Risco WT30V2 Users Manual

NovaTM 30 Wireless Supervised Photoelectric Smoke Detector Installation Instructions
GENERAL DESCRIPTION
Nova 30 is a battery-powered photoelectric smoke detector with a built-in supervised wireless transmitter. When sufficient smoke is detected or the test feature is operated, the detector will sound its alarm horn and the transmitter will send an ALARM message. If the alarm condition remains, the message will be repeated 2 or more times (with 65 second intervals). The Alarm output in the receiver will remain activated until the alarm condition is cleared.
The smoke alarm provides the following features:
Smoke Alarm/base lock discourages unauthorized
removal of the smoke alarm by requiring a screwdriver to remove the alarm from the base.
CleanMe™ Self-diagnostics monitors its own sensitivity and operational status. If the smoke alarms drifts out of the sensitivity range or fails internal diagnostics, it extinguishes its LED
Internal Signal Outputs
The smoke alarm provides the following signals for interfacing:
Alarm
Alarm restore
Low battery
Maintenance alert (Visible only)
Selecting a Location
Selecting a suitable location is critical to the operation of smoke alarms. This equipment should be installed in accordance with the National Fire Protection Association’s (NFPA) Standard 72. See Figure 2.
A-8-1.2.1.C Are More Smoke Alarms Desirable?
The required number of smoke alarms might not provide reliable early warning protection for those areas separated by a door from the areas protected by the required smoke alarms. For this reason, it is recommended that the householder consider the use of additional smoke alarms for those areas for increased protection. The additional areas include the basement, bedrooms, dining room, furnace room, utility room, and hallways not protected by the required smoke alarms. The installation of smoke alarms in kitchens, attics (finished or unfinished), or garages is not normally recommended, as these locations occasionally experience conditions that can result in improper operation.
Important: Regulations pertaining to smoke alarm installations vary from state to state. For more information, contact your local fire department or local authority having jurisdiction.
1
In addition to NFPA 72, use the following location guidelines to optimize performance and reduce the chance of false alarms from the alarm:
Locate ceiling-mounted smoke alarms in the center of a room or hallway at least 4 inches from any
walls or partitions.
Locate wall-mounted smoke alarms so the top of
the alarm is 4 to 12 inches below the ceiling.
Locate in a suitable environment as follows:
Temperature between 40ºF (4.4ºC) and 100ºF
(37.8ºC))
Humidity between 0 and 95% non-
condensing
Locate away from air conditioners, heating
registers and any other ventilation source that may interfere with smoke entering the alarm.
Mount smoke alarms on a firm permanent surface.
Locate away from large metallic objects when listed
with a transmitter.
Installing the Alarm
1. If you are using the alarm/base lock, remove the
two knockouts on the mounting base. See Figure 3.
2. Slide the battery compartment cover away from the
alarm to unsnap it and lift it off. See Figure 4.
3. Follow the write mode procedure as described in
the receiver installation of the operational manual.
4. Observing proper polarity, insert two 3V lithium
batteries into the alarm battery compartment and replace the battery compartment cover.
5. Write message will be sent automatically 10 seconds after installing the batteries.
6. Remove the red plastic dust cover from the alarm.
The alarm is shipped with a dust cover for protection on construction sites with dusty environments.
7. Using the two screws and anchors provided,
mount the base
8. Attach the alarm to the mounting base as follows:
Line up the raised tab on the lip of the alarm
with the slot on lip of the mounting base. See figure. 4
Insert the smoke alarm into the base and
turn clockwise approximately 15 degrees. It should snap firmly into place.
Important: the alarm cannot be attached to the mounting base if no batteries are installed.
9. Test the alarm (see Smoke Testing the Alarm).
Smoke Testing the Smoke Alarm
Smoke alarms should be tested in place annually using smoke or canned aerosol simulated smoke. Follow the
∗ To generate an additional right mode message,
disconnect the batteries for 30 seconds and then reconnect them.
instructions on the canned smoke or use the following steps to test the alarm with smoke:
1. Hold a smoldering punk or cotton wick close to
the smoke entry openings.
2. Gently direct the smoke into the alarm for 20
seconds or until an alarm is indicated.
BE SURE TO PROPERLY EXTINGUISH THE SMOKE SOURCE AFTER TESTING! The alarm LED should remain on and the alarm will sound a temporal rhythm until the Test/Silence button is pressed. The alarm automatically resets when smoke is no longer present.
Understanding the Test/Silence Button
The Test/Silence button on the alarm performs three functions as follows:
Testing = Press the Test/Silence button for 2 seconds. The alarm performs a sounder test and a sensitivity test.
Silence alarm = Press to silence the sounder during an alarm. After a few minutes, the sounder and alarm resume if smoke is still present.
Silence trouble chirp = Press to silence a trouble chirp. The trouble chirp resumes after 24 hours if the trouble condition is not corrected.
2
Testing the Alarm Sensitivity
The smoke alarm provides a sensitivity level test mode that allows you to check the smoke alarms sensitivity using the Test/Silence button and the LED indicator on the alarm as follows:
1. Press the Test/Silence button on the smoke alarm for 2 seconds. Once the test starts, the alarm LED flashes one to
nine times.
2. Count the number of times the LED flashes and use the following table to determine the status of the smoke
sensitivity and what action to take, if any.
Flashes Obscuration
%/ft (approx)
1 N/A Unserviceable hardware
2, 3 N/A Detector is not sensitive
4 3.1 5 2.6 6 2.1 7 1.6 8, 9 N/A Detector is too sensitive. Verify that the smoke chambers is snapped down securely.
After the flashes, if the sensitivity is within limits and all other tests pass, the alarm goes into alarm and resets after 3 seconds.
If the sensitivity is not within limits, or an unserviceable hardware fault has been detected, the smoke alarm LED
extinguishes until the alarm is serviced.
Indication Action
Reset unit and rerun sensitivity test. If the error persists,
fault detected.
enough. Detector is within normal sensitivity range.
replace the unit. Clean the unit. Reset unit and run sensitivity test. If the error persists, replace the unit N/A
Clean the unit and replace the smoke chamber.
Attaching and Removing the Smoke Alarm
To remove the smoke alarm from the mounting base,
grasp the alarm and turn it counterclockwise approximately 15 degrees. The smoke alarm should snap off of the mounting base.
To remove the alarm from the mounting base when the
alarm/base lock is used, insert a small screwdriver into the
locking tab slot on the side of the base and press in while simultaneously turning the alarm counterclockwise 15 degrees. See Figure 5.
Attach the smoke alarm to its mounting base as follows:
Line up the raised tab on the lip of the smoke alarm
with slot on the lip of the mounting base. See Figure 4.
Insert the smoke alarm into the base and turn
clockwise approximately 15 degrees. It should snap
firmly into place.
Understanding the LED
The LED on the alarm indicates the status of the alarm as follows:
FLASHING = Flashes every 9 seconds to indicate normal operation. ON = Detects smoke.
OFF = Trouble or maintenance is required.
When to Replace the Batteries
The Nova 30 smoke alarm requires two 3V lithium A batteries as listed on the battery compartment cover. The required batteries are available where other batteries are sold.
Battery life is a minimum of 1 year and varies depending on how often the alarm is tested. When the batteries are low, the alarm extinguishes its LED and chirps every 30 seconds until the batteries are replaced. The sounder can be silenced for 24 hours by pushing the Test/Silence button.
3
Loading...
+ 4 hidden pages