Risco ProSYS Quick Programming

Quick Programming Setup
ProSYS Ver 7.xx
For detailed information please refer to the full ProSYS Installer Manual
provided on our website: www.riscogroup.com
2 ProSYS Quick Programming Setup
Table of Contents
Introduction.......................................................................................................................... 3
I. Suitable Locations ............................................................................................................ 3
II. Installing Hardware (Devices) ......................................................................................... 3
1. BUS Connection ......................................................................................................... 3
2. Setting Zone Inputs Connection ................................................................................ 5
3. Wiring Auxiliary Devices (Sensors) ........................................................................... 6
4. Wiring Internal Bell ..................................................................................................... 6
5. Bell Tamper Wiring (Terminal Bell TMP) ................................................................... 6
6. Wiring UO1 to Activate Any External Stand-alone Siren .......................................... 7
7. Wiring Important BUS Accessories ........................................................................... 7
III. Programming the System ............................................................................................. 10
Power Up and Enter Installer Mode ............................................................................. 10
Identifying the Connected Devices (including BUS Detectors) ................................. 11
Programming: SYSTEM ............................................................................................... 11
Programming: Wireless ZONES .................................................................................. 12
Programming: ZONES Wired & Wireless (Attributes) ................................................ 13
Programming BUS Detectors ...................................................................................... 14
Programming: Dialer (For PSTN Dialing) .................................................................... 17
Programming: PROG OUTPUTS .................................................................................. 18
Codes (Changing the Installer code) ........................................................................... 19
System Backup ............................................................................................................. 19
Exiting Programming Mode ......................................................................................... 19
Installer Programming Menu Maps ................................................................................... 20
Technical Specifications ................................................................................................... 26
CE Declaration of Conformity ...................................................................................... 27
Compliance Statement ................................................................................................. 27
RISCO Group Limited Warranty .................................................................................. 28
Contacting RISCO Group ............................................................................................. 28
ProSYS Quick Programming Setup 3
Introduction
This simple setup procedure guide covers all common ProSYS programming steps (based on factory default settings) required in order to have a working system.
UL Note:
For more comprehensive instructions for UL installations refer to the installer manual (5IN1383).
I. Suitable Locations
Decide where to position your ProSYS control panel. A central location is often the best place, making wiring to expanders and accessories easier. It is advisable to prepare a plan of expander/accessory physical locations in advance to the installation, as this will determine which type of expander is required at each location. The control panel location should be:
In a dry place near an AC power supply (switched off).
With a good earth connection.
With access to the customer’s phone lines.
With access to the routing of cables for the system from detection devices.
Warning:
If connecting remote power supplies, do NOT connect the Red wire (+12v) between the Power Supply Unit and ProSYS. For UL installations, the AC adapter is not to be connected to a wall outlet controlled by an external switch. Recommended locations for mounting the panel shall be in accordance with the National Electrical Code, ANSI/NFPA 70, the Standard for Installation and Classification of Burglar and Holdup Alarm Systems, UL 681, and the Standard for Central-Station Alarm Services, UL 827
II. Installing Hardware (Devices)
1. BUS Connection
The set of four terminals on the left of the Main Panel represent the Expansion BUS. These terminals support the connection of keypads and expansion modules. The connections are terminal-to-terminal with color-coded wires, as follows:
AUX RED +12V power
BUS 1 YEL Yellow DATA
COM BLK Black 0V common BUS 1 GRN Green DATA
Notes:
The parallel wiring system supports parallel connections from any point along the wiring. The maximum wire run permitted is 300 meters (1000 feet) for all legs of the BUS. The ProSYS has 2 separate BUS connections. If one BUS is shorted or there is any kind of problem that interrupts the BUS data, the other BUS will continue to operate normally.
4 ProSYS Quick Programming Setup
1.1 Setting BUS Accessory ID Numbers
Each accessory has its ID category number, which is defined by dipswitches. Before setting power on, define each module’s ID number by setting the dipswitches as follows:
ID
Dipswitches
ID
Dipswitches
1 2345 12345
01 OFF OFF OFF OFF OFF 17 OFF OFF OFF OFF ON 02 ON OFF OFF OFF OFF 18 ON OFF OFF OFF ON 03 OFF ON OFF OFF OFF 19 OFF ON OFF OFF ON 04 ON ON OFF OFF OFF 20 ON ON OFF OFF ON 05 OFF OFF ON OFF OFF 21 OFF OFF ON OFF ON 06 ON OFF ON OFF OFF 22 ON OFF ON OFF ON 07 OFF ON ON OFF OFF 23 OFF ON ON OFF ON 08 ON ON ON OFF OFF 24 ON ON ON OFF ON 09 OFF OFF OFF ON OFF 25 OFF OFF OFF ON ON 10 ON OFF OFF ON OFF 26 ON OFF OFF ON ON 11 OFF ON OFF ON OFF 27 OFF ON OFF ON ON 12 ON ON OFF ON OFF 28 ON ON OFF ON ON 13 OFF OFF ON ON OFF 29 OFF OFF ON ON ON 14 ON OFF ON ON OFF 30 ON OFF ON ON ON 15 OFF ON ON ON OFF 31 OFF ON ON ON ON 16 ON ON ON ON OFF 32 ON ON ON ON ON
Notes:
1: Most accessories have 4 Dipswitches while the BUS Detectors have 5 Dipswitches 2: IDs 9-16 are available for keypads, proximity key readers and BUS Detectors. ID 17-32 is only available for
BUS Detectors.
3. You may have up to 128 BUS detectors. Each detector must have a unique ID on the BUS zone expander that it is connected to, therefore each ID can be used twice or more - once on each BUS zone expander.
Devices are split into ‘Families’. Each ‘Family’ of devices has sequential identification numbers which are set by the Dipswitches. The first module in each category is defined as ID= 1. If a Dipswitch is changed on any device, it is necessary to remove power from that device and re­power. Families that have sequential ID numbers are:
Keypads
Zone Expanders (8 Wired Zone Expander, 16 Wired Zone Expander, 8 Wireless Zone
Expander, 16 Wireless Zone Expander)
Outputs (8 Open Collector Outputs, 4 Relay Outputs, X-10 Outputs)
Power Supplies (3Amp Power Supplies and 1.5 Amp Power Supplies)
BUS Zones
For example: Each Zone Expander (Hardwired Expander and Wireless Expander) has sequential numbering such as 1,2,3,4 etc…
ID1 (First Zone Expander) = DIP Switch ‘1 off, 2 off, 3 off, 4 off’ = [↓↓↓↓] ID2 (Second Zone Expander) = DIP Switch ‘1 on, 2 off, 3 off, 4 off’ = [↑↓↓↓] ID3 (Third Zone Expander) = DIP Switch ‘1 off, 2 on, 3 off, 4 off’ = [↓↓] ID4 (Fourth Zone Expander) = DIP Switch ‘1 on, 2 on, 3 off, 4 off’ = [↑↑↓↓]
The first zone on ‘Zone Expander’ 1 will be ZONE 09 The last zone on ‘Zone Expander’ 1 will be ZONE 16 or 24 (depending on 8/16 zones on the zone expander). The first zone on ‘Zone Expander’ 2 will follow on from the last zone on ‘Zone Expander’ 1. See NOTE 1 below.
Notes:
1: On Wireless Zone Expanders, there are two banks of Dipswitches. One bank for ZONE ID number and one
bank for Wireless KEYFOB ID number. Wireless Keyfob ID numbers can be 1, 2, 3 or 4.
2: The main unit can support a maximum load of 1.4 Amp. If more current is required install additional
power supply modules (1.5 or 3 Amp).
3: On 3 AMP Supervised Power Supplies, there are two programmable outputs. These programmable outputs
belong to the ‘Output’ family. There are two Dipswitches on the 3 AMP PSU, one for the PSU ID and one for the OUTPUT ID.
ProSYS Quick Programming Setup 5
Maximum number of Devices possible:
ProSYS16 ProSYS40 ProSYS128
Total number of zone expanders 1x8 4x8 or 2x16 or 2x8 + 1x16 1x8 + 7x16 Outputs expanders 2 4 8 Keypads 812 16 Power Supply
88 8
ProSound Siren
88 8
2. Setting Zone Inputs Connection
The following diagrams illustrate the various possible zone connections.
Notes:
It is recommended that you use an End-of-Line Resistor at the far end of each hardwired zone to prevent short-circuits (16 resistors are supplied). For a zone with a tamper switch, you can use a Double End-of-Line Resistor to save additional Main Panel connections. For UL installations use only UL listed EOL resistors, Risco P/N KTRESUL. For UL installations use only listed cables for the connection of detectors and accessories.
2.1 Connection on the main unit (ProSYS 7), G3 zone expanders (ProSYS EZ8G3, EZ16G3) or Inputs on iWISE BUS
Note:
TEOL uses normally-closed (NC) contacts in a zone to distinguish between alarm, tamper condition and fault/AM condition using 4.7 KΩ +6.8 KΩ + 12 KΩ End-of-Line resistors.
Notes:
The values in the diagram above refer to ProSYS version 7.xx. NO and NC cannot be used in UL installation. Zone expander EZ16G3 is not UL listed.
Note:
When connecting non-RISCO TEOL detectors to the ProSYS panel, a 20KΩ resistor to the fault terminal (instead of the 12KΩ as depicted at left) is required.
6 ProSYS Quick Programming Setup
2.2 Connection on the main unit (ProSYS 5), Zone expanders (ProSYS EZ8,
EZ16)
END OF LINE ZONE
(N.O CONTACT)
zone com
ALARM
2.2 K
DETECTOR
NORMALLY OPEN ZONE
CONFIGURATION
ALARM
zone com
DETECTOR
NORMALLY CLOSED
ZONE CONFIGURATION
ALARM
zone
com
DETECTOR
END OF LINE ZONE
(N.C CONTACT)
2.2 K
zone com
ALARM
DETECTOR
DOUBLE END OF LINE
ZONE CONFIGURATION
com
2.2 K
ALARM TAMPER
zone
2.2 K
DETECTOR
Note:
The values in the diagram above refer to ProSYS version 5.xx and below.
3. Wiring Auxiliary Devices (Sensors)
Use the Auxiliary Power AUX (+) COM (-) terminals to power PIRs, glass-break detectors (4­wire types), smoke detectors, audio switches, photoelectric systems and/or any device that requires a 12V DC power supply. The total power from the AUX terminals should not exceed 600mA.
Note:
If the auxiliary outputs are overloaded (exceed 600mA) and are shut down, you must disconnect all loads from the outputs for a period of at least 10 seconds before you reconnect any load to the auxiliary outputs.
4. Wiring Internal Bell
The Bell/LS terminal provides power to the internal siren. When connecting an internal sounding device, pay attention to the polarity. It is important to position the BELL/LS Dip Switch SW1 correctly. The position varies depending on the type of internal siren. A maximum of 900 mA may be drawn from this terminal.
Notes:
1. To avoid Bell Loop Trouble, if no connections are made to an internal siren, use a 2.2KΩ resistor in its
place.
2. Loudspeaker should not be used in UL installations.
3. For UL installations use UL listed sirens, for example: Outdoor siren: Honeywell AB12., Indoor siren:
Honeywell 747 or Honeywell Wave 2.
4. For UL985 installations the fire temporal pattern must be defined as YES (Quick key [1][2][14]).
5. Bell Tamper Wiring (Terminal Bell TMP)
Connect the bell tamper to the BELL TMP and COM terminals on the Main Panel using 2.2KΩ resistor in serial.
Important:
If you DO NOT use the terminal TMP BELL, remember to connect a 2.2KΩ resistor (Resistor colors: Red, Red, Red) BELL between TMP and COM.
PROSYS MAIN PANEL
BELL TMP
COM
2.2 K EOL
RESISTOR
BELL TAMP ER
ProSYS Quick Programming Setup 7
6. Wiring UO1 to Activate Any External Stand-alone Siren
Output UO1 has 3 terminals C, N.C. and N.O. and can be configured to provide a positive voltage, negative voltage or a contact depending on the J10 jumper located on the main board.
Positive (POS): When the J10 connector is placed on POS, the C terminal on UO1 supplies
13.8V
Negative (NEG): When the J10 connector is placed on NEG, the C terminal on UO1 supplies COM
Single pin: If the J10 connector is placed only on 1 pin, the UO1 acts as a dry contact.
7. Wiring Important BUS Accessories
7.1 Wiring the Voice Module
The Voice Module provides native audible information about the status of your ProSYS system, and enables any remote, touch-tone (DTMF) telephone to act as a keypad for the system. The diagram below shows the main components of the electronic form of voice:
BUS Connection – JP1
The connection to the main BUS can be made through the terminals of the module voice AUX (RED), COM (BLK), BUS (YEL) and BUS (GRN) as illustrated. When placed near the ProSYS main unit you can use the supplied 4-wire cable that is dedicated to connecting with the voice module (JP1) to the BUS ProSYS
ProSYS
AUX
RED
COM
BLK
BUS
YEL GRN
Voice
Module
AUX
RED
COM
BLK
BUS
YEL GRN
Voice Connection – JP2
Connects the Voice module (JP2) to the VOICE connector on the ProSYS Main Panel via the supplied cable (essential for normal operation of the Voice module). Through this connector, the module transmits the voice audio signals to the central ProSYS who then sends them on the telephone line for remote communication with the phone numbers dedicated to Follow Me destinations. This connection is necessary for the proper functioning of the module.
Identical
Connectors
8 ProSYS Quick Programming Setup
7.2 ProSound - BUS Siren Connection
Connect the siren according to the diagram. Set the related Dipswitches for BUS mode operation.
Dipswitch CONFIG 2 should be in ON position for ProSound BUS connection Dipswitch CONFIG 4: Defines the siren sound rhythm (ON = Slow, Off = Fast) Dipswitch ID1: 1-3: Set ID BUS Number. Up to 8 sirens can be connected to the ProSYS Dipswitch ID1 4: Set different siren sound
Notes:
The PROX and TRBL outputs are deactivated in BUS mode configuration. To protect the battery against deep discharge, the battery will automatically disconnect below 10.5 VDC. The siren will not operate when a battery is not connected. The ProSound is not UL listed.
BUS
GRN
YEL
COM
BLK
SPEAKER
AUX
RED
LED
TRBL
PROX
TAMPER
F
R
C + C - ST
123 4
ON
ID1
TAMPER
PS
+
-
BLK
RED
MAN
AUTO
C +
C -
TRIG S TROB
LED2
POWER
To Internal
Speaker
To
ProSYS
Panel
BUS
123 4
ON
CONFIG
INT EXT
To
Battery
(To Int.
Tam per)
7.3 Wiring the GSM
Important:
Do NOT make any connection to the RED Power terminal from the security panel.
PHONE
LINESE
T
PHONE
LINESE
T
ProSYS Main GSM/GPR S Module
Telephone cable to bring the voice mess ages from
the ProSYS to the m odule
BUS GSM
/
GPRS
To PSTN Line from
the Wall
To telephone set
ProSYS Quick Programming Setup 9
7.4 Wiring BUS Detectors
The ProSYS supports integration of BUS detectors. Up to 32 addressable BUS detectors can be assigned to the main unit without the need to add any additional hardware zone expanders (using virtual zones). To assign more than 32 BUS detectors (up to 128) you need to add BUS Zone Expanders. For full installation instructions refer to the instructions supplied with each BUS detector.
Connecting BUS Detectors to the ProSYS panel:
1. Set the BUS detector ID number (1-32) using the detector's Dipswitches.
Note:
For WatchOUT, LuNAR, and WatchIN set the switch that defines the detector operation mode to BUS mode.
2. Wire the BUS terminals (RED), COM (BLK), BUS (YEL) and BUS (GRN) to the ProSYS BUS.
Note:
For maximum operation stability, it is best NOT to exceed a total 300 meters (1000 feet) of wiring from the BUS detector to the ProSYS panel.
Connecting BUS Detectors using a BUS Zone Expander:
1. Set the BUS Zone Expander ID number (1-8) using the Dipswitches SW1 1-3.
2. Using SW2 Dipswitches, set the number of zones this expander will support (8,16,24,32)
3. Wire the BUS Zone Expander terminals marked as TO PANEL to the ProSYS BUS.
4. Set the BUS detector ID number (1-32) using the detector's Dipswitches.
Note:
Do not repeat the same ID twice on the same BUS zone expander.
5. Wire each detector's BUS terminals to the relevant BUS zone expander's terminals marked as TO DEVICE.(see figure below)
Note:
For maximum operation stability, it is best NOT to exceed a total of:
300 meters (1000 feet) of wiring from the BUS Zone Expander to the ProSYS panel.
300 meters (1000 feet) of wiring from the BUS Zone Expander to the last BUS detector.
Loading...
+ 19 hidden pages