5
Notes
Enclosure heaters with fans
Model No. SK 110 V 3105.410 3105.420 3105.430
Model No. SK 230 V 3105.380 3105.390 3105.400
Dimensions mm
W
H
D
103
200
103
103
200
103
103
200
103
Hole distance mm 171
Rated operating voltage V, Hz 110 or 230 V, 50/60
Continuous thermal output
at T
u
= 10 ûC
250 W
1)
400 W
1)
800 W
1)
Pre-fuse gG for 110 V 4 A 6 A 10 A
Pre-fuse gG for 230 V 4 A 6 A 6 A
1)
Output with fan.
We reserve the right to make technical modifications.
A
Enclosure heaters without fans
Model No. SK 3105.310 3105.320 3105.330 3105.340 3105.350 3105.360 3105.370
Dimensions mmWH
D
45
120
46
45
120
46
64
155
56
64
155
56
64
230
56
90
165
75
90
180
75
Hole distance mm 42 60
Rated operating
voltage Volt, Hz
110 – 240 V, 50/60
Continuous thermal
output at T
u
= 10 ûC
8 – 10 W 18 – 20 W 23 – 30 W 49 – 50 W 63 – 75 W 86 – 100 W
130 – 150 W
Pre-fuse T 2 A 4 A
Special voltages available on request. We reserve the right to make technical modifications.
A
1. Technical speciÞcations
2. Mounting
The panel heater is fitted vertically, i.e. with
the connection terminal or fan facing downwards. To permit the required convection, a
minimum clearance to the adjacent components must be observed. A safety clearance
of at least 300 mm must be left above the
heater in the case of heaters with fans, and
100 mm for heaters without fans. (For both
a thermal safety clearance to the sides of
60 mm and 100 mm at the bottom is
required).
If these clearances are observed, the ambient temperature does not rise above 65 ˚C.
2.1 Snap-type fastening onto a 35 mm
support rail DIN EN 50 022 (Fig. 1.1).
2.2 Screw fastening onto the mounting plate
(Fig. 1.2).
It should be ensured that the heater and connection cables are mounted firmly and securely. Electric cables must not touch the body
of the heater fan and must not be routed
directly past the hot air outlet.
The heater must not be mounted in the vicinity of flammable materials.
Rittal enclosure heater assembly instructions
EN