Rish Eine+ Operating Manual

Page 1
RISH Eine+
Operating Manual
2-60-006-00-00510_Rev_E 3/2018
1
Page 2
PROGRAMMABLE DC DPM
Installation & Operating Instructions
Section Contents
Introduction
Measurement Reading Screens
3.
4. Installation
Programming
3.1 Setup Screens
3.1.1 Meter Type Selection
3.1.2 Normal Meter
3.1.2.1 Input start value
3.1.2.2 Display end value
3.1.2.3 Display start value
3.1.2.4 Bent function selection
3.1.2.5 Input bent value
3.1.2.6 Display bent value
3.1.3 Power Factor Meter
3.1.3.1 Input start value
3.1.3.2 PF end value
3.1.3.3 PF start value
4.1 EMC Installation Requirements
4.2 Case Dimensions and Panel Cut-out
4.3 Wiring
4.4 Auxiliary Supply
4.5 Fusing
4.6 Earth / Ground Connections
5.
Connection Diagrams Specifications
6.
DC Voltmeter : Eine Voltage
+
DC Ammeter : Eine Current
+
3.2 Other Display Indications
3
Page 3
mV
mA
Available Models :
1. Introduction
The Eine+ is a series of panel mounted 96 x 96mm and 48x96 Digital Panel Meters for the measurement of DC Voltage and Current.
The instrument integrates accurate measurement technology. The parameters are displayed with Ultra high bright LED display with 14mm Digit height. Programmable DPM can be configured and programmed on site for the following: Input start and bent values, Display start, end and bent values. The front panel has two push buttons through which the user can enter into programming mode and can configure the meter.
1. Eine+ mV
2. Eine+ mA
3. Eine+ V
4. Eine+ A
V
A
A
UP DOWN
4
Page 4
2. Measurement Reading Screen
In normal operation the user is presented with the measurement reading screens. These screens may be scrolled through keys one at a time in incremental order by pressing the key and in decrementing order by pressing key.
Screen 1 : Voltage
Screen 3 : Ambient Temperature (°F)
Screen 1 : Current
Screens of Eine
+
mA
mV
Screen 2 : Ambient Temperature (°C)
mV
mV
A flashing message of “°F” will be shown at intervals of 1.5 sec.
Note: All the screen shown in manual is for reference(Screens are applicable for both models i.e., 48x96 & 96x96)
5
Page 5
A
Exit from setup Parameter to Main Display
Press both keys to enter Setup
PF
(PF display)
(Sec 3.1.3)
inP.S
(Input start)
(Sec 3.1.3.1)
nor
(normal display)
(Sec 3.1.2)
Eine+ Setup Parameter Screen
tYPE
(Meter Type)
(Sec 3.1.1)
(PF end value)
PF-E
(Sec 3.1.3.2)
PF-S
(PF start value)
(Sec 3.1.3.3)
inP.S
(Input start)
(Sec 3.1.2.1)
dSP.E
(Display end value)
(Sec 3.1.2.2)
dSP.S
(Display start value)
(Sec 3.1.2.3)
bEnt
(Bent function on/off)
(Sec 3.1.2.4)
inP.b
(Input bent value)
(Sec 3.1.2.5)
dSP.b
(Display bent value)
(Sec 3.1.2.6)
A
A
OFF
ON
6
Page 6
3. Programming
The following sections comprise step by step procedures for configuring the meter for individual user requirements. To access the set-up screens press and hold the
“ ” and “ ” keys simultaneously.
This will take the User into the Meter Type Screen. (section 3.1.1)
3.1 Setup Screens
3.1.1 Meter type
This screen is used to set the meter type. The user can scroll between the following options using the “ up” key
nor: normal operation PF: operate as Power Factor DPM
Pressing the “ down” key will accept the present type and advance to Input Start value selection(section 3.1.2.1).
Pressing the “ up” key again will enter the meter type edit mode and user can scroll through the types available. Pressing the “ down” key advances to the meter type confirmation menu.
Meter Type Confirmation
This screen will only appear following the edit of meter type.
Pressing the “ down” key sets the displayed type and will advance to Input Start value selection (section 3.1.2.1).
7
Page 7
This screen allows the user to set the Start value of Input. The Start value can be set from -100% to 20% of Input End value for all models, except for 500 & 1000V models in which Start value range is from 0 to 20% of Input End value, where Input End value is the Nominal Input value of the meter.
3.1.2.1 Input Start Value (inP.S)
3.1.2 Normal Meter
NOTE: Decimal point will be fixed depending upon the Nominal Input value of meter.
Eg. For 20mA model, decimal pt. will be fixed after second digit. Hence, Input start value of 04.00 will correspond to 4mA.
Initially, ‘inP.S’ message is displayed on screen following which user can start editing Input Start value by pressing the “ ” key. After entering the edit mode, by pressing the “ ”key user can turn the ‘-’ symbol On or Off. If ‘-’ symbol is On then Input Start value will be set as negative. Pressing the “ ” key will set the ‘-’ symbol and editing of first digit will start. By pressing the “ ”key user can scroll the value from 0 to 9 or it will get restricted by Input End value.
Pressing the “ ” key will set the first digit and advance the operation to next digit. Similarly, user can edit the remaining three digits. After all four digits have been set, pressing the “ ” key will advance to the Input Start value confirmation mode.
Pressing the “ ” key will re-enter into the Start value edit mode. Pressing the “ ” key will confirm the set value. If meter type had been earlier selected as ‘nor’ then operation will advance to Display End value selection (section 3.1.2.2) , otherwise if ‘PF’ had been selected then it will advance to PF end value selection (section 3.1.3.2).
8
Page 8
3.1.2.2 Display End Value (dSP.E)
This screen allows the user to set the Display End value which will correspond to the Input End value. The End value can be set from -9999 to -10 or +10 to +9999 counts.
Initially,‘dSP.E’ message is displayed on screen following which user can start editing Display End value by pressing the “ ” key. Instead on pressing the “ ” key will confirm the present value and advance to Display Start value selection (section 3.1.2.3).
After entering the edit mode, by pressing the “ ” key user can turn the ‘-’ symbol On or Off. If ‘-’ symbol is On then Display End value will be set as negative else it will be positive. Pressing the “ ” key once will set the ‘-’ symbol. Next, on pressing “ ” key editing of Decimal point will start. With each press of the same key, the Decimal point will shift towards right by one digit. Pressing the “ ” key will set the decimal point position and advance to digit editing.
By pressing the “ ” key user can scroll the value from 0 to 9. Pressing the “ ” key will set the first digit and advance the operation to next digit. Similarly, user can edit the remaining three digits. After all four digits have been set, pressing the “ ” key will advance to the Display End value confirmation mode.
Pressing the “ ” key will re-enter into the End value edit mode. Pressing the “ ” key will confirm the set value and advance to Display Start value selection (section 3.1.2.3).
NOTE: The decimal point position can only be set in the Display End value screen and the same will reflect in the measurement screen.
9
Page 9
3.1.2.3 Display Start Value (dSP.S)
This screen allows the user to set the Display Start value which will correspond to the Input Start value. If the Display End value is negative then Start value can be set from 90% of End value to +9999 counts, otherwise if the End value is positive then Start value can be set from -9999 to 90% of End value.
Initially, ‘dSP.S’ message is displayed on screen following which user can start editing Display Start value by pressing the “ ” key. Instead on pressing the “ ” key will confirm the present value and advance to Bent Function Selection menu (section 3.1.2.4).
After entering the edit mode, by pressing the “ ” key user can turn the ‘-’ symbol On or Off. If ‘-’ symbol is On then Display Start value will be set as negative else it will be positive. Pressing the “ ” key will set the ‘-’ symbol and editing of first digit will start. By pressing the “ ” key user can scroll the value from 0 to 9.
Pressing the “ ” key will set the first digit and advance the operation to next digit. Similarly, user can edit the remaining three digits. After all four digits have been set, pressing the “ ” key will advance to the Display Start value confirmation mode.
Pressing the “ ” key will re-enter into the Start value edit mode. Pressing the “ ” key will confirm the set value and advance to Bent Function Selection menu (section 3.1.2.4).
10
Page 10
3.1.2.4 Bent Function Selection
This screen allows the user to enable or disable the bent characteristics function. This is applicable only to Normal meter type, and not to PF meter.
Initially, ‘bEnt’ message is displayed on screen. On pressing the “ ” key, the meter will enter the Bent function edit mode and user can scroll between yes and no.
YES: Bent function is enabled no: Bent function is disabled
Pressing the “ ” key will accept the displayed condition. If Bent function is enabled, then the meter will advance to Input Bent value selection (section 3.1.2.5) otherwise will exit the Setup menu and return to measurement mode.
3.1.2.5 Input Bent Value (inP.b)
This screen appears only when Bent Function has been enabled. This screen allows the user to set the Input Bent value. The Bent value can be set in-between (Input Start value + (1.5% of Input End value)) and 98.5% of Input End value.
Initially, ‘inP.b’ message is displayed on screen following which user can start editing Input Bent value by pressing the “ ” key. Instead on pressing the “ ” key will confirm the present value and advance to Display Bent value selection (section 3.1.2.6). After entering the edit mode, by pressing the “ ” key user can turn the ‘-’ symbol On or Off. If ‘-’ symbol is On then Input Bent value will be set as negative. Pressing the “ ” key will set the ‘-’ symbol and editing of first digit will start. By pressing the “ ” key user can scroll the value from 0 to 9 or it will get restricted depending upon Input Start and End value.
11
Page 11
This screen appears only when Bent Function has been enabled. This screen allows the user to set the Display Bent value. The Bent value can be set in-between
(Display Start value + (1.5% of Display End value)) and 98.5% of Display End value.
3.1.2.6 Display Bent Value (dSP.b)
Initially, ‘dSP.b’ message is displayed on screen following which user can start editing Display Bent value by pressing the “ ” key. Instead on pressing the “ ” key will confirm the present value and exit the Setup menu to return to measurement mode. After entering the edit mode, by pressing the “ ” key user can turn the ‘-’ symbol On or Off. If ‘-’ symbol is On then Display Bent value will be set as negative. Pressing the “ ” key will set the ‘-’ symbol and editing of first digit will start. By pressing the “ ” key user can scroll the value from 0 to 9 or it will get restricted depending upon Display Start and End value.
Pressing the “ ” key will set the first digit and advance the operation to next digit. Similarly, user can edit the remaining three digits. After all four digits have been set, pressing the “ ” key will advance to the Display Bent value confirmation mode. Pressing the “ ” key will re-enter into the Bent value edit mode. Pressing the “ ” key will confirm the set value and exit the Setup menu to return to measurement mode.
Pressing the “ ” key will set the first digit and advance the operation to next digit. Similarly, user can edit the remaining three digits. After all four digits have been set, pressing the “ ” key will advance to the Input Bent value confirmation mode. Pressing the “ ” key will re-enter into the Bent value edit mode. Pressing the “ ” key will confirm the set value and advance to Display Bent value selection (section 3.1.2.6).
12
Page 12
3.1.3.2 PF End Value (PF-E)
3.1.3 Power Factor Meter
This screen allows the user to set the PF End value which will correspond to the Input End value. The End value can be set from -1 to +1 (quadrants 1 & 2).
Initially, ‘PF-E’ message is displayed on screen following which user can start editing PF End value by pressing the “ ” key. Instead on pressing the “ ” key will confirm the present value and advance to PF Start value selection (section 3.1.3.3).
Capacitive
Inductive
Capacitive
Inductive
PHASOR DIAGRAM
Phasor
Diagram
3.1.3.1 Input Start Value (inP.S)
Refer section 3.1.2.1.
13
Page 13
After entering the edit mode, by pressing the “ ” key user can turn the ‘-’ symbol On or Off. If ‘-’ symbol is On then PF End value will be set as negative else it will be positive. ‘L’ (inductive) or ‘C’ (capacitive) are automatically displayed depending on the quadrant in which value is being set. Pressing the “ ” key will set the ‘-’ symbol and digit editing will start.
By pressing the “ ” key user can scroll the value between 0 and 1. Pressing the “ ” key will set the first digit and advance the operation to next digit. Similarly, user can edit the remaining two digits from 0 to 9 if first digit is 0. After all three digits have been set, pressing the “ ” key will advance to the PF End value confirmation mode.
Pressing the “ ” key will re-enter into the End value edit mode. Pressing the “ ” key will confirm the set value and advance to PF Start value selection (section 3.1.3.3).
NOTE: The decimal point position will remain fixed after the first digit, both in setup and in the measurement screen.
3.1.3.3 PF Start Value (PF-S)
This screen allows the user to set the PF Start value which will correspond to the Input Start value. The Start value can be set from -1 to +1 (quadrants 3 & 4). Refer the Phasor diagram. If the End value is -1 or +1, then the Start value will get restricted to -0.98 or +0.98 respectively.
Initially, ‘PF-S’ message is displayed on screen following which user can start editing Display Start value by pressing the “ ” key. Instead on pressing the “ ” key will confirm the present value and exit the Setup menu to return to measurement mode.
14
Page 14
After entering the edit mode, by pressing the “ ” key user can turn the ‘-’ symbol On or Off. If ‘-’ symbol is On then PF Start value will be set as negative else it will be positive. ‘L’ (inductive) or ‘C’ (capacitive) are automatically displayed depending on the quadrant in which value is being set. Pressing the “ ” key will set the ‘-’ symbol and digit editing will start.
By pressing the “ ” key user can scroll the value between 0 and 1. Pressing the “ ” key will set the first digit and advance the operation to next digit. Similarly, user can edit the remaining two digits from 0 to 9 if first digit is 0. After all three digits have been set, pressing the “ ” key will advance to the PF Start value confirmation mode. Pressing the “ ” key will re-enter into the Start value edit mode. Pressing the “ ” key will confirm the set value and exit the Setup menu to return to measurement mode.
3.2 Other Display Indications
-oL-
Indication
– – – –
Overload indication above 125% input
Description
When display count exceeds 9999
–ve reading
For 4-20mA range, if meter setting is as follows: input start value = 04.00, display end value = 20.00 & display start value = 00.00, then if input falls below 4mA or input gets disconnected, then meter will show negative reading
If negative input is given to 500/1000 V meter (for eg. due to wrong connection) , it will display value same as that displayed for no input value(according to input start, display start and display end values set by user).
0 reading
15
Page 15
As the front of the enclosure conforms to IP 50. additional protection to the panel may be obtained by the use of an optional panel gasket. The terminals at the rear of the product should be protected from liquids.
The meter should be mounted in a reasonably stable ambient temperature and where the operating temperature is
0
within the range -10 to 55 C . Vibration should be kept to a minimum and the product should not be mounted where it will be subjected to excessive direct sunlight.
Easy Clip-in
mounting
Swivel screw
4. Installation
Mounting of EINE+ is featured with easy “Clip- in” mounting. Push the meter in panel slot (size 92 x92 mm), it will click fit into panel with the four integral retention clips on two sides of meter. If required Additional support is provided with swivel screws (optional) as shown in figure.
16
Page 16
17
For 48 x 96mm-Mounting of Rish Eine+ DC DPM 48 x 96 is featured with easy “Clip- in” mounting. Push the meter in panel slot (size 48.5 x 96 mm), it will click fit into panel with the four integral retention clips on two sides of meter. The front of the enclosure conforms to
IP54. Additional protection to the panel may be obtained by the use of an optional panel gasket. The terminals at the rear of the product should be protected from liquids.
The Rish Eine+ DC DPM should be mounted in a reasonably stable ambient temperature and where the operating temperature is within the range -10°C to 55°C . Vibration should be kept to a minimum and the product should not be mounted where it will be subjected to excessive direct sunlight.
Caution
1. In the interest of safety and functionality this product must be installed by a qualified engineer, abiding by any local regulations.
2. Voltages dangerous to human life are present at some of the terminal connections of this unit. Ensure that all supplies are de-energised before attempting any connection disconnection.
3. These products do not have internal fuses therefore external fuses must be used to ensure safety under fault conditions.
58.1mm
5mm
66.6mm
Page 17
4.1 EMC Installation Requirements
This product has been designed to meet the certification of the EU directives when installed to a good code of practice for EMC in industrial environments, e.g.
1. Screened output and low signal input leads or have provision for fitting RF suppression components, such as ferrite absorbers, line filters etc., in the event that RF fields cause problems. NOTE: It is good practice to install sensitive electronic instruments that are performing critical functions, in EMC enclosures that protect against electrical interference which could cause a disturbance in function.
2. Avoid routing leads alongside cables and products that are, or could be, a source of interference.
3. To protect the product against permanent damage, surge transients must be limited to 2kV pk. It is good EMC practice to suppress differential surges to 2kV at the source. The unit has been designed to automatically recover in the event of a high level of transients. In extreme circumstances it may be necessary to temporarily disconnect the auxiliary supply for a period of greater than 5 seconds to restore correct operation.
4. ESD precautions must be taken at all times when handling this product.
18
Page 18
4.2 Case Dimensions and Panel Cut Out
92mm+0.8
92mm+0.8
Panel Cutout
Front Display Area
96mm
96 mm
27 mm
6 mm
35 mm
MAX PANEL THICKNESS 0.18”,5mm
4.3 Wiring
Input connections are made directly to screw-type terminals with indirect wire pressure. Numbering is clearly marked on the connector. Choice of cable should meet
2
local regulations. Terminal for inputs will accept up to 4mm (12 AWG) or
2
2.5mm (12AWG) Standard.
Note : 1) It is recommended to use wire with lug for connection with meter.
2) For disconnecting the device a switch or circuit-breaker shall be included at the site and shall be within easy reach of the operator. The specification are as below. For Aux. = At least 1.5 times of applied Power supply. For Measuring Input = At least 1.5 times of applied measuring inputs.
For 48 x 96 mm
96.0mm
48.0mm
Display Area
For 96 x 96 mm
45mm+0.8
92mm+0.8
58.1mm
5mm
66.6mm
Mounting Position Installation Cutout
19
Page 19
5. Connection Diagrams
-
-10...10mA
-20...20mA
-1...1A
-5...5A
-75...75mV
-150...150mV
-5...5V
-10...10V
Aux Supply
+
+
0...500V
0...1000V
L N
1 32
13 14
20
1 2 3 4 5 6 7 8
B A
Aux Supply
L N
Aux Supply
NL
+
-
0...500V
0...1000V
+
-
96x96 model
48x96 model
4.4 Auxiliary Supply
Eine+ should ideally be powered from a dedicated supply.
4.5 Fusing
It is recommended that all voltage lines are fitted with 1 amp HRC fuse.
4.6 Earth/Ground Connections
For safety reasons, panels and accesoriess should be grounded in accordance
-
3
1
Page 20
Auxiliary Supply :
AC-DC Auxiliary Supply 40V to 300V AC/DC (+/- 5%)
Frequency Range
45 to 65 Hz
VA Burden
< 4.5 VA at 240V, 50Hz
AC Auxiliary Supply
80V to 300V AC [For 96x96 Model]
Overload Withstand :
Current
Voltage
2 X Rated Value for 1 Second, repeated
4 X Rated Value for 1 Second, repeated
10 times at 10 second interval.
5 times at 5 min interval.
Overload Indication :
“-oL-” (If input is greater than 125% of nominal value)
Nominal Input Current Ranges
Max continuous input current 120% of nominal value Voltage Drop < 600 mV
-10...0...10 mA, -20...0...20 mA, 4...20 mA,
-1...0...1 V, -5...0...5 V
Measuring Range (Eine Current) :
+
Input Current < 300 uA
Max continuous input voltage 120% of nominal value
0...500 V, 0...1000 V
-5...0...5 V, -10...0...10 V
Nominal Input Voltage Ranges
-75...0...75 mV, -150...0...150 mV,
Measuring Range (Eine Voltage) :
+
6. Specifications :
20-60V DC / 20-40V AC (+/- 5%)
21
Page 21
Display :
1 line 4-digits 7 segment LED display
Type
For Displaying Negative sign
Annunciator LED
2 Keys
Controls :
User Interface
Digit height
14mm
Applicable Standards :
IEC 61326-1: 2005
IEC 61010-1: 2010, Permantly Connected
EMC
Safety
IEC 60529
IP for water & dust
10V/m min-Level 3 industrial low level Electromagnetic radiation environment
-9999...+9999
Display Range
0.05% / °C, plusTemperature Coefficient
0.025% / °C
Zero point drift
Influence of Variations :
Reference conditions for Accuracy :
Reference temperature
0 0
23 C + 2 C
Auxiliary Supply Voltage
Rated value ±1%
Auxiliary Supply Frequency
Rated value ±1%
Accuracy :
Current (mA / A)
<0.5% of Display End value ± 1 digit Voltage (mV / V)
<0.5% of Display End value ± 1 digit
±3 °C Ambient Temperature
use.
22
Page 22
Enclosure :
IP50(For 96x96 model)
Front
IP20
Back
Dimension and weight :
Bezel Size (DIN 43718)
40mm
Overall Depth
310g Approx.
Weight
96mm X 96mm
Panel Cut-Out
92 + 0.8mm X 92 + 0.8mm
Polycarbonate HousingMaterial
Screw-type terminals
Terminals
IP54(For 48x96 model)
For 96 x 96mm
Safety :
2
III
Pollution Degree Installation Category High Voltage Test
2.2 kV AC, 50 Hz for 1 minute
Environmental conditions :
0
-10 to 55 C
0
-25 to 70 C 0 .. 90 % (Non condensing)
Minimum 3 minute
15g in 3 planes 10 .. 55 Hz, 0.15mm amplitude
Operating temperature Storage temperature
Relative humidity
Warm up time
Shock
Vibration
23
Page 23
24
The Information contained in these installation instructions is for use only by installers trained
It is the user's responsibility to determine the suitability of the installation method in the user's field conditions. Manufacturer only obligations are those in Manufacturer standard
Conditions of Sale for this product and in no case will Manufacturer be liable for any other
to make electrical power installations and is intended to describe the correct method of installation for this product. However, Manufacturer has no control over the field condition
which influence product installation.
Incidental, indirect or consequential damages arising from the use or misuse of the products.
Bezel Size (DIN 43718)
<75mm
Overall Depth
250 grams Approx.
Weight
48mm X 96mm
Panel Cut-Out
45 + 0.8mm X 92 + 0.8mm
For 48 x 96mm