Rishabh Instruments RISH Master 3430i, RISH Master 3480 Operating Manual

RISH Master 3430i
RISH Master 3430i
Operating Manual
Touch Screen Digital Multi-function Meter
Installation & Operating Instructions
INDEX
Section Contents
2. Measurement Reading Screens
3. Programming
3.1 Password Protection
3.2 Menu selection
3.2.1 System Parameter selection screen
3.2.2 Communication Parameter selection screen
3.2.1.1 System type
3.2.1.2 Potential transformer Primary value
3.2.1.3 Current transformer Primary value
3.2.1.4 Current transformer Secondary value
3.2.1.5 Auto Scrolling
3.2.1.6 Low current noise cutoff
3.2.1.7 Energy On Resolution
3.2.1.8 Energy digit reset count
3.2.1.9 Energy Update Rate
3.2.2.1 Address Setting
3.2.2.2 RS 485 Baud rate
3.2.2.3 RS 485 Parity selection & Stop bit Selection
3.1.1 Change Password
1
3.2.4.1 Relay 1 output selection menu
3.2.4.2 Relay 2 output selection menu
3.2.4.3 Parameter setting for Analog Output-1
3.2.4.4 Parameter setting for Analog Output-2
Relay Output
6.
5.
Analog Output
3.2.5 Brightness & Contrast
4. Touch screen calibration.
3.2.6 RGB Color Code
9.
Installation
9.1
EMC Installation Requirements
9.2
9.3
Wiring
9.4 Auxiliary Supply Fusing
Earth / Ground Connections
8.
Phaser Diagram
RS 485 (Modbus) output
7.
Case Dimensions and Panel Cut-out
11.
Specication
10.
Connection Diagrams
12.
Connection for Optional Pulse output / RS 485 /Analog Ouput
Pulse output
6.1
3.2.4 Output Option selection screen (menu)
3.2.3.1 Resetting Parameter
3.2.3 Reset Parameter selection screen
9.5
9.6
2
1. Introduction
This instrument is a panel mounted 96 x 96mm DIN Quadratic Digital metering system for the measurement of important electrical parameters like AC voltage, AC Current, Frequency, Power, Energy(Active / Reactive / Apparent) . The instrument integrates accurate measurement of technology (All Voltage & Current measurements are True RMS upto 15th Harmonic) with 320x240 Pixels touch screen TFT LCD display.
This instrument can be congured and programmed at site for the following:
PT Primary, CT Primary, CT Secondary (5A or1A) and 3 phase 3W or 3 Phase 4W system.
The front panel has a 3.5” Touch Screen through which the user can move across the available measurement readings, reset the energy, Min/Max (System Voltage and System Current) and congure the
product settings.
3
TABLE 1:
Measured Parameters
System Voltage System Current
Frequency
Voltage VL1-N(4wire only) Voltage VL2-N(4wire only) Voltage VL3-N(4wire only) Voltage VL1-L2 Voltage VL2-L3 Voltage VL3-L1 Current L1 Current L2 Current L3
Units of
Volts
Amps
Hz
Volts Volts Volts Volts Volts
Volts Amps Amps
Neutral Current ( 4 wire only )
Amps Amps
Measurement
Active Import Energy (8 Digit resolution)
kWh kWh
Active Export Energy (8 Digit resolution)
Active Power Reactive Power
Apparent Power Power Factor
Phase Angle (1P2W/3P4W)
Kwatts
KVAr
KVA
Degree
kVArh
Reactive Import Energy (8 Digit resolution)
kVArh
Reactive Export Energy (8 Digit resolution)
kVAh
Apparent Energy (8 Digit resolution)
( for 3 / 4 wire)
( for 3 / 4 wire)
( for 3 / 4 wire)
( for 3 / 4 wire)
( for 3 / 4 wire)
( for 3 / 4 wire)
4
Measured Parameters
Units of
Measurement
I1 THD I2 THD
V1 THD* V2 THD*
V3 THD*
%
I3 THD System Voltage THD System Current THD
% %
% % %
%
% Pictorial representation of Phasor Diagram (1P2W / 3P4W) Pictorial representation of Voltage Waveform Pictorial representation of Current Waveform Pictorial representation of VA Waveform per phase(1P2W /3P4W)
*Note : THD Parameters are L-N in case of 3P 4W & L-L in case of 3P 3W .
( for 3 / 4 wire)
( for 3 / 4 wire)
( for 3 / 4 wire)
( for 3 / 4 wire)
( for 3 / 4 wire)
( for 3 / 4 wire)
2. Measurement Reading Screens
In normal operation the user is presented with one of the measurement reading screens out of several screens. These screens from particular submenu may be scrolled through one at a time in incremental order by touching the “ key” and in decremental order by touching “ key” on that screen.
5
APPARENT
ENERGY
REACTIVE EXPORT
ACTIVE
REACTIVE
EXPORT
IMPORT
ACTIVE
IMPORT
RESET
COMMUNICATION
MAIN MENU
SYSTEM
SYSTEM TYPE
PT PRIMARY
PT SECONDARY
CT PRIMARY
CT SECONDARY
AUTO SCROLL
(Sec 3.2.1.1)
(Sec 3.2.1.2)
(Sec 3.2.1.3)
(Sec 3.2.1.4)
(Sec 3.2.1.5)
(Sec 3.2.1.7)
CURRENT
VOLTAGE
SYSTEM
A
A
FREQUENCY
SYSTEM
SYSTEM
PARAMETERS
SYSTEM Max.
SYSTEM Min.
VALUES
VALUES
SYSTEM
POWER
THD.VOLTAGE
AND CURRENT
PHASE VOLTAGE
% THD
LINE CURRENT
L1 PHASE
L2 PHASE
L3 PHASE
NEUTRAL
(Sec 3.2.4)
POWER
CHANGE
(Sec 3.1)
ENERGY
AA
A
B
LINE CURRENT
% THD
LINE - NEUTRAL
LINE - LINE
VOLTAGE
VOLTAGE
WAVEFORM
WAVEFORM
L3 PHASE
L2 PHASE
L1 PHASE
WAVEFORM
WAVEFORM
WAVEFORM
POWER
POWER
POWER
Parameter Screens Single Phase
PHASOR
DIAGRAM
POWER
FACTOR
CURRENT
POWER
PHASE
ANGLE
FACTOR
6
APPARENT
ENERGY
REACTIVE EXPORT
REACTIVE IMPORT
EXPORT
ACTIVE
ACTIVE
IMPORT
RESET
PARAMETERS
COMMUNICATION
MAIN MENU
SYSTEM
SYSTEM TYPE
NOISE CUTOFF
(Sec 3.2.1.1)
LOW CURR.
CURRENT
VOLTAGE
SYSTEM
Max. VALUES
PHASER
A
A
FREQUENCY
FACTOR
SYSTEM
SYSTEM POWER
PARAMETERS
Min. VALUES
SYSTEM
POWER
THD:VOLTAGE
& CURRENT
(Sec 3.2.2.3)
PHASE
% THD
Line Current
Neutral Current
OPTIONS
(Sec 3.2.4)
POWER
CHANGE
PASSWORD
(Sec 3.1)
ENERGY
AA
A
B
LINE CURRENT
% THD
DIAGRAM
Line - Line
VOLTAGE
Line - Neutral
VOLTAGE
NOTE: SCREENS MARKED WITH * ARE AVAILABLE
*
*
*
*
*
(Sec 3.2.2.3)
(Sec 3.2.2.3)
WAVEFORM
WAVEFORM
CURRENT
L3 PHASE
WAVEFORM *
L2 PHASE
WAVEFORM *
L1 PHASE
WAVEFORM *
POWER
POWER
FACTOR
SYSTEM
L3 PHASE
POWER *
L2 PHASE
POWER
L1 PHASE
POWER
PHASE
ANGLE *
ONLY IN 4W SYSTEM (NOT IN 3 WIRE SYSTEM)
Parameter Screens 3 Phase
SYSTEM
SYSTEM
VOLTAGE
7
Setup Parameter Screens
PULSE
OUTPUT
ENERGY
PULSE
PULSE
DURATION
RATE
ANALOG OUTPUT 1
ANALOG OUTPUT 2
selection)
(Acc. To Table 2)
(Analog 2 parameter
RS485 PARITY
PT PRIMARY
CT PRIMARY
CT SECONDARY
AUTO SCROLL
NOISE CUTOFF
LOW CURR.
RS485
BAUD RATE
RS485
ADDRESS
(Analog 1 parameter
selection)
(Acc. To Table 2)
RESET MAX VOLTAGE & CURRENT RESET MIN VOLTAGE & CURRENT
RESET ALL
PASSWORD
(Sec 3.2.1)
PARAMETERS
PARAMETERS
COMMUNICATION
PARAMETERS
SYSTEM TYPE
BRIGHTNESS
& CONTRAST
CHANGE
PASSWORD
RESET
PARAMETERS
OPTIONS
OUTPUT
RELAY
RELAY
OUTPUT 1
OUTPUT 2
RESET ALL ENERGIES
RESOLUTION
ENERGY
RESET COUNT
UPDATE RATE
ENERGY DIGIT
ENERGY
RGB COLOR CODE
SYSTEM
8
3.1. Password Protection
Password protection can be enabled to prevent unauthorised access to set-up screens, by default password is “0000”.
Password protection is enabled by selecting any four digit number.
3. Programming
The following sections comprise step by step procedures for conguring the instrument for individual user requirements.
To access the set-up screens touch on the “ SETUP ” icon in Main Menu. This will take the User into the Password Protection Entry Stage(Section 3.1).
After touching “ SETUP” icon Password protection screen is displayed. Screen consists of 0 to 9 digit input keypad for entering the password very similar to any calculator in touchscreen mobile.
“Enter Password” is displayed on screen at start so that user can enter
password using displayed keypad.
Touching “ key” will display 1 in display area, similarly user can enter remaining 3 digits.
For deleting any digit while entering password, user can touch
“ key”.
DEL
ENTER
ENTER
1
After entering the complete password user needs to conrm password by touching “ key’’.
If Entered password is correct then “Password Accepted” is displayed on screen & user will on
screen & user will enter into setup menu.
Password conrmed.
If Entered password is wrong then “Password Rejected” is displayed on screen & user need to re-enter the password
Password Incorrect.
After wrong password is entered, user needs to touch “ key ” for trying another password.
9
Change Password Option is the second last option in list of “SETUP” submenu, so can be accessed by a simple touch on “ Change Password” button.
In this screen user rst needs to enter the current password.
3.1.1 Change Password
& now user can enter the new 4 digit password.
After input of correct password,“PASSWORD ACCEPTED”is displayed
After entering new password user needs to touch “ key” to
After conrming “PASSWORD CHANGED” is displayed on screen,
which ensures successful changing of the password.
New Password conrmed.
conrm.
3.2 Menu selection.
After entering in the SUBMENU 6 - SETUP, user will be asked to enter password & after input of correct password list of following parameters will be displayed on screen :-
3.2.1 SYSTEM PARAMETERS
3.2.2 COMMUNICATION PARAMETERS
ENTER
10
Touching on SYSTEM PARAMETER will open the system parameters list screen.Then these
touching the “ key” and in decremental order by touching “ key” on given touch screen.
screens from particular parameter may be scrolled through one at a time in incremental order by
3.2.1 System Parameters Selection
After entering in the “SYSTEM PARAMETERS”, List of following parameters will be displayed :-
3.2.1.1 SYSTEM TYPE
3.2.1.2 PT PRIMARY
3.2.1.3 CT PRIMARY
3.2.1.4 CT SECONDARY
3.2.1.5 AUTO SCROLL
3.2.1.6 LOW CURRENT NOISE CUTOFF
3.2.3 RESET PARAMETERS
3.2.4 OUTPUT OPTIONS
3.2.5 BRIGHTNESS & CONTRAST
3.2.1.1 System Type
on screen. Touching radio button in front of particular type will select
This screen is used to set the system type .
Two types: 3 phase 3 wire & 3 phase 4 wire system are displayed
that type.
Touch on “ key” will conrm the system type.
return to previous menu.
Touching the “ key” will keep the old selected setting and will
Note : If system type is changed, relay parameter selection & analog output selection
will be set to NONE.
3.2.1.7 ENERGY RESOLUTION
3.2.1.8 ENERGY DIGIT RESET COUNT
3.2.1.9 ENERGY UPDATE RATE
SYSTEM TYPE
3-PHASE 4 WIRE FOR 3 PHASE STAR CONNECTED LOAD
3-PHASE 3 WIRE FOR 3 PHASE DELTA CONNECTED LOAD
OK
BACK
OK
BACK
11
Here again 0 to 9 digit input keypad is provided to set value of PT
Primary, & user can conrm this value with a simple touch “
3.2.1.2 Potential Transformer Primary Value
The nominal full scale voltage will be displayed as Line to Line Voltages for 3 Phase 3 wire and
This screen can be accessed only from system parameters list menu.
key”. “ key” is used to multiply value by 1000.
In case presently displayed Potential Transformer Primary value together
with the Current Transformer Primary value, previously set, would result
in a maximum power of greater than 666.6 MVA per phase,”Invalid
value” will be displayed. Then the valid range will be displayed.
Valid range of PT primary setting value is from
display “INVALID VALUE” followed by correct
100V L-L to 692.8KV L-L.
ENTER
K
3 Phase 4 wire and 1 Phase 2 wire for Single Phase.
If value outside the range is entered, It will
3.2.1.3 Current Transformer Primary Value
The nominal Full Scale Current that will be displayed as the Line currents. This screen enables the user to display the Line currents inclusive of any transformer ratios, the values displayed representthe Current in Amps.
In case presently displayed Current Transformer Primary Value together with the Potential Transformer Primary Value results in a
Here again 0 to 9 digit input keypad is provided to set value of CT
Primary & user can conrm this value with a simple touch on
This screen can be accessed only from system parameters list menu.
“ key”. “ key” is used to multiply value by 1000.
ENTER CT PRIMARY VALUE
CT PRIMARY
ENTER
K
restricted to 1157A.
maximum power of greater than 666.6 MVA, “invalid value” will be displayed. Example:
If primary value of PT is set as 692.8kV L-L (max value) then primary value of Current is
range of parameter.
12
The “Maximum Power” restriction of 666.6 MVA refers to 120% of nominal current and 120% of nominal voltage, i.e, 462.96 MVA nominal power per phase.
Valid range of CT primary setting value is from 1 to 9999. If
value outside the range is entered, It will display “INVALID VALUE”
followed by correct range of parameter.
INVALID VALUE
CT PRIMARY
3.2.1.4 Current Transformer Secondary Value
This screen is used to set the secondary value for Current Transformer.
Touching radio button in front of particular option will select that option.
Two options: 1 AMPERE & 5 AMPERE are displayed on screen.
Touch on “ key” will conrm the setting. Touching the
“ key” will keep the old selected setting and will return
to previous menu.
OK
OK
BACK
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
V
VVV
0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
V
VVV
0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
V
VVV
0.000
0.000
CT SECONDARY
5 AMPERE
1 AMPERE
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
V
VVV
0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
V
VVV
0.000
0.000
CT SECONDARY
1 AMPERE
5 AMPERE
OK
BACK
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
VVVV
0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
VVVV
0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
VVVV
0.000
0.000
CT SECONDARY
1 AMPERE
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
VVVV
0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
VVVV
0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
VVVV
0.000
0.000
AUTO - SCROLL
ALL
VOLTAGE
POWER
NONE
SYSTEM
CURRENT
ENERGY
OK
BACK
OK
OK
BACK
3.2.1.5 Auto Scrolling
This screen allows user to enable screen scrolling. Seven options :
POWER, ENERGY & NONE are displayed on screen. Touching radio
ALL, SYSTEM, VOLTAGE, CURRENT
button in front of particular option will select that option. Selecting
Touch on “ key” will conrm the setting.
particular option means, only screens which are under that submenu will be scrolled automatically. Selecting NONE will disable Auto-Scroll.
Touching the “ key” will keep the old selected setting and will return to previous menu.
13
3.2.1.6 Low Current Noise Cutoff.
This screen allows the user to set Low noise current cutoff in mA.
screen. Touching radio button in front of particular option will
Two options, 0 MILLI-AMPERE & 30 MILLI-AMPERE are displayed on
select that option.
Touch on “ key” will conrm the setting.
and will return to previous menu.
Touching the “ key” will keep the old selected setting
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
CT SECONDARY
5 AMPERE
1 AMPERE
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
LOW CURRENT NOISE CUTOFF
0 MILLI-AMPERE
30 MILLI-AMPERE
OK
BACK
BACK
OK
OK
While in Auto-scrolling mode, touch sense for entire screen will be disabled except for the top right most corner where “A” symbol would be displayed stating that meter is in Auto­scroll mode. Touching on “A” will show two options “ON” and “OFF”. Touching on “ON” will continue auto scrolling & touching on “OFF” will stop auto-scrolling & return to normal mode.
BACK
OK
OK
depending as per the user’s requirement . This setting is applicable for all types of energy.
3.2.1.7 ENERGY RESOLUTION
This screen enable user to set energy in terms of Wh / kWh / MWh on Rs485 Output
screen. Touching radio button in front of particular option will
Three options: WATT, KILO-WATT & MEGA-WATT are displayed on
select that option. Touch on “ key” will conrm the setting.
and will return to previous menu.
Touching the “ key” will keep the old selected setting
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
CT SECONDARY
5 AMPERE
1 AMPERE
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
ENERGY ON RS485
WATT (W)
KILO-WATT (KW)
MEGA-WATT (MW)
OK
BACK
Note : Default value is set to ‘WATT’ i.e. Energy on Modbus will be in
terms of Wh/VArh/VAh respectively.
14
3.2.1.10 ENERGY DIGIT RESET COUNT (ROLLOVER COUNT)
This screen enables the user for setting maximum energy count after which energy will rollover to zero depending on the setting of Wh, kWh & Mwh in Energy resolution option.
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
CT SECONDARY
5 AMPERE
1 AMPERE
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
ENERGY DIGIT RESET COUNT
7 DIGITS
9 DIGITS
11 DIGITS
8 DIGITS
10 DIGITS
12 DIGITS
13 DIGITS
14 DIGITS
OK
BACK
If Energy resolution is in WATT then rollover count can be from 7 to 14 DIGITS.
If Energy resolution is in KILO-WATT then rollover count can be from 7 to 12 DIGITS. If Energy resolution is in MEGA-WATT then rollover count can be from 7 to 9 DIGITS.
Touching radio button in front of particular option will select that option.
Touch on “ key” will conrm the setting.
OK
OK
Touching the “ key” will keep the old selected setting
BACK
and will return to previous menu.
Note :-
1) Default value of energy digit reset count is set to “14” i.e if energy crosses the 14 digit count it will rollover to zero.
2) If Energy Resolution is set to kW & energy digit reset count is set to 12, Energy screen on display will show “-------” i.e energy overow when energy crosses the 11 digit count.
3) If Energy Resolution is set to MW & energy digit reset count is set to 9, Energy screen on display will show “-------” i.e energy overow when energy crosses the 8 digit count.
3.2.1.9 Energy Update Rate
ENERGY UPDATE RATE
ENTER ENERGY RATE IN MIN
15
3.2.2.1 RS485 Address Setting
This screen applies to the RS 485 output only. This screen allows
the user to set RS485 address parameter for the instrument.
Here again 0 to 9 digit input keypad is provided to set RS485 address & user can conrm this value with a simple touch
This screen can be accessed only from Communication
Parameters List menu.
on “ key”.
The range of allowable address is 1 to 247. If value outside the range is entered, it will display “INVALID VALUE” followed by the correct range of parameter.
3.2.2.2 RS 485 Baud Rate
This screen allows the user to set Baud Rate of RS 485 port.
screen. Touching radio button in front of particular option will
Four options: 2400, 4800, 9600, 19200 Bauds are displayed on
select that option.
Touch on “ key” will conrm the setting.
and will Return to previous menu.
Touching the “ key” will keep the old selected setting
3.2.2.3 RS485 PARITY
3.2.2.1 RS485 ADDRESS
3.2.2.2 RS485 BAUD RATE
3.2.2 Communication Parameter Selection :
After entering in the “COMMUNICATION PARAMETERS” list of following parameters will be displayed
ENTER RS485 ADDRESS
RS485 ADDRESS
RS485 ADDRESS
INVALID VALUE
ENTER
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
VL2
V
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
VL2
V
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
VL2
V
0.000
0.000
0.000
CT SECONDARY
5 AMPERE
1 AMPERE
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
VL2
V
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
VL2
V
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
VL2
V
0.000
0.000
0.000
RS485 BAUD RATE
2400
4800
9600
19200
OK
BACK
BACK
OK
OK
16
3.2.2.3 RS 485 Parity & Stop bit Selection
This screen allows the user to set Parity & number of stop bits.
Touching radio buttion in front of particular option will select that option.
Four options: ODD PARITY WITH ONE STOP BIT, NO PARITY
WITH ONE STOP BIT, NO PARITY WITH TWO STOP BITS,
EVEN PARITY WITH ONE STOP BIT are displayed on screen.
Touch on “ key” will conrm the setting.
will return to previous menu.
Touching the “ key” will keep the old selected setting and
3.2.3.1 Resetting Parameter
These screens allow the users to reset all the parameters
like Energy, Min, Max Voltage and Current.
3.2.3 Reset Parameter Selection:-
For resetting specic parameter user can touch on that parameter.
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
VL2
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
VL2
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
VL2
5 AMPERE
1 AMPERE
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
VL2
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
VL2
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
VL2
RS485 PARITY & STOP BITS
ODD PARITY WITH ONE STOP BIT
NO PARITY WITH ONE STOP BIT
NO PARITY WITH TWO STOP BIT
EVEN PARITY WITH ONE STOP BIT
OK
BACK
OK
OK
BACK
Touching on any parameter will display the conrmation dialog, now
a touch on “ key” will conrm the resetting of that particular
User can reset other parameters in similar manner.
Parameter.
YES
For example resetting All Energies will display a conrmation
dialog as shown in the screen beside.
Touching on “ key” will move back to Reset parameters menu
NO
MIN
17
3.2.4. Output Option selection menu
After entering in the “OUTPUT OPTIONS”, List of following parameters will be displayed :-
3.2.4.1 RELAY-1
3.2.4.2 RELAY-2
3.2.4.3 ANALOG-1
3.2.4.4 ANALOG-2
3.2.4.1 Relay1 output Selection menu
This screen applies to the Relay1 Output option Selection .
Touching any option will open screens of parameters
Touch on “ key” will take back to Output
Options screen.
related to that option.
3.2.4.1.1 Pulse output
After entering in the “RELAY-1 OUTPUT”, List of following parameters will be displayed.
3.2.4.1.1.1 ENERGY
3.2.4.1.1.2 PULSE DURATION
3.2.4.1.1.3 PULSE RATE These settings are used to assign Relay1 in Pulse output mode.
OUTPUT OPTIONS
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
V
0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
V
0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
V
0.000
0.000
CT SECONDARY
5 AMPERE
1 AMPERE
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
V
0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
V
0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
V
0.000
0.000
RELAY-1 PULSE OUTPUT
OUTPUT OPTIONS
ENERGY : NONE
PULSE DURATION : 200
PULSE RATE : 10
18
3.2.4.1.1.1 Assignment of Energy to pulse output (Relay 1) :
This screen allows the user to assign energy to pulse output (for Relay 1)
Following six options are displayed:-
Touching radio button in front of any particular option will select that option. Touch on “ key” will conrm the setting.
Apparent Energy
Import Energy ( Active )
Export Energy ( Active )
Import Energy (Reactive)
Export Energy (Reactive)
Touching the “ key” will keep the old selected setting and
3.2.4.1.1.2 Pulse Duration Selection:
This screen applies only to the Pulsed output mode of both the relays.
This screen allows the user to set Relay energisation time in milliseconds.
radio button in front of particular option will select that option.
Three options: 60, 100, 200 ms are displayed on screen. Touching
Touch on “ key” will conrm the setting.
and will return to previous menu.
Touching the “ key” will keep the old selected setting
3.2.4.1.1.3 Pulse Rate
This screen applies only to the Pulsed output mode of both the relays.
The screen allows user to set the energy pulse rate divisor. Divisor values can be selected through 1,10, 100,1000.Touching radio button in front of particular value will select that value.
will return to previous menu.
Touch on “ key” will conrm the setting.
Touching the “ key” will keep the old selected setting
and will return to previous menu.
Pulse rate divisor is set to 1, when Energy on Rs485 is set to kWh
or MWh.
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
VL2
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
VL2
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
VL2
5 AMPERE
1 AMPERE
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
VL2
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
VL2
LINE-NEUTRAL VOLTAGE
VL2
VL2
VL2
VL2
RELAY-1 ENERGY ASSIGNMENT
APPARENT ENERGY
IMPORT ENERGY(ACTIVE)
EXPORT ENERGY(ACTIVE)
IMPORT ENERGY(REACTIVE)
EXPORT ENERGY(REACTIVE)
OK
BACK
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
V
VVV
0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
V
VVV
0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
V
VVV
0.000
0.000
CT SECONDARY
5 AMPERE
1 AMPERE
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
V
VVV
0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
V
VVV
0.000
0.000
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
V
VVV
0.000
0.000
RELAY-1 PULSE RATE DIVISOR
1
10
100
1000
OK
BACK
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
CT SECONDARY
5 AMPERE
1 AMPERE
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
LINE-NEUTRAL VOLTAGE
VL2
VL2VL2
RELAY-1 PULSE DURATION
60 MILLI-SECONDS 100 MILLI-SECONDS 200 MILLI-SECONDS
OK
BACK
OK
OK
OK
OK
OK
OK
BACK
BACK
BACK
19
3.2.4.2 Relay 2 Output Selection
Conguration of Relay 2 for Pulse or Limit Output is same as Relay 1. If you Select the Pulse output option for Relay 1 same setting will be applicable for Relay 2 except assignment of energy to Pulse output (i.e. Energy assignment of both relay can be different.)
3.2.4.3 Parameter setting for Analog Output 1 ( Optional )
This option allows the user to set analog output 1 to corresponding measured parameter. A simple touch on “ANALOG-1”row will open screen having list of parameters.( Refer table2
for Analog Parameter”) Touch on “ key” will conrm the setting. Touching the “ key” will keep the old selected setting and will return to previous menu.
BACK
OK
OK
Touch on “ key” will conrm the setting. Touching the “ key” will keep the old selected setting and will return to previous menu.
3.2.4.4 Parameter setting for Analog Output 2 ( Optional )
This option allows the user to set analog output 2 to corresponding measured parameter. A simple touch on “ANALOG-2”row will open screen having list of parameters.( Refer table2 for Analog Parameter)
3.2.5 Brightness & Contrast
The brightness & contrast of the TFT LCD screen can be varied by
Touching the DEFAULT key will set brightness and contrast as per factory settings. Touching the BACK key will move back to the setup menu without making any changes.
the user by sliding the sliders. Touching the “ key” will
conrm the current brightness contrast setting.
BACK
OK
OK
OK
OK
20
3.2.6 RGB Color Code (only for 3 Phase 3 Wire / 4 Wire)
This screen allows user to set the values of Red, Green and Blue components of colors used to display the parameters of all three phases. Different colors can be assigned to each phase using combination of Red, Green and Blue component values. L1,L2,L3 will be set to the assigned color.
To set these values, touch the corresponding rectangular section, 0 to 9 digit input keypad will appear. After entering the value using this keypad, user can conrm this value with a simple touch on “ key”.
“ key” is used to go back to previous screen.
140
R B
G
L1
L2
L3
RGB COLOR CODE
0 0
255 204191
0 255 0
RGB COLOR CODE
VALID RANGE IS : 0 to 255
COLOR R
G
B
Light Blue Maroon Pink Purple
Red Silver Violet White
Yellow
255 255 0
255 255 255
143 0 255
191 191 191
255 0 0
161 33 240
255 191 204
176 48 97
173 217 230
COLOR
R
G
B
Dark Pink Dark Purple
Dark Red Dark Violet
Dark Yellow Gold Gray Green
Indigo
74 0
0 255 0
128 128 128
212 176 56
156 135 13
148 0 212
140 0 0
48 26 51
232 84 128
130
Standard color combinations
COLOR
R
G
B
Brass
Blue
Brown
Black
Bronze
Copper
Dark Blue Dark Brown Dark Green
0 51
102 66 33
0 0 140
184 115 51
166 41 41
204 128 51
181 166 66
0 0 255
0
0
0
33
The allowable range for these values is 0 to 255. If a value outside this range is entered, it will display “ VALID RANGE IS : 0 TO 255”.
NOTE : Colors similar to background are not recommended.
21
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
CT SECONDARY
OK
5 AMPERE
1 AMPERE
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
IMPORTANT. Performing touch screen calibration. Press & hold the center of the lled circle
Touch screen to continue.
4 Touch screen calibration
This instrument is able to perform calibration to ensure the proper operation of the units touch screen functionalities. The calibration procedure will correct the problem of out of tolerance touch screen malfunction. Note that errors corrected by this calibration procedure are specic only to touch screen operation.
For starting touch screen calibration, touch the screen any where for 1 sec at system reset. After that touch screen calibration will start & the message shown besides will be displayed. Touch the screen to continue.
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
CT SECONDARY
OK
5 AMPERE
1 AMPERE
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
Hold the lled circle
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
CT SECONDARY
OK
5 AMPERE
1 AMPERE
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
Release the lled circle
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
CT SECONDARY
OK
5 AMPERE
1 AMPERE
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
Hold the lled circle
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
CT SECONDARY
OK
5 AMPERE
1 AMPERE
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
Hold the lled circle
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
CT SECONDARY
OK
5 AMPERE
1 AMPERE
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
Press on the lled circle
Follow the instructions displayed. Press & hold the center of the lled red circle for at least 2 seconds. Release when message for release is being displayed. For accurate results try to touch the center of the lled circle.
22
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
CT SECONDARY
OK
5 AMPERE
1 AMPERE
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
Press on the lled circle
Repeat the same procedure for the remaining 3 corner circles.
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
CT SECONDARY
OK
5 AMPERE
1 AMPERE
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
Hold screen for 1 sec after system reset to REPEAT the calibration procedure.
Touch screen to continue.
After successful calibration, the message shown besides would be displayed. Touch the screen to continue.
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
CT SECONDARY
OK
5 AMPERE
1 AMPERE
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
LINE-NEUTRAL VOLTAGE
VOLTAGE
MAIN
VL2
VL2
VL2
V
VVVV
0.000
0.000
0.000
Error in calibration
Touch screen to re-calibrate.
If the touch screen was not calibrated properly, “Error in calibration”message would be shown & the user will be asked to recalibrate the touch screen. In such case the meter will retain the previously stored touch - screen calibration values unless a successful calibration is being performed.
23
5. Analog Output ( optional ) :
This module provides two d.c. isolated outputs .There are two output
1) Two 0 - 1mA outputs , internally powered .
2) Two 4 - 20mA outputs , internally powered .
The 0 -1mA output module has an 0V return on each end of the 4 way connector ( Please refer section 15 for connection details )
On both modules the output signals are present on pins A1(Analog Output 1) & A2 (Analog Output 2)
0
0 (12 mA)
0
181 (4 mA)
0
180 (20 mA)
0
90 (16 mA)
0
270 (8 mA)
These outputs can be individually assigned to represent any one of the measured and displayed Parameters.
All settlings are user congurable via the user interface screen. See Analog o/p selection for details .
* Note : Refer diagrams 1 & 2
Diagram 1 : ( 4 -20 mA )
24
Diagram 2 : ( 0 - 1 mA )
0
0 (0.5 mA)
0
181 (0 mA)
0
180 (1 mA)
0
90 (0.75 mA)
0
270 (0.25 mA)
TABLE 2 : Parameter for Analog
INPUT VOLTAGE L1
Sr.
No.
Parameter
0
1
2
INPUT VOLTAGE L2
2 3
INPUT VOLTAGE L3
None
4
INPUT CURRENT IL1
3P 4W
1P 2W
3P 3W
Range
0 - 100 % 0 - 100 % 0 - 100 %
0 - 100 %
5
INPUT CURRENT IL2
6
INPUT CURRENT IL3
0 - 100 % 0 - 100 %
0 - 120 %
  
 
 
7
ACTIVE POWER L1
 
 
Note : Parameters 1,2,3 are L-N Voltage for 3P 4W & L-L Voltage for 3P 3W.
25
0 - 120 %
8
ACTIVE POWER L2
0 - 120 %
9
ACTIVE POWER L3
0 - 120 %
10
APPARENT POWER L1
0 - 120 %
11
APPARENT POWER L2
12
APPARENT POWER L3
13
REACTIVE POWER L1
14
REACTIVE POWER L2
15
REACTIVE POWER L3
16
POWER FACTOR L1
17
POWER FACTOR L2
18
POWER FACTOR L3
19
PHASE ANGLE L1
20
PHASE ANGLE L2
21
PHASE ANGLE L3
0 - 120 % 0 - 120 % 0 - 120 %
22
VOLTAGE AVG
24
CURRENT AVG
27
ACTIVE POWER SUM
29
APPARENT POWER SUM
31
REACTIVE POWER SUM
32
POWER FACTOR AVG
34
PHASE ANGLE AVG
36
FREQUENCY
0 - 100 % 0 - 100 %
0 - 120 % 0 - 120 %
0 - 120 %
 
 
 
 
 
     
  
 
 
 
 
 
Sr. No.
Parameter
3P 4W
1P 2W
3P 3W
Range
101
INPUT VOLTAGE L12
102
INPUT VOLTAGE L23
103
INPUT VOLTAGE L31
113
NEUTRAL CURRENT
0 - 100 % 0 - 100 % 0 - 100 %
0 - 100 %
0 - 120 %
45 to 66 Hz
0 0
181 / 0 / -180
0 0
181 / 0 / -180
0 0
181 / 0 / -180
0 0
181 / 0 / -180
0 0
181 / 0 / -180
0 0
181 / 0 / -180
0 0
181 / 0 / -180
0 0
181 / 0 / -180
26
6. Relay output (Optional) :
This is provided with either 1 or 2 relay for pulse output.instrument
6.1 Pulse Output :
Pulse output is the potential free, very fast acting relay contact which can be used to drive an external mechanical counter for energy measurement. This pulse output can be congured to any of the following parameter instrument’s through setup parameter screen
1) Active Energy (Import)
2) Active Energy (Export)
3)Reactive Energy (Import)
4)Reactive Energy (Export)
5)Apparent Energy
27
* System power = 3 x CT(Primary) x PT(Primary)L-N for 3 Phase 4 Wire System power = Root3 x CT(Primary) x PT(Primary)L-L for 3 Phase 3 Wire
Above options are also applicable for Apparent and Reactive Energy.
Pulse Duration 60 ms,100 ms or 200 ms
Divisor
1
10
100
1000
Pulse rate
Pulse
System Power*
1per Wh
1per 10Wh
1per 100Wh
1 per 1000Wh
1per kWh
1per 10kWh
1per 100kWh
1 per 1000kWh
1per Mwh
1per 10MWh
1per 100MWh
1per 1000MWh
Up to 3600W
Up to 3600W
Up to 3600W
Up to 3600W
Up to 3600kW
Up to 3600kW
Up to 3600kW
Up to 3600kW
Above 3600kW
Above 3600kW
Above 3600kW
Above 3600kW
TABLE 3 : Energy Pulse Rate Divisor
1.For Energy Output in Wh
Divisor
1
Pulse rate
Pulse
System Power* 1 per kWh 1 per 1000kWh
1 per 1000MWh
Up to 3600W
Up to 3600kW Above 3600kW
2. For Energy Output in Kwh
Divisor
1
Pulse rate
Pulse
System Power* 1 per Mwh 1 per 1000Mwh
1 per 1000Gwh
Up to 3600W
Up to 3600kW Above 3600kW
3. For Energy Output in Mwh
28
7. RS 485 ( ModBus ) Output :
This supports MODBUS (RS485) RTU protocol( 2-wire ) .instrument
Connection should be made using twisted pair shielded cable. All "A" and "B" connections are daisy chained together. The screens should also be connected to the “Gnd” terminal. To avoid the possibility of loop currents, an Earth connection should be made at one point on the network.Loop (ring) topology does not require any termination load. Line topology
may or may not require terminating loads depending on the type and length of cable used.
The impedance of the termination load should match the impedance of the cable and be at bothends of the line. The cable should be terminated at each end with a 120 ohm (1/4 Watt min.) resistor.
RS 485 network supports maximum length of 1.2km. Including the Master, a maximum of 32 instruments can be connected in Rs485 network.The permissible address range for the
is between 1 and 247 for 32 instruments. Broadcast Mode (address 0) is not allowed.instrument
The maximum latency time for the is 200ms i.e. this is the amount of time that instrument can pass before the rst response character is output.
After sending any query through software ( of the Master) , it must allow 200ms of time to elapse before assuming that the is not going to respond. If slave does not instrument respond within 200 ms, Master can ignore the previous query and can issue fresh query to the slave.
29
The each byte in RTU mode has following format:
8-bit binary, hexadecimal 0-9, A-F
2 hexadecimal characters contained in each 8-bit eld of the message
4 bytes (32 bits) per parameter.
Floating point format ( to IEEE 754) Most signicant byte rst (Alternative least signicant byte rst)
Format of Data Bytes
2 byte Cyclical Redundancy Check (CRC)
Error Checking Bytes
1 start bit, 8 data bits, least signicant bit sent rst 1 bit for even/odd parity 1 stop bit if parity is used; 1 or 2 bits if no parity
Byte format
Communication Baud Rate is user selectable from the front panel between 2400, 4800, 9600, 19200 bps.
Exception Cases : An exception code will be generated when the receives instrument ModBus query with valid parity & error check but which contains some other error ( e.g. Attempt to set floating point variable to an invalid value ) The response generated will be “Function code” Ored with HEX (80H ). The exception codes are listed below
Function code :
03
Read Holding Registers
Read content of read /write location ( 4X )
04
Read input Registers
Read content of read only location ( 3X )
16
Presets Multiple Registers
Set the content of read / write locations ( 4X )
30
03
Illegal Data Value
Attempt to set a floating point variable to an invalid value
01
Illegal function
This function code is not supported by the instrument.
02
Illegal Data Address
Attempt to access an invalid address or an attempt to read or write part of a floating point value
Two consecutive 16 bit registers represent one parameter. Refer table 4 for the addresses of 3X registers (Parameters measured by the instruments). Each parameter is held in the 3X registers. Modbus Code 04 is used to access all parameters.
Example :
To read parameter , Volts 3 : Start address = 04 (Hex) Number of registers = 02
Note : Number of registers = Number of parameters x 2
Each Query for reading the data must be restricted to 20 parameters or less. Exceeding the 20 parameter limit will cause a ModBus exception code to be returned.
Query :
Accessing 3 X register for reading measured values:
Device Address
Function Code
Start Address High
Start Address Low
Number of Registers Hi
Number of Registers Lo
CRC Low
CRC High
01 (Hex)
04 (Hex)
00 (Hex)
04(Hex) 00 (Hex)
02(Hex) 30 (Hex) 0A (Hex)
Start Address High : Most signicant 8 bits of starting address of the parameter requested. Start Address low :Least signicant 8 bits of starting address of the parameter requested.
31
Number of register Hi : Most signicant 8 bits of Number of registers requested. Number of register Lo : Least signicant 8 bits of Number of registers requested.
(Note : Two consecutive 16 bit register represent one parameter.)
Response: Volt3 (219.25V)
Device Address
Function Code
Byte Count
Data Register1 High Byte
01 (Hex)
04 (Hex)
04 (Hex)
43 (Hex) 5B (Hex)
41 (Hex) 21 (Hex) 6F (Hex)
Data Register1 Low Byte
Data Register2 High Byte
Data Register2 Low Byte
CRC Low
CRC High
9B (Hex)
Byte Count : Total number of data bytes received. Data register 1 High Byte : Most signicant 8 bits of Data register 1 of the parameter requested.
Data register 1 Low Byte : Least signicant 8 bits of Data register 1 of the parameter requested. Data register 2 High Byte : Most signicant 8 bits of Data register 2 of the parameter requested.
(Note : Two consecutive 16 bit register represent one parameter.)
Data register 2 Low Byte : Least signicant 8 bits of Data register 2 of the parameter requested.
Table 4 : 3 X register addresses (measured parameters)
3P 4W
3P 3W
3P 4W
3P 3W
 
 
   
     
1P 2W
Parameter
Volts 1
Volts 2 Volts 3 Current 1
Current 2 Current 3
W1
Modbus Start Address Hex
High Byte
Low Byte
High ByteHigh Byte
00
0
00
2
00
4
00
6
00
8
00
A
00
C
Address (Register)
Sr. No.
30001
1
30003
2
30005
3
30007
4
30009
5
30011
6
30013
7
32
30023 12 30025 13 30027 14
30029 15 30031 16 30033 17 30035 18 30037 19 30039 20
30041 21 30043 22 30045 23
30047 24 30049 25 30051 26 30053 27
30055 28
30057 29 30059 30 30061 31 30063 32
Address (Register)
Sr. No.
30015 8 30017 9 30019 10
.
30021 11
VA3 VAR1 VAR2
VAR3 PF1 PF2 PF3 Phase Angle 1 Phase Angle 2
Phase Angle 3 Volts Ave Volts Sum
Current Ave Current Sum Watts Ave Watts Sum
VA Ave
VA Sum VAr Ave VAr Sum PF Ave
Parameter
W2
W3
VA1
Parameter
VA2
00
16
00
18
00
1A
00
1C
00
1E
00
20
00
22
00
24
00
26
00
28
00
2A
00
2C
00
2E
00
30
00
32
00
34
00
36
00
38
00
3A
00
3C
00
3E
Modbus Start Address Hex
High Byte
Low Byte
High ByteHigh Byte
00
E
00
10
00
12
Modbus Start Address Hex
00
14
 
       
   
 
3P 4W
1P 2W
3P 3W
3P 4W
3P 3W
33
30065
33
30067
34
30069
35
30071
36
30073
37
30075
38
30077
39
30079
40
30081
41
Address (Register)
Sr. No.
30133 30135
30141
30143
67 68 71 72
PF Sum Phase Angle Ave Phase Angle Sum Freq Wh Import Wh Export
VARh Import VARh Export VAh
Parameter
Volts Ave Max
Volts Ave Min
Current Ave Max Current Ave Min
00
40
00
42
00
44
00
46
00
48
00
4A
00
4C
00
4E
00
50
Modbus Start Address Hex
High Byte
Low Byte
High ByteHigh Byte
Modbus Start Address Hex
00 00
00 00
84
86 8C 8E
 
   
1P 2W
   
 
 
 
3P 4W
3P 3W
3P 4W
3P 3W
 
   
30145
73
Active Import Energy(Wh)*
00
90
30149
75
Reactive Import Energy (VARh)*
00
94
30151
76
Reactive Export Energy (VARh)*
00
96
30153
77
Apparent Energy (VAh)*
00
98
30147
74
Active Export Energy (Wh)*
00
92
30201
101
VL 1 - 2 ( Calculated )
00
C8
 
   
 
   
30203 30205 30207 30209
30211
30213
102 103 104 105 106 107
VL 2 - 3 ( Calculated ) VL 3 - 1 ( Calculated ) V1 THD( % ) V2 THD( % ) V3 THD( % ) I1 THD( % )
00 00 00 00 00 00
CA CC CE D0 D2 D4
34
Address (Register)
Sr. No.
Parameter
Modbus Start Address Hex
High Byte
Low Byte
High ByteHigh Byte
Modbus Start Address Hex
1P 2W
3P 4W
3P 3W
3P 4W
3P 3W
 
 
  
 
  
30215 30217 30219 30221 30225
108 109 110 111 113
I2 THD( % )
I3 THD( % ) System Voltage THD( % ) System Current THD( % ) I neutral
00
00 00 00 00
D6 D8 DA DC E0
Each setting is held in the 4X registers .ModBus code 03 is used to read the current setting and code 16 is used to write/change the setting. Refer Table 5 for 4 X Register
Example : Reading System type
System type : Start address = 0A (Hex) Number of registers =
Note :Number of registers = Number of Parameters x
Accessing 4 X register for Reading & Writing :
Device Address
Function Code
Start Address High
Start Address Low
Number of Registers Hi
Number of Registers Lo
CRC Low
CRC High
01 (Hex)
03 (Hex)
00 (Hex)
0A (Hex)
00 (Hex)
02 (Hex)
E4 (Hex)
09 (Hex)
Note : Parameters 1,2,3 are L-N Voltage for 3P 4W & L-L Voltage for 3P 3W .
35
Response: System Type ( 3phase 4 wire = 3 )
Device Address
Function Code
Byte Count
Data Register1 High Byte
01 (Hex)
03 (Hex)
04 (Hex)
40 (Hex)
Data Register1Low Byte
40 (Hex)
Data Register2 High Byte
00 (Hex)
00(Hex)
Data Register2 Low Byte
EE (Hex)
CRC Low
CRC High 27 (Hex)
Byte Count : Total number of data bytes received.
Data register 1 High Byte : Most signicant 8 bits of Data register 1 of the parameter requested. Data register 1 Low Byte : Least signicant 8 bits of Data register 1 of the parameter requested.
Data register 2 High Byte : Most signicant 8 bits of Data register 2 of the parameter requested.
(Note : Two consecutive 16 bit register represent one parameter.)
Data register 2 Low Byte : Least signicant 8 bits of Data register 2 of the parameter requested.
Start Address High : Most signicant 8 bits of starting address of the parameter requested. Start Address low :Least signicant 8 bits of starting address of the parameter requested.
Number of register Hi : Most signicant 8 bits of Number of registers requested. Number of register Lo : Least signicant 8 bits of Number of registers requested.
(Note : Two consecutive 16 bit register represent one parameter.)
36
Example : Writing System type
System type : Start address = 0A (Hex) Number of registers = 02
Query:( Change System type to 3phase 3wire = 2 )
01 (Hex)
10 (Hex)
Device Address
Function Code
00 (Hex)
Starting Address Hi
0A(Hex)
Starting Address Lo
00 (Hex)
Number of Registers Hi
02(Hex)
Number of Registers Lo
04 (Hex)
Byte Count
40 (Hex)
Data Register-1High Byte
00(Hex)
Data Register-1 Low Byte
00(Hex)
00(Hex)
66 (Hex)
10 (Hex)
Data Register-2 Low Byte
CRC High
CRC Low
Data Register-2 High Byte
Byte Count : Total number of data bytes received.
Data register 1 High Byte : Most signicant 8 bits of Data register 1 of the parameter requested. Data register 1 Low Byte : Least signicant 8 bits of Data register 1 of the parameter requested.
Data register 2 High Byte : Most signicant 8 bits of Data register 2 of the parameter requested.
Data register 2 Low Byte : Least signicant 8 bits of Data register 2 of the parameter requested.
37
(Note : Two consecutive 16 bit register represent one parameter.)
Response:
Device Address
Function Code
Start Address High
Start Address Low
Number of Registers Hi
01 (Hex)
10 (Hex)
00 (Hex)
0A(Hex)
00 (Hex)
Number of Registers Lo 02(Hex)
CRC Low
61 (Hex)
CRC High CA (Hex)
Start Address High : Most signicant 8 bits of starting address of the parameter requested. Start Address low :Least signicant 8 bits of starting address of the parameter requested.
Number of register Hi : Most signicant 8 bits of Number of registers requested. Number of register Lo : Least signicant 8 bits of Number of registers requested.
(Note : Two consecutive 16 bit register represent one parameter.)
Table 5 : 4 X register addresses
Address (Register)
Parameter
No.
Parameter
Modbus Start Address Hex
High Byte
Low Byte
40007
4
Sys Voltage
00
06
Read / Write
R
40009
5
Sys Current
00
08
R40009
5
Sys Current
00
08
R
6
Sys Type
00
0A
40011
00
R/Wp
3
00
04
40005 R/Wp
Energy on RS485
38
R
00
0C
7
Pulse Width R/Wp
00
40015
8
00
14
40021
11
Node Address.
00
16
40023
12
Pulse Divisor
R/Wp
00
00
18
40025
13
19
Min Reset
Wp
00
00
1A
40027
14
20
Max Reset
Wp
Wp
00
00
1C
40029
15
21
Analog Out 1- Para Sel
R/Wp
00
00
1E 24 26 28 50
40031 40037
40039 40041 40081
16
41
Analog Out 2- Para Sel Sys Power
Energy Digit reset Count Word Order
Energy update rate
R/Wp
R/Wp
R/Wp
.
R
40013
Reset parameters W Wp
0E
45 46
47
48
49
50 51
52 53
Red color code of phase1
Green color code of phase1
Blue color code of phase1 Red color code of phase2
Green color code of phase2 Blue color code of phase2
Red color code of phase3
Green color code of phase3
Blue color code of phase3
R/Wp R/Wp R/Wp
R/Wp R/Wp R/Wp R/Wp
R/Wp R/Wp
00 00 00
00 00 00 00
00 00
58 5A 5C
5E 60 62
64 66 68
40085
40089 40091 40093 40095
40097
40099 40101 40103
40105
R/Wp R/Wp
00 00
54 56
43 44
Brightness
Contrast
40087
Address (Register)
Parameter
No.
Parameter
Modbus Start Address Hex
High Byte
Low Byte
Read / Write
39
Explanation for 4 X register :
Address Parameter Description
40005
40007
System Voltage
This address is read only and displays System Voltage
40009
System Current
This address is read only and displays System Current
This address is used to set the System type. Write one of the following value to this address.
1 = 1 Phase 2 Wire (Read only for 1P2W) 2 = 3 Phase 3 Wire 3 = 3 Phase 4 Wire.
Writing any other value will return error .
40011
System Type
40013
Pulse Width of Relay
This address is used to set pulse width of the Pulse output. Write one of the following values to this address:
60 : 60 ms 100 : 100 ms 200 : 200 ms
Writing any other value will return error .
40015
Reset Parameters
Write one of the following values to this address: 0 : Energy Reset 2 : Min Reset 3 : Max Reset 6 : Reset All
Energy display on Modbus
This address is used to set energy display on MODBUS in Wh,
KWh & Mwh. Write one of the following value to this address.
1 = Energy in Wh. 2 = Energy in KWh. 3 = Energy in MWh.
40021
Node Address
This register address is used to set Device address between 1 to 247 .
40
Address Parameter Description
40023
Pulse Divisor
40025
Min - Reset This address is used to reset the Min parameters value.
Write Zero value to this register to reset the Min parameters. Writing any other value will return an error.
40027
Max - Reset This address is used to reset the Max parameters value.
Write Zero value to this register to reset the Max parameters. Writing any other value will return an error.
This address is used to set pulse divisor of the Pulse output. Write one of the following values to this address for Wh:
1 : Divisor 1 10 : Divisor 10 100 : Divisor 100
1000 : Divisor 1000 & in KWh & MWh Divisior will be 1 default. Writing any other value will return an error.
Pulse rate divisor is set to 1, when Energy on Rs485 is set
to kWh or MWh.
40031
Analog Out 2­Para Set
This address is used to set the parameter for Analog Output 2.. Write one of the parameter no. As per the options given in Table 2 for Analog & Limit Output Parameters. Writing any other value will return an error.
40037
Sys Power
System Power (Read Only) is the Nominal system power based on the values of Nominal system volts and Nominal system current.
40039
This address is used to set the rollover count for energy. If Energy on Rs485 is in Wh rollover count can be from 7 to 14. If it is in KWh then rollover count can be from 7 to 12 & for MWh rollover count can be from 7 to 9.
Energy digit Reset Count
41
is from 2 to 85.
Default value is 42. This address allows to read or set the value of
contrast of display LCD. The valid range is from 6 to 23. Default value is 9.
Default value for phase 1 : 160, 82, 45; phase 2 : 0, 0, 0 and phase 3 : 128, 128, 128.
Address Parameter Description
R
40041
40081
Word Order
Energy update rate
Energy update rate is the time after which Energy registers are updated. This time is user settable from 1 - 60 minutes
Word Order controls the order in which the receives instrument or sends floating - point numbers:- normal or reversed register order.In normal mode, the two registers that make up a floating point numbers are sent most signicant bytes rst. In reversed register mode , the two registers that make up a floating point numbers are sent least signicant bytes rst. To set the mode, write the value ‘2141.0’ into this register­the instrument will detect the order used to send this value and set that order for all ModBus transaction involving floating point numbers.
40085
40089 to 40105
RGB Color Code for L1, L2, L3
This addresses allow to read or set the value of Red, Green, Blue component of color used to display phase 1, phase 2, phase 3 parameters respectively.
The valid range is 0 to 255.
40087
42
EVEN
19200
9600
9600
9600
NONE NONE
ODD
Baud Rate
Parity
Stop Bit
Decimal value
01
02
01
01
15 08 09
10
ODD
9600
4800 4800
NONE
NONE
4800
4800 2400
2400
2400
2400
NONE NONE
ODD
EVEN
ODD
EVEN
02
01
01 01
02
01
01
01
01
11
04 05
06 07 00
01 02
03
NOTE : Codes not listed in the table above may give rise to unpredictable results including loss of communication. Excise caution when attempting to change mode via direct Modbus writes.
4
Export Reactive Energy
Apparent Energy
Import Reactive Energy
Code
1
0
2 3
Conguration
Import Active Energy
Export Active Energy
Table 7 : Pulse1 & Pulse2 Conguration select
Table 6 : RS 485 Set-up Code
19200
NONE
19200
EVEN
19200
NONE
Baud Rate
Parity
Stop Bit
Decimal value
01
01
02
13
14
12
43
8. Phaser Diagram :
Inductive
Capacitive
Capacitive
Inductive
90 degrees (0.000)
0 degrees (+1.000)
180 degrees (-1.000)
270 degrees (0.000)
-
+
2
4
+
-
Connections Quadrant
Power ( P )
Sign of
Active
Power ( Q )
Sign of
Reactive
Factor ( PF )
Sign of
Power
Inductive /
Capacitive
Import
1
+ P
+ Q
+
L
Import
4
+ P
- Q
+
C
Export
2
- P
+ Q
-
C
Export
3
- P
- Q
-
L
44
Inductive means Current lags Voltage
Capacitive means Current leads Voltage
9. Installation
Mounting is by four side clamps, slide the side clamps through side slot till side clamp gets rmly locked in a groove (Refer g.) Consideration should be given to the space required behind the instrument to allow for bends in the connection cables.
SLIDE IN THIS DIRECTION AND LOCK
PANEL
Meter
When the instrument displays Active power ( P )with “ + ” ( positive sign ) , the connection is “ Import ” .
When the instrument displays Active power ( P )with “ - ” ( negative sign ) , the connection is “ Export ” .
As the front of the enclosure conforms to IP54 it is protected from water spray from all directions, additional protection to the panel may be obtained by the use of an optional panel gasket.
The terminals at the rear of the product should be protected from liquids.
The instrument should be mounted in a reasonably stable ambient temperature and where the operating temperature is within the range
0
-10 to 55 C . Vibration should be kept to a minimum and the product should not be mounted where it will be subjected to excessive direct sunlight.
45
9.1 EMC Installation Requirements
This product has been designed to meet the certication of the EU directives when installed to a good code of practice for EMC in industrial environments, e.g.
1. Screened output and low signal input leads or have provision for tting RF suppression components, such as ferrite absorbers, line lters etc., in the event that RF elds cause
problems.
Note: It is good practice to install sensitive electronic instruments that are performing critical functions, in EMC enclosures that protect against electrical interference which could cause a disturbance in function.
2. Avoid routing leads alongside cables and products that are, or could be, a source of
Caution
1. In the interest of safety and functionality this product must be installed by a qualied engineer, abiding by any local regulations.
2. Voltages dangerous to human life are present at some of the terminal connections of this unit. Ensure that all supplies are de-energised before attempting any connection or disconnection.
3. These products do not have internal fuses therefore external fuses must be used to ensure safety under fault conditions.
interference.
4. ESD precautions must be taken at all times when handling this product.
3. To protect the product against permanent damage, surge transients must be limited to 2kV pk. It is good EMC practice to suppress differential surges to 2kV at the source. The unit has been designed to automatically recover in the event of a high level of transients. In extreme circumstances it may be necessary to temporarily disconnect the auxiliary supply for a period of greater than 5 seconds to restore correct operation.
The Current inputs of these products are designed for connection in to systems via Current Transformers only, where one side is grounded.
46
9.2 Case Dimension and Panel Cut Out
3.78”
96mm
FRONT DISPLAY
AREA
3.78”
96mm
3.15”
80mm
3.62”
92mm
PANEL CUTOUT
3.62”
92mm
MAX PANEL THICKNESS 0.18”,5mm
9.3 Wiring
Input connections are made directly to screw-type terminals with indirect wire pressure. Numbering is clearly marked in the plastic moulding. Choice of cable should meet local
2
regulations. Terminal for both Current and Voltage inputs will accept upto 3mm x 2 diameter cables.
Note : It is recommended to use wire with lug for connection with meter.
47
10. Connection Diagrams
3-PHASE 3-WIRE UNBALANCED LOAD
DIGITAL METERING SYSTEM
P1
S1
P1
S1
L N AUX
SUPPLY
L1 L2 L3
N
L
O
A
D
2
5
8
3
4
6
7
9
9.4 Auxiliary Supply
The should ideally be powered from a dedicated supply, however it may be instrument powered
from the signal source, provided the source remains within the limits of the chosen auxiliary voltage.
9.5 Fusing
It is recommended that all voltage lines are tted with 1 amp HRC fuses.
9.6 Earth/Ground Connections
For safety reasons, CT secondary connections should be grounded in accordance with local regulations.
48
3-PHASE 4-WIRE UNBALANCED LOAD
DIGITAL METERING SYSTEM
2
5
8
11 1
3
4
6
7
9
13
14
L N AUX
SUPPLY
P1
S1
S1
P1
P1
S1
L1 L2 L3
N
L
O
A
D
SINGLE PHASE
DIGITAL METERING SYSTEM
P1
S1
L N
AUX
SUPPLY
L
N
L O A D
2
3
49
System CT primary values
Std. Values from 1 to 9999A
Inputs
Nominal input voltage (AC RMS)
Max continuous input voltage
Max short duration input voltage
Nominal input voltage burden
Phase-Neutral 63.5 / 133 / 239.6 / 254 V
L-N
L-L
120% of Rated Value
2 x Rated Value (1s application repeated 10 times
at 10s intervals)
0.2VA approx. per phase
Max continuous input current 120 % of Rated Value Nominal input current burden 0.6 VA approx. per phase Max short duration current input
20 x Rated Value (1s application repeated 5 times at 5 min. intervals)
Auxiliary
Standard nominal Auxillary
supply voltages & Frequency
d.c. supply voltage tolerance +10 % / -10 % of Rated Value
a.c. supply frequency range 45 to 66 Hz
100 - 250V AC- DC (45-66Hz),
12 - 48V DC
Nominal input current 5A AC rms
(1 or 5 Amp secondaries)
a.c. supply voltage tolerance +10 % / -10 % of Rated Value
Line-Line 110 / 230 / 415 / 440 V
a.c. supply burden 6.5 V
A
d.c. supply burden 3W
11. Specication :
System
3 Phase 3 Wire / 3 phase 4 Wire programmable at site
1 Phase 2 Wire as per order
50
Power Factor
1 % of Unity
Frequency
40 .. 70 Hz
Power Factor
0.5 Lag ... 1 ... 0.8 Lead
Accuracy
Voltage 0.5 % of range C urrent
0.5 % of range
Frequency
0.15% of mid frequency
Active Energy
1.0 % of range
0.5 % of range
Active Power
0.5 % of range
Re- Active Power
0.5 % of range
Apparent Power
Apparant Energy
1.0 % of range
Accuracy 1:
Re - Active Energy
1.0 % of range
Current 5 .. 120 % of Rated Value
Angle
1 % of range
Analog Output
1 % of Output end value Total Harmonic Distortion Neutral Current
4 % of range.
Accuracy 0.5:
Voltage 0.5 % of range C urrent
0.5 % of range
Frequency
0.15% of mid frequency
Active Energy
0.5 % of range
0.5 % of range
Active Power
0.5 % of range
Re- Active Power
0.5 % of range
Apparent Power
1 %
Operating Measuring Ranges
Voltage
5 .. 120 % of Rated Value
51
Reference conditions for Accuracy :
0 0
23 C + 2 C 50 or 60Hz ± 2%
Reference temperature Input frequency
Power Factor
1 % of Unity
Angle
1 % of range
Analog Output
1 % of Output end value
Total Harmonic Distortion
Neutral Current
4 % of range
Voltage C urrent
± 0.2 % of range ± 0.2 % of range
Frequency
0.15% of mid frequency
Active Energy
± 0.2 % of range
± 0.2 % of range
Active Power
± 0.2 % of range
Re- Active Power
± 0.2 % of range
Apparent Power
Re - Active Energy Apparant Energy
± 0.2 % of range
Power Factor
± 1 % of Unity
Angle
± 1 % of range
Analog Output
± 1 % of Output end value
Total Harmonic Distortion
± 1 %
Accuracy 0.2:
± 0.2 % of range
Neutral Current
± 4 % of range
Sinusoidal (distortion factor 0.005)
Input waveform
Rated Value + 1 %
Auxiliary supply voltage Auxiliary supply frequency
Rated Value + 1 %
Voltage Range
50... 100% of Nominal Value.
60... 100% of Nominal Value for THD.
1 %
Apparent Energy
0.5 % of range
Re - Active Energy
0.5 % of range
52
Current Range
10... 100% of Nominal Value.
Power
cosØ / sinØ = 1
10... 100% of Nominal Current &
50... 100% of Nominal Voltage.
For Active / Reactive Power & Energy
20... 100% of Nominal Value for THD.
Power Factor / Phase Angle 40... 100% of Nominal Current &
50... 100% of Nominal Voltage.
Nominal range of use of inuence quantities for measurands
50 .. 120 % of Rated Value 10 .. 120 % of Rated Value Rated Value + 10 %
0
0 to 50 C
Voltage Current
Input frequency Temperature
Auxiliary supply voltage
Auxiliary supply frequency
Rated Value + 10 % Rated Value + 10 %
Temperature Coefcient
0
0.025% / C for Voltage (50..120% of Rated Value)
(For Rated value range of use
0
0.05% / C for Current ( 10..120% of Rated Value )
0
0... 50 C )
Error change due to variation of an influence quantity
2 * Error allowed for the reference condition applied in the test.
pixels Approx. 1 seconds
Update
Display
3.5” Graphical LCD, resolution 320x240
TFT LCD
Controls
Resistive Touch screen
User Interface
53
Standards
IEC 61326 10V/m min-Level 3 industrial low level electromagnetic radiation environment IEC 61000-4-3. IEC 61010-1 , Year 2001
EMC Immunity
Safety
IEC 60529
IP for water & dust
Isolation
2.2 kV RMS 50 Hz for 1 minute between all electrical circuits
Dielectric voltage withstand test between circuits and accessible surfaces
Environmental
0
-10 to 55 C
0
-20 to +65 C 0 .. 90 % RH 3 minute (minimum) 15g in 3 planes
10 .. 55 Hz, 0.15mm amplitude IP 54 as per IEC 60529
Operating temperature Storage temperature
Relative humidity Warm up time
Shock Vibration Enclosure ( front only )
Enclosure
96mm x 96mm DIN Quadratic
Style
Polycarbonate Housing ,
Material
Self extinguish & non dripping as per UL 94 V-0 Screw-type terminals
Terminals
< 80 mm
Depth
0.620 kg Approx.
Weight
54
Pulse output Option ( 1 or 2 Relay ) :
1NO + 1NC
Relay
240VDC , 5Amp.
Switching Voltage & CurrentSwitching Voltage & Current
1 per Wh (up to 3600W), 1 per kWh (up to 3600kW), 1 per MWh (above 3600 kW)
Default Pulse rate Divisor
Pulse rate Divisors
Programmable on site 1 per 10Wh (up to 3600W),
1 per 10kWh (up to 3600kW), 1 per 10MWh (above 3600 kW)
10
1 per 100Wh (up to 3600W), 1 per 100kWh (up to 3600kW), 1 per 100MWh (above 3600 kW)
100
1 per 1000Wh (up to 3600W), 1 per 1000kWh (up to 3600kW), 1 per 1000MWh (above 3600 kW)
1000
60ms , 100ms or 200ms
Pulse Duration
Note : Above conditions are also applicable for Reactive & Apparent Energy .
ModBus ( RS 485 ) Option :
ModBus ( RS 485 )
Protocol
19200 , 9600 , 4800 or 2400
Baud Rate
( Programmable ) Odd or Even, with 1 stop bit,
Parity
Or None with 1 or 2 stop bits
Analog Output Option :
0 ... 1mA dc into 0 - 2 kohm
Linear
Uni-directional, internally powered .
Note : Pulse rate divisor is set to 1, when Energy on Rs485 is set to kWh or MWh.
4 ... 20mA dc into 0 - 500 ohm
Uni-directional, internally powered.
55
N/O N/C
COM
Relay 1
N/O N/C
COM
Relay 2
N/O N/C
COM
Relay 1
12. Connection for Optional Pulse Output / RS 485 / Analog Output ( rear view of the instrument ) :
1. One Pulse Output (One Limit Output)
2. Two Pulse Output ( Two Limit Output)
B A
Gnd
RS 485
3. RS 485 Output
56
A1 A2
Gnd
4 -20 mA
Gnd
4. Two Analog Output
A1 A2
Gnd
0 - 1mA
N/O N/C
COM
Relay 2
Gnd
N/O N/C
COM
Relay 2
B A
Gnd
RS 485
5. One Pulse (One Limit) + RS 485 Output
6. One Pulse (One Limit) + Two Analog Output
57
8. RS 485 Output + One Pulse (One Limit) + Two Analog Output
A1 A2
Gnd
0 - 1mA
N/O N/C
COM
Relay 2
B A
Gnd
RS 485
Gnd
9. Two Pulse (Two Limit) + RS 485 Output
N/O N/C
COM
Relay 1
N/O N/C
COM
Relay 2
B A
Gnd
RS 485
7. RS 485 + Two Analog Output
A1 A2
Gnd
4 -20 mA
B A
Gnd
RS 485
Gnd
58
The Information contained in these installation instructions is for use only by installers trained to make electrical power installations and is intended to describe the correct method
It is the user's responsibility to determine the suitability of the installation method in the
of installation for this product.
user’s eld conditions.
59
RISH Master 3430i
RISH Master 3430i
60
Loading...