensure the safety of the system, carry out all essential tasks, and are therefore in a position to identify and avert all potential threats.
3 Device description

3.1 General

Chillers are used for the central and economical cooling and supply of a cooling medium (water + glycol, see sec­tion6.1 "Cooling medium water-glycol mixture") in the event of physical separation between the place where cooling is required and the refrigeration. The cooling me­dium is supplied using a pipe system.
EN
Fig. 2: View from rear (3320200 and 3334300)
Key fig. 1 and fig. 2
1 Side air outlet, right 2 Side cover, right 3 Filler nozzle for cooling medium (behind louvred grilles) 4 Louvred grille for air inlet 5Display 6 Side cover, left 7 Side air outlet, left 8 Cooling medium connection, inlet 9 Tank drain nozzle (stop valve) 10 Adjustable overflow valve (bypass) 11 Rating plate 12 Cooling medium connection, return 13 Air outlet, rear 14 Radial fan 15 Master switch 16 Electrical interfaces
Fig. 1: View from front (3320200 and 3334300)
Rittal Chiller Blue e+ 7
EN
5
4
2
3
1
16 15
14
13
11
12
10
9
6
7
8
3 Device description
Key fig. 3 and fig. 4
1 Side air outlet, right 2 Side cover, right 3 Filler nozzle for cooling medium (behind louvred grilles) 4 Louvred grille for air inlet 5Display 6 Side cover, left 7 Side air outlet, left 8 Cooling medium connection, inlet 9 Tank drain nozzle (stop valve) 10 Adjustable overflow valve (bypass) 11 Rating plate 12 Cooling medium connection, return 13 Air outlet, rear 14 Radial fan 15 Master switch 16 Electrical interfaces
Note: The motor circuit-breaker of the cooling me-
dium pump is accessed by opening the roof plate. See also Q1 in section12.1 "Block di­agram".
The chiller is equipped with an open reservoir for the cooling medium.
Fig. 3: View from front (3334400)

3.2 General functional description

The chiller comprises four main components (see fig. 5): – Evaporator coil (item 12), – refrigerant compressor (item 13), – condenser (item 1) with fan (item 2), – control or expansion valve (item 4), which are connected together by pipes. A pressure
switch (item 14) limits the maximum pressure in the re­frigerant circuit. The refrigerant R134a (CH2FCF3) is chlorine-free. Its Ozone Depletion Potential (ODP) is 0. A filter drier (item 3) which is integrated into the hermet­ically sealed refrigerant circuit provides effective protec­tion against moisture, acid, dirt particles, and foreign bodies. A temperature control with temperature probe (item 6) ensures that the cooling medium is maintained at a preset setpoint temperature.
In the evaporator coil (item 12), the liquid refrigerant is converted to a gaseous state. The heat necessary for this purpose is taken from the cooling medium in the
Fig. 4: View from rear (3334400)
8 Rittal Chiller Blue e+
plate heat exchanger, which has the effect of cooling the cooling medium. The refrigerant is compressed in the compressor (item 13). As a result the refrigerant has a higher temperature than the ambient air. The DC inverter technology enables load-specific speed control of the compressor motor, so that only the power actually needed is supplied.
This heat is dissipated to the ambient air over the surface of the condenser (item 1), resulting in the refrigerant liquefying again. A water-cooled condenser may option­ally be used (see section3.6.6 "Water-cooled condens­er").
3 Device description
1
12
2
13
14
11
9
7
8
10
6
3
4
P
S
5
F
D
E
B
C
A
50 101520253035
6
5
4
3
2
1
P
Q
The refrigerant is injected into the evaporator (item 12) via an electronic expansion valve (item 4), causing it to expand and as a consequence is able to absorb the heat from the cooling medium (water or water-glycol mixture).
The cooling medium is pumped to the equipment in an additional circuit via the cooling medium tank (item 10) and the cooling medium pump (item 9). The flow sensor (item 11) ensures that the evaporator (item 12) is pro­tected against freezing and running dry if the flow rate is too low. The level switch (item 5) emits a warning if the level in the cooling medium tank is too low. The inlet temperature of the cooling medium (water or water-gly­col mixture) is regulated using the temperature sensor (item 6) on the water outlet. Optionally, an inverter pump may also be used, so that the cooling medium pump is also speed-controlled.
A layout drawing of the refrigerant circuit may be found in fig. 5.

3.3 Control

The chillers are fitted with a controller for setting the functions of the chiller. Operation using this controller is described in section7 "Operation". Within the compressor speed range from 25...100%, the compressor is in continuous control mode. During con­tinuous control mode, the control accuracy of the water inlet temperature is ±0.5 K or better. At smaller loads re­quiring a speed of less than 25%, the compressor switches to cycle mode, and the control accuracy of the water inlet temperature is adjusted to ±2 K (refer to the performance curves on the Rittal website).

3.4 Characteristic curves

3.4.1 Characteristic curves of pump

Characteristic curves measured under the following conditions:
– Ambient temperature (T – Medium temperature (T – Cooling medium "water"
) = 32°C
a
) = 18°C
w
EN
Fig. 5: Schematic diagram of refrigerant circuit
Key
1 Condenser, air-cooled 2 Condenser fan (radial fan) 3 Filter dryer 4Expansion valve 5 Fill level monitoring 6 Temperature sensor 7 Fill nozzle 8 Tank drain nozzle 9 Cooling medium pump 10 Cooling medium tank 11 Flow sensor 12 Evaporator (plate heat exchanger) 13 Compressor 14 Pressure-operated switch
Rittal Chiller Blue e+ 9
Fig. 6: Characteristic curves
Key fig. 6
A 3320200 standard pump 50 Hz B 3320200 standard pump 60 Hz C 3320200 reinforced pump 50 Hz (option) or
3334300 and 3334400 standard pump 50 Hz
D 3320200 reinforced pump 60 Hz (option) or
3334300 and 3334400 standard pump 60 Hz E 3334300 and 3334400 reinforced pump 50 Hz (option) F 3334300 and 3334400 reinforced pump 60 Hz (option) P External static pressure [bar] Q Delivery flow [l/min]
The flow speed of the circulating medium is monitored with a flow sensor. The sensor has a preset alarm threshold and a variable warning threshold that can be
3 Device description
EN
set by the operator. When the warning threshold is reached, a message is produced, and when the alarm threshold is reached, a fault is generated.
If the flow rate of the circulating medium during opera­tion drops below 4 l/min, the integrated flow sensor will trip.

3.4.2 Performance diagrams

The performance diagrams can be found on the Rittal website.

3.5 Safety devices

– In the cooling circuit, the chiller has a type-tested pres-
sure monitor (to EN 12263) which switches off the chiller if the maximum admissible pressure is exceed­ed. Once the pressure drops back below the admissi­ble pressure, the unit will automatically resume opera­tion.
– Temperature monitoring prevents the evaporator coil
from icing over. The compressor gradually reduces the output within the range 100...25%. If the risk of icing persists for more than 2 minutes, the compressor will switch off completely. At higher temperatures, the unit automatically returns to control mode.
– The compressor motor and the fan motor are moni-
tored and protected by the inverter to prevent over­loading.
– The cooling medium pump has a motor circuit-breaker
to prevent overcurrent and short-circuits.
– To ensure smooth-running and reliable operation (for
example after reaching the setpoint temperature or af­ter a fault), the compressor automatically switches back on after a delay.
– The chiller has floating contacts on terminals 8 to 10 of
the signal connector (X2), via which system messages from the device may be polled, e.g. using a PLC (2 x normally closed or normally open contacts).

3.6 Options

3.6.1 Inverter pump

The cooling medium pump can be designed as an in­verter pump. In such cases, the pump is speed-con­trolled depending on the actual cooling medium demand (see section12.5 "Operation of inverter pump").

3.6.2 Reinforced pump

For applications requiring a higher cooling medium throughput or pressure, the cooling medium pump can be designed in a higher output category.

3.6.3 Outdoor

The "Outdoor" option allows the chiller to be sited out­side. To this end, the chiller is coated with a special spray-finish. Outdoor siting means that the air at the sys­tem installation site is not additionally subject to waste process heat.
For outdoor siting, a rain canopy should be provided by the customer to protect the chiller from downpours.
Note: With outdoor siting of the chiller, it is impor-
tant to ensure that a suitable cooling medium is used (see section6.2 "Filling the cooling medium"). This is the only scenario in which operation to -20°C is admissible.

3.6.4 Oil/emulsion

Oil or an emulsion may also be used as a cooling medi­um, instead of the water/glycol mixture used as stand­ard. In such cases, the components in the cooling circuit are adapted accordingly, and the thermal capacity of the cooling medium must be stored in the control system.
Note: For the purpose of these instructions, we
have assumed that a water/glycol mixture is used as the cooling medium.

3.6.5 Free Cooling

The "Free Cooling" option allows you to cool without the refrigerant circuit in so-called hybrid mode. If this type of cooling is preselected in the control system, with out­door siting of the chiller, the system first attempts to use only the (cold) ambient air to cool the cooling medium. If this is no longer possible because the external tempera­tures are too high, it automatically activates the conven­tional cooling circuit to supply the required cooling me­dium temperature.

3.6.6 Water-cooled condenser

The condenser may be water-cooled. In such cases, a separate cooling circuit must be connected to the con­denser.

3.6.7 Tank heating

A tank heater may be installed to pre-heat the cooling medium or for frost protection. A setting is made in the control system to determine when the tank heater is switched on and off.

3.7 Proper use, foreseeable misuse

The chiller is only used for cooling water-glycol mixtures. Any other use is deemed improper. One exception to this is operation with the "oil/emulsion" option (see sec­tion3.6.4 "Oil/emulsion").
When using other fluids, please refer to the technical specifications in the appendix, or contact the manufac­turer. Under no circumstances should the specified lim­its in the technical data be exceeded.
The chiller is state of the art and built according to rec­ognised safety regulations. Nevertheless, improper use can pose a threat to the life and limb of the user or third
10 Rittal Chiller Blue e+

4 Transport

parties, or result in possible damage to the system and other property.
Consequently, the chiller must only be used properly and in a technically sound condition! Any malfunctions which impair safety should be rectified immediately.
Proper use also includes the observance of the docu­mentation provided and compliance with the inspection and maintenance conditions, and strictly professional use as defined in DIN EN 61000-3-2.
Rittal GmbH & Co. KG is not liable for any damage which may result from failure to comply with the documenta­tion provided. The same applies to failure to comply with the valid documentation for any accessories used.
Inappropriate use may be dangerous. Examples of inap­propriate include:
– Use of the chiller for cooling flammable or combustible
substances.
– The chiller must never be used for the direct cooling of
liquids used in the food industry (e.g. drinking water). – Use of impermissible tools. – Improper operation. – Improper rectification of malfunctions. – Use of accessories not approved by Rittal GmbH &
Co. KG.

3.8 Supply includes

Qty. Description
1Chiller
1 Shipping bag with
1 – Assembly and operating instructions
1 – Connector
1 – Signal connector
4 – Eyebolt and plastic washer
2 – M25 screw connection
1 – M20 screw connection
Tab. 2: Scope of supply

4.2 Unpacking

Only transport the chiller in its original packaging ma-
terial before commissioning for the first time.
Remove the packaging materials from the chiller.
Note: After unpacking, the packaging materials must be disposed of in an environmentally friendly way.
Check the chiller for any damage that may have oc-
curred during transport.
Note: Damage and other faults, e.g. incomplete de-
livery, should be reported immediately, in writing, to the shipping company and to Rittal GmbH & Co. KG.
Check the supply contents for completeness (see sec-
tion 3.8 "Supply includes").

4.3 Transport

If the chiller is stored or transported at temperatures be­low freezing, return to room temperature before com­missioning. This instruction also applies to the external condenser circuit for a water-cooled condenser (option).
When transporting the chiller, please make allowance
for the weight specified in section12.3 "Technical specifications".
Use lifting gear with a suitable load capacity.If it is necessary to move the chiller in the factory, you
must disconnect all connections on the chiller.
Before transporting, empty the water circuit and tank
(see section8 "Inspection and maintenance").
Prevent excessive vibration.Only transport the chiller upright.Only transport the chiller on the pallet supplied with the
chiller or with the eyebolt provided (fig. 7, item 1). Serrated washers for earthing are fitted to the eyebolts in the mounted state. After transportation, the eyebolts are exchanged for the pan-head screws provided. Plas­tic washers are included in the bag of accessories to protect the paint.
Protect the chiller from unintentional movement (e.g.
when being transported by vehicle).
EN
4Transport

4.1 Delivery

The chiller is supplied in a packaging unit in a fully as­sembled state.
Check the packaging carefully for signs of damage.
Traces of oil on damaged packaging indicate a loss of refrigerant and/or a leak in the chiller. Any packaging damage may be the cause of a subsequent functional failure.
Rittal Chiller Blue e+ 11
EN
1
1
1
1
4 Transport
Fig. 7: Eyebolt for transportation (3320200)
12 Rittal Chiller Blue e+
5 Assembly and connection
710 mm450 mm
1020 mm
450 mm
710 mm

5.1 Dimensions

5 Assembly and connection

EN
450 mm
820 mm
Fig. 8: Dimensions 3320200 and 3334300
710 mm
450 mm
710 mm
Fig. 9: Dimensions 3334400

5.2 Installation site requirements

– The chiller must be adequately protected from external
weather conditions.
– If the ambient air contains a high concentration of dust
or oily substances, the chiller should be fitted with a metal filter (see section11.4 "Metal filter (aluminium fil­ter)").
Rittal Chiller Blue e+ 13
– The supporting surface should be flat and sufficiently
robust to hold the weight (see section12.3 "Technical
specifications") during operation. – If the chiller is sited outdoors, the "Outdoor" option
must be used (see section3.6.3 "Outdoor"). – The ambient temperature must lie within the limit val-
ues indicated in the technical specifications (see sec-
tion12.3 "Technical specifications").
5 Assembly and connection
300 mm
EN
– In order to prevent performance losses caused by
pressure drops in the pipework, the chiller should be sited as close as possible to the equipment.
– At least one of the openings (left or right) must be freely
accessible to enable the unhindered expulsion of hot air (see fig. 11). To allow connection of the supply lines and facilitate maintenance and repair work, the mini­mum distances shown under fig. 10 should be ad­hered to.
– In order to avoid an "air short-circuit" (mixing of air in-
take and waste air) and ensure full cooling perfor­mance, the minimum distances shown under fig. 10 should likewise be adhered to.
300 mm 800 mm
Caution! The connection of an air intake / waste air duct is inadmissible.
To prevent performance losses, do not install the chill-
er near any form of heating.
Outdoor siting
Chillers must be installed such that they cannot become damaged by internal traffic and transport operations.

5.3 Installing the chiller

Install the chiller on an even, firm surface. The maxi-
mum permissible deviation from the vertical is 2°.
Avoid the production of noise due to vibration (vibra-
tion dampers, sheets of foam rubber).

5.4 Making the hydraulic connection

Caution! Risk of damage to the cooling medium pump due to soiling in the cooling medi­um circuit! Flush the cooling medium cir­cuit prior to connecting the chiller.
Fig. 10: Minimum distances, front/rear
Fig. 11: Minimum distances, sides
Ensure the room is adequately ventilated by installing
the chiller such that the warm exhaust air does not heat the room excessively.
In case of installation in a "small" room, it is imperative
that you provide forced ventilation, as otherwise the heat dissipated will build up.
The cooling medium outlet (fig. 2 or fig. 4, item 8) on the chiller must be connected to the cooling medium inlet on the equipment to be cooled. At the same time, the cool­ing medium inlet (fig. 2 or fig. 4, item 12) on the chiller must be connected to the cooling medium outlet on the equipment to be cooled. Please observe the following:
– To avoid condensation, always connect the equip-
ment using insulated pipelines and/or hoses.
– The nominal width of the piping must correspond at
least to the nominal width of the media connections on the chiller.
– The cooling medium infeed to the chiller must be pres-
sureless, because the tank used in the system is open
to the atmosphere. – Never connect the chiller to the drinking water supply. – The pipework must be approved for the maximum
pressure expected (see section12.3 "Technical spec-
ifications").
Note: The use of steel pipes or galvanised steel
pipes is inadmissible.
Prior to commissioning, it is imperative that the cooling medium pump is filled with cooling medium and bled (see section6.3 "Bleeding the cooling medium pump").
14 Rittal Chiller Blue e+
5 Assembly and connection
Caution! An insufficient flow rate will trigger the safety devices in the chiller. Pay atten­tion to the minimum pressure required and the minimum flow rate required (see section12.3 "Technical specifications").
If the cooler on the equipment to be cooled is higher than the chiller, we recommend installing a non-return valve in the feed as well as a solenoid valve in the cooling medium circuit return to prevent the tank from overflow­ing.
A bypass valve should be connected between the inlet and return to protect the cooling medium pump. This opens automatically, for example, if the equipment cycle is shut off. Section6.5 "Adjusting the bypass valve" de­scribes how to set the bypass valve.

5.5 Connecting the cooling circuit (optional)

If the chiller is equipped with the "water-cooled con­denser" option (see section3.6.6 "Water-cooled con­denser"), a cooling water supply must additionally be connected to the condenser.
Additionally make the cooling water connections to
the condenser.

5.6 Making electrical connection

When carrying out the electrical installation, observe all
applicable national and regional regulations as well as the regulations from the responsible utility company.
– Electrical installation must only be carried out by a
qualified electrician who is responsible for compliance with the existing standards and regulations.
– All cables routed into the wiring compartment have to
be insulated for the maximum voltage of the power supply.
Note: The mains supply must be of a shielded de-
sign to guarantee the level of EMC protec­tion.
– The cable shielding can contact the earth
terminal to the enclosure inside the con­nection box (fig.13, item 1).
– To ensure the proper functioning of internal presso-
stats in the event of a malfunction, a slow (time delay) line fuse of no less than 15 A is required.
– Low-noise potential equalisation must be guaranteed
with the mains connection. As a general principal, the chiller must be integrated into the building's potential equalisation system.
– The conductor cross-sections of the power cable
must be selected according the rated current (see rat­ing plate).
– The connection must be made with the field rotating
clockwise. The direction of rotation of the field can be measured at the connection terminals L1, L2 and L3. Connect with a clockwise rotating field to ensure that the cooling medium pump motor rotates in the correct direction.
Overvoltage protection and supply line load
– The chiller does not have its own overvoltage protec-
tion. Measures must be taken by the operator at the supply end to ensure effective lightning and overvolt­age protection.
– The mains voltage must not deviate by more than the
tolerance specified in section12.3 "Technical specifi­cations".
– The chiller and its power electronics are designed in
accordance with overvoltage category III. If the com­bined output of the frequency converters, power con­verters or transformers in the network where the de­vice is being operated is >70 kVA, the customer must connect a Class II surge voltage protector in the mains supply line upstream of the chiller. The surge voltage protector must be designed to EN 61800 -1. The fol­lowing values may be assumed as starting-points for the design:
Transformers, power electronics
70 kVA…100kVA 40J
100 kVA…200kVA 80J
200 kVA…400kVA 160J
400 kVA…800kVA 320J
Tab. 3: Design of the surge voltage protector
Assumed discharge energy
EN
Connection data
– The connected voltage and frequency must corre-
spond to the ranges stated on the rating plate. The units support multiple voltages.
– The chiller must be connected to the mains via an all-
pole isolating device.
– If a motor circuit-breaker or circuit-breaker is used, it
should be selected in accordance with EN 60898-1 (tripping characteristic type D).
Rittal Chiller Blue e+ 15
Interfaces
If you would like system messages from the chiller to be evaluated via the alarm relay, you should also connect a suitable low-voltage cable to the X2 signal connector (see section5.6.2 "Connecting the alarm relay query de­vice"). If you require remote activation of the chiller, this can likewise be achieved via the X2 signal connector (see section5.6.3 "External activation") and appropriate pro­gramming (see section7.4.2 "Remote").
Loading...
+ 33 hidden pages