Rish Master 3430 Operating Manual

Page 1
RISH Master 3430
RISH Master 3430
Operating Manual
%THD
Page 2
Section
Multi-function Digital Meter
Installation & Operating Instructions
1. Introduction
2. Measurement Reading Screens
3. Programming
3.1 Password Protection
INDEX
3.2 Set Up Screens
3.2.1 System Type
3.2.2 Potential Transformer Primary value
3.2.4 Current Transformer Primary value
3.2.5 Current Transformer Secondary value
3.2.6 Reset
3.2.8 Low current noise cutoff
3.2.9 RS 485 Device Address
3.2.10 RS 485 Baud rate
3.2.11 RS 485 Parity Selection
3.2.12 Assignment of Energy to Pulse output-1
3.2.13 Assignment of Energy to Pulse output-2
3.2.7 Auto Scrolling
3.2.3 Potential Transformer Secondary value
1
Page 3
DMAN-00IM-0647 Rev D - 06/2018
3.2.15 Pulse rate
3.2.16 Parameter setting for Analog output -1
3.2.17 Parameter setting for Analog output -2
3.2.18 Energy update rate
3.2.19 Energy digit reset count.
3.2.20 Energy display on Modbus
3.2.14 Pulse duration
10.
Specification
8. Installation
8.1 EMC Installation Requirements
8.2 Case Dimensions and Panel Cut-out
8.3
Wiring
8.4 Auxiliary Supply
8.5 Fusing
8.6 Earth / Ground Connections
9.
Connection Diagrams
11.
Connection for Optional Pulse output / RS 485 /Analog Ouput
4. Analog output option
Relay Output (optional)
5. Rs485 MODBUS Output
7.
Phaser Diagram
6.
2
Page 4
1. Introduction
The 3430 is a panel mounted 96 x 96mm DIN Quadratic Digital metering system for the measurement important electrical parameters like AC voltage, AC Current, Frequency, Power, Energy(Active / Reactive / Apparent) .
The instrument integrates accurate measurement technology (All Voltages &
Current measurements are True RMS upto 15th Harmonic) with 3 line 4 digits
Ultra high brightness LED display.
3430 can be configured and programmed
at site for the following : PT Primary, PT Secondary, CT Primary,
CT Secondary (5A or1A) and 3 phase 3W
or 3 Phase 4W system.
Down
Up
VRY
KVAr
Sys
V
x1000
KVArh
IN
Ph R
KAh
VYB
A
KVA
Min
x1000
Hz
KVAh
Ph Y
%THD
Angle
KW
VBR
Max
x1000
P.F. KWh Ph B
Down
Up
Max KVAr
V
x1000
KVArh
Angle
A
KVA
Min
x1000
Hz
D
kVAh
KW
kAh
x1000
P.F.
kWh
%THD
The screen shown on left is of 3 Phase Meter.
The front panel has two push buttons through which the user may scroll through the available measurement readings, reset the energy (Import/Export) Min/Max (System Voltage and System Current) and configure the product.
The screen shown further is of 1 Phase Meter.
3
Page 5
TABLE 1:
Measured Parameters
System Voltage System Current Voltage VL1-N(4wire only) Voltage VL2-N(4wire only) Voltage VL3-N(4wire only) Voltage VL1-L2 Voltage VL2-L3 Voltage VL3-L1 Current L1 Current L2 Current L3
Units of
Volts
Amps
Volts Volts Volts Volts Volts
Volts Amps Amps
Neutral Current ( 4 wire only )
Amps Amps
Measurement
Active Import Energy (8 Digit resolution)
kWh kWh
Active Export Energy (8 Digit resolution)
Active Power (System / Phase (4 wire only) ) Reactive Power (System / Phase (4 wire only))
Apparent Power (System / Phase (4 wire only)) Power Factor (System / Phase (4 wire only))
Phase Angle ( Phase(4 wire only))
Kwatts
KVAr
KVA
Degree
kVArh
Reactive Import Energy (8 Digit resolution)
kVArh
Reactive Export Energy (8 Digit resolution)
kVAh
Apparent Energy (8 Digit resolution)
( for 3 / 4 wire)
( for 3 / 4 wire)
( for 3 / 4 wire)
( for 3 / 4 wire)
( for 3 / 4 wire)
( for 3 / 4 wire)
4
Page 6
*Note : THD Parameters are L-N in case of 3P 4W & L-L in case of 3P 3W .
Measured Parameters
Units of
Measurement
I1 THD I2 THD
V1 THD* V2 THD*
V3 THD*
%
I3 THD System Voltage THD System Current THD
% %
% % %
% %
( for 3 / 4 wire)
( for 3 / 4 wire)
( for 3 / 4 wire)
( for 3 / 4 wire)
( for 3 / 4 wire)
( for 3 / 4 wire)
5
Page 7
2. Measurement Reading Screens
In normal operation the user is presented with one of the measurement reading screens out of several screens. These screens may be scrolled through one at a time in incremental order by pressing the “ Up key” and in decremental order by pressing “ Down key”.
Parameter Screens 1 Phase
System Voltage System Current
System Active Power
Phase Angle
Frequency
System Power Factor
Reactive Power Apparent Power Active Power
Active Energy Import
Min. System Voltage Min. System Current
Active Energy Export
Reactive
Energy Import
Reactive
Energy Export
Apparent
Energy
Max. System Voltage Max. System Current
System Voltage
Current % THD
6
Page 8
Parameter Screens 3 Phase
System Voltage System Current
System Active Power
R Phase V L-N* Y Phase V L-N*
B Phase V L-N*
R Phase Current Y Phase Current
B Phase Current
Neutral Current*
Frequency
System Power Factor
Reactive Power Apparent Power
Active Power
Active Energy Import
Min. System Voltage Min. System Current
Active Energy Export
Reactive
Energy Import
Reactive
Energy Export
Apparent
Energy
Max. System Voltage Max. System Current
R Phase Reactive Power*
R Phase Apparent Power*
R Phase Active Power*
Y Phase Reactive Power*
Y Phase Apparent Power*
Y Phase Active Power*
B Phase Reactive Power*
B Phase Apparent Power*
B Phase Active Power*
Phase Angle R* Phase Angle Y*
Phase Angle B*
Phase Power Factor R* Phase Power Factor Y*
Phase Power Factor B*
Voltage %
THD
Current %
THD
System Voltage
Current % THD
VRY V L-L VYB V L-L
VBR V L-L
A
A
NOTE: SCREENS MARKED WITH * ARE AVAILABLE
ONLY IN 4W SYSTEM (NOT IN 3 WIRE SYSTEM)
7
Page 9
Setup Parameter Screens
SYS*
(System Type)
PtPr
(PT Primary)
PtSc
(PT Secondary)
CtPr
(CT Primary)
CtSc
(CT Secondary)
rsEt
(reset parameter)
Auto
(Auto Scrolling)
n.Cut
(Noise Current Cutoff)
Addr
(Modbus address)
bAUd
(baud rate)
Prty
(Parity
bits)
none (No Parameter) ALL (All Parameter) E (Energy) hi (Max Values) Lo(Min V
alues) Select any one option using down key
rl1
(Relay 1 )
rl2
(Relay2)
puls
(Pulse Duration)
rAtE
(Pulse Divisor)
codE
(Password)
AnL1
(Analog1 Parameter
Selection)
AnL2
(Analog1 Parameter
Selection)
Enrt
(Energy update rate)
Edrc
(Energy digit reset
count)
En.OP
(Energy Output on
Modbus)
*Note :Sys type selection screen is not available in 1 phase.
8
Page 10
3.1. Password Protection
Password protection can be enabled to prevent unauthorized access to set-up screens, by default password protection is not enabled.
Password protection is enabled by selecting a four digit number other than 0000, setting a password of 0000 disables the password protection.
3. Programming
The following sections comprise step by step procedures for configuring the 3430 for individual user requirements.
To access the set-up screens press and hold the “ Key simultaneously for 5 seconds. This will take the User into the Password Protection Entry Stage (Section 3.1).
Down” and “ Up”
VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F. KWh Ph B
KAh
%THD
9
Page 11
VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F. KWh Ph B
KAh
%THD
Enter Password, second digit entered, prompt for third digit. (* Denotes that decimal point will be flashing).
Use the “ Down” key to scroll the value of the third digit from 0 through to 9, the value will wrap from 9 round to 0.
Press the “ Up” key to advance to next digit.
VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F. KWh Ph B
KAh
%THD
Enter Password, third digit entered, prompt for fourth digit. (* Denotes that decimal point will be flashing).
Use the “ Down” key to scroll the value of the fourth digit from 0 through to 9, the value will wrap from 9 round to 0.
Press the “ Up” key to advance to verification of the password.
VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F. KWh Ph B
KAh
%THD
10
Page 12
Enter Password, fourth digit entered, awaiting verification of the password.
VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F.
KWh
Ph B
KAh
%THD
Pressing the “ Up” key will advance to the
Password confirmed.
Pressing “ Down” key will advance to the “New / change Password” entry stage.
VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F. KWh Ph B
KAh
%THD
Password Incorrect.
The unit has not accepted the Password entered.
Pressing the " Down" key will return to the Enter Password stage.
Pressing the “ Up” key exits the Password menu and returns operation to the measurement reading mode.
VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F. KWh Ph B
KAh
%THD
Menu selection
11
Page 13
New / Change Password, first digit entered, prompting for second digit. (*Decimal point indicates that this will be flashing).
Pressing the “ Down” key will scroll the value of the second digit from 0 through to 9, the value will wrap from 9 round to 0.
Pressing the “ Up” key to advance the operation to the next digit and sets the second digit, in this case to “1”
VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F. KWh Ph B
KAh
%THD
New / Change Password (*Decimal point indicates that this will be flashing).
Pressing the “ Down” key will scroll the value of the first digit from 0 through to 9, the value will wrap from 9 round to 0.
Pressing the “ Up” key to advance the operation to the next digit and sets the first digit, in this case to “2”
VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F. KWh Ph B
KAh
%THD
New / Change Password, second digit entered, prompting for third digit. (*decimal point indicates that this will be flashing).
Pressing the “ Down” key will scroll the value of the third digit from 0 through to 9, the value will wrap from 9 round to 0.
Pressing the “ Up” key to advance the operation to the next digit and sets the third digit, in this case to “5”
VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F. KWh Ph B
KAh
%THD
12
Page 14
type confirmation menu.
New / Change Password, third digit entered, prompting for fourth digit. (* denotes that decimal point will be flashing).
Pressing the “ Down” key will scroll the value of the fourth digit from 0 through to 9, the value will wrap from 9 round to 0.
Pressing the “ Up” key to advance the operation to the “New Password Confirmed” and sets the fourth digit, in this case to “3”.
VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F.
KWh Ph B
KAh
%THD
VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F. KWh Ph B
KAh
%THD
New Password confirmed.
Pressing the “ Down” key will return to the “New/Change Password”.
Pressing the “ Up” key will advances to the
Menu selection screen.(see section 3.2).
3.2 Set up Screens
3.2.1 System Type
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB KVA Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
This screen is used to set the system type . System type ”3” for 3 phase 3 wire & “4” for 3 phase 4 wire system.
Pressing the “ Up” key accepts the present
primary value Edit” menu (see section 3.2.2)
value and advances to the “Potential transformer
Pressing the “ Down” key will enter the system type
edit mode and scroll the values through values available .
Pressing the “ Up” key advances to the system
13
Page 15
This screen will only appear following the edit of system type. If system type is to be Downed again,
Pressing the “ Down” key will return to the system type edit stage by blanking the bottom line of the display
Pressing the “ Up” key sets the displayed value and will advance to “Potential Transformer Primary Value Edit” menu. (See section 3.2.2)
System Type Confirmation
Pressing the “ Up” key accepts the present value and advances to the “potential Transformer secondary Value edit” menu. (See Section 3.2.3)
Pressing the “ Down” key will enter the “Potential Transformer Primary Value Edit” mode.
Initially the “multiplier must be selected, pressing the “ Down” key will move the decimal point position to the right until it reaches # # # .# after which it will return to #. # # #.
Pressing the “ Up” key accepts the present multiplier (decimal point position) and advances to the “potential Transformer primary Digit Edit” mode.
3.2.2 Potential Transformer Primary Value
The nominal full scale voltage which will be displayed as the Line to Line voltages for all
system types. The values displayed
represent the voltage in kilovolts (note the x1000 enunciator).
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB KVA Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB KVA Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
14
Page 16
Potential Transformer primary Digit Edit
Pressing the “ Down” key will scroll the value of the most significant digit from 0 through to 9 unless the presently displayed Potential Transformer Primary Value together with the Current Transformer Primary
Value, previously set, would result in a maximum power
of greater than 666.6 MVA per phase in which case the digit range will be restricted.
Pressing the “ Up” key accepts the present value at the cursor position and advances the cursor to the
next less significant digit.
The PT Primary value can be set from 100V L-L to 692.8 kV L-L.
Note : the flashing decimal point indicates the cursor position, a steady decimal point will be present to identify the scaling of the number until the cursor position coincides with the steady decimal point position. At this stage the decimal point will flash.
When the least significant digit has been set pressing the “ Up” key will advance to the “Potential Transformer Primary Value Confirmation” stage.
Screen showing display of 0.120 kV i.e. 120 Volts indicating steady decimal point and cursor flashing at the “hundreds of volts” position.
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB KVA Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
15
Page 17
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB KVA Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
L-L
Note : 0.120 kV i.e. 120 V
Potential Transformer Primary Value Confirmation
This screen will only appear following an edit of the Potential Transformer Primary Value.
If the scaling is not correct, pressing the “ Down” key will return to the “Potential Transformer Primary Value Edit” stage.
Pressing the “ Up” key sets the displayed value and will advance to the Potential Transformer secondary Value (See Section 3.2.3)
3.2.3 Potential Transformer secondary Value
The value must be set to the nominal full scale secondary voltage which will be obtained from the Transformer when the potential transformer(PT)primary is supplied with the voltage defined in 3.2.1.2. potential transformer primary voltage. The ratio of full scale primary to full scale secondary is defined as the transformer ratio.
The Valid range of instrument is from 100 to 600V
Transformer Secondary Value Edit” mode. “Down” key will scroll the value of the most significant digit from available range of PT secondary value
Pressing the “ Down” key will enter the “Potential
Pressing the “ Up” key accepts the present value and advances to the “Current Transformer Primary Value edit” menu. (See Section 3.2.4)
Pressing the “ Up” key accepts the present value at the cursor position and advances the cursor to the next less significant digit.
L-L .
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB KVA Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
16
Page 18
Note : the flashing decimal point indicates the cursor position, a steady decimal point will be present to identify the scaling of the number until the cursor position coincides with the steady decimal point position. At this stage the decimal point will flash.
When the least significant digit has been set pressing the “ Up” key will advance to the “Potential Transformer secondary Value Confirmation” stage.
3.2.4 Current Transformer Primary Value
The nominal Full Scale Current that will be displayed as the Line currents. This screen enables the user to display the Line currents inclusive of any transformer ratios, the values displayed represent the Current in Amps.
Pressing the “ Up” key accepts the present value and advances to the Current Transformer Secondary Value (See Section 3.2.5)
Potential Transformer Secondary Value Confirmation
This screen will only appear following an edit of the Potential Transformer Secondary Value.
If the scaling is not correct, pressing the “ Down” key will return to the “Potential Transformer Secondary Value Edit”
Pressing the “ Up” key sets the displayed value and will advance to the current Transformer Primary Value (See Section 3.2.4)
Pressing the “ Down” key will enter the “Current Transformer Primary Value Edit” mode.
This will scroll the value of the most significant digit from 0 through to 9,unless the presently
displayed Current Transformer Primary Value together with the Potential Transformer
VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F.
KWh
Ph B
KAh
%THD
17
Page 19
range will be restricted, the value will wrap.
Example: If primary value of PT is set as
692.8kV L-L (max value) then primary value
Pressing the “ Up” key will advance to the next less significant digit. (* Denotes that decimal point will be flashing).
Primary Value results in a maximum power of greater than 666.6 MVA in which case the digit
when the “ Up” key is pressed.
The “Maximum Power” restriction of 666.6 MVA refers to 120% of nominal current and 120% of nominal voltage, i.e, 462.96 MVA nominal power per phase.
When the least significant digit had been set, pressing the “ Up” key will advance to the “Current Transformer Primary Value Confirmation” stage.
The minimum value allowed is 1, the value will be forced to 1 if the display contains zero
of Current is restricted to 1157A.
Current Transformer Primary Value Confirmation.
This screen will only appear following an edit of the
.
If the scaling is not correct, Pressing the “ Down” key will return to the “ Current Transformer Primary
Value”Edit stage with the most significant digit highlighted (associated decimal point flashing)
and the bottom line of the display will be blanked.
Pressing the “ Up” key sets the displayed value and
will advance to the “Current Transformer Secondary Value Edit” menu. (See Section 3.2.5)
Current Transformer Primary Value.
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB
KVA Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB KVA Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
18
Page 20
3.2.5 Current Transformer Secondary Value
This screen is used to set the secondary value for Current Transformer. Secondary value “5” for 5A or “1” for 1A can be selected. Pressing “ Up” key accepts the present value and advances to the Reset parameter screen (See Section 3.2.6)
Pressing the “ Down” key will enter the CT Secondary value edit mode and scroll the value through the values available.
Pressing the “ Up” key will advance to the CT Secondary value confirmation.
CT Secondary value confirmation
This screen will only appears following an edit of CT secondary value .
If secondary value shown is not correct, pressing the Down key will return to CT secondary edit stage by blanking the bottom line of the display.
Pressing “ Up” key sets the displayed value and will advance to reset parameter menu.
(See Section 3.2.6)
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB KVA
Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB
KVA Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
19
Page 21
Pressing the “ Down” key will enter the “Reset option” mode and scroll through Parameter and wrapping back to None.
Pressing “ Up” key advances to Auto scroll selection screen
The following screens allow the users to reset the All parameters,Energy , Lo(Min), hi(Max).
3.2.6 Reset Parameter :
Reset option select, (Resets ALL resettable parameter)
The user has scrolled through to the “ALL” .
Pressing “ Up” key will select the value and advance to the “Reset ALL Confirmation” Mode &.
Will reset all resettable parameter.
VYB
VRY
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F. KWh Ph B
KAh
%THD
KVAr
Demand
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB KVA Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
20
Page 22
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB KVA Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB KVA Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB KVA Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
Reset option select, (Reset Energy)
The user has scrolled through to the “E” Energy value.
Pressing “ Up” key will select the value and advance to the “Reset Energy Confirmation” Mode.
Reset Energy Confirmation.
Pressing “ Up” key resets the all Energy parameters and advances to the Auto scroll setting. (see section 3.2.7.)
Pressing the “ Down” key will re-enter the “Reset option” mode.
Reset ALL Confirmation.
Pressing the “ Down” key will re-enter the “Reset option Select mode.
Pressing “ Up” key resets ALL the readings and advances to the Auto scroll.
21
Page 23
3.2.7 Auto Scrolling :
Pressing “ Up” key accepts the present status and advance to the Low Current noise cutoff (See Section 3.2.8).
This screen allows user to enable screen scrolling.
Auto scrolling Edit.
VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F. KWh Ph B
KAh
%THD
Pressing the “ Up” key will select the status displayed and advance to the Low Current noise cutoff (See Section 3.2.8)
Pressing the “ Down” key will enter the “Auto Screen Scrolling Edit” and toggle the status ‘Yes’ and ‘No’.
VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F.
KWh
KAh
%THD
Max
Ph B
3.2.8 Low Current noise cutoff.
This screen allows the user to set Low noise current cutoff in mA.
.
Pressing “ Up” key accepts the present value and advance to Rs485 address selection.
Pressing the “ Down” key will enter the “Low current noise cutoff Edit” mode and scroll the “Value” through 0 & 30 and wrapping back to 0. Setting 30 will display measured currents as 0 below 30 mA.
Low current cutoff Edit.
(See section 3.2.9)
VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F. KWh Ph B
KAh
%THD
22
Page 24
Low current noise cutoff Confirmation.
Pressing “ Up” key set displayed value and Advance to the Rs485 address selection.
(See section 3.2.9)
pressing the “ Down” key will re-enter the “Low current Noise cutoff Edit” mode.
3.2.9 RS 485 Address Selection:
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB
KVA Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
This screen applies to the RS 485 output only. This screen allows the user to set RS485
address for instruments
Enter Address, prompt for first digit.
(* Denotes that decimal point will be flashing).
Press the “ Down” key to scroll the value of the first digit
Press the “ Up” key to advance to next digit.
The range of allowable address is 1 to 247 .
VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F.
KWh Ph B
KAh
%THD
23
Page 25
VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F.
KWh Ph B
KAh
%THD
Enter Address, first digit entered, prompt for second
digit (* Denotes that decimal point will be flashing).
Use the “ Down” key to scroll the value of the
Press the “ Up” key to advance to next digit.
VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F.
KWh
Ph B
KAh
%THD
Enter Address, second digit entered, prompt for third digit (* Denotes that decimal point will be flashing).
Use the “ Down” key to scroll the value of the third digit
VYB
VRY
KVAr
Sys
V
A
KVA
Min
KW
VBR
Angle
Max
x1000
KVArh
x1000
x1000
IN
Ph R
Hz
KVAh
Ph Y
P.F. KWh Ph B
KAh
%THD
Address confirmation Screen.
This Screen confirms the Address set by user .
Press the “ Up” key to advance to next Screen
“Rs485 Baud Rate” (See Section 3.2.10)
Pressing the “ Down” key will reenter the “Address Edit” mode.
second digit
24
Page 26
RS 485 Baud Rate confirmation :
Pressing “ Down” key will be re-enter into Baud Rate Edit mode .
3.2.10 RS 485 Baud Rate :
This screen allows the user to set Baud Rate of RS 485 port.
The values displayed on screen are in kbaud .
Pressing “ Up” key accepts the present value and advance to the Parity Selection (see section 3.2.11).
Pressing the “ Down” key will enter the “Baud Rate Edit” mode and scroll the value through 2.4, 4.8, 9.6 ,
19.2 and back to 2.4
Pressing the “ Up” key will select the value and advances to the Parity Selection (see section 3.2.11).
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB
KVA Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB KVA Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
25
Page 27
3.2.11 RS 485 Parity Selection :
This screen allows the user to set Parity & number of stop bits of
RS 485 port.
Pressing “ Up” key accepts the present value and advance to the Pulse output 1 selection (see section 3.2.12).
Pressing the “ Down” key will enter the “Parity & stop bit Edit” mode and scroll the value through
odd : odd parity with one stop bit no 1 : no parity with one stop bit
no 2 : no parity with two stop bit
E : even parity with one stop bit
Pressing the “ Up” key will set the value and advances to the Pulse output Selection (see section 3.2.12).
RS 485 Parity confirmation :
Pressing “ Down” key will be re-enter into Parity Edit mode .
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB KVA Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB
KVA Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
26
Page 28
3.2.12. Assignment of Energy to pulse output 1 :
Pressing “ Up” key accepts the present setting and advance to “Assignment of Energy to Pulse Output 2”(see section 3.2.13).
This screen allows the user to assign pulse output1 to energy
Pressing the “ Down” key will enter into edit mode and scroll through the energy setting
A - E : Apparent Energy I - E : Import Energy ( Active )
E - E : Export Energy ( Active ) I - rE : Import Reactive Energy E - rE : Export Reactive Energy
Pressing the “ Up” key will set the value and advances to the “Assignment of Energy to pulse output 2”(see section 3.2.13).
Pulse output1 confirmation :
Pressing “ Down” key will be re-enter into edit mode .
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB KVA Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB KVA
Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
27
Page 29
3.2.13. Assignment of Energy to pulse output 2 :
This screen allows the user to assign pulse output 2 to energy
Pressing “ Up” key accepts the present setting and advance to “Pulse Duration”(see section
3.2.14).
Pressing the “ Down” key will enter into edit mode and scroll through the energy setting
A - E : Apparent Energy
I - E : Import Energy ( Active ) E - E : Export Energy ( Active ) I - rE : Import Reactive Energy E - rE : Export Reactive Energy
Pressing the “ Up” key will set the value and
advances to the “Pulse duration”(see section
3.2.14).
Pulse output 2 confirmation :
Pressing “ Down” key will be re-enter into edit mode .
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB KVA Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB KVA Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
28
Page 30
Pressing “ Up” key set displayed value and will advance to Pulse rate (see section 3.2.15)
Pulse Duration Confirmation.
This screen will only appear following an edit of the Pulse duration.
pressing the “ Down” key will re-enter the “Pulse Duration Edit” mode.
3.2.14 Pulse Duration :
This screen applies to the Relay Pulsed output only.
This screen allows the user to set Relay energise time in milliseconds.
Pressing “ Up” key accepts the present value and advance to the Pulse rate (see section 3.2.15).
Pressing the “ Up” key will select the value and advances to “Pulse Duration Confirmation”.
Pressing the “ Down” key will enter the “Pulse Duration Edit” mode and scroll the value through 60, 100, 200 and wrapping back to 60.
Pulse Duration Edit.
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB KVA
Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB
KVA Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
29
Page 31
Pressing the “ Down” key will enter the “Pulse rate divisor Edit” mode and scroll the value through the values 1,10,100,1000 wrapping back to 1 in Wh but in KWh & MWh pulse rate divisor is only 1 .
3.2.15. Pulse Rate
This screen applies to the Relay Output option only. The screen allows user to set the energy pulse rate divisor. Divisor values can be selected through 1,10,100,1000 in Wh .
Pressing “ Up” key accepts the presents value and advances to the “Analog output 1” menu (See section 3.2.16).
Pressing the “ Up” key advances to the “Pulse rate Divisor Confirmation” menu.
Pulse Rate Divisor Confirmation.
This screen will only appear following an edit of the Pulse rate divisor.
If the Pulse rate shown is not correct, pressing the
“ Down” key will return to the “Pulse rate divisor
Edit” stage by blanking the bottom line of the
display.
Pressing “ Up” key sets the displayed value and will advance to the “Analog output 1” menu.
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB
KVA Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB
KVA Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
30
Page 32
31
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
Pressing the “ Down” key will re-enter the “ Analog output 1 Edit”
Analog output 1 Confirmation :
Pressing the “ Up” key sets the displayed value and will advance to the Analog output 2 selection ( see section 3.2.17 )
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
3.2.16 Analog Output 1 Selection : ( Optional )
This screen is for analog output 1 only . It allows the user to set analog output 1 to corresponding measured parameter . Refer table “ Parameter for Analog output “.
Pressing “ Up” key accepts the present value and advance to the Analog output 2 selection (see section
3.2.17). Pressing the “ Down” key will enter the
“ Analog output 1 Edit” mode and scroll the values, as per Table “ Parameter for Analog output”
Pressing the “ Up” key advance to the Analog output 1 confirmation screen .
A
VYB KVA Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
A
VYB
KVA Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
Page 33
32
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
3.2.17 Analog Output 2 Selection : ( Optional )
This screen is for analog output 2 only . It allows the user to set analog output 2 to corresponding measured parameter . Refer table “ Parameter for Analog output “.
Pressing “ Up” key accepts the present value and advances to Energy update rate screen.
Pressing the “ Down” key will enter the “ Analog output 2 Edit” mode and scroll the values, as per Table “ Parameter for Analog output”
Pressing the “ Up” key advance to the Analog output 2 confirmation screen .
A
VYB KVA Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
Pressing the “ Down” key will re-enter the “ Analog output 2 Edit”
Analog output 2 Confirmation :
Pressing the “ Up” key sets the displayed value and will advances to Energy update rate screen.
A
VYB KVA
Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
Page 34
Pressing the “ Down” key will enter the Energy update rate edit mode. This will scroll the value of most significant digit.
Pressing the “ Up” key sets the displayed value and will advances to Energy digit reset count screen.
This screen is for energy update rate. it allows user to
set energy update rate in minutes. It is settable from
1 to 60 min.
3.2.18 Energy Update Rate :
Pressing “ Up key “ will advance to Energy update rate confirmation screen. Pressing the “ Down” key will re-enter Energy update rate edit mode.
Pressing the “ Down” key will scroll the value of second digit.
Pressing the “ Up” key sets the displayed value and advances to Energy digit reset count” menu.
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB
KVA Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
Pressing the “ Up” key sets the displayed value and will advance to Energy display on Modbus menu.
3.2.19 Energy Digit reset count :
This screen enables user for setting maximum energy count “ after which energy will rollback to zero depends upon setting of Wh,KWh,& MWh.
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB KVA Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
Pressing “ Up key “ will advance to next less significant digit. (* Denotes that decimal point is flashing).
Pressing the “ Down” key will enter the Energy digit
reset count edit mode. This will scroll the value of reset
count from7 to 14 for Wh, from 7 to 12 for KWh & from
7 to 9 for MWh.
33
Page 35
Pressing the “ Up” key sets the displayed value and will advance to “Energy on Modbus menu.
Pressing “ Up key “ will advance to Energy digit reset count confirmation screen. Pressing the “ Down” key will re-enter Energy digit reset count edit mode.
Note :
1) Default value is set to “14” i.e if energy count crosses 14 digit it will rollback to zero.
2) Energy displays on modbus is set to (2) & energy digit reset count is set to 12. Energy screen on display will show “-------” i.e energy overflow .when energy crosses the 11 digit count.
3) Energy displays on modbus is set to (3) & energy digit reset count is set to 9.Energy screen on display will show “-------” i.e energy overflow .when energy crosses the 8 digit count.
Pressing “ Up” key accepts the presents value
and returns to measurement screen.
3.2.20 Energy Display on modbus
Pressing the “ Down” key will enter the “Energy Display
On Modbus Edit” mode and scroll the value through the values 1,2 & 3 wrapping back to 1. 1 : Energy In Wh 2 : Energy in KWh 3: Energy in MWh.
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB KVA Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
This screen enable user to set energy in terms of Wh / KWh / MWh on RS 485 Output depending as per the requirement .Same applicable for all types of energy.
Ex. If energy display on modbus is set Wh & It will set Energy digit count to 10 then energy will reset after “9,999,999,999” & then will Rollback to zero.
34
Page 36
Pressing “ Up” key sets the displayed value and will return to measurement screen.
Energy Display On Modbus Confirmation.
This screen will only appear following an edit of the Energy Display On Modbus.
VRY
KVAr
Sys
V
KW
VBR
Angle
Max
x1000
KVArh
x1000
IN
Ph R
P.F.
KWh
Ph B
A
VYB KVA
Min
x1000
Hz
KVAh
Ph Y
%THD
x1000
Hz
KVAh
Ph Y
%THD
Pressing the “ Down” key will enter the “Energy Display On Modbus Edit” stage by blanking the bottom line of the display.
Note : Default value is set to ‘1’ i.e. Energy on Modbus will be in
terms of Wh/VArh/VAh resp.
Pressing the “ Up” key advances to the returns to Measurement screen.
35
Page 37
36
4. Analog Output ( optional ) :
This module provides two d.c. isolated outputs .There are two output options
1) Two 0 - 1mA outputs , internally powered .
2) Two 4 - 20mA outputs , internally powered .
The 0 -1mA output module has an 0V return on each end of the 4 way connector ( Please refer section 15 for connection details )
On both modules the output signals are present on pins A1(Analog Output 1) & A2 (Analog Output 2)
These outputs can be individually assigned to represent any one of the measured and displayed Parameters.
All settlings are user congurable via the user interface screen. See Analog o/p selection ( section 3.2.16 & section 3.2.17 ) for details .
* Note : Refer diagrams 1 & 2
Page 38
37
Diagram 1 : ( 4 -20 mA )
0
0 (12 mA)
0
181 (4 mA)
0
180 (20 mA)
0
90 (16 mA)
0
270 (8 mA)
Diagram 2 : ( 0 - 1 mA )
0
0 (0.5 mA)
0
181 (0 mA)
0
180 (1 mA)
0
90 (0.75 mA)
0
270 (0.25 mA)
Page 39
38
TABLE 2 : Parameter for Analog Output
0 - 120 %
8
ACTIVE POWER L2
0 - 120 %
9
ACTIVE POWER L3
0 - 120 %
10
APPARENT POWER L1
0 - 120 %
11
APPARENT POWER L2
12
APPARENT POWER L3
13
REACTIVE POWER L1
14
REACTIVE POWER L2
15
REACTIVE POWER L3
16
POWER FACTOR L1
17
POWER FACTOR L2
18
POWER FACTOR L3
19
PHASE ANGLE L1
20
PHASE ANGLE L2
21
PHASE ANGLE L3
0 - 120 % 0 - 120 % 0 - 120 % 0 - 120 %
0 0
181 / 0 / -180
0 0
181 / 0 / -180
0 0
181 / 0 / -180
0 0
181 / 0 / -180
0 0
181 / 0 / -180
0 0
181 / 0 / -180
22
VOLTAGE AVG
24
CURRENT AVG
0 - 100 % 0 - 100 %
  
 
 
 
     
  
 
 
INPUT VOLTAGE L1
Sr. No.
Parameter
0
1
2
INPUT VOLTAGE L2
2 3
INPUT VOLTAGE L3
None
4
INPUT CURRENT IL1
3P 4W
1P 2W
3P 3W
Range
0 - 100 % 0 - 100 % 0 - 100 %
0 - 100 %
5
INPUT CURRENT IL2
6
INPUT CURRENT IL3
0 - 100 % 0 - 100 %
0 - 120 %
  
 
 
7
ACTIVE POWER L1
 
 
Analog Output
Page 40
39
0
181 / 0 / -180
27
ACTIVE POWER SUM
29
APPARENT POWER SUM
31
REACTIVE POWER SUM
32
POWER FACTOR AVG
34
PHASE ANGLE AVG
0 - 120 % 0 - 120 %
0 - 120 %
  
 
 
 
 
 
Sr. No.
Parameter
3P 4W
1P 2W
3P 3W
Range
Analog Output
0
181 / 0 / -180
101
INPUT VOLTAGE L12
102
INPUT VOLTAGE L23
103
INPUT VOLTAGE L31
113
NEUTRAL CURRENT
0 - 100 % 0 - 100 % 0 - 100 %
0 - 100 %
Note : Parameters 1,2,3 are L-N Voltage for 3P 4W & L-L Voltage for 3P 3W .
(1) For Frequency 0% corresponds to 40 Hz & 120% corresponds to 70 Hz. (2) For Angle and PF 0% corresponds to 0 Deg. & 100% corresponds to 360 Deg.
36
Frequency
45 to 65 Hz
Page 41
System power = Root3 x CT(Primary) x PT(Primary)L-L for 3 Phase 3 Wire
5. Relay output (Optional) :
This is provided with either 1 or 2 relay for pulse output . instrument
Pulse Output :
Pulse output is the potential free, very fast acting relay contact which can be used to drive an external mechanical counter for energy measurement.
Pulse Duration 60 ms,100 ms or 200 ms
Divisor
1
10
100
1000
Pulse rate
Pulse
System Power*
1per Wh
1per 10Wh
1per 100Wh
1 per 1000Wh
1per kWh
1per 10kWh
1per 100kWh
1 per 1000kWh
1per Mwh
1per 10MWh
1per 100MWh
1per 1000MWh
Up to 3600W
Up to 3600W
Up to 3600W
Up to 3600W
Up to 3600kW
Up to 3600kW
Up to 3600kW
Up to 3600kW
Above 3600kW
Above 3600kW
Above 3600kW
Above 3600kW
TABLE 3 : Energy Pulse Rate Divisor
1.For Energy Output in Wh
Divisor
1
Pulse rate
Pulse
System Power*
1 per kWh
1 per 1000kWh
1 per 1000MWh
Up to 3600W
Up to 3600kW Above 3600kW
2. For Energy Output in Kwh
Divisor
1
Pulse rate
Pulse
System Power* 1 per Mwh 1 per 1000Mwh 1 per 1000Gwh
Up to 3600W
Up to 3600kW Above 3600kW
3. For Energy Output in Mwh
This pulse output can be congured to any of the following parameter instrument’s through setup parameter screen
1) Active Energy (Import)
2) Active Energy (Export)
3) Reactive Energy (Import)
4) Reactive Energy (Export)
5) Apparent Energy
* System power = 3 x CT(Primary) x PT(Primary)L-N for 3 Phase 4 Wire
Above options are also applicable for Apparent and Reactive Energy.
40
Page 42
6. RS 485 ( ModBus ) Output :
This supports MODBUS (RS485) RTU protocol( 2-wire ) .instrument
Connection should be made using twisted pair shielded cable. All "A" and "B" connections are daisy chained together. The screens should also be connected to the “Gnd” terminal. To avoid the possibility of loop currents, an Earth connection should be made at one point on the network.Loop (ring) topology does not require any termination load. Line topology
may or may not require terminating loads depending on the type and length of cable used.
The impedance of the termination load should match the impedance of the cable and be at bothends of the line. The cable should be terminated at each end with a 120 ohm (1/4 Watt min.) resistor.
RS 485 network supports maximum length of 1.2km. Including the Master, a maximum of 32 instruments can be connected in Rs485 network.The permissible address range for the
is between 1 and 247 for 32 instruments. Broadcast Mode (address 0) is not allowed.instrument
The maximum latency time for the is 200ms i.e. this is the amount of time that instrument can pass before the rst response character is output.
After sending any query through software ( of the Master) , it must allow 200ms of time to elapse before assuming that the is not going to respond. If slave does not instrument respond within 200 ms, Master can ignore the previous query and can issue fresh query to the slave.
41
Page 43
The each byte in RTU mode has following format:
8-bit binary, hexadecimal 0-9, A-F 2 hexadecimal characters contained in each 8-bit eld of
the message
4 bytes (32 bits) per parameter. Floating point format ( to IEEE 754)
Most signicant byte rst (Alternative least signicant byte rst)
Format of Data Bytes
2 byte Cyclical Redundancy Check (CRC)
Error Checking Bytes
1 start bit, 8 data bits, least signicant bit sent rst 1 bit for even/odd parity 1 stop bit if parity is used; 1 or 2 bits if no parity
Byte format
Communication Baud Rate is user selectable from the front panel between 2400, 4800, 9600, 19200 bps.
Exception Cases : An exception code will be generated when the receives instrument ModBus query with valid parity & error check but which contains some other error ( e.g. Attempt to set oating point variable to an invalid value ) The response generated will be “Function code” Ored with HEX (80H ). The exception codes are listed below
Function code :
03
Read Holding Registers
Read content of read /write location ( 4X )
04
Read input Registers
Read content of read only location ( 3X )
16
Presets Multiple Registers
Set the content of read / write locations ( 4X )
42
Page 44
03
Illegal Data Value
Attempt to set a oating point variable to an invalid value
01
Illegal function
This function code is not supported by the instrument.
02
Illegal Data Address
Attempt to access an invalid address or an attempt to read or write part of a oating point value
Two consecutive 16 bit registers represent one parameter. Refer table 4 for the addresses of 3X registers (Parameters measured by the instruments). Each parameter is held in the 3X registers. Modbus Code 04 is used to access all parameters.
Example :
To read parameter , Volts 3 : Start address = 04 (Hex) Number of registers = 02
Note : Number of registers = Number of parameters x 2
Each Query for reading the data must be restricted to 20 parameters or less. Exceeding the 20 parameter limit will cause a ModBus exception code to be returned.
Query :
Accessing 3 X register for reading measured values:
Device Address
Function Code
Start Address High
Start Address Low
Number of Registers Hi
Number of Registers Lo
CRC Low
CRC High
01 (Hex)
04 (Hex)
00 (Hex)
04(Hex) 00 (Hex)
02(Hex) 30 (Hex) 0A (Hex)
Start Address High : Most signicant 8 bits of starting address of the parameter requested. Start Address low :Least signicant 8 bits of starting address of the parameter requested.
43
Page 45
Number of register Hi : Most signicant 8 bits of Number of registers requested. Number of register Lo : Least signicant 8 bits of Number of registers requested.
(Note : Two consecutive 16 bit register represent one parameter.)
Response: Volt3 (219.25V)
Device Address
Function Code
Byte Count
Data Register1 High Byte
01 (Hex)
04 (Hex)
04 (Hex)
43 (Hex) 5B (Hex)
41 (Hex) 21 (Hex) 6F (Hex)
Data Register1 Low Byte
Data Register2 High Byte
Data Register2 Low Byte
CRC Low
CRC High
9B (Hex)
Byte Count : Total number of data bytes received. Data register 1 High Byte : Most signicant 8 bits of Data register 1 of the parameter requested.
Data register 1 Low Byte : Least signicant 8 bits of Data register 1 of the parameter requested. Data register 2 High Byte : Most signicant 8 bits of Data register 2 of the parameter requested.
(Note : Two consecutive 16 bit register represent one parameter.)
Data register 2 Low Byte : Least signicant 8 bits of Data register 2 of the parameter requested.
Table 4 : 3 X register addresses (measured parameters)
3P 4W
3P 3W
 
 
   
     
1P 2W
Parameter
Volts 1 Volts 2 Volts 3
Current 1 Current 2 Current 3
W1
Modbus Start Address Hex
High Byte
Low Byte
00
0
00
2
00
4
00
6
00
8
00
A
00
C
Address (Register)
Sr. No.
30001
1
30003
2
30005
3
30007
4
30009
5
30011
6
30013
7
44
Page 46
30023 12 30025 13 30027 14
30029 15 30031 16 30033 17 30035 18 30037 19 30039 20
30041 21 30043 22 30045 23
30047 24 30049 25 30051 26 30053 27
30055 28
30057 29
30059 30 30061 31
30063
32
Address (Register)
Sr. No.
30015 8 30017 9 30019 10
.
30021 11
VA3 VAR1 VAR2 VAR3 PF1 PF2 PF3 Phase Angle 1 Phase Angle 2
Phase Angle 3 Volts Ave Volts Sum
Current Ave Current Sum Watts Ave Watts Sum
VA Ave VA Sum
VAr Ave VAr Sum PF Ave
Parameter
W2
W3
VA1
VA2
00
16
00
18
00
1A
00
1C
00
1E
00
20
00
22
00
24
00
26
00
28
00
2A
00
2C
00
2E
00
30
00
32
00
34
00
36
00
38
00
3A
00
3C
00
3E
Modbus Start Address Hex
High Byte
Low Byte
00
E
00
10
00
12
00
14
 
       
   
 
3P 4W
1P 2W
3P 3W
30065
33
PF Sum
00
40
45
Page 47
30071
36
30073
37
30075
38
30077
39
30079
40
30081
41
Address (Register)
Sr. No.
51
Freq Wh Import Wh Export
VARh Import VARh Export VAh
Parameter
00
46
00
48
00
4A
00
4C
00
4E
00
50
Modbus Start Address Hex
High Byte
Low Byte
 
   
1P 2W
 
     
3P 4W
3P 3W
30067
34
30069
35
Phase Angle Ave Phase Angle Sum
00
42
00
44
 
30109
00
6C
Wh Import
Overow Count
00
6E
Wh Export
Overow Count
00
70
Varh Import
Overow Count
00
72
Varh Export
Overow Count
00
74
Vah Overow
Count
30111
30113
30115
30117
52
53
54
55
30143
60
Current Ave Min
00
8E
30147
30149
62
63
30145
00
90
61
Wh Import
57 58 59
30133
30135
30141
Volts Ave Max Volts Ave Min
84 86
8C
Current Ave Max
00 00 00
 
 
 
(On Update Rate)
00
92
Wh Export
(On Update Rate)
00
94
Varh Import
(On Update Rate)
46
Page 48
1P 2W
3P 4W
3P 3W
 
      
 
      
Address (Register)
Sr. No.
30203 30205 30207 30209
30211 30213 30215 30217 30219
69 70 71 72 73
74
75 76 77
Parameter
VL 2 - 3 ( Calculated ) VL 3 - 1 ( Calculated ) V1 THD( % ) V2 THD( % ) V3 THD( % ) I1 THD( % )
I2 THD( % ) I3 THD( % ) System Voltage THD( % )
Modbus Start Address Hex
High Byte
Low Byte
00 00 00 00 00 00
00 00 00
CA CC CE D0 D2 D4
D6 D8 DA
30201
VL 1 - 2 ( Calculated )
00
C8
 
 
30151
30153
30197
30199
64
65
66
67
00 00
C4 C6
Model Number Version Number
68
 
00
96
Varh Export
(On Update Rate)
00
9A
Vah
(On Update Rate)
Note : Parameters 1,2,3 are L-N Voltage for 3P 4W & L-L Voltage for 3P 3W .
30225
79
I neutral
00
E0
47
Page 49
Start Address High : Most signicant 8 bits of starting address of the parameter requested. Start Address low :Least signicant 8 bits of starting address of the parameter requested.
Number of register Hi : Most signicant 8 bits of Number of registers requested. Number of register Lo : Least signicant 8 bits of Number of registers requested.
(Note : Two consecutive 16 bit register represent one parameter.)
Device Address Function Code
Start Address High
Start Address Low Number of Registers Hi Number of Registers Lo
CRC Low
CRC High
01 (Hex) 03 (Hex)
00 (Hex) 0A (Hex) 00 (Hex)
02 (Hex) E4 (Hex) 09 (Hex)
Each setting is held in the 4X registers .ModBus code 03 is used to read the current setting and code 16 is used to write/change the setting. Refer Table 5 for 4 X Register addresses.
Example : Reading System type System type : Start address = 0A (Hex) Number of registers = 02
Note :Number of registers = Number of Parameters x 2
Accessing 4 X register for Reading & Writing :
48
Page 50
Data Register2 High Byte
00 (Hex)
00(Hex)
Data Register2 Low Byte
EE (Hex)
CRC Low CRC High 27 (Hex)
Byte Count : Total number of data bytes received.
Data register 1 High Byte : Most signicant 8 bits of Data register 1 of the parameter requested. Data register 1 Low Byte : Least signicant 8 bits of Data register 1 of the parameter requested.
Data register 2 High Byte : Most signicant 8 bits of Data register 2 of the parameter requested.
(Note : Two consecutive 16 bit register represent one parameter.)
Data register 2 Low Byte : Least signicant 8 bits of Data register 2 of the parameter requested.
Example : Writing System type
System type : Start address = 0A (Hex) Number of registers = 02
Query:( Change System type to 3phase 3wire = 2 )
01 (Hex) 10 (Hex)
Device Address Function Code
00 (Hex)
Starting Address Hi
0A(Hex)
Starting Address Lo
00 (Hex)
Number of Registers Hi
02(Hex)
Number of Registers Lo
Device Address
Function Code Byte Count Data Register1 High Byte
01 (Hex)
03 (Hex) 04 (Hex) 40 (Hex)
Data Register1Low Byte
40 (Hex)
Response: System Type ( 3phase 4 wire = 3 )
49
Page 51
04 (Hex)
Byte Count
40 (Hex)
Data Register-1High Byte
00(Hex)
Data Register-1 Low Byte
00(Hex)
00(Hex)
66 (Hex)
10 (Hex)
Data Register-2 Low Byte
CRC High
CRC Low
Data Register-2 High Byte
Byte Count : Total number of data bytes received.
Data register 1 High Byte : Most signicant 8 bits of Data register 1 of the parameter requested. Data register 1 Low Byte : Least signicant 8 bits of Data register 1 of the parameter requested.
Data register 2 High Byte : Most signicant 8 bits of Data register 2 of the parameter requested.
(Note : Two consecutive 16 bit register represent one parameter.)
Data register 2 Low Byte : Least signicant 8 bits of Data register 2 of the parameter requested.
Response:
Device Address
Function Code
Start Address High
Start Address Low
Number of Registers Hi
01 (Hex)
10 (Hex)
00 (Hex)
0A(Hex)
00 (Hex)
Number of Registers Lo 02(Hex)
CRC Low
61 (Hex)
CRC High CA (Hex)
50
Page 52
Start Address High : Most signicant 8 bits of starting address of the parameter requested. Start Address low :Least signicant 8 bits of starting address of the parameter requested.
Number of register Hi : Most signicant 8 bits of Number of registers requested. Number of register Lo : Least signicant 8 bits of Number of registers requested.
(Note : Two consecutive 16 bit register represent one parameter.)
Table 5 : 4 X register addresses
Address (Register)
Parameter
No.
Parameter
Modbus Start Address Hex
High Byte
Low Byte
40007
4
Sys Voltage
00
06
Read / Write
R
40009
5
Sys Current
00
08
R
6
Sys Type
00
0A
40011 R/Wp
00
0C
40019
7
Pulse Width R/Wp
00
40015
8
RS 485 Set-up Code
R/Wp
00
14
40021
11
Node Address.
00
16
40023
12
Pulse Divisor
R/Wp
00
18
40025
13
Min Reset
Wp
00
1A
40027
14
Max Reset
Wp
00
1C
40029
15
Analog Out 1- Para sel
R/Wp
00
1E
40031
16
Analog Out 2- Para sel
R/Wp
00
20
40033
17
R/Wp
00
22
40035
18
CT Primary
R/Wp
3
00
04
40005 R/Wp
Energy on RS485
.
R/Wp
00
10
40013
Reset parameters W Wp
PT Primary
0E
12
51
Page 53
40039
20
-
00
26
Address (Register)
Parameter
No.
Parameter
Modbus Start Address Hex
High Byte
Low Byte
Read / Write
00
24
40037
19
System Power
R
40041
21
00
28
Register Order/Word Order R/Wp
22
40043 R/Wp
CT Secondary PT Secondary
00
2A
00
2C
40045
23
R/Wp
00
30
40049
25
Pulse2 Parameter select
R/Wp
00
3C
40061
31
R/Wp
00
46
40071
36
Password
R/W
00
4E
40079
40
30mA Noise Current Elimination
R/Wp
Pulse1 Parameter select
Energy digit reset count
R/Wp
00
50
40081
41
Energy Update Rate
R/Wp
00
52
40083
42
Model Number
R
40107 40109
40111
40113
54 55 56
57
58 60 61 62
Wh Import Start Count
Wh Export Start Count
Varh Import Start Count
Varh Export Start Count
Vah Start Count
Wh Import Overow Start Count
Wh Export Overow Start Count
Varh Import Overow Start
R/Wp R/Wp R/Wp
R/Wp
R/Wp R/Wp
R/Wp
R/Wp
00 00 00
00
00 00
00
00
6A 6C 6E
70
72 76
78
7A
40115 40119
40121
40123
63
64
Varh Export Overow Start
Vah Overow Start Count
R/Wp
R/Wp
00
00
7C
7E
40125
40127
Count
Count
Auto Scroll40077
39
R/W
00
4C
52
Page 54
Explanation for 4 X register :
Address Parameter Description
40005
40007
System Voltage
This address is read only and displays System Voltage
40009
System Current
This address is read only and displays System Current
This address is used to set the System type. Write one of the following value to this address. 1 = 1 Phase 2 Wire (Read only for 1P2W) 2 = 3 Phase 3 Wire 3 = 3 Phase 4 Wire. Writing any other value will return error .
40011
System Type
40013
Pulse Width of Relay
This address is used to set pulse width of the Pulse output. Write one of the following values to this address: 60 : 60 ms 100 : 100 ms 200 : 200 ms Writing any other value will return error .
40015
Reset Parameters
This address is used to reset the parameters by writing following. 0 : Energy reset 2 : Sys. Min reset 3 : Sys. Max reset 6 : Reset all.
Writing any other value will return an error.
Energy display on Modbus
This address is used to set energy display on MODBUS in Wh,
KWh & Mwh. Write one of the following value to this address. 1 = Energy in Wh. 2 = Energy in KWh. 3 = Energy in MWh.
53
Page 55
Address Parameter Description
40019
Rs485 Set-up Code
This address is used to set the baud rate, Parity, Number of stop bits. Refer to Table 6 for details.
40021
Node Address
This register address is used to set Device address between 1 to 247 .
40023
Pulse Divisor
40025
Min - Reset This address is used to reset the Min parameters value.
Write Zero value to this register to reset the Min parameters. Writing any other value will return an error.
40027
Max - Reset
This address is used to reset the Max parameters value. Write Zero value to this register to reset the Max parameters. Writing any other value will return an error.
This address is used to set pulse divisor of the Pulse output. Write one of the following values to this address for Wh: 1 : Divisor 1 10 : Divisor 10 100 : Divisor 100 1000 : Divisor 1000 & in KWh & MWh Divisior will be 1 default. Writing any other value will return an error.
Pulse rate divisor is set to 1, when Energy on Rs485 is set
to kWh or MWh.
40029
Analog Out 1­Para Set
This address is used to set the parameter for Analog Output 1. Write one of the parameter no. As per the options given in Table 2 for Analog Output Parameters. Writing any other value will return an error.
40031
Analog Out 2-
Para Set
This address is used to set the parameter for Analog Output 2.. Write one of the parameter no. As per the options given in Table 2 for Analog Output Parameters. Writing any other value will return an error.
54
Page 56
Address Parameter Description
40037
Sys Power
System Power (Read Only) is the Nominal system power based on the values of Nominal system volts and Nominal system current.
40041
Word Order Word Order controls the order in which the receives instrument
or sends oating - point numbers:- normal or reversed register order.In normal mode, the two registers that make up a oating point numbers are sent most signicant bytes rst. In reversed register mode , the two registers that make up a oating point numbers are sent least signicant bytes rst. To set the mode, write the value ‘2141.0’ into this register­the instrument will detect the order used to send this value and set that order for all ModBus transaction involving oating point numbers.
This address allows the user to set CT Primary value. The maximum settable value is 9999 & also depends on the per phase 666.6MVA Restriction of power combined with PT primary
40035
CT Pimary
40039
40033
PT Primary This address allows the user to set PT Primary value.
The maximum settable value is 692.8kV L-L depends on the per phase 666.6MVA Restriction of power combined with CT primary
This address is used to set the rollover count for energy. If Energy on Rs485 is in Wh rollover count can be from 7 to 14. If it is in KWh then rollover count can be from 7 to 12 & for MWh rollover count can be from 7 to 9.
Energy digit Reset Count
55
Page 57
Address Parameter Description
40049
Pulse 1 parameter select
40045
PT secondary This address is used to read and write the PT secondary value.
The valid range for PT Secondary is 100 VLL to 600 VLL.
This address is used to assign the Parameter to Relay1
refer table 7.
40043
CT secondary
This address is used to read and write the CT secondary value write one of the following values to this address. 1=1A CT secondary 5=5A CT secondary writing any other value will return an error.
40061
Pulse 2 Parameter
This address is used to assign the Parameter to Relay2 refer table 7.
40071
Password
This address is used to set & reset the password. Valid Range of Password can be set is 0000 - 9999 .
1) If password lock is present & if this location is read it will return zero.
2) If Password lock is absent & if this location is read it will return One.
3) If password lock is present & to disable this lock first send valid password to this location then write “0000” to this location
4) If password lock is present & to modify 4X parameter rst send valid password to this location so that 4X parameter will be accessible for modication.
5) If for in any of the above case invalid password is send then meter will return exceptional error 2.
Select
56
Page 58
Address Parameter Description
40079
30mA Noise current Elimination
This address is used to activate or de-activate the 30 mA noise current elimination write 0-Deactivate 30 (Decimal)-Activate Writing any other value will return an error.
40081
Energy Update Rate
Energy Update Rate is the time after which energy registers are updated. This time is user settable from 1 - 60 minutes.
40083
This Address is Read Only. This Address shows the Model Number of the meter
Model Number
to 40117
Energy Start Count
40107
The user can set respective energy starting count in these registers (before the user can write values to these locations user needs to check register 40005 i.e Energy on RS485 and register 40036 i.e Energy digit reset count). Valid range is 0-9999999. For E.g if Energy on RS485 is in K and Energy digit reset count is 7 the start count should be in k and value should be less than 7 digits.
40077
Auto Scroll
This address is used to activate or de-activate the Auto scroll setting. 0-Deactivate 1 (Decimal)-Activate Writing any other value will return an error.
57
Page 59
Address Parameter Description
to 40129
Energy
40119
The user can set respective Energy Overow starting count in these registers. Valid range is 0-999999.
Overow Start
Count
19200
NONE
19200
EVEN
19200
NONE
Baud Rate
Parity
Stop Bit
Decimal value
01
01
02
13
14
12
EVEN
19200
9600 9600
9600
NONE NONE
ODD
01
02
01
01
15 08 09
10
ODD
9600
4800
4800
NONE
NONE 4800 4800
2400
2400
2400
2400
NONE NONE
ODD
EVEN
ODD
EVEN
02
01
01 01
02
01
01
01
01
11 04 05
06 07 00
01 02
03
NOTE : Codes not listed in the table above may give rise to unpredictable results including loss of communication. Excise caution when attempting to change mode via direct Modbus writes.
Table 6 : RS 485 Set-up Code
58
Page 60
6.1 User Assignable Modbus Registers:
This contains the 20 user assignable registers in the address range of 0x200 instrument (30513) to 0x226 (30551) (see Table 8). Any of the parameter addresses ( 3X register addresses Table 4)) accessible in the instrument can be mapped to these 20 user assignable registers. Parameters (3X registers addresses ) that resides in different locations may be accessed by the single request by re-mapping them to adjacent address in the user assignable registers area. The actual address of the parameters ( 3X registers addresses) which are to be assessed via address 0x200 to 0x226 are specied in 4x Register 0x200 to 0x213 (see Table 9).
30513
257
00
Modbus Start Address (Hex)
Assignable Reg 1
30515
258
02
02
Assignable Reg 2
30517
259
04
02
Assignable Reg 3
30519
260
06
02
Assignable Reg 4
30521
261
08
02
Assignable Reg 5
30523
262
0A
02
Assignable Reg 6
Table 8 : User Assignable 3X Data Registers
Address (Register)
Parameter
Number.
Assignable Register
02
High Byte Low Byte
Table 7 : Pulse1 & Pulse2 Conguration
4
Export Reactive Energy
Apparent Energy
Import Reactive Energy
Code
1
0
2 3
Conguration Import Active Energy Export Active Energy
59
Page 61
30533
267
14
02
Assignable Reg 11
30535
268
16
02
Assignable Reg 12
30537
269
18
02
Assignable Reg 13
30539
270
1A
02
Assignable Reg 14
30541
271
1C
02
Assignable Reg 15
30543
272
1E
02
Assignable Reg 16
30545
273
20
02
Assignable Reg 17
30547
274
22
02
Assignable Reg 18
30549
275
24
02
Assignable Reg 19
30551
276
26
02
Assignable Reg 20
Modbus Start Address (Hex)
30525
263
0C
02
Assignable Reg 7
30527
264
0E
02
Assignable Reg 8
30529
265
10
02
Assignable Reg 9
Address (Register)
Parameter
Number.
Assignable Register
High Byte Low Byte
30531
266
12
02
Assignable Reg 10
Table 9 : User Assignable mapping register ( 4X registers)
40514
258
Mapped Add for register #0x0202
02
01
40515
259
Mapped Add for register #0x0204
02
02
260
Mapped Add for register #0x0206
02
03
40516
02
04
40517
261
Mapped Add for register #0x0208
02
05
40518 262
Mapped Add for register #0x020A
06
40519
263
Mapped Add for register #0x020C
02
07
40520 264
Mapped Add for register #0x020E
00
40513
257
Mapped Add for register #0x0200
02
02
Modbus Start Address (Hex)
Address (Register)
Parameter
Number.
Mapping Register
High Byte Low Byte
60
Page 62
02
08
40521
265
Mapped Add for register #0x0210
09
02
0A
02
40522
266
Mapped Add for register #0x0212
40523
267
Mapped Add for register #0x0214
Modbus Start Address (Hex)
Address (Register)
Parameter
Number.
Mapping Register
High Byte Low Byte
0B
02
0C
02
0D
02
0E
02
0F
02
10
02
11
02
12
02
13
02
40524
268
Mapped Add for register #0x0216
40525
269
Mapped Add for register #0x0218
40526
270
Mapped Add for register #0x021A
40527
271
Mapped Add for register #0x021C
40528
272
Mapped Add for register #0x021E
40529
273
Mapped Add for register #0x0220
40530
274
Mapped Add for register #0x0222
40531
275
Mapped Add for register #0x0224
40532
276
Mapped Add for register #0x0226
Example : Assigning parameter to user assignable registers
To access the voltage2 (3X address 0x0002) and Power Factor1 (3X address 0x001E) through user assignable register assign these addresses to 4x register (Table 10 ) 0x0200 and 0x0201 respectively .
Assigning Query:
01 (Hex)
Device Address
10 (Hex)
Function Code
02 (Hex)Starting Address Hi 00 (Hex)Starting Address Lo 00 (Hex)*
Number of Registers Hi
02(Hex)*
Number of Registers Lo
61
Page 63
00 (Hex) 1E (Hex)
CB (Hex) 07 (Hex)
00 (Hex)
04 (Hex)
02 (Hex)
Data Register-2 Low Byte
Byte Count
CRC High
Data Register-1 Low Byte
Data Register-2 High Byte
Data Register-1High Byte
}
Voltage 2 * (3X Address 0x0002)
Power Factor 1 * (3X Address 0x001E)
}
CRC lOW
Reading Parameter data through User Assignable Registers:
In assigning query Voltage2 and Power Factor1 parameters were assigned to 0x 200 and 0x201(Table10) which will point to user assignable 3xregisters 0x200 and 0x202 (table9). So to read Voltage2 and PowerFactor1 data reading query should be as below.
Device Address Function Code
Start Address High Start Address Low Number of Registers Hi
Number of Registers Lo CRC Low CRC High
01 (Hex) 10 (Hex) 02 (Hex) 00 (Hex)
00 (Hex) 02 (Hex)
40 (Hex) 70 (Hex)
Response :
62
Page 64
Query:
Device Address Function Code Start Address High
Start Address Low Number of Registers Hi Number of Registers Lo
CRC Low CRC High
01 (Hex) 04 (Hex)
02 (Hex) 00 (Hex) 00 (Hex) 04 (Hex) **
F0 (Hex) 71 (Hex)
Start Address High : Most signicant 8 bits of starting address of User assignable register. Start Address low :Least signicant 8 bits of starting address of User assignable register.
Number of register Hi : Most signicant 8 bits of Number of registers requested. Number of register Lo : Least signicant 8 bits of Number of registers requested.
**Note : Two consecutive 16 bit register represent one parameter. Since two parameters are requested four registers are required
Response : (Volt2 = 219.30 / Power Factor1 = 1.0)
01 (Hex) 04 (Hex)
Device Address Function Code
08 (Hex) 43 (Hex) 5B (Hex)
4E (Hex)
Byte count
}
Voltage 2 Data
Data Register-1 Low Byte Data Register-2 High Byte
Data Register-1High Byte
04 (Hex)
Data Register-2 Low Byte
63
Page 65
User Assignable mapping Registers ( 4X Registers Table10 )
Voltage 2 (0x0002)
Power Factor 1 (0x001E)
Wh Import (0x0048)
Frequency (0x0046)
VAh (0x0050)
Current 1 (0x0006)
User Assignable Data Registers ( 3X Registers Table 9 )
0x200
(16 bit)
0x201
(16 bit)
0x203
(16 bit)
0x202
(16 bit)
0x204
(16 bit)
0x205
(16 bit)
0x206
(16 bit)
0x207
(16 bit)
0x224
(16 bit)
0x225
(16 bit)
0x226
(16 bit)
0x227
(16 bit)
0x200
0x202
0x204
0x206
0x224
0x226
0x200
0x201
0x202
0x203
0x212
0x213
(Starting
Address)
}
00 (Hex) 00 (Hex) 79 (Hex)
3F (Hex)
3F (Hex) 80 (Hex)
Data Register-4 Low Byte
CRC High
CRC Low
Data Register-3 Low Byte Data Register-4 High Byte
Data Register-3 High Byte
Power Factor 1Data
(Starting
Address)
64
Page 66
7.Phasor Diagram :
To get the data through User assignable Register use following steps:
1) Assign starting addresses(Table3) of parameters of interest to a “User assignable mapping registers” in a sequence in which they are to be accessed (see section “Assigning parameter to user assignable registers”)
2) Once the parameters are mapped data can be acquired by using “User assignable data register “ Starting address . i.e to access data of Voltage2, Power factor1,Wh import, Frequency send query with starting address 0x200 with number of register 8 or individually parameters can be accessed for example if current1 to be accessed use starting address 0x212. (See section Reading Parameter data through User Assignable Registers)
Inductive
Capacitive
Capacitive
Inductive
90 degrees (0.000)
0 degrees (+1.000)
180 degrees (-1.000)
270 degrees (0.000)
-
+
2
4
+
-
65
Page 67
Connections Quadrant
Power ( P )
Sign of
Active
Power ( Q )
Sign of
Reactive
Factor ( PF )
Sign of
Power
Inductive /
Capacitive
Import
1
+ P
+ Q
+
L
Import
4
+ P
- Q
+
C
Export
2
- P
+ Q
-
C
Export
3
- P
- Q
-
L
Inductive means Current lags Voltage
Capacitive means Current leads Voltage
8. Installation
Mounting is by four side clamps, slide the side clamps through side slot till side clamp gets rmly locked in a groove (Refer g.) Consideration should be given to the space required behind the instrument to allow for bends in the connection cables.
SLIDE IN THIS DIRECTION AND LOCK
PANEL
Meter
When the instrument displays Active power ( P )with “ + ” ( positive sign ) , the connection is “ Import ” .
When the instrument displays Active power ( P )with “ - ” ( negative sign ) , the connection is “ Export ” .
66
Page 68
8.1 EMC Installation Requirements
This product has been designed to meet the certication of the EU directives when installed to a good code of practice for EMC in industrial environments, e.g.
1. Screened output and low signal input leads or have provision for tting RF suppression components, such as ferrite absorbers, line lters etc., in the event that RF elds cause
problems.
Note: It is good practice to install sensitive electronic instruments that are performing critical functions, in EMC enclosures that protect against electrical interference which could cause a disturbance in function.
2. Avoid routing leads alongside cables and products that are, or could be, a source of
Caution
1. In the interest of safety and functionality this product must be installed by a qualified engineer, abiding by any local regulations.
2. Voltages dangerous to human life are present at some of the terminal connections of this unit. Ensure that all supplies are de-energised before attempting any connection or disconnection.
3. These products do not have internal fuses therefore external fuses must be used to ensure safety under fault conditions.
As the front of the enclosure conforms to IP54 it is protected from water spray from all directions, additional protection to the panel may be obtained by the use of an optional panel gasket.
The terminals at the rear of the product should be protected from liquids.
The instrument should be mounted in a reasonably stable ambient temperature and where the operating temperature is within the range
0
-10 to 55 C . Vibration should be kept to a minimum and the product should not be mounted where it will be subjected to excessive direct sunlight.
interference.
67
Page 69
4. ESD precautions must be taken at all times when handling this product.
3. To protect the product against permanent damage, surge transients must be limited to 2kV pk. It is good EMC practice to suppress differential surges to 2kV at the source. The unit has been designed to automatically recover in the event of a high level of transients. In extreme circumstances it may be necessary to temporarily disconnect the auxiliary supply for a period of greater than 5 seconds to restore correct operation.
The Current inputs of these products are designed for connection in to systems via Current Transformers only, where one side is grounded.
8.2 Case Dimension and Panel Cut Out
3.78”
96mm
FRONT DISPLAY
AREA
3.78”
96mm
3.15”
80mm
3.62”
92mm
PANEL CUTOUT
3.62”
92mm
MAX PANEL THICKNESS 0.18”,5mm
8.3 Wiring
Input connections are made directly to screw-type terminals with indirect wire pressure. Numbering is clearly marked in the plastic moulding. Choice of cable should meet local
2
regulations. Terminal for both Current and Voltage inputs will accept upto 3mm x 2 diameter cables.
Note : It is recommended to use wire with lug for connection with meter.
68
Page 70
9. Connection Diagrams
3-PHASE 3-WIRE UNBALANCED LOAD
DIGITAL METERING SYSTEM
P1
S1
P1
S1
L N AUX
SUPPLY
L1 L2 L3
N
L
O
A D
2
5
8
3
4
6
7
9
8.4 Auxiliary Supply
The should ideally be powered from a dedicated supply, however it may be powered instrument from the signal source, provided the source remains within the limits of the chosen auxiliary voltage.
8.5 Fusing
It is recommended that all voltage lines are tted with 1 amp HRC fuses.
8.6 Earth/Ground Connections
For safety reasons, CT secondary connections should be grounded in accordance with local regulations.
69
Page 71
3-PHASE 4-WIRE UNBALANCED LOAD
DIGITAL METERING SYSTEM
2
5
8
11 1
3
4
6
7
9
13
14
L N AUX
SUPPLY
P1
S1
S1
P1
P1
S1
L1 L2 L3
N
L
O
A
D
SINGLE PHASE
DIGITAL METERING SYSTEM
P1
S1
L N AUX
SUPPLY
L
N
L O A D
2
3
70
Page 72
System CT primary values
Std. Values from 1 to 9999A
Inputs
Nominal input voltage (AC RMS)
Max continuous input voltage
Max short duration input voltage
Nominal input voltage burden
Phase-Neutral 57.7 - 346 V
L-N
L-L
120% of Rated Value
2 x Rated Value (1s application repeated 10 times
at 10s intervals)
0.35 VA approx. per phase
Max continuous input current 120 % of Rated Value Nominal input current burden 0.3 VA approx. per phase Max short duration current input
20 x Rated Value (1s application repeated 5 times at 5 min. intervals)
Nominal input current 1A / 5A AC rms
(1 or 5 Amp secondaries)
Line-Line 100 - 600 V
10. Specication :
System 3 Phase 3 Wire / 3 phase 4 Wire programmable at site
Auxiliary
Standard nominal Auxillary
supply voltages & Frequency
a.c. supply frequency range 45 to 66 Hz
60 - 300 V AC- DC OR
65 - 300 V AC- DC with Ethernet / Analog Output
a.c. supply burden 5 VA approx.
d.c. supply burden 4 W approx.
12 - 60 V AC - DC
7 VA approx. with Ethernet / Analog Output
5 W approx. with Ethernet / Analog Output
1 Phase 2 Wire as per order
71
Page 73
Power Factor
1 % of Unity
Frequency
40 .. 70 Hz
Power Factor
0.5 Lag ... 1 ... 0.8 Lead
Accuracy
Voltage 0.5 % of range C urrent
0.5 % of range
Frequency
0.15% of mid frequency
Active Energy
1.0 % of range
0.5 % of range
Active Power
0.5 % of range
Re- Active Power
0.5 % of range
Apparent Power
Apparant Energy
1.0 % of range
Accuracy 1:
Re - Active Energy
1.0 % of range
Current 5 .. 120 % of Rated Value
Angle
1 % of range
Analog Output
1 % of Output end value Total Harmonic Distortion Neutral Current
4 % of range.
Accuracy 0.5:
Voltage 0.5 % of range C urrent
0.5 % of range
Frequency
0.15% of mid frequency
Active Energy
0.5 % of range
0.5 % of range
Active Power
0.5 % of range
Re- Active Power
0.5 % of range
Apparent Power
1 %
Operating Measuring Ranges
Voltage
10 .. 120 % of Rated Value
72
Page 74
Reference conditions for Accuracy :
0 0
23 C + 2 C 50 or 60Hz ± 2%
Reference temperature Input frequency
Power Factor
1 % of Unity
Angle
1 % of range
Analog Output
1 % of Output end value
Total Harmonic Distortion
Neutral Current
4 % of range
Voltage C urrent
± 0.2 % of range ± 0.2 % of range
Frequency
0.15% of mid frequency
Active Energy
± 0.2 % of range
± 0.2 % of range
Active Power
± 0.4 % of range
Re- Active Power
± 0.2 % of range
Apparent Power
Re - Active Energy Apparant Energy
± 0.2 % of range
Power Factor
± 1 % of Unity
Angle
± 1 % of range
Analog Output
± 1 % of Output end value
Total Harmonic Distortion
± 1 %
Accuracy 0.2:
± 0.5 % of range
Neutral Current
± 4 % of range
Sinusoidal (distortion factor 0.005)
Input waveform
Rated Value + 1 %
Auxiliary supply voltage Auxiliary supply frequency
Rated Value + 1 %
Voltage Range
50... 100% of Nominal Value.
60... 100% of Nominal Value for THD.
1 %
Apparent Energy
0.5 % of range
Re - Active Energy
0.5 % of range
73
Page 75
74
Current Range
10... 100% of Nominal Value.
Power
cosØ / sinØ = 1
10... 100% of Nominal Current &
50... 100% of Nominal Voltage.
For Active / Reactive Power & Energy
20... 100% of Nominal Value for THD.
Power Factor / Phase Angle 40... 100% of Nominal Current &
50... 100% of Nominal Voltage.
Nominal range of use of inuence quantities for measurands
50 .. 120 % of Rated Value 10 .. 120 % of Rated Value Rated Value + 10 %
0
0 to 50 C
Voltage Current
Input frequency Temperature
Auxiliary supply voltage
Auxiliary supply frequency
Rated Value + 10 % Rated Value + 10 %
Temperature Coefcient
0
0.025% / C for Voltage (50..120% of Rated Value)
(For Rated value range of use
0
0.05% / C for Current ( 10..120% of Rated Value )
0
0... 50 C )
Error change due to variation of an inuence quantity
2 * Error allowed for the reference condition applied in the test.
Approx. 1 seconds
Update
Display
3 Line 4 Digits, (Digit Height 11mm)
LED
Controls
Two Push Buttons
User Interface
Page 76
Standards
IEC 61326 10V/m min-Level 3 industrial low level electromagnetic radiation environment IEC 61000-4-3. IEC 61010-1 , Year 2001
EMC Immunity
Safety
IEC 60529
IP for water & dust
Isolation
2.2 kV RMS 50 Hz for 1 minute between all electrical circuits
Dielectric voltage withstand test between circuits and accessible surfaces
Environmental
0
-10 to 55 C
0
-20 to +65 C 0 .. 90 % RH 3 minute (minimum) 15g in 3 planes
10 .. 55 Hz, 0.15mm amplitude
IP 54 as per IEC 60529
Operating temperature Storage temperature
Relative humidity Warm up time
Shock Vibration Enclosure ( front only )
Enclosure
96mm x 96mm DIN Quadratic
Style
Polycarbonate Housing ,
Material
Self extinguish & non dripping as per UL 94 V-0 Screw-type terminals
Terminals
< 80 mm
Depth
0.620 kg Approx.
Weight
75
Page 77
Pulse output Option ( 1 or 2 Relay ) :
1NO + 1NC
Relay
240VDC , 5Amp.
Switching Voltage & CurrentSwitching Voltage & Current
1 per Wh (up to 3600W), 1 per kWh (up to 3600kW), 1 per MWh (above 3600 kW)
Default Pulse rate Divisor
Pulse rate Divisors
Programmable on site
1 per 10Wh (up to 3600W), 1 per 10kWh (up to 3600kW), 1 per 10MWh (above 3600 kW)
10
1 per 100Wh (up to 3600W), 1 per 100kWh (up to 3600kW), 1 per 100MWh (above 3600 kW)
100
1 per 1000Wh (up to 3600W), 1 per 1000kWh (up to 3600kW), 1 per 1000MWh (above 3600 kW)
1000
60ms , 100ms or 200ms
Pulse Duration
Note : Above conditions are also applicable for Reactive & Apparent Energy .
ModBus ( RS 485 ) Option :
ModBus ( RS 485 )
Protocol
19200 , 9600 , 4800 or 2400
Baud Rate
( Programmable ) Odd or Even, with 1 stop bit,
Parity
Or None with 1 or 2 stop bits
Note : Pulse rate divisor is set to 1, when Energy on Rs485 is set to kWh or MWh.
Analog Output Option :
0 ... 1mA dc into 0 - 2 kohm
Linear
Uni-directional, internally powered .
4 ... 20mA dc into 0 - 500 ohm
Uni-directional, internally powered.
76
Page 78
11. Connection for Optional Pulse Output / RS 485 / Analog Output ( rear view of the instrument ) :
1. RS 485 Output + One Pulse + Two Analog Output
A1 A2
Gnd
0 - 1mA
N/O N/C
COM
Relay 2
B A
Gnd
RS 485
Gnd
2. Two Pulse + RS 485 Output
N/O N/C
COM
Relay 1
N/O N/C
COM
Relay 2
B A
Gnd
RS 485
3. Ethernet
77
Page 79
The Information contained in these installation instructions is for use only by installers trained to make electrical power installations and is intended to describe the correct method
It is the user's responsibility to determine the suitability of the installation method in the
of installation for this product.
user’s eld conditions.
78
Loading...