Risco RWX35S Installation And User Manual

WL Smoke & Heat, 91 5
Model: RWX35S
Installation and User Guide
EN
FR ES IT NL
PR
2
Language Page
3
13
23
33
43
53
EN
FR
ES
IT
NL
PR
3
Introduction
RISCO Group's new Wireless 2-Way Smoke & Heat Detector combine the most advanced technologies within a contemporary, compact and streamlined design, the ideal choice for homeowners seeking the highest safety standards. The smoke & heat detector h been designed for use in family homes, apartments or small offices. The smoke & heat detector is easy to install, and is compatible with RISCO Group’s wireless systems.
NOTE: The smoke and heat alarm is not suitable for use in leisure accommodation vehicles.
How it works
Smoke & Heat
Smoke is detected employing an advanced photoelectric chamber, while temperature is monitored with four separate heat sensors that measure the rate­of-rise, as well as the absolute temperature. With a choice of selecting either smoke or heat detection or a combination of the two, the smoke & heat detector offers a more sensitive and dependable product for early detection of fire hazards in different environments with a reduced risk of false alarms.
The principal function of the smoke & heat detector is to detect smoke and / or heat and then to set off a local alarm. An alarm is activated by the troubled detector and the system’s receiver is informed about the alert.
Main Features
Bi-directional wireless communication
Wireless, combined smoke and heat detection
Simple battery replacement performed by the customer
Multiple heat sensors measuring fixed temperature and rate-of-rise
provide accurate readings and high false-alarm immunity (Smoke & Heat mode)
Visual LED indicates alarms, standby mode, and low battery
Built-in test mode activates self-test and alarm-sounding
Ceiling / wall tamper
EN
4
Modern look and feel
Simple to install
Selecting a Device Location
Where to install your smoke alarm / heat detector
Install a smoke & heat detector in the hallway outside of every separate
sleeping area (see Figure 1). Two detectors are necessary in a building with two areas with bedrooms.
Install a smoke & heat detector in every room that is used as a sleeping
area.
Install a smoke & heat detector on every floor in a multi-floor home (see
Figure 2).
Install at least two smoke & heat detectors in every home.
Install smoke & heat detectors at both ends of a hallway between
bedrooms if the hallway is more than 12 meters long.
In basements, install detectors at the bottom of basement stairs.
For upper story’s, install detectors at the top of the staircase leading to
the story.
Make sure that the path of the smoke to the detector is not blocked by a
door or another obstacle.
Install additional detectors in your living room, dining room, family
room and attic as well as in the laundry and storage rooms.
Install smoke & heat detectors as close as possible to the center of the
ceiling. If it is not practical, install the detector no closer than 30cm to walls or corners (see Figure 3).
If installing on the ceiling is not possible and state and local authorities
allow the installation of the detectors on walls, assemble them on walls at a distance of 30cm – 50cm from the ceiling (see Figure 3).
If your home has a sloped ceiling or gables, try to install the detectors
90cm from the highest point of the ceiling, measuring horizontally (see Figure 4).
5
Figure 1: Installation locations for smoke & heat detectors in single- family apartments or homes with only one sleeping area
Figure 2: Installation locations for smoke & heat detectors in multiple- floor apartments or homes
Figure 3: Recommendations for best and acceptable installation locations for installing smoke & heat detectors.
Figure 4: Recommended installation location for smoke & heat detectors in rooms with sloped ceilings or gables (slope >20 degrees).
Where not to install your smoke & heat detector
A false alarm can be triggered if smoke & heat detectors are installed where they cannot function properly. To prevent such false alarms, do not install smoke & heat detectors as follows:
In areas with constant fresh air supply. Movement of fresh air can keep
smoke from entering the smoke & heat detector, thereby limiting its effectiveness.
Near paint thinner vapors.
In very hot or cold areas, such as near air conditioners, heaters or fans.
In areas with still air, such as under pointed roofs or in corners between
walls and ceiling. Still air can prevent smoke from reaching the detector (see Figure 3 and Figure 4 for recommended installation locations).
Areas prone to insects. If insects enter the sensor chamber of a detector,
they can trigger false alarms. If you have a bug problem, take care of it before you install detectors.
6
Near fluorescent lights, since electromagnetic fields from fluorescent
lighting can trigger false alarms. Install smoke & heat detectors at least
1.5m from such lights.
Where the “heat only” mode can be used
To prevent false alarms, you can use your detector in “heat only” mode. Use the detector in this mode only in or near areas where typically only harmless combustion particles exist which do not present a fire hazard. If the distance of the detector to places at which combustion particles normally exist – for example in kitchens – is less than 6 meters, install the detector as a heat detector only and as far away from the combustion particles as possible. To prevent false alarms, make sure the ventilation in such places is good. Never try to prevent false alarms by switching off the detector.
Other locations:
In damp or humid areas or near bathrooms with showers. The humidity
in the air can get into the measuring chamber and form droplets as it cools, which can then trigger false alarms.
In very dirty or dusty areas. Dirt and dust can collect in the measuring
chamber of the detector and cause it to become over-sensitive. In addition, dirt and dust can block the openings to the measuring chamber and prevent the detector from detecting smoke.
Installation
The smoke & heat detector must be assembled on the ceiling or, if necessary, on the wall. The smoke & heat detector cannot be networked with other detectors.
Before installation, read the sections titled “Where to install your smoke & heat detector” and “Where not to install your smoke & heat detector”, in these operating
instructions.
Installing the detector
1. Select the installation location.
2. Remove the plastic mounting bracket from the detector (see Figure 5).
7
Figure 5 Figure 6 Figure 7
3. Using the mounting holes as a template, secure the mounting bracket to the
mounting surface (see Figure 7).
4. Open the battery compartment cover (see Figure 8).
Figure 8
5. Place the batteries into the battery holder while observing polarity.
6. Connect the battery cable to the battery connector
7. Insert the battery holder in the battery compartment and close the battery
compartment cover.
8. Configure the detector (see Configuring the detector).
9. To Install the detector on the mounting bracket, align the base rib with the
bracket rib, insert the base hooks into the bracket cavities and then turn the detector clockwise (see Figure 9).
Battery Compartment
Tamper
Battery Holder
8
Figure 9 Figure 10
NOTE: Closing the detector bracket may be a little difficult. While closing the bracket the
test button may possibly be pressed.
Replacing the Battery
1. Remove the plastic mounting bracket from the detector (see Figure 5).
2. Remove the old battery.
3. Insert the new battery while observing battery polarity (see Figure 11).
4. Close the battery compartment cover.
Figure 11
Configuration
Configuring the detector
To ensure the detector can detect the system receiver, register the detector by entering the 11-digit serial code or perform the following steps for assigning the RF:
1. Set the system receiver to “Learn” mode.
2. If not already performed, connect the battery.
3. Send an allocation message by pressing the tamper button for at least 3
seconds (or connect the detector to the mounting bracket) until the system receiver indicates that it has received the allocation message.
Upon successful registration, the detector’s green LED indicator makes 4 short blinks.
LED Indicator
9
Visual / Audible Indicators
If the red LED indicator (see Figure 10) flashes once every 30 seconds, the detector is functioning normally.
If the red LED indicator flashes constantly and repetitive beeps are heard, the detector is reacting to a fire alarm (primary or secondary).
A short beep once every 30 seconds indicates low battery or trouble condition. If a fire alarm is activated, press the cover up firmly (see Testing the detector) to
silence the alarm and temporarily disable (for approx. 10 minutes) the alarm activation.
Detector parameters
The following detector parameters can be defined from the system receiver:
Parameter Option
Operational Mode: Smoke only*, Heat only or Smoke and Heat Supervision Time: 1-255 (15 min*)
* = default
See your system receiver’s installation / configuration manual for more
information about defining detector parameters.
Testing the detector
To ensure that your detector is functioning correctly, test it once a week using the following procedure:
1. Press the cover up firmly (see Figure 12). If the detector is functioning
correctly, a fire alarm is activated (see Visual / Audible Indicators) and an alert message is sent to the system receiver.
NOTE: A short beep once every 30 seconds indicates that the test is unsuccessful. You must have the detector repaired or replaced immediately.
Figure 12
2. Release pressure to restore the alarm activation.
10
NOTE: It is recommended to press the center of the detector for the quick test results.
Cleaning and Maintenance
Clean the detector with a dry or damp cloth to remove dirt or dust.
To clean the detector:
1. Remove the detector from the mounting bracket.
2. Open the battery cover and disconnect the battery.
3. Open the detector housing and disconnect the PCB from the holding snaps.
4. Use a paintbrush to remove any dirt and reconnect the PCB.
5. Close the housing, reconnect the battery and replace the battery cover.
6. Reconnect the detector to the mounting bracket
7. Check if the detector is functioning properly.
To ensure the detector continues to function properly, you must test it once a week (see Testing the detector).
To replace the detector batteries:
1. Remove the detector from the plastic mounting bracket.
2. Open the battery compartment cover.
3. Remove the old batteries.
4. Insert the new battery while observing battery polarity (see Figure 11), and
close the battery compartment cover.
5. Reconnect the detector to the mounting bracket.
Replace the batteries once a year or whenever the low battery signal tone sounds. NOTE:
Low battery signal tone - If the detector beeps once every 30 seconds, the detector’s batteries are low. Replace the batteries immediately. After you reconnect the detector to the mounting bracket, you need to check the smoke alarm (see Testing the detector).
11
Technical Specification
Parameter Description
Smoke Alarm Photoelectrical chamber with optical sensor for
detecting smoke
Heat detector 4 sensors for measuring temperature increase,
alarm will be triggered at 60°C Operating modes Smoke + Heat (OR Logic), Only Smoke, Only Heat Indicators Audible (Piezo) and visual (LED) Volume of the warning Min. 85 dB at 3m (10’) Sound frequency 3.25 kHz Power Supply CR123A 3V x 4 Standby power consum. 0.02mA (typical) Alarm power consum. 100mA Battery life 4 years (typical) Low battery threshold 2.65 V In event of low battery One beep every 30 seconds Operating temperature 0°C to 55°C Humidity during operation 10% to 85% RH, no condensation or icing Color White Dimensions (D x H) Ø 133.8 x 50.2 mm (Ø 5.27 x 1.98) Weight 360 g (net) Supervision monitoring 1-255 min. (user defined) Wireless trans. Power 10mW Wireless range Up to 300m (unobstructed) Standards Compliance EN14604:2005/AC:2008. 1134-CPR-186
NOTE: Only the “Smoke Operation Mode” is
approved to EN14604.
Ordering Information
Model Description
RWX35S WL Smoke & Heat Detector, 868Mhz
12
RWX35S WL Smoke & Heat Detector, 915Mhz
FCC ID: JE4RWX35S915
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) This device must accept any interference received, including interference
that may cause undesired operation.
Changes or modifications to this equipment which are not expressly approved by the party responsible for compliance (RISCO Group's.) could void the user's authority to operate the equipment.
FCC Note
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment on and off, the user is encouraged to try to correct the interference by one or more of the following measures:
Reorient or relocate the receiving antenna. Increase the separation between the equipment and the receiver. Connect the equipment into an outlet on to a different circuit from that
to which the receiver is connected.
Consult the dealer or an experienced radio/TV technician for help.
13
RED Compliance Statement
Hereby, RISCO Group declares that this equipment is in compliance with the essential requirements and other relevant provisions of Directive 2014/53/EU. For the CE Declaration of Conformity please refer to our website: www.riscogroup.com.
CE CPR Approval
The wireless smoke and heat detector, RWX35S, designed by RISCO Ltd in Israel, assembled in Israel, has been tested and approved according to the CPR directive 305/2001/EU, standard EN 14604:2005/AC:2008 by ANPI, BELGIUM number 1134­CPR-186.
14
Introduction
Le nouveau détecteur de fumée et de chaleur sans fil bidirectionnel de RISCO Group, qui allie les technologies les plus avancées dans un design contemporain, constitue le choix idéal des propriétaires soucieux de garantir la sécurité de leurs biens. Le détecteur de fumée et de chaleur a été conçu pour une utilisation dans des villas, des appartements ou des petits bureaux. Facile à installer, le détecteur de fumée et de chaleur est compatible avec les systèmes de sécurité sans fil de RISCO Group.
REMARQUE : l'utilisation du détecteur de fumée et de chaleur est déconseillée dans des habitations mobiles.
Mode de fonctionnement
Fumée et chaleur
La fumée est détectée à l'aide d'une chambre photoélectrique à la pointe de la technologie, tandis que quatre capteurs thermiques distincts mesurent les hausses de température et la température absolue. En permettant à l'utilisateur de sélectionner la détection de fumée, la détection de chaleur ou une combinaison des deux, le détecteur de fumée et de chaleur offre davantage de sensibilité et de fiabilité pour la détection précoce des risques d'incendie dans divers environnements, tout en réduisant les fausses alarmes.
La principale fonction de ce détecteur est de détecter la fumée et/ou la chaleur, puis d'activer une alarme locale. Une alarme est déclenchée par le détecteur et le récepteur du système est informé de l'alerte.
Caractéristiques principales
Communication sans fil bidirectionnelle
Détection combinée de fumée et de chaleur, sans fil
Remplacement simple des piles par le client
Plusieurs capteurs thermiques mesurant la température fixe et les
hausses de températures qui offrent des analyses précises et une immunité optimale contre les fausses alarmes (mode Fumée et chaleur)
FR
15
Des LEDs lumineuses qui indiquent les alarmes, le mode de veille et le
niveau de batterie faible
Le mode de test intégré effectue un test automatique pour tester le son
des alarmes
Autoprotection à l’arrachement (Plafond / Mur)
Design moderne
Simple à installer
Choix un emplacement d'installation
Emplacements d'installation recommandés pour le détecteur de fumée et de chaleur
Installez le détecteur de fumée et de chaleur dans un couloir, en dehors
de chaque chambre (reportez-vous à la Figure 1). Deux détecteurs sont nécessaires dans un logement avec deux espaces séparés de chambres.
Installez un détecteur de fumée et de chaleur dans chaque pièce utilisée
comme chambre à coucher.
Installez un détecteur de fumée et de chaleur à chaque étage dans un
logement à plusieurs étages (reportez-vous à la Figure 2).
Quel que soit le type de logement, installez au moins deux détecteurs de
fumée et de chaleur.
Installez les détecteurs de fumée et de chaleur aux deux extrémités d'un
couloir entre les chambres si le couloir mesure plus de 12 mètres de long.
En sous-sol, installez les détecteurs en bas des escaliers.
À l'étage supérieur, installez les détecteurs en haut de l'escalier qui mène
à cet étage.
Assurez-vous que le chemin de la fumée vers le détecteur n'est pas
obstrué par une porte ou un autre obstacle.
Installez des détecteurs supplémentaires dans votre pièce à vivre, salle à
manger, séjour et grenier, ainsi que dans la buanderie et les pièces de rangement.
Installez les détecteurs de fumée et de chaleur le plus près possible du
centre du plafond. Si vous n'y parvenez pas, installez le détecteur à plus de 30 cm des murs ou des angles (reportez-vous à la Figure 3).
Si l'installation au plafond s'avère impossible et que les autorités locales
16
et nationales autorisent l'installation murale des détecteurs, installez-les sur des murs à une distance de 30 cm à 50 cm du plafond (reportez-vous à la Figure 3).
Si votre logement est muni de toits à pignon ou inclinés, essayez
d'installer les détecteurs à 90 cm du point le plus haut sur le plafond, lorsque vous le mesurez horizontalement (reportez-vous à la Figure 4).
Figure1 : emplacements d'installation des détecteurs de fumée et de chaleur dans des appartements individuels ou des logements avec une seule zone de chambres
Figure 2 : emplacements d'installation des détecteurs de fumée et de chaleur dans les appartements ou les maisons à plusieurs étages
Figure 3 : recommandations pour installer les détecteurs de fumée et de chaleur de façon optimale
Figure 4 : emplacement d'installation recommandé pour les détecteurs de fumée et de chaleur dans des pièces munies de toits à pignon ou inclinés (pente > 20 degrés).
Emplacements d'installation déconseillés pour le détecteur de fumée et de chaleur
Il est possible qu'une fausse alarme se déclenche si les détecteurs de fumée et de chaleur sont installés dans un endroit où ils ne peuvent pas fonctionner correctement. Pour éviter les fausses alarmes, n'installez pas les détecteurs de fumée et de chaleur dans les endroits suivants :
Dans des endroits constamment refroidis. Le mouvement de l'air froid
risque d'empêcher la fumée de pénétrer dans le détecteur de fumée et de chaleur et donc de limiter son efficacité.
Salle á manger Cuisine
Chambre á coucher
Salon
Détecteurs de fumée pour sécurité minimale
Détecteurs de fumée pour plus de sécurité
Chambre á
coucher
Chambre á
coucher
Chambre à
coucher
Chambre à coucher
Chambre à
coucher
Cuisine
Rez-de-
chaussée
Sous-sol
Garage
Détecteurs de fumée pour sécurité minimale
Plafond
15 cm (6 in)
maximum
10 cm (4 in)
minimum
10 cm (4 in)
J amais ici
Centre
du plafond
Meilleur emplacement
Emplacement acceptable
Détecteur
3 feet
90 cm
Distance horizontale par rapport au sommet
17
À proximité de vapeurs de diluant.
Dans les endroits très chauds ou très froids, notamment à proximité de
climatiseurs, de radiateurs ou de ventilateurs.
Dans les endroits où l'air est statique, notamment sous des toits pointus
ou dans des angles entre les murs et le plafond. L'air statique peut empêcher la fumée d'atteindre le détecteur (reportez-vous à la Figure 3 et à la Figure 4 pour connaître les emplacements d'installation recommandés).
Dans des endroits où peuvent proliférer les insectes. Si des insectes
pénètrent dans la chambre optique d'un détecteur, ils peuvent déclencher de fausses alarmes. En cas de prolifération d'insectes, prenez les mesures nécessaires pour les éradiquer avant d'installer les détecteurs.
À proximité de lampes fluorescentes, car les champs électromagnétiques
de ces lampes peuvent déclencher de fausses alarmes. Installez les détecteurs de fumée et de chaleur à au moins 1,5 m de ces lampes.
Cas d'utilisation du mode « Chaleur uniquement »
Pour éviter les fausses alarmes, vous pouvez utiliser votre détecteur en mode « Chaleur uniquement ». Utilisez le détecteur dans ce mode uniquement dans des endroits contenant des particules de combustion inoffensives ne présentant aucun risque d'incendie. Si la distance qui sépare le détecteur et les endroits contenant des particules de combustion (notamment des cuisines) est inférieure à 6 mètres, installez le détecteur en mode Chaleur uniquement aussi loin que possible des particules de combustion. Pour éviter les fausses alarmes, assurez-vous que ces endroits sont correctement ventilés. N'essayez jamais d'éviter les fausses alarmes en éteignant le détecteur.
Autres endroits :
Dans des endroits humides ou à proximité de salles de bain munies de
douches. L'humidité dans l'air peut pénétrer dans la chambre de mesure et former des gouttelettes après refroidissement, ce qui risque de déclencher de fausses alarmes.
Dans des endroits extrêmement sales ou poussiéreux. La saleté et la
poussière peuvent s'accumuler dans la chambre de mesure du détecteur et la rendre ultra-sensible. Par ailleurs, la saleté et la poussière peuvent obstruer les orifices de la chambre de mesure et empêcher le détecteur de détecter la fumée.
18
Installation
Le détecteur de fumée et de chaleur doit être installé sur un plafond ou, lorsque cela est nécessaire, sur un mur. Il est impossible de mettre en réseau le détecteur de fumée et de chaleur avec d'autres détecteurs. Avant de procéder à l'installation, lisez les sections intitulées « Emplacements
d'installation recommandés pour le détecteur de fumée et de chaleur » et « Emplacements d'installation déconseillés pour le détecteur de fumée et de chaleur » de ce document.
Installation du détecteur
1. Sélectionnez l'emplacement d'installation.
2. Retirez le support de montage en plastique du détecteur (reportez-vous à la
Figure 5).
Figure 5
Figure 6
Figure 7
3. Utilisez les trous de fixation comme gabarits pour fixer le support de
montage à la surface de montage (reportez-vous à la Figure 7).
4. Ouvrez le couvercle du compartiment à piles (reportez-vous à la Figure 8).
Figure 8
5. Placez les piles dans leur emplacement en respectant les polarités.
Compartiment à piles
Autoprotection
Emplacement des piles
19
6. Raccordez le câble de la batterie au connecteur de batterie.
7. Insérez le bloc des piles dans le compartiment à piles et fermez le couvercle.
8. Configurez le détecteur (reportez-vous à la section Configuration du détecteur).
9. Pour fixer le détecteur au support de montage, alignez la nervure de la base
sur la nervure du support, insérez les crochets de la base dans les cavités du support, puis faites pivoter le détecteur dans le sens des aiguilles d'une montre (reportez-vous à la Figure 9).
Figure 9
Figure 10
REMARQUE : Il est possible que vous ayez des difficultés à fermer le support du détecteur. Il
est par ailleurs possible que vous appuyiez par inadvertance sur le bouton de test lors de la fermeture du support.
Remplacement des piles
1. Retirez le support de montage en plastique du détecteur (reportez-vous à la
Figure 5).
2. Retirez les piles usagées.
3. Insérez les piles neuves en respectant les polarités (reportez-vous à la Figure
11).
4. Fermez le couvercle du compartiment à piles.
Figure 11
Voyant
20
Configuration
Configuration du détecteur
Pour vérifier que le détecteur est en mesure de détecter le récepteur du système, enregistrez le détecteur en saisissant le code série à 11 chiffres ou procédez comme suit pour un adressage par RF :
1. Configurez le récepteur du système en mode d’adressage.
2. Si cela n'est pas déjà fait, connectez la batterie.
3. Envoyez un message d'adressage en appuyant sur le bouton d'autoprotection
pendant au moins 3 secondes (ou placez le détecteur sur son support de montage) jusqu'à ce que le récepteur du système indique qu'il a reçu le message d'adressage.
Une fois l'enregistrement terminé, le voyant vert du détecteur clignote brièvement 4 fois consécutives.
Témoins lumineux/sonores
Si le voyant rouge (reportez-vous à la Figure 10) clignote toutes les 30 secondes, le détecteur fonctionne normalement.
Si le voyant rouge clignote constamment et des bips répétitifs sont émis, le détecteur réagit à une alarme incendie (primaire ou secondaire).
Un signal sonore bref toutes les 30 secondes indique un niveau de batterie faible ou un problème.
Si une alarme incendie se déclenche, appuyez fermement sur le boîtier (reportez- vous à la section Test du détecteur) pour rendre silencieuse l'alarme et désactiver temporairement l’alarme (environ 10 minutes).
Paramètres du détecteur
Vous pouvez définir les paramètres suivants du détecteur sur le récepteur du système :
Paramètre
Option
Mode de fonctionnement :
Fumée uniquement*, Chaleur uniquement ou Fumée et chaleur
Délai de supervision :
1-255 (15 min*)
* = Valeur par défaut Reportez-vous au guide d'installation/configuration du récepteur de votre
système pour définir les paramètres du détecteur.