Rishabh RISH CON - I Operating Manual

IC 15001063
REV. C - 17/12/13
Operating Manual
I
Programmable Current Transducer
RISH CON - I
1 Introduction
2 Input and Output screens 3 Programming
3.1 Programming via Front LCD & Two keys
3.1.1 Password Protection
3.1.1.1 Password verification
3.1.1.2 Editing Existing Password
3.1.2 Current Transformer parameter Setting
3.1.2.1 Current Transformer primary
value
3.1.2.2 Current Transformer secondary
value
3.1.3 Communication Parameter Setting
3.1.3.1 Address Setting
3.1.3.2 RS 485 Baud rate
3.1.3.3 RS 485 Parity selection
3.1.4 Output Type selection
3.1.4.1 Output 1 Type selection
3.1.4.2 Output 2 Type selection
3.1.5 Input characteristics Setting
3.1.5.1 End value of input
3.1.5.2 Start value of input
3.1.5.3 Elbow Function Selection
3.1.5.4 Elbow value of input
1
Programmable Current Transducer
Installation & Operating Instructions
Current Transducer
SectionContents
3.1.6 Output characteristics Setting
3.1.6.1 Output 1 characteristics Setting
3.1.6.1.1 End value of output 1
3.1.6.1.2 Start value of output 1
3.1.6.1.3 Elbow value of output 1
3.1.6.2 Output 2 characteristics Setting
3.1.6.2.1 End value of output 2
3.1.6.2.2 Start value of output 2
3.1.6.2.3 Elbow value of output 2
3.2 Programming Via programming port available at
front of Transducer using optional PRKAB600 Adapter.
Installation
5.1 EMC Installation Requirements
5.2 Case Dimensions
5.3 Wiring
5.4 Auxiliary Supply
5.5 Fusing
5.6 Earth / Ground Connections
5.7 Maintenance
6. Specifications
7. Connection Diagrams
3.3
DIP Switch setting for output
4.
Programming Via optional RS485(MODBUS)
communication port.
3.3.1 RS 485 ( ModBus )
4.1 Accessing 3X Resistors
4.2 Accessing 4X Resistors
5.
2
1. Introduction
The Current Transducer is a DIN Rail/wall mounted 43.5 X
65.5mm Transducer.
Input Current and Output Voltage / Current is displayed on LCD and indicated by LED’s.
The Current Transducer is used to measure and convert AC Current input into proportional DC current or voltage output signal. Output signal generated is proportional to the True RMS (upto 15th Harmonic) of the input Current.
Current Transducer can be configured and programmed at site for the following CT Primary ,CT Secondary (1A to 5A) , Input Characteristics (i.e start, end and elbow value of Input) and Output parameters (i.e as Voltage or as Current and Characteristics of start, end and elbow value of outputs).
A
A
1.1 LED Indication
3
Green LED Continuous ON
Green LED Continuous ON
Green LED Continuous ON
Red LED Continuous ON
Red LED Continuous ON
LED Operating Status
Output1 Voltage
Output1 Current
Output2 Voltage
Output2 Current
O/P 2
ON
O/P 1
LED
LED Operating Condition
Aux. Supply healthy Condition
The front panel has two keys through which the user may scroll through the output screens and configure the product.
2. Input and Output screens
In normal operation the user is presented with display test screen followed by version screen to one of the output screen. These screens may be scrolled through one at a time Output 1 or Output 2 by pressing the “ Up key” or “ Down key”.
screen 1 : Display Test Screen 2 : Version Screen
Table 1: Measured parameters
Measured parameters
Unit of Measurement
Current
A
Screen 3 : Current Input and Output 1 as Voltage
Screen 4 : Current Input and Output 1 as Current
4
Screen 5 : Current Input and Screen 6 : Current Input & Output 2 as Voltage Output 2 as Current
l
3. Programming
3.1 Programming via Front LCD & Two keys
The following sections comprise step by step procedures for configuring the Current Transducer for individual user requirements.
To access the set-up screens press & hold the“ down” & “ up” keys simultaneously for 5 seconds. This will take the User into the Password Protection Entry Stage .
Programming of transducer can be done in three ways :
3.1. Programming Via Front LCD & two keys.
3.2. Programming Via Programming port available at front of
Current transducer using option PRKAB60 Adapter.
3.3. Programming Via optional RS485(MODBUS)
communication port.
5
3.1.1. Password Protection
3.1.1.1 Password verification
Password protection can be enabled to prevent unauthorised access to set-up screens, by default password protection is not enabled.
Password protection is enabled by selecting a four digit number other than 0000, setting a password of 0000 disables the password protection.
Enter Password, prompt for first digit. (*Denotes that digit will be flashing).Pressing the “ Down” key will scroll the value of the first digit from 0 through t o 9 , t h e value will wrap from 9 round to 0. Pressing the “ Up” key will advance the operation to the next digit and set the first digit.
In the special case where the Password is “0000”pressing the “ Up” key when advance to password set or confirm screen.
Enter Password, first digit entered, prompt for second digit. (*Denotes that digit will be flashing). Pressing the “ Down key will scroll the value of the second digit from 0 through to 9, the value will wrap from 9 round to 0.
Pressing the “ Up” key will advance the operation to the next digit and set the second digit. In this case to “2”.
A
6
Enter Password, second digit entered, prompt for third digit. (*Denotes that digit will be flashing). Pressing the “ Down” key will scroll the value of the third digit from 0 through to 9, the value will wrap from 9 round to 0.
Pressing the “ Up” key will advance the operation to the next digit and set the third digit. In this case to “3”.
Enter Password, third digit entered, prompt for fourth digit.
(*Denotes that digit will be flashing).
Pressing the “ Down” key will scroll the value of the fourth digit from 0 through to 9, the value will wrap from 9 round to 0. Pressing the “ Up” key will
advance the operation to the “Password Set / Confirmed” and set the fourth digit. In this case to “4”.
Password Set/Confirmed.
Pressing “ Down” key will
enter to the “New /change Password”
entry stage.(section 3.1.1.2) Pressing the “ Up” key will confirm New password and advance to current Transformer parameter setting (section 3.1.2).
7
*
Password Incorrect.
This screen is displayed when the unit has not accepted the Password entered. Pressing the " Down" key will re-enter to the “Enter Password” entry stage. Pressing the “ Up” key will exit the setup menu.
3.1.1.2 Editing Existing Password
New / Change Password
(*Denotes that digit will be flashing). Pressing the “ Down” key will scroll the value of the first digit from 0 through to 9, the value will wrap from 9 round to 0.
Pressing the “ Up” key will advance the operation to the next digit and set the first digit, in this case to “4”.
Enter New Password, first digit
entered, prompting for second
digit. (*Denotes that digit will be
flashing).
Pressing the “ Down” key will
scroll the value of the second
digit from 0 through t o 9 , t h e
value will wrap from 9 round to 0. Pressing the “ Up” key will advance the operation to the next digit and set the second digit, in this case to “1”.
8
Enter New Password, second digit entered, prompting for third digit.
(*Denotes that digit will be flashing). Pressing the “ Down” key will scroll the value of the third digit from 0 through to 9, the value will wrap from 9 round to 0.
Pressing the “ Up” key will advance the operation to the next digit and set the third digit, in this case to “ 4”
Enter New Password, third digit entered, prompting for fourth digit.
(*denotes that digit will be
flashing).
Pressing the “ Down” key will
scroll the value of the fourth digit from 0 through to 9, the value will wrap from 9 round to 0.
Pressing the “ Up” key will advance the operation to the “New Password Confirmed” and set the fourth digit, in this case to “1”.
New/changed Password confirmed.
Pressing the “ Down” key wi ll re-enter to the “New Password”entry stage. Pressing the “ Up” key will confirm new password and a d v a n c e to th e C u r r e n t
Transformer parameter Setting (section 3.1.2).
9
A
*
3.1.2. Current Transformer Parameter Setting
3.1.2.1 Current Transformer primary value
This screen allows the user to set the CT Primary value from 1 to 9999 A.
Pressing the “ Down” key will
enter the “New/Change CT
Primary value edit” mode.
Pressing “ Up” key will confirm
the present value as CT Primary
and advance to the CT secondary
setting (section 3.1.2.2).
New / Change CT Primary value
(*Denotes that digit will be flashing). Pressing the “ Down” key will scroll the value of the first digit from 0 through to 9, the value will wrap from 9 round to 0 Pressing the “ Up” key will
advance the operation to the next digit and set the first digit, in this case to “0”
Enter New / Change CT Primary value, first digit entered, prompting for second digit. (*Denotes that digit will be flashing). Pressing the “ Down” key will scroll the value of the second digit from 0 through to 9, the value will wrap from 9 round to 0.
A
10
Pressing the “ Up” key will advance the operation to the next digit and set the second digit, in this case to “0”.
Enter New / Change CT Primary value, second digit entered, prompting for third digit. (*Denotes that digit will be flashing). Pressing the “ Down” key will scroll the value of the third digit from 0 through to 9, the value will wrap from 9 round to 0.
Pressing the “ Up” key will advance operation to the next digit and set the third digit, in this case to “0”.
Enter / New CT primary value third digit entered, prompt for fourth digit (* Denotes that digit will be flashing).
Pressing the “ Down” key will
scroll the value of the fourth digit
from 0 through to 9, the
value will wrap from 9 round to 0.
Pressing the “ Up” key will
advance the operation to the “New
/ Changed CT Primary value confirmation” and set the fourth digit, in this case to “5”.
New/changed CT Primary value confirmed.
Pressing the “ down” key will
re-enter to the “New / Change CT
11
Primary value.
Pressing the “ Up” key will confirm New CT Primary value & advance to the CT secondary setting (section 3.1.2.2).
This screen allows the user to set the CT Secondary value. Pressing the “ Down” key will enter the “New/Change CT Secondary value edit” mode . Pressing the “ Up” key will confirm the present value as CT Secondary and advance to the
Communication parameter Setting (section 3.1.3).
New / Change CT Secondary value
( * Denotes that digit will be flashing ). Pressing the “ Down” key will scrollthe value of the fourth digit from 1 through to 5, the value will wrap from 5 round to 1. Pressing the “ Up” key will advance the operation to the “New / Changed CT Secondary value confirmation” and sets the fourth digit, in this case to “5”.
New/changed CT Secondary
value confirmed.
Pressing the “ Down” key will
return to the “New / Change CT
3.1.2.2 Current Transformer secondary value
12
Secondary value edit” mode. Pressing the “ Up” key will confirm the CT Secondary & advance to the Communication parameter Setting (section
3.1.3).
3.1.3. Communication Parameter Setting
3.1.3.1 Address Setting
This screen applies to the RS 485 output only. This screen allows the user to set RS485 parameter for instruments. The range of allowable address is 1 to 247
Pressing “ Down” key will advance to the “New/Change address value edit” mode. Pressing the “ Up” key will confirm the present value as Address and advance to Baud Rate selection (3.1.3.2).
New/Change Address value (*Denotes that digit will be flashing). First digit is always blank. Pressing the “ Down “ key will scroll the value of the second digit from 0 through to 2, value will wrap from 2 round to 0. Pressing the “ Up” key will advance the operation to the next
digit and set the second digit, in this case to “0”
Enter New/change Address value, second digit entered, prompting for third digit. (*Denotes that digit will be flashing). Pressing the “ Down” key will scroll the value of the third digit
13
from 0 through to 9, the value will wrap from 9 round to 0. Pressing the “ Up” key will advance the operation to the next digit and set the third digit, in this case to “9”.
Enter New/Change Address value, third digit entered, prompting for fourth digit. (*denotes that digit will be flashing). Pressing the “ Down” key will scroll the value of the fourth digit from 0 through to 9, the value will wrap from 9 round to 0. Pressing the “ Up” key will
advance the operation to the New/changed Address value confirmed’ and set the fourth digit in this case to “6”
New/Changed Address value confirmed.
Pressing the “ Down” key will re­enter to the ‘New/change Address value edit”mode. Pressing the” Up key will confirm New Address value and advance to Baud Rate selection (section 3.1.3.2).
3.1.3.2 RS 485 Baud rate
This screen allows the user to set Baud Rate of RS 485 port . The values displayed on screen are in kbaud Pressing the “ Down” key will enter the ‘baud Rate edit” mode and scroll the
14
value through 2.4,4.8,9.6,19.2 and back to 2.4(values are flashing). Pressing “ Up” key will confirm the present value as Baud rate and advance to the Parity Selection (section 3.1.3.3).
RS 485 Baud Rate confirmation
Pressing “ Down” key will be re­enter into the. “Baud Rate Edit” mode. Pressing the “ Up” key will confirm the Baud rate value and advance to the Parity Selection (section
3.1.3.3).
3.1.3.3 RS 485 Parity Selection
This screen allows the user to set Parity & number of stop bits of RS 485 port. Pressing the “ Down” key will enter the “Parity & stop bit edit” mode and scroll the value through
E : even parity with one stop bit odd : odd parity with one stop bit no. 1S : no parity with one stop bit no. 2S : no parity with two stop bit
Pressing “ Up” key accepts the present value and advance to the Output Type selection (section 3.1.4).
15
RS 485 Parity confirmation
Pressing “ Down” key will be re­enter into Parity Edit mode. Pressing the “ Up” key will set the value and advance to the Output Type selection (section 3.1.4).
3.1.4. Output Type Selection
3.1.4.1 Output 1 Type selection
This screen allows the user to set the output 1 type as Voltage or Current. Pressing the “ Down” key will enter the “output 1 type edit” mode and scroll between voltage and current.
Pressing “ Up” key will confirm the present type for Output 1 and advance to the Output 2 type selection (section 3.1.4.2).
Output 1 Type confirmation
Pressing “ Down” key will re-
enter into Output 1 type Edit
mode.
Pressing the “ Up” key will set
the type and advance to the
Output 2 type selection(section
3.1.4.2).
3.1.4.2 Output 2 Type Selection
This screen allows the user to set the output 2 type as a
16
voltage or current.
Pressing the “ Down” key will
enter the “output 2 type edit”
mode and scroll between
voltage and current.
Pressing “ Up” key accepts
the present type for Output 2
and advance to the Input Characteristics setting (section 3.1.5).
Output 2 Type confirmation
Pressing “ Down” key will re-
enter into Output 2 type Edit
mode.
Pressing the “ Up” key will set
the type and advance to the
Input Characteristics setting
(section 3.1.5).
3.1.5. Input characteristics Setting
3.1.5.1 End value of Input
This screen allows the user to set
the End value of Input. End
value of Input can be set from
50% to 120% of set CT
secondary value.
Pressing the “ Down” key will
enter the “New/Change End
value of Input edit” mode.
Note: After Changing Output Type please insure to change DIP Switch setting (Refer Section 3.3.1). If DIP Switches are already change then switch ON/OFF Transducer.
17
A
Pressing “ Up” key will confirm the present value as End value of Input and advance to the Start value of Input setting (section 3.1.5.2).
New / Change End value of
Input
(*Denotes that digit will be
flashing).
Pressing the “ Down” key will
scroll the value of the second
d i g it f r om 0 ( 2 ) t hr o u gh
to1(6), the value will wrap from 1(6) round to 0(2) for 1A(5A) CT secondary. Pressing the “ Up” key will advance the operation to the next digit and set the second digit, in this case to “5”.
Enter New / Change End value of
Input, second digit entered,
prom pting for third digit.
(*Denotes that digit will be
flashing).
Pressing the “ Down” key will
scroll the value of the third digit
from 0 through to 9, the value will
wrap from 9 round to 0.
Pressing the “
to the next digit and set the third digit, in this case to “0”.
Enter New /Change End value of Inp u t,thi rd d i git en tere d , prompting for fourth digit.
up” key will
advance the operation
18
A
*
A
*
A
*
(*Denotes that digit will be flashing). Pressing the “ Down” key will scroll the value of the fourth
digit from 0 through to 9, the value will wrap from 9 round to 0.
Pressing the “ Up” key will advance to confirmation screen & set the fourth digit, in this case to “0”.
New/changed End value of Input confirmed.
Pressing the “ Down” key will re- enter to the “New / Change End value of Input edit” mode. Pressing the “ Up” key will confirm New End value of Input and advance to the Start value of
Input setting (section 3.1.5.2).
3.1.5.2 Start value of Input
This screen allows the user to set the Start value of Input. Start value of input can be set up to 80 % of end value of input. Pressing the “ Down” key will enter New/Change Start value of Input edit” mode. Pressing “ Up” key will confirm
the present value as Start value of Input and advance to the Elbow function selection (section 3.1.5.3)
New / Change Start value of Input
(*Denotes that digit will be flashing). Pressing the “ Down” key will scroll the value of the second digit from 0 through to 4, the value will wrap from 4 round to 0
A
19
A
depending on set value of End value of Input. Pressing the“ Up” key will advance the operation to the next digit and set
the second digit, in this case to “0”
Enter New / Change Start value of Input, second digit entered, prompting for third digit. (*Denotes that digit will be flashing). Pressing the “ Down” key will scroll the value of the third digit from 0 through to 9, the value will wrap from 9 round to 0 depending on set value of End value of Input. Pressing the “ Up” key will
advance the operation to the next digit and set the third digit, in this case to “5”.
Enter New / Change Start value of Input, third digit entered prompting for fourth digit. (* denotes that digit will be flashing). Pressing the “ Down” key will scroll the value of the fourth digit from 0 through to 9, the value will
wrap from 9 round to 0 depending on set value of End value of Input. Pressing “ Up” key will advance to confirmation screen & set 4th digit. In this case to “0”.
20
*A *
New/Changed Start value of Input confirmation
Pressing the “ Down” key will re-enter to the "New/Changed Start value of Input edit” mode Pressing the “ Up” key will confirm New Start value of Input and advance to the Elbow function Selection (section
3.1.5.3).
3.1.5.3 Elbow Function selection
This screen allows the user to enable or disable Elbow function of input. Pressing the “ Down” key will enter the Section of Elbow function of Input edit mode and scroll the value between yes and no.
Yes : Elbow function is enabled. No : Elbow function is disabled. Pressing “ Up “ key will accept the displayed condition & advance to the Elbow value of Input selection (section.3.5.4) or Output Characteristics setting (section 3.1.6).
Elbow Function of Input
confirmation
Pressing “ Down” key will re­enter into Elbow function of Input Edit mode. Pressing “ Up” key will confirm the displayed condition and advance to the Elbow value of
21
Input selection (Section 3.1.5.4) or Output Characteristics selection (Section 3.1.6.
3.1.5.4 Elbow value of Input
This screen appears only when Elbow function is enabled. This screen allows the user to set the Elbow value of the Input. The Elbow value of Input can be set between 1.5% of Set End value of Input.
Pressing the “ Down” key will enter the “New/Change Elbow value of the Input edit” mode. Pressing “ Up” key will confirm the present value as Elbow value of the Input and advance to be Output Characteristics selectin (Section 3.1.6).
New/Change Elbow value of the input
(”Denotes that digit will be flashing).
Pressing the “ Down” key will scroll the value of the second digit from 0 through to 5, the value will wrap from 5 round to 0
depending on set value of End value of Input. Pressing the “ Up Key will advance the operation to the next digit and set the second digit, in this case to “4” Enter New / Change Elbow value of the Input, second digit entered, prompting for third digit. (*Denotes that digit will be flashing).
Pressing the “ Down” key will scroll the value of the third digit from 0# rough to 9, the value will wrap from 9 round to 0
22
depending on set value of End value of Input.
Pressing the “ Up” key will advance the operation to the next digit and set the third digit, in this case to “1”.
Enter New / Change Elbow value of the Input, third digit entered, prompting for fourth digit. (*denotes that digit will be
flashing).
Pressing the “ Down” key will scroll the value of the fourth digit from 0 through to 9, the value will
wrap from 9 round to 0 . Pressing the “ Up” key will advance the operation to the “New / Changed Elbow value of the Input confirmation” and set the fourth digit, in this case to “0”.
New/changed Elbow value of the Input confirmed.
Pressing the “ Down” key will re-enter to the “New / Change Elbow value of the Input”.
Pressing the “ Up” key will confirm New Elbow value of the Input and advance to the Output Characteristics setting (section
3.1.6).
23
A
3.1.6 Output Characteristics Setting
3.1.6.1 Output 1 Characteristics Setting
3.1.6.1.1 End value of output 1
This screen allows the user to set the End value of Output 1, (considerd as DC Current).
The End value of Current Output is fixed at 20mA. Pressing the “ Down” key value remains constant because End value is fixed. Pressing “ Up” key will confirm the present value as End value of the Output 1 and advance to the Start value of Output 1 setting
(section 3.1.6.1.2).
3.1.6.1.2 Start value of output 1
This screen allows the user to set the Start value of Output 1,(considerd as DC Current). Start value of Output can be set up to 20% of End value of Output. Pressing the “ Down” key will enter the “ New/Change Start value of the Output 1 edit” mode.
Pressing “ Up” key will confirm the present value as Start value of the Output 1 and advance to the selection of Elbow value of Output1 (section 3.1.6.1.3) or Output 2 Characteristics setting (section 3.1.6.2)
A
24
New / Change Start value of the Output 1
(*Denotes that digit will be flashing). Pressing the “ Down” key will not affect the first digit It always remains 0.
Pressing the “ Up” key will advance the operation to the next digit and set the first digit in every case to ‘0’.
Enter New / Change Start value of the Output 1, first digit entered, prompting for second digit. (*Denotes that digit will be flashing).
Pressing the “ Down” key will
scroll the value of the second digit
from 0 through to 4, the value will
wrap from 4 round to 0 depending
on the set End value of Output.
Pressing the “ Up” key will
advance the operation to the next
digit and set the second digit, in
this case to “0”.
Enter New / Change Start value of
the Output 1, second digit entered,
prompting for third digit. (*Denotes
that digit will be flashing).
Pressing the “ Down” key will scroll the value of the third digit from 0 through to 9, the value will wrap from 9 round to 0 depending
A
*
A
*
A
*
25
A
*
on the set End value of Output. Pressing the “ Up” key will advance the operation to the next digit and set the third digit, in this case to “0”.
Enter New / Change Start value of the Output 1, third digit entered, prompting for fourth digit. (* denotes that digit will be flashing).
Pressing the “ Down” key will scroll the value of the fourth digit from 0 through to 9, the value will wrap from 9 round to 0 depending on the set End value of Output.
Pressing the “ Up” key will advance the operation to the “New / Changed Start value of the Output 1” confirmation and set the fourth digit, in this case to “0”.
New/changed Start value of the Output 1 confirmed.
Pressing the “ Down” key will re-enter to the “New / Change Start value of the Output 1”. Pressing the “ Up” key will confirm New Start value of the
Output 1 and advance to the selection of Elbow value of Output1(section 3.1.6.1.3) or Output 2 characteristics setting (section 3.1.6.2)
3.1.6.1.3 Elbow value of output 1
This screen appears only when Elbow function is enabled. This screen allows the user to set the Elbow value of Output 1(considerd as DC Current). The Elbow value can be set any value between set Start value of Output and End value of Output.
26
A
A
A
*
A
*
Pressing the “ Down” key will enter the“ New/Change Elbow value of the Output1 edit” mode. Pressing “ Up” key will set the present value as Elbow value of the Output 1 and advance to the Out p ut 2 C hara c teri s tics setting (section 3.1.6.2).
New / Change Elbow value of the Output 1
(*Denotes that digit will be flashing) Pressing the “ Down” key will scroll value of the first digit from 0 through 2, value the value will wrap from 2 round to 0. Pressing the “ Up” key will advance the operation to the next
digit and set the first digit, in this case to “1”.
Enter New / Change Elbow value of the Output 1, first digit entered, prompting for second digit. (*Denotes that digit will be lashing). Pressing the “ Down” key will scroll the value of the second digit from 0 through to 9, the
value will wrap from 9 round to 0 depending on the set End value of Output. Pressing the “ Up” key will advance operation to the next digit and set the second digit, in this case to “1”.
27
Enter New / Change Elbow value of the Output 1, second digit entered, prompting for third digit. (*Denotes that digit will be flashing). Pressing the “ Down” key will scroll the value of the third digit
from 0 through to 9, the value willwrap from 9 round to 0 depending on the set End value of Output. Pressing the “ Up” key will advance the operation to the next digit and set the third digit, in this case to “0”.
Enter New / Change Elbow value
of the Output 1, third digit entered,
prompting for fourth digit. (*
denotes that digit will be flashing).
Pressing the “ Down” key will
scroll the value of the fourth digit
from 0 through to 9, the value will
wrap from 9 round to 0 depending
on the set End value of Output.
Pressing the “ Up” key will advance the operation to the “New / Changed Elbow value of the Output 1 confirmation” and set the fourth digit, in this case to “0”.
New/changed Elbow value of
the Output 1 confirmed.
Pressing the “ Down” key will re-
enter to the “New / Change Elbow
value of the Output 1”.
28
A
*
A
*
A
Pressing the “ Up” key will confirm New Elbow value of the Output 1 and advance to the Output 2 Characteristics setting (section 3.1.6.2).
3.1.6.2 Output 2 Characteristics selection
3.1.6.2.1 End value of output 2
This screen allows the user to set
the End value of Output 2,
(considerd as DC Voltage).
The End value of Voltage Output is
fixed at 10V.
Pressing the “ Down” key, value
remains constant because end
value is fixed. Pressing “ Up” key will set the present value as End value of the Output 2 and advance to the Start value of Output setting (section3.1.6.2.2).
3.1.6.2.2 Start value of output 2
This screen allows the user to set the Start value of Output 2,(considerd as DC Voltage). Start value of output can be set up to 20 % of End value of Output.
Pressing the “ Down” key will
enter the “New/Change Start
value of the Output 2 edit” mode.
Pressing “ Up” key will confirm
the present value as Start value of
the Output 2 and advance to the
Elbow value of Output setting
(section 3.1.6.2.3) or exit setup
menu.
29
*
New / Change Start value of the Output 2
(*Denotes that digit will be flashing).Pressing the “ Down” key will not affect the value of first digit, it is always 0. Pressing the “ Up” key will advance the operation to the next digit and set the first digit, in every case to “0”.
Enter New / Change Start value of the Output 2, first digit entered, prompting for second digit. (*Denotes that digit will be flashing). Pressing the “ Down” key will scroll the value of the second digit from 0 through to 2 the
value will wrap from 2 round to 0. Pressing the “ Up” key will advance the operation to the next digit and set the second digit, in this case to “1”.
Enter New / Change Start value
of the Output 2, second digit
entered, prompting for third digit.
(*Denotes that digit will be
flashing).
Pressing the “ Down” key will
scroll the value of the third digit
from 0 through 9, the value will
wrap from 9 round to 0. Pressing the “ Up” key will advance the operation to the next digit and set the third digit, in this case to “5”.
30
*
*
Enter New / Change Start value of the Output 2, third digit entered, prompting for fourth digit. (* denotes that digit will be flashing). Pressing the “ Down” key will scroll the value of the fourth digit from 0 through to 9, the value will
wrap from 9 round to 0. Pressing the “ Up” key will advance the operation to the “New / Changed Elbow value of the Output 2 confirmation” and set the fourth digit, in this case to “0”.
New/changed Start value of the Output 2 confirmed.
Pressing the “ Down” key will
re-enter to the “New / Change
Start value of the Output 2”.
Pressing the “ Up” key will
confirm New Start value of the
Output 2 and advance to the
Elbow value of Output setting
(section 3.1.6.2.3) or exit setup
menu, If elbow not enabled.
3.1.6.2.3 Elbow value of output 2
This screen appears only when
Elbow function is enabled.
This screen allows the user to set
the Elbow value of Output2
(considered as DC Voltage).
The Elbow value can be set any
value between set Start value and
End value of Output.
31
*
Pressing the “ Down” key will enter the “New/Change Elbow value of the Output 2 edit” mode. Pressing “ Up” key will confirm the present value as Elbow value of the Output 2 and exit setup menu.
New / Change Elbow value of the Output 2
(*Denotes that digit will be flashing).
Pressing the “ Down” key will scroll the value of the first digit from 0 through to 1, the value will wrap from 1 round to 0. Pressing the “ Up” key will advance the operation to the next digit and set the first digit, in this case to “0”.
Enter New / Change Elbow value of the Output 2, first digit entered, prompting for second digit. (*Denotes that digit will be flashing). Pressing the “ Down” key will scroll the value of the second digit from 0 through to 9, the
value will wrap from 9 round to 0 depending the set End
value of Output2. Pressing the “ Up” key will advance the operation to the next digit and set the second digit, in this case to “5”.
Enter New / Change Elbow value of the Output 2, second digit
*
*
*
32
entered, prompting for third digit. (*Denotes that digit will be flashing). Pressing the “ Down” key will scroll the value of the third digit from 0 through to 9, the value will wrap from 9 round to 0 depending the set End value of Output. Pressing the “ Up” key will advance the operation to the next digit and set the third digit, in this case to “0”.
Enter New / Change Elbow value of theOutput 2, third digit entered, prompting for fourth digit. (*denotes that digit will be flashing). Pressing the “ Down” key will scroll the value of the fourth digit
from 0 through to 9, the value will wrap from 9 round to 0 depending the set End value of Output. Pressing the “ Up” key will advance the operation to the “New / Changed Elbow value of the Output 2 confirmation” and set the fourth digit, in this case to “0”.
New/changed Elbow value of the Output 2 confirmed.
Pressing the “ Down” key will re- enter to the “New / Change Elbow
value of the Output 2”.
Pressing the “ Up” key will
confirm New Elbow value of the
Output 2 and exit setup menu.
33
*
3.2
For programming of transducer, steps to be followed are
Step 1 : DIP Switch setting
DIP Switches should configure for desired Output type as per given in section 3.3.1
Step 2 : programming
Programming Via Programming port available at front of Transducers using optional PRKAB60 Adapter
A PC with RS 232 C interface along with the programming cable PRKAB60 and the configuration software are required to program the transducer.
( Details of t he programming cable and the software are to be found in the separate Data sheet: PRKAB 60 Le.)
The connections between “PC PRKAB 60 Transducer. The power supply must be applied to before it can be programmed. The Configuration software is supplied on a CD. The programming cable PRKAB600 adjusts the signal level and provides the electrical insulation between the PC and Transducers.
34
PRKAB 600
Programming
Power supply
Transducer Programing cable
Software CD
Transducer
connector
35
3.3 Programming Via optional RS485 (MODBUS) communication port.
1) To change O/P switches from Current to Voltage or vice versa, ensure that transducer should be Electrically dead and all connection wires should be disconnected.
(Refer section 4 for programming through MODBUS)
3.3.1: DIP Switch Setting for Changing Output type
The Transducer output type can be changed from DC current to DC voltage depending upon user requirement on site. To change output type user has to set the transducer output type parameter either to voltage or current along with DIP switch setting. The transducer output type parameters can be configured using one of the three below given methods.
A) PRKAB 601(optional) : Using PRKAB601 through Transducer programming port (COM) and using PC based configuration software.
B) Front display (optional): Using front display user can enter into programming mode and can change the output type.
C) Modbus Rs485(optional): Using Modbus interface user can configure the output type refer Modbus Rs485 section.
Note: If DIP switch setting is done first and then output type parameter is configured using either of the above three methods then switch OFF - ON the Transducer. For changing DIP switches follow these steps
Switches of Output 2,can be set for desired Output type Voltage or Current.
Switches of Output 1,can be set for desired Output type Voltage or Current.
36
2
3
4
6) After inserting the front cover insert the Interface card PCB and back cover..
Insert the Interface card PCB and Back cover, press in direction of arrow.
7) After inserting the Back cover transducer, can be used for required application..
37
Insert the front cover, press in direction of arrow.
5) After changing the switches for desired Output, Insert the front cover.
4. RS 485 ( ModBus )
Current Transducer supports MODBUS (RS485) RTU protocol( 2-wire )Connection should be made using twisted pair shielded cable. All "A" and "B" connections are daisy chained together. The screens should also be connected to the “Gnd” terminal. To avoid the possibility of loop currents, an Earth connection should be made at one point on the network. Loop (ring) topology does not require any termination load. Line topology may or may not require terminating loads depending on the type and length of cable
used. The impedance of the termination load should match
the impedance of the cable and be at both ends of the line. The cable should be terminated at each end with a 120 ohm (1/4 Watt min.) resistor.
RS 485 network supports maximum length of 1.2km. Including the Master, a maximum of 32 instruments can be connected in RS485 network. The permissible address range for Current Transducer is between 1 and 247 for 32 instruments. Broadcast Mode (address 0) is not allowed.
The maximum latency time of current transducer is 200ms i.e. this is the amount of time that can pass before the first response character is output.
After sending any query through software ( of the Master) , it must allow 200 ms of time to elapse before assuming that the Current Transducer is not going to respond. If slave does not respond within 200 ms, Master can ignore the previous query and can issue fresh query to the slave.
38
03
Read Holding Registers
Read content of read /write location ( 4X )
04
Read input Registers
Read content of read only location ( 3X )
16
Presets Multiple Registers
Set the content of read / write locations ( 4X )
Exception Cases : An exception code will be generated when Current Transducer receives ModBus query with valid parity & error check but which contains some other error ( e.g. Attempt to set floating point variable to an invalid value ) The response generated will be “Function code” ORed with HEX (80H ).The exception codes are listed below
Communication Baud Rate is user selectable from the front panel between 2400, 4800, 9600, 19200 bps.
The each byte in RTU mode has following format
Format of Data Bytes
Error Checking Bytes
Byte format
4 bytes (32 bits) per parameter. Floating point format ( to IEEE 754) Most significant byte first (Alternative least significant byte first)
8-bit binary, hexadecimal 0-9, A-F 2 hexadecimal characters contained in each 8­bit field of the message
2 byte Cyclical Redundancy Check (CRC)
1 start bit, 8 data bits, least significant bit sent first 1 bit for even/odd parity 1 stop bit if parity is used; 1 or 2 bits if no
Function code
39
4.1 Accessing 3 X register for reading measured values
Two consecutive 16 bit registers represent one parameter. Refer table 2 for the addresses of 3X registers (Parameters measured by the instruments). Each parameter is held in the 3X registers. Modbus Code 04 is used to access all parameters.
Example
To read parameter , Current: Start address= 06(Hex)Number of registers=02
Note : Number of registers = Number of parameters x 2
Each Query for reading the data must be restricted to 20 parameters or less. Exceeding the 20 parameter limit will cause a ModBus exception code to be returned.
01
Illegal function The function code is not supported by
Current Transducer.
02
Illegal Data Address
Attempt to access an invalid address or an attempt to read or write part of a floating point value
03
Illegal Data Values
Attempt to set a floating point variable to an invalid value
Query
Device
Address
Function
Code
Start
Address
High
Start
Address
Low
Number
of
Registers
Hi
Number
of
Registers
Lo
CRC Low
CRC High
01
(Hex)
04
(Hex)
00
(Hex)06(Hex)
00
(Hex)
02
(Hex)
91
(Hex)
CA
(Hex)
40
Start Address High : Most significant 8 bits of starting
address of the parameter requested.
Start Address low : Least significant 8 bits of starting
address of the parameter requested
Number of register Hi: Most significant 8 bits of Number of
registers requested.
Number of register Lo: Least significant 8 bits of Number
of registers requested. (Note : Two consecutive 16 bit register represent one parameter.)
Response: Current (5.0A)
Device
Address
Function
Code
Byte
Count
Data
Register1
High Byte
CRC High
01
(Hex)
04
(Hex)
04
(Hex)
40
(Hex)
A0
(Hex)
00
(Hex)
00
(Hex)
EE
(Hex)
Data
Register1
Low
Byte
Data
Register2
High Byte
Data
Register2
Low
Byte
66
(Hex)
CRC Low
Byte Count : Total number of data bytes received. Data register 1 High Byte: Most significant 8 bits of Data
register 1 of the parameter requested.
Data register 1 Low Byte: Least significant 8 bits of Data
register 1 of the parameter requested.
Data register 2 High Byte : Most significant 8 bits of Data
register 2 of the parameter requested.
Data register 2 Low Byte: Least significant 8 bits of Data
register
2 of the parameter requested.
(Note : Two consecutive 16 bit register represent one parameter.)
41
4.2 Accessing 4 X register for Reading & Writing
Each setting is held in the 4X registers .ModBus code 03 is used to read the current setting and code 16 is used to write/change the setting. Refer Table 3 for 4 X Register addresses.
Example : Reading Device address Device address : Start address = 0E (Hex) Number of registers
= 02
Table 2 : 3 X register addresses (measured parameters)
Modbus Start
Address Hex
High Byte Low Byte
Parameter
Parameter
No.
Address
(Register)
30007
1
Current
00 06
Device Address Function Code Start Address High
Start Address Low Number of Registers Hi Number of Registers Lo CRC Low
CRC High
01 (Hex) 03 (Hex) 00 (Hex)
0E(Hex) 00 (Hex) 02 (Hex) A5 (Hex)
C8 (Hex)
Start Address High : Most significant 8 bits of starting
address of the parameter requested.
Start Address low : Least significant 8 bits of starting
address of the parameter requested.
Query
42
Number of register Hi : Most significant 8 bits of Number of
registers requested.
Number of register Lo : Least significant 8 bits of Number of
registers requested. (Note : Two consecutive 16 bit register represent one parameter.)
Response: Device address ( 1 )
Device Address Function Code Byte Count
Data Register1 High Byte Data Register1Low Byte Data Register2 High Byte
Data Register2 Low Byte
CRC Low CRC High
01 (Hex) 03 (Hex) 04 (Hex)
3F (Hex) 80 (Hex)
00 (Hex)
00 (Hex)
F7 (Hex) CF(Hex)
Byte Count : Total number of data bytes
received.
Data register 1 High Byte : Most significant 8 bits of Data
register 1 of the parameter requested.
Data register 1 Low Byte : Least significant 8 bits of Data
register
1 of the parameter requested.
Data register 2 High Byte : Most significant 8 bits of Data
register
2 of the parameter requested.
Data register 2 Low Byte : Least significant 8 bits of Data
register 2 of the parameter requested.
43
Query:( Change Device address to 2)
Device Address Function Code
Byte Count Data Register-1 High Byte
Data Register-1Low Byte Data Register-2 High Byte
Data Register-2 Low Byte
CRC Low CRC High
01 (Hex) 10 (Hex)
04 (Hex) 40 (Hex)
00 (Hex)
00 (Hex)
00 (Hex)
67 (Hex) E3(Hex)
Starting Address High Starting Address Low
Number of Registers Hi Number of Registers Lo
00 (Hex) 0E(Hex)
00 (Hex) 02 (Hex)
44
(Note : Two consecutive 16 bit register represent one parameter.)
Example : Writing Device address
Device address : Start address = 0E (Hex) Number of registers = 02
Byte Count : Total number of data bytes received. Data register 1 High Byte : Most significant 8 bits of Data
register 1 of the parameter requested.
Data register 1 Low Byte : Least significant 8 bits of Data
register 1 of the parameter requested.
Data register 2 High Byte : Most significant 8 bits of Data
register 2 of the parameter requested.
Start Address High : Most significant 8 bits of starting
address of the parameter requested.
Start Address low : Least significant 8 bits of starting
address of the parameter requested.
Number of register Hi: Most significant 8 bits of
Number of registers requested.
Number of register Lo : L east si gnifi c ant 8 b its o f
Number of registers requested.
(Note : Two consecutive 16 bit register represent one parameter.)
Table 3 : 4 X register addresses
Device Address Function Code Start Address High
Start Address Low Number of Registers Hi Number of Registers Lo CRC Low
CRC High
01 (Hex) 10 (Hex) 00 (Hex)
0E (Hex) 00 (Hex) 02 (Hex) 20 (Hex)
0B (Hex)
Response
45
Data register 2 Low Byte : Least significant 8 bits of Data
register 2 of the parameter requested.
(Note: Two consecutive 16 bit register represent one parameter.)
Modbus Start Address Hex
Parameter No.
1
3
2
Address (Register)
40001 40003 40005
Parameter
-
-
Mode selection
Read / Write
-
R/Wp
-
-
00
-
High Byte
-
02
-
Low Byte
46
Modbus Start Address Hex
20
Para­meter No.
7 8
11 12 13
14 15 16 17 18
19
9
10
40039
Address (Register)
40019
40015
40021 40023 40025
40027 40029
40031 40033 40035
40037
40013
40017
-
Parameter
CT Secondary
Password
-
-
Sim_Output A Sim_Output B
Analog O/P Type 1
Analog O/P Type 2
-
-
Device address
RS 485 Setup
-
Read / Write
-
R/Wp
R/Wp
-
-
Wp
Wp
R/Wp
-
R/Wp
-
-
R/Wp R/Wp
-
00 00
-
00 00 00
-
00
-
-
-
00 00
High Byte
-
0C
-
1A 1C 1E
-
22
-
-
-
10
0E
12
Low Byte
4 5 6
40007 40009
40011
CT Primary
-
-
-
-
R/Wp
-
-
00
0A
-
-
This is used to select the Mode of operation.Normal mode = 1. Simulation mode = 2.
This address allows the user to set CT Primary value. The maximum settable value is 9999..
This address is used to read and write the CT secondary value in range between 1A to 5A.
40003
Mode Selection
40011
CT Pimary
400 31
CT Secondary
Explanation for 4 X register
This address is used to set the simulation Output B to 10% of Output by writing 1000 and 100% of Output by writing 10000 .
This address is used to set the Baud rate, Parity, No of Stop bits.
This address is used to set & reset the password. Valid Range of Password can be set is 0000 - 9999
This address is used to set the simulation Output A to 10% of Output by writing 1000 and 100% of Output by writing 10000 .
This address is used to set the Analog O/P Type 1 as Voltage/Current.
Voltage = 1 ,Current = 2.
This address is used to set the Analog O/P Type 2 as Voltage/Current.
Voltage = 1 , Current = 2.
40017
RS 485 Setup
40019
Password
40027
Sim_ Output A
40029
Output B
Sim_
40031
Analog O/P Type 1
40035
Analog O/P Type 2
This address is used to set the Device Address between 1 to 247.
40015
Device Adress
Note: After Changing Analog Output Type1/Type 2 please
insure to change DIP Switch setting (Refer Section 3.3.1). If DIP Switches are already change then switch ON/OFF Transducer.
Table 4 : RS 485 Set-up Code
47
19200 19200
19200
9600
19200
NONE
NONE
ODD
EVEN
NONE
Baud Rate Parity
Stop Bit
Decimal value
01
01 01
01
02
13
14 15
08
12
Note : Codes not listed in the table above may give rise to unpredictable results including loss of communication. Exercise caution when attempting to change mode via direct Modbus writes.
Current Transducer
The can be mounted either on a top-hat rail or directly on to a wall or a mounting plate.
5. Installation
The front of the enclosure conforms to IP 40. The terminals of the product should be protected from liquids. The Current
Transducer should be mounted in a reasonably stable ambient temperature and where the operating temperature is
0
within the range 0 to 45 C . Vibration should be kept to a minimum and the product should not be mounted where it will be subjected to excessive direct sunlight.
48
9600 9600
EVEN
NONE
02
01
09 10
9600 4800 4800 4800 4800 2400
2400 2400
2400
ODD NONE NONE
NONE NONE
ODD
EVEN
ODD
EVEN
Stop Bit
ParityBaud Rate Decimal value
02
01
01 01
02
01
01 01
01
11 04 05 06 07 00
01
02 03
Caution
1. In the interest of safety and functionality this product
must be installed by a qualified engineer, abiding by any local regulations.
2. Voltages dangerous to human life are present at some
of the terminal connections of this unit. Ensure that all supplies are de-energised before attempting any connection or disconnection.
3. These products do not have internal fuses therefore
external fuses must be used to ensure safety under
fault conditions.
5.1 EMC Installation Requirements
This product has been designed to meet the certification of the EU directives when installed to a good code of practice for EMC in industrial environments, e.g.
1. Screened output and low signal input leads or have provision for fitting RF suppression components, such as ferrite absorbers, line filters etc., in the event that RF fields cause problems.
Note: It is good practice to install sensitive electronic instruments that are performing critical functions, in EMC enclosures that protect against electrical interference which could cause a disturbance in function.
2. Avoid routing leads alongside cables and products that are, or could be, a source of interference.
3. To protect the product against permanent damage, surge transients must be limited to 2kV pk. It is good EMC practice to suppress differential surges to 2kV at the source. The unit
49
has been designed to automatically recover in the event of a high level of transients. In extreme circumstances it may be necessary to temporarily disconnect the auxiliary supply for a period of greater than 5 seconds to restore correct operation.
The Current inputs of these products are designed for connection in to systems via Current Transformers only, where one side is grounded.
4. ESD precautions must be taken at all times when handling this product.
5.2 Case Dimensions
5.3 Wiring
Input connections are made directly to screw-type terminals
with indirect wire pressure. Choice of cable should meet local regulations. Terminal for Current inputs will accept up to 2x 2.5mm cables.
5.4 Auxiliary Supply
it may be powered from the signal source, provided the source remains within the limits of the chosen auxiliary voltage. A switch or circuit, may
² or 1x 4mm²
Transducer should ideally be powered from a dedicated supply, however
be used in close
proximity to the equipment &
100.9
43.5
65.5
106.5
50
within easy reach of the OPERATOR & It shall be marked as the disconnecting device for the equipment.
No maintenance is required.
5.5 Fusing
It is recommended that all voltage lines are fitted with 1 amp HRC fuses.
5.6 Earth/Ground Connections
For safety reasons, CT secondary connections should be grounded in accordance with local regulations.
5.7: Maintenance
6. Specifications
Input
Nominal input Current I 1 A< I < 5 A
N N
(AC RMS) (CT Secondary range) CT Primary range 1 A to 9999 A Nominal Frequency F 45 to 66 Hz
N
Input burden < 0.2 VA at I
N
Overload Capacity: 1.2 * I continuously,
N
10 * I for 3 second, repeated
N
5 times at 5 minute intervals.
50 *I for 1 second, repeated 1 time
N
at 1 hour interval (max 250 A).
51
Auxiliary
AC/DC Auxiliary Supply 60V….300 VAC-DC ±5%
24V….60 VAC-DC ±10%
Auxiliary Supply 40......65 Hz
frequency range Auxiliary Supply consumption
Measuring Output Y ( Single or Optional Dual)
Output type Load independent DC Voltage or
DC Current (Onsite selectable through DIP switches &
Programming.) Load independent DC - 0…20mA / 4…20mA OR output 0…10V. Output burden with DC 0 < R < 15V/Y2 current output Signal
Output burden with DC Y2/(2 mA)< R < voltage output Signal
Current limit under < 1.25 * Y2 with current output overload R=0 < 100 mA with Voltage output
Voltage limit under R= < 1.25 * Y2 with voltage output
< 30 V with current output Residual Ripple in <1% pk-pk Output signal Response Time < 400 ms.
52
VA for one output£8
£ 10VA for two outputs
60V…….300 VAC-DC
24V…….60 VAC-DC
VA for one output£5
£ 6VA for two outputs
Y
X
Y0
X0
Y2
X2
Y
X
Y0
X0
Y2
X2
Output characteristics
1) Example of setting with Linear characteristics
Y0 Y2 X0 X2
1
1
or C=1
C=
Linear characteristics
C=
Y1 - Y0 X2 X1 - X0 Y2
or C=1
C=
Y1 Y2 X1 X2
1
1
or C=1
Bent characteristics
53
Accuracy: ( Acc. to IEC 60688)
Reference Value Output end Value Y2 (Voltage or Current) Basic Accuracy 0.2*C Factor C (The Highest value applies)
X0 = Start value of input Y0 = Start value of output X1 = Elbow value of input Y1 = Elbow value of output X2 = End value of input Y2 = End value of output R = Rated value of I = Nominal input current .
N N
output burden
Ambient temperature 23°C +/- 1°C Pre-conditioning 30 min acc. to IEC EN - 60688 Input Variable Rated Current Input waveform Sinusoidal, Form Factor 1.1107 Input signal frequency 50 or 60Hz Auxiliary supply voltage Rated Value Auxiliary supply frequency Rated Value Output Load Rn =7.5 V / Y2 ± 1%With DC current output signal.
Rn = Y2 / 1 mA ± 1% With DC Voltage output signal. Miscellaneous Acc. to IEC EN - 60688
Reference conditions for Accuracy
54
Y
X
Y0
X0
Y2
X2
YY
Y
X
Y0
X0
Y2
X2
Y1
X1
X1
Y1
2) Example of setting with Bent characteristics:
Additional Error
Temperature influence ± 0.2% /10°C Influence of Variations: As per IEC EN-60688 standard. Output stability < 30min
Safety
Protection Class II (Protection Isolated, EN 61010) Protection IP 40, housing according to EN 60 529
IP 20,terminal according to EN 60 529 IP Pollution degree 2 Installation Category III Insulation Voltage 1min. ( EN 61 010-1) 7700V DC, Input versus outer surface
5200V DC, Input versus all other circuits 5200V DC, Auxiliary supply versus outer
surface and output
690V DC, Output versus output versus
RS485 versus outer surface.
Installation Data
Mechanical Housing Lexan 940 (polycarbonate)
Flammability Class V-0 acc. To UL 94, self extinguishing, non dripping, free of halogen Mounting position Rail mounting / wall mounting Weight Approx. 0.4kg
Connection Terminal
Connection Element Conventional Screw type terminal with indirect wire pressure
2
Permissible cross section < 4.0 mm single wire or 2
2
of the connection lead x 2.5mm Fine wire
55
Environmental
Nominal range of use 0 °C...23 °C... 45 °C
(usage Group II)
Storage temperature -40 °C to 70 °C Relative humidity of < 75% annual mean Altitude 2000m max
Ambient tests
EN 60 068-2-6 Vibration Acceleration ± 2 g
Frequency range 10....150...10Hz,
Rate of frequency sweep 1 octave/minute Number of cycles 10, in each of the three axes EN 60 068-2-27 Shock Acceleration 3 x 50g
3 shocks in each direction EN 60 068-2-1/-2/-3 Cold, Dry, Damp heat IEC 61000-4-2/-3/-4/-5/-6 IEC 61326 Electromagnetic compatibility.
Location Indoor use
7. Connection Diagram
56
5 6
7
8
1
2
3
4
Input I
~ ~
Aux
~
~
+
-
Output-1
+
-
Output-2
+
-
(Optional)
57
58
Meaning of symbols on the instrument
Warning concerning a point of danger (Attention:observe documentation)
Equipment protected throught by Double insulation or reinforced insulation
DC voltage /Current
AC/DC voltage
3.7
Isolation between input versus all other circuit is 3.7 KV.
Notes
59
Notes
60
Notes
61
The Information contained in these installation instructions is for use only by installers trained to make electrical power installations and is intended to describe the correct method of installation for this product. However, Manufacturer has no control over the field condition which influence product installation. It is the user's responsibility to determine the suitability of the installation method in the user's field conditions. Manufacturer only obligation are those in manufacturer condition of sale for this product or in no case will manufacturer be liable for any other incidental, indirect or consequential damages arising from the use or misuse of the products.
Notes
62
Notes
63
RISHABH
INSTRUMENTS
Measure, Control & Record with a Difference
F-31, M.I.D.C., Satpur, Nashik 422 007, India. Tel. : +91 253 2202162, 2202202, Fax : +91 253 2351064 Email : marketing@rishabh.co.in www.rishabh.co.in
RISHABH INSTRUMENTS PVT. LTD.
Loading...