Risco ProSYS Quick Programming

Quick Programming Setup
ProSYS Ver 7.xx
For detailed information please refer to the full ProSYS Installer Manual
provided on our website: www.riscogroup.com
2 ProSYS Quick Programming Setup
Table of Contents
Introduction.......................................................................................................................... 3
I. Suitable Locations ............................................................................................................ 3
II. Installing Hardware (Devices) ......................................................................................... 3
1. BUS Connection ......................................................................................................... 3
2. Setting Zone Inputs Connection ................................................................................ 5
3. Wiring Auxiliary Devices (Sensors) ........................................................................... 6
4. Wiring Internal Bell ..................................................................................................... 6
5. Bell Tamper Wiring (Terminal Bell TMP) ................................................................... 6
6. Wiring UO1 to Activate Any External Stand-alone Siren .......................................... 7
7. Wiring Important BUS Accessories ........................................................................... 7
III. Programming the System ............................................................................................. 10
Power Up and Enter Installer Mode ............................................................................. 10
Identifying the Connected Devices (including BUS Detectors) ................................. 11
Programming: SYSTEM ............................................................................................... 11
Programming: Wireless ZONES .................................................................................. 12
Programming: ZONES Wired & Wireless (Attributes) ................................................ 13
Programming BUS Detectors ...................................................................................... 14
Programming: Dialer (For PSTN Dialing) .................................................................... 17
Programming: PROG OUTPUTS .................................................................................. 18
Codes (Changing the Installer code) ........................................................................... 19
System Backup ............................................................................................................. 19
Exiting Programming Mode ......................................................................................... 19
Installer Programming Menu Maps ................................................................................... 20
Technical Specifications ................................................................................................... 26
CE Declaration of Conformity ...................................................................................... 27
Compliance Statement ................................................................................................. 27
RISCO Group Limited Warranty .................................................................................. 28
Contacting RISCO Group ............................................................................................. 28
ProSYS Quick Programming Setup 3
Introduction
This simple setup procedure guide covers all common ProSYS programming steps (based on factory default settings) required in order to have a working system.
UL Note:
For more comprehensive instructions for UL installations refer to the installer manual (5IN1383).
I. Suitable Locations
Decide where to position your ProSYS control panel. A central location is often the best place, making wiring to expanders and accessories easier. It is advisable to prepare a plan of expander/accessory physical locations in advance to the installation, as this will determine which type of expander is required at each location. The control panel location should be:
In a dry place near an AC power supply (switched off).
With a good earth connection.
With access to the customer’s phone lines.
With access to the routing of cables for the system from detection devices.
Warning:
If connecting remote power supplies, do NOT connect the Red wire (+12v) between the Power Supply Unit and ProSYS. For UL installations, the AC adapter is not to be connected to a wall outlet controlled by an external switch. Recommended locations for mounting the panel shall be in accordance with the National Electrical Code, ANSI/NFPA 70, the Standard for Installation and Classification of Burglar and Holdup Alarm Systems, UL 681, and the Standard for Central-Station Alarm Services, UL 827
II. Installing Hardware (Devices)
1. BUS Connection
The set of four terminals on the left of the Main Panel represent the Expansion BUS. These terminals support the connection of keypads and expansion modules. The connections are terminal-to-terminal with color-coded wires, as follows:
AUX RED +12V power
BUS 1 YEL Yellow DATA
COM BLK Black 0V common BUS 1 GRN Green DATA
Notes:
The parallel wiring system supports parallel connections from any point along the wiring. The maximum wire run permitted is 300 meters (1000 feet) for all legs of the BUS. The ProSYS has 2 separate BUS connections. If one BUS is shorted or there is any kind of problem that interrupts the BUS data, the other BUS will continue to operate normally.
4 ProSYS Quick Programming Setup
1.1 Setting BUS Accessory ID Numbers
Each accessory has its ID category number, which is defined by dipswitches. Before setting power on, define each module’s ID number by setting the dipswitches as follows:
ID
Dipswitches
ID
Dipswitches
1 2345 12345
01 OFF OFF OFF OFF OFF 17 OFF OFF OFF OFF ON 02 ON OFF OFF OFF OFF 18 ON OFF OFF OFF ON 03 OFF ON OFF OFF OFF 19 OFF ON OFF OFF ON 04 ON ON OFF OFF OFF 20 ON ON OFF OFF ON 05 OFF OFF ON OFF OFF 21 OFF OFF ON OFF ON 06 ON OFF ON OFF OFF 22 ON OFF ON OFF ON 07 OFF ON ON OFF OFF 23 OFF ON ON OFF ON 08 ON ON ON OFF OFF 24 ON ON ON OFF ON 09 OFF OFF OFF ON OFF 25 OFF OFF OFF ON ON 10 ON OFF OFF ON OFF 26 ON OFF OFF ON ON 11 OFF ON OFF ON OFF 27 OFF ON OFF ON ON 12 ON ON OFF ON OFF 28 ON ON OFF ON ON 13 OFF OFF ON ON OFF 29 OFF OFF ON ON ON 14 ON OFF ON ON OFF 30 ON OFF ON ON ON 15 OFF ON ON ON OFF 31 OFF ON ON ON ON 16 ON ON ON ON OFF 32 ON ON ON ON ON
Notes:
1: Most accessories have 4 Dipswitches while the BUS Detectors have 5 Dipswitches 2: IDs 9-16 are available for keypads, proximity key readers and BUS Detectors. ID 17-32 is only available for
BUS Detectors.
3. You may have up to 128 BUS detectors. Each detector must have a unique ID on the BUS zone expander that it is connected to, therefore each ID can be used twice or more - once on each BUS zone expander.
Devices are split into ‘Families’. Each ‘Family’ of devices has sequential identification numbers which are set by the Dipswitches. The first module in each category is defined as ID= 1. If a Dipswitch is changed on any device, it is necessary to remove power from that device and re­power. Families that have sequential ID numbers are:
Keypads
Zone Expanders (8 Wired Zone Expander, 16 Wired Zone Expander, 8 Wireless Zone
Expander, 16 Wireless Zone Expander)
Outputs (8 Open Collector Outputs, 4 Relay Outputs, X-10 Outputs)
Power Supplies (3Amp Power Supplies and 1.5 Amp Power Supplies)
BUS Zones
For example: Each Zone Expander (Hardwired Expander and Wireless Expander) has sequential numbering such as 1,2,3,4 etc…
ID1 (First Zone Expander) = DIP Switch ‘1 off, 2 off, 3 off, 4 off’ = [↓↓↓↓] ID2 (Second Zone Expander) = DIP Switch ‘1 on, 2 off, 3 off, 4 off’ = [↑↓↓↓] ID3 (Third Zone Expander) = DIP Switch ‘1 off, 2 on, 3 off, 4 off’ = [↓↓] ID4 (Fourth Zone Expander) = DIP Switch ‘1 on, 2 on, 3 off, 4 off’ = [↑↑↓↓]
The first zone on ‘Zone Expander’ 1 will be ZONE 09 The last zone on ‘Zone Expander’ 1 will be ZONE 16 or 24 (depending on 8/16 zones on the zone expander). The first zone on ‘Zone Expander’ 2 will follow on from the last zone on ‘Zone Expander’ 1. See NOTE 1 below.
Notes:
1: On Wireless Zone Expanders, there are two banks of Dipswitches. One bank for ZONE ID number and one
bank for Wireless KEYFOB ID number. Wireless Keyfob ID numbers can be 1, 2, 3 or 4.
2: The main unit can support a maximum load of 1.4 Amp. If more current is required install additional
power supply modules (1.5 or 3 Amp).
3: On 3 AMP Supervised Power Supplies, there are two programmable outputs. These programmable outputs
belong to the ‘Output’ family. There are two Dipswitches on the 3 AMP PSU, one for the PSU ID and one for the OUTPUT ID.
ProSYS Quick Programming Setup 5
Maximum number of Devices possible:
ProSYS16 ProSYS40 ProSYS128
Total number of zone expanders 1x8 4x8 or 2x16 or 2x8 + 1x16 1x8 + 7x16 Outputs expanders 2 4 8 Keypads 812 16 Power Supply
88 8
ProSound Siren
88 8
2. Setting Zone Inputs Connection
The following diagrams illustrate the various possible zone connections.
Notes:
It is recommended that you use an End-of-Line Resistor at the far end of each hardwired zone to prevent short-circuits (16 resistors are supplied). For a zone with a tamper switch, you can use a Double End-of-Line Resistor to save additional Main Panel connections. For UL installations use only UL listed EOL resistors, Risco P/N KTRESUL. For UL installations use only listed cables for the connection of detectors and accessories.
2.1 Connection on the main unit (ProSYS 7), G3 zone expanders (ProSYS EZ8G3, EZ16G3) or Inputs on iWISE BUS
Note:
TEOL uses normally-closed (NC) contacts in a zone to distinguish between alarm, tamper condition and fault/AM condition using 4.7 KΩ +6.8 KΩ + 12 KΩ End-of-Line resistors.
Notes:
The values in the diagram above refer to ProSYS version 7.xx. NO and NC cannot be used in UL installation. Zone expander EZ16G3 is not UL listed.
Note:
When connecting non-RISCO TEOL detectors to the ProSYS panel, a 20KΩ resistor to the fault terminal (instead of the 12KΩ as depicted at left) is required.
6 ProSYS Quick Programming Setup
2.2 Connection on the main unit (ProSYS 5), Zone expanders (ProSYS EZ8,
EZ16)
END OF LINE ZONE
(N.O CONTACT)
zone com
ALARM
2.2 K
DETECTOR
NORMALLY OPEN ZONE
CONFIGURATION
ALARM
zone com
DETECTOR
NORMALLY CLOSED
ZONE CONFIGURATION
ALARM
zone
com
DETECTOR
END OF LINE ZONE
(N.C CONTACT)
2.2 K
zone com
ALARM
DETECTOR
DOUBLE END OF LINE
ZONE CONFIGURATION
com
2.2 K
ALARM TAMPER
zone
2.2 K
DETECTOR
Note:
The values in the diagram above refer to ProSYS version 5.xx and below.
3. Wiring Auxiliary Devices (Sensors)
Use the Auxiliary Power AUX (+) COM (-) terminals to power PIRs, glass-break detectors (4­wire types), smoke detectors, audio switches, photoelectric systems and/or any device that requires a 12V DC power supply. The total power from the AUX terminals should not exceed 600mA.
Note:
If the auxiliary outputs are overloaded (exceed 600mA) and are shut down, you must disconnect all loads from the outputs for a period of at least 10 seconds before you reconnect any load to the auxiliary outputs.
4. Wiring Internal Bell
The Bell/LS terminal provides power to the internal siren. When connecting an internal sounding device, pay attention to the polarity. It is important to position the BELL/LS Dip Switch SW1 correctly. The position varies depending on the type of internal siren. A maximum of 900 mA may be drawn from this terminal.
Notes:
1. To avoid Bell Loop Trouble, if no connections are made to an internal siren, use a 2.2KΩ resistor in its
place.
2. Loudspeaker should not be used in UL installations.
3. For UL installations use UL listed sirens, for example: Outdoor siren: Honeywell AB12., Indoor siren:
Honeywell 747 or Honeywell Wave 2.
4. For UL985 installations the fire temporal pattern must be defined as YES (Quick key [1][2][14]).
5. Bell Tamper Wiring (Terminal Bell TMP)
Connect the bell tamper to the BELL TMP and COM terminals on the Main Panel using 2.2KΩ resistor in serial.
Important:
If you DO NOT use the terminal TMP BELL, remember to connect a 2.2KΩ resistor (Resistor colors: Red, Red, Red) BELL between TMP and COM.
PROSYS MAIN PANEL
BELL TMP
COM
2.2 K EOL
RESISTOR
BELL TAMP ER
ProSYS Quick Programming Setup 7
6. Wiring UO1 to Activate Any External Stand-alone Siren
Output UO1 has 3 terminals C, N.C. and N.O. and can be configured to provide a positive voltage, negative voltage or a contact depending on the J10 jumper located on the main board.
Positive (POS): When the J10 connector is placed on POS, the C terminal on UO1 supplies
13.8V
Negative (NEG): When the J10 connector is placed on NEG, the C terminal on UO1 supplies COM
Single pin: If the J10 connector is placed only on 1 pin, the UO1 acts as a dry contact.
7. Wiring Important BUS Accessories
7.1 Wiring the Voice Module
The Voice Module provides native audible information about the status of your ProSYS system, and enables any remote, touch-tone (DTMF) telephone to act as a keypad for the system. The diagram below shows the main components of the electronic form of voice:
BUS Connection – JP1
The connection to the main BUS can be made through the terminals of the module voice AUX (RED), COM (BLK), BUS (YEL) and BUS (GRN) as illustrated. When placed near the ProSYS main unit you can use the supplied 4-wire cable that is dedicated to connecting with the voice module (JP1) to the BUS ProSYS
ProSYS
AUX
RED
COM
BLK
BUS
YEL GRN
Voice
Module
AUX
RED
COM
BLK
BUS
YEL GRN
Voice Connection – JP2
Connects the Voice module (JP2) to the VOICE connector on the ProSYS Main Panel via the supplied cable (essential for normal operation of the Voice module). Through this connector, the module transmits the voice audio signals to the central ProSYS who then sends them on the telephone line for remote communication with the phone numbers dedicated to Follow Me destinations. This connection is necessary for the proper functioning of the module.
Identical
Connectors
8 ProSYS Quick Programming Setup
7.2 ProSound - BUS Siren Connection
Connect the siren according to the diagram. Set the related Dipswitches for BUS mode operation.
Dipswitch CONFIG 2 should be in ON position for ProSound BUS connection Dipswitch CONFIG 4: Defines the siren sound rhythm (ON = Slow, Off = Fast) Dipswitch ID1: 1-3: Set ID BUS Number. Up to 8 sirens can be connected to the ProSYS Dipswitch ID1 4: Set different siren sound
Notes:
The PROX and TRBL outputs are deactivated in BUS mode configuration. To protect the battery against deep discharge, the battery will automatically disconnect below 10.5 VDC. The siren will not operate when a battery is not connected. The ProSound is not UL listed.
BUS
GRN
YEL
COM
BLK
SPEAKER
AUX
RED
LED
TRBL
PROX
TAMPER
F
R
C + C - ST
123 4
ON
ID1
TAMPER
PS
+
-
BLK
RED
MAN
AUTO
C +
C -
TRIG S TROB
LED2
POWER
To Internal
Speaker
To
ProSYS
Panel
BUS
123 4
ON
CONFIG
INT EXT
To
Battery
(To Int.
Tam per)
7.3 Wiring the GSM
Important:
Do NOT make any connection to the RED Power terminal from the security panel.
PHONE
LINESE
T
PHONE
LINESE
T
ProSYS Main GSM/GPR S Module
Telephone cable to bring the voice mess ages from
the ProSYS to the m odule
BUS GSM
/
GPRS
To PSTN Line from
the Wall
To telephone set
ProSYS Quick Programming Setup 9
7.4 Wiring BUS Detectors
The ProSYS supports integration of BUS detectors. Up to 32 addressable BUS detectors can be assigned to the main unit without the need to add any additional hardware zone expanders (using virtual zones). To assign more than 32 BUS detectors (up to 128) you need to add BUS Zone Expanders. For full installation instructions refer to the instructions supplied with each BUS detector.
Connecting BUS Detectors to the ProSYS panel:
1. Set the BUS detector ID number (1-32) using the detector's Dipswitches.
Note:
For WatchOUT, LuNAR, and WatchIN set the switch that defines the detector operation mode to BUS mode.
2. Wire the BUS terminals (RED), COM (BLK), BUS (YEL) and BUS (GRN) to the ProSYS BUS.
Note:
For maximum operation stability, it is best NOT to exceed a total 300 meters (1000 feet) of wiring from the BUS detector to the ProSYS panel.
Connecting BUS Detectors using a BUS Zone Expander:
1. Set the BUS Zone Expander ID number (1-8) using the Dipswitches SW1 1-3.
2. Using SW2 Dipswitches, set the number of zones this expander will support (8,16,24,32)
3. Wire the BUS Zone Expander terminals marked as TO PANEL to the ProSYS BUS.
4. Set the BUS detector ID number (1-32) using the detector's Dipswitches.
Note:
Do not repeat the same ID twice on the same BUS zone expander.
5. Wire each detector's BUS terminals to the relevant BUS zone expander's terminals marked as TO DEVICE.(see figure below)
Note:
For maximum operation stability, it is best NOT to exceed a total of:
300 meters (1000 feet) of wiring from the BUS Zone Expander to the ProSYS panel.
300 meters (1000 feet) of wiring from the BUS Zone Expander to the last BUS detector.
10 ProSYS Quick Programming Setup
III. Programming the System
Power Up and Enter Installer Mode
1. Connect Mains power. The keypad displays "Partition 1".
2. Press
[7][1] to go into the installer programming menu.
3. If a Master/Manager code is required, press [1][2][3][4]
(Default Master Code).
4. You are prompted for the Installer Code.
For ProSYS16, press [0][1][1][6]
(Default Installer Code)
For ProSYS40, press [0][1][4][0]
(Default Installer Code)
For ProSYS128, press [0][1][2][8]
(Default Installer Code)
5. You are now in the Installer Programming mode. Move to the section "Identifying the connected devices" as described below. Quick Keys shown (in square brackets) can be pressed when at the ‘Main Menu’ instead of using the Up/Down keys.
Notes:
If required, you can default the panel to manufacturer's default settings as follows:
1. Disconnect all power from the main panel.
2. Position the default Dip Switch 2 to ON position.
2. Connect the Mains power. Wait until the keypad displays “To Install Press * ”.
3. Press * and enter the default installer code, depending on the ProSYS type. The system automatically enters the automatic accessories settings process.
4. Change the position of Dip Switch 2 to OFF position .
5. Move to the section "Identifying the connected devices" as described below.
Navigating through the menus:
When navigating through the ProSYS menus, the following keys are used:
-
- to enter numeric values where required
- to scroll up or down through the menu options displayed
- Enter / Save (to move into the displayed menu or to save the data that you have changed)
- to toggle displayed menu options from ‘N’ to ‘Y’ and vice-versa
- to go back / quit / don’t save
If you do not know where you are in the menu structure, press
repeatedly to return to the
main menu.
Entering Text Descriptions (Labels):
Key [1] = 1ABCDEFGHIJKLM Key [2] = 2NOPQRSTUVWXYZ Key [4] = 1abcdefghijklm Key [5] = 2nopqrstuvwxyz
Key
= Move cursor Left
Key
= Move cursor Right
Key
= Save
ProSYS Quick Programming Setup 11
Identifying the Connected Devices (including BUS Detectors)
Automatic Settings (QUICK KEYS = [7][5])
Note:
In most cases, when entering Installer mode with the default Dip Switch 2 in ON position , the system will ‘assume’ that this is a ‘virgin’ installation and take you immediately to Auto Settings. If the keypad is already showing “AUTO SETTINGS”, skip to step 3 below.
1. Using the / keys, select [ACCESSORIES] and press .
2. Using the
/ keys, select [AUTO SETTINGS].
3. Press
to begin the Auto Settings process in which it identifies all the devices on
the BUS.
4. Verify that the Keypad displays all the devices you have connected. If a device does not appear, ensure that you have given it a unique ID within its “family”.
5. Press
to accept what is being displayed and move on to the next device found.
6. Repeat steps 4 and 5 until all devices have been shown.
Bus Test (QUICK KEYS = [7][3])
The BUS test will send multiple test commands to each device connected to the system to ensure good connectivity.
1. Using the / keys, select [BUS TEST] and press .
2. Using the
/ keys, check that every device shown reports 99% or higher.
Note:
If a low reading is experienced, check connections with the device and repeat the BUS test.
Programming: SYSTEM
SYSTEM - Timers (Entry/Exit Times etc)
QUICK KEYS = [1][1]
1. Using the / keys, select [TIME DEFINE] and press .
2. Using the
/ keys, select the required timer option and press .
Note:
Some options have more menu levels which are accessed by pressing the [#] key.
3. Using the numeric keys, change the selected option to the desired value and press
.
SYSTEM - Controls (Audible Panic, Installer Reset, EN Settings, etc.)
QUICK KEYS = [1][2]
1. Using the / keys, select [SYSTEM CONTROL] and press .
2. Using the
/ keys, select the option required and press .
3. Using the
key, select [Y] (Yes) or [N] (No)
4. Repeat step 2 and 3 until all required options have been set, then press
.
12 ProSYS Quick Programming Setup
SYSTEM - Set Clock
QUICK KEYS = [1][3]
1. Using the / keys, select [SET CLOCK] and press .
2. Using the
/ keys, select [SYSTEM TIME] and press .
3. Using the numeric keys, enter the current time and press
.
4. Using the
/ keys, select [SYSTEM DATE] and press .
5. Using the numeric keys, enter the day (01 to 31).
6. Using the
key, select the current month.
7. Press the
button once to advance the cursor one position right.
8. Using the numeric keys, enter the current year and press
.
Programming: Wireless ZONES
ZONES - Wireless Calibration (Wireless Receiver background noise threshold setting)
QUICK KEYS = [2][9][5]
1. Using the / keys, select [MAINTENANCE] and press .
2. Using the
/ select [WL CALIBRATE] and press .
3. Using the
/ select the Wireless Receiver and press .
4. Using the
key, choose [Y] (Yes) to ‘Re-Calibrate’ the Wireless Receiver and press
.
5. After a short while, the measured background noise will be shown.
6. Add 10 to the displayed ‘NEW THOLD’ (New Threshold) by using the numeric keys and
press
.
Explanation:
The Calibration measurement above shows the amount of background ‘noise’ that the receiver can ‘hear’ on the same frequency as the RISCO wireless devices. This ‘noise’ could be neighboring devices of another system or other devices operating on the same frequency nearby. These are ‘unwanted’ signals that the ProSYS wireless receiver must be told ‘not to listen to’. The threshold (set above) is the absolute minimum signal strength needed to be heard from a wireless device in order for the receiver to effectively ‘hear it’. This ‘threshold’ is set at ten above the background ‘noise’ (recommended) making the receiver ignore the unwanted signals. With this threshold set, the ProSYS receiver will only hear its own devices which are nearer and have a signal strength greater that the threshold level set.
ZONES - Wireless Zone Allocation (Enrolling the wireless devices)
QUICK KEYS = [2][9][6]
1. Using the / keys, select [MAINTENANCE] and press .
2. Using the
/ keys, select [WL ZONE ALLOC] and press .
3. Using the numeric keys, enter the desired zone number and press
.
4. Using the
/ keys, select [(RE)WRITE] and press .
5. Depending on the wireless device enrolled, please do one of the following:
ProSYS Quick Programming Setup 13
For Wireless PIRs, Door Contacts, Flood Detectors, Shock Detectors - Close the
tamper
For Wireless Smoke Detectors, Fit the batteries and lid, then do nothing for 10-30
seconds
For Wireless PANIC Pendants, press the button(s) for 10 seconds (Cannot be
Supervised)
6. Using the
/ keys, select [SUPERVISED] or [NONE SUPERVISED] for this
wireless device.
7. Repeat steps 3 to 6 until all required wireless devices have been enrolled.
ZONES - Wireless Communication Test (Signal strength of the wireless devices)
QUICK KEYS = [2][9][7]
1. Using the / keys, select [MAINTENANCE] and press .
2. Using the
/ keys, select [WL COMM TEST] and press .
3. Activate all wireless devices in turn.
4. Using the
/ keys, observe the signal strength received from each device
zone number.
Note:
Make sure that the signal strengths are at least 10 units higher than the receiver threshold level.
Programming: ZONES Wired & Wireless (Attributes)
The bold sub headings below are ‘Main Menu’ headings.
The
key is pressed to move into the various sub menus.
To return to the ‘Main Menu’ headings at any time, press [*] repeatedly.
1. Using the Up/Down keys, select [ONE BY ONE] and press .
2. Using the numeric keys, enter the desired zone number and press
.
PARTITIONS
3. Using the numeric keys, select or deselect the relevant partitions to which this zone will
belong to and press
.
GROUP SETS
4. Using the [A], [B], [C] or [D], keys, select the required group and press .
ZONE TYPE
5. Using the Up/Down keys, select the required zone type and press .
ZONE SOUND
6. Using the / keys, select the required zone sound option and press .
Note:
This determines if the zone will ‘be silent’, ’cause Bell to activate’, ‘cause Buzzer to activate’, ‘cause Bell and Buzzer to activate’, ‘create keypad bleep for chime’ etc… when the zone is opened/causes an alarm condition. ‘Buzzer’ refers to the sound emitted from the Keypad(s).
14 ProSYS Quick Programming Setup
ZONE TERMINATION (Only applicable for hard wired zones)
7. Using the
/ keys, select the required zone termination type and press
.
ZONE RESPONSE
8. Using the / keys, select the required response time and press .
ZONE LABELS (Zone description text)
QUICK KEYS = [2][8]
9. Using the / keys, select [LABEL] and press .
10. Using the numeric keys, enter the desired zone number and press
.
11. Using the keys listed below, enter the required text for the zone description and press
. (See page 10 for entering text descriptions.)
12. Repeat steps 10 and 11 for all zones requiring description text.
Programming BUS Detectors
The following section describes the flow of adding BUS detectors to the ProSYS. BUS detectors can be programmed to the main unit or to a BUS zone expander.
Programming BUS detectors on the Main BUS
Step 1: Adding BUS Detector to the Main Unit
QUICK KEYS = [7][1][9][5]:
Note:
If you have already performed Auto Settings skip to Step 2 below: Assign BUS Detectors to a Zone ID and set basic parameters.
1. From the main installer menu press [7][1][9][5] to access the BUS Zone category.
2. Using the
/ keys select a BUS detector ID number as set by the detector's
Dipswitches (01-32)
Note:
The bottom line in the display shows "(0:yy) Type: None". In the 0:yy designation, the 0 represents that the BUS detector is on the main unit and is not assigned to a BUS Zone Expander. The yy represents the BUS detector ID number (up to 32) as set by the detector's DIP switches.
3. Using the / keys move to the Type field. Use the key to select the detector's type.
4. Repeat steps 2 and 3 for other BUS detectors.
Note:
If required you can add virtual zones to the system. Virtual zones are cost effective. They enable to use up to 32 BUS Zones on the main unit without adding physical zone expanders. To add a Virtual BUS zone expander select type VBZ08 or VBZ16 when adding a zone expander (Quick key [7][1][2]).
Step 2: Assign BUS Detectors to a Zone ID and set basic parameters
Each BUS zone detector should be assigned to a zone. BUS zones on the main unit can be assigned to a virtual zone or to a physical wired zone. They cannot be assigned to wireless zones or zones located on a BUS zone expander
1. From the main installer menu press [2] to enter the Zones menu.
2. Using the
/ keys, select [ONE BY ONE] and press .
ProSYS Quick Programming Setup 15
3. Using the numeric keys, enter the desired zone number and press .
Note:
You can select any zone number that is not defined on a Wireless Zone Expander or a BUS Zone Expander.
4. Press to access the Partitions category.
5. Define Partitions, Groups, Zone Type and Zone Sound.
6. In the Termination category select BUS Zone and press
. The following is
displayed:
Z:001 LINK TO: (0:yy) TYPE:NONE
Z:001 LINK TO: (0:yy) TYPE:NONE
7. Select the BUS zone number (designated by yy) to assign to the programmed zone. The TYPE field will be updated automatically when selecting the zone.
8. Press
. Define a label and press to confirm.
9. Repeat steps 3-8 for all required BUS zones.
Step 3: Programming the BUS Detectors Full Parameters
1. From the main Installer menu select [2] Zones > [0] Miscellaneous > [3] BUS Zone Parameters.
2. Select the zone number that the BUS zone was assigned to and press
.
3. Configure the parameters for the relevant BUS detector
Programming BUS Detectors on a BUS Zone Expander
Step 1: Adding the BUS Zone Expander to ProSYS
QUICK KEYS = [7][1][2]:
Note:
If you already performed Auto Settings skip to Step 2 below: Assign BUS Detectors to a Zone ID and set basic parameters.
1. From the main installer menu press [7][1][2] to enter the add BUS zone expander menu.
2. Using the
/ keys select a BUS Zone Expander ID.
3. Using the
/ keys move to Type. Use the key to select a type (BZE08,
BZE16, BZE24 or BZE32 zone expander) based on the Dipswitches you set on the
expander. Press
.
4. Using the
key, select the detector type of each BUS detector connected to this
BUS zone expander.
Note:
The bottom line in the display shows "(x:yy) Type: None" . In the x:yy designation, the x represents the BUS Zone Expander ID number and the yy represents the BUS detector ID number that is connected to the zone expander, as set by the detector's Dipswitches.
5. Press to move to the next BUS detectors.
Step 2: Assign BUS Detectors to a Zone ID and set basic parameters
1. From the main installer menu press [2] to enter the Zones menu.
2. Using the
/ keys, select [ONE BY ONE] and press . The following is
displayed:
ZONE ONE BY ONE: ZONE=001 (X:YY)
ZONE ONE BY ONE: ZONE=001 (X:YY)
16 ProSYS Quick Programming Setup
3. Using the numeric keys, select a zone number whose designation (x:yy) is equivalent to the one defined for the BUS detector. (The x represents the BUS Zone Expander ID number and the yy represents the BUS detector ID number as set by the detector's ID Dipswitches).
Press
to access the Partitions category.
4. Define Partitions, Groups, Zone Type and Zone Sound.
5. In the Termination category select a BUS Zone and press
.
6. Press
. Define a label and press to confirm.
7. Repeat steps 3-7 for all required BUS zones.
Step 3: Setting the BUS Detectors Parameters
1. From the main Installer menu select [2] Zones > [0] Miscellaneous > [3] BUS Zone Parameters.
2. Select the zone number that the BUS Zone was assigned to and press
.
3. Configure the parameters for the relevant BUS detector.
Programming the Input on the iWISE BUS Detector
The iWISE BUS detectors have additional input on board.
1. Add iWISE BUS detector to the system as described in the Programming BUS Detectors section.
2. From the main installer menu press [2] to enter the Zones menu.
3. Using the
/ keys, select [ONE BY ONE] and press .
4. Using the numeric keys, enter the desired zone number and press
.
Note:
You can select any zone number that is not defined on a Wireless Zone Expander or a BUS Zone Expander.
5. Press to access the Partitions category.
6. Define Partitions, Groups, Zone Type and Zone Sound.
7. In the Termination category select one of the following options: BUS Zone Input N/C, BUS Zone Input EOL, BUS Zone Input DEOL, BUS Zone Input N/O, BUS Zone Input
TEOL. Press
.
8. Press
. Select the BUS zone that the input zone belongs to. The Type field will be
updated automatically when selecting the zone.
9. Press
. Define the loop response time.
10. Press
, assign a label and press .
11. Repeat steps 3-10 for all required iWISE inputs.
Note for iWISE BUS Detectors:
The iWISE BUS detectors have additional input. The parameters of this input are the same as any other regular wired zone in the system, with the exception that this input should be linked to one of the zones in the system. For further information refer to instructions supplied with the product.
ProSYS Quick Programming Setup 17
Programming: Dialer (For PSTN Dialing)
The bold sub headings below are ‘Main Menu’ headings.
The
key is pressed to move into the various sub menus.
To return to the ‘Main Menu’ headings at any time, press
repeatedly.
DIALER - Link-Up (MS Telephone numbers and Communication format)
QUICK KEYS = [5][1]
1. Using the / keys, select [LINK-UP] and press .
2. Using the
/ keys, select [MS LINK-UP] and press .
3. Using the
/ keys, select [MS 1 LINK-UP] and press .
4. Using the
/ keys, select [PSTN/VOICE] and press .
Note:
It is the assumption that a regular phone line is used for communication to MS.
5. Using the numeric keys, enter the Primary MS phone number and press .
6. Using the
/ keys, select [MS 2 LINK-UP] and press .
7. Using the
/ keys, select [PSTN/VOICE] and press .
Note:
It is the assumption that a regular phone line is used for communication to MS.
8. Using the numeric keys, enter the Secondary MS phone number and press .
DIALER - Accounts (Site Code/ID)
QUICK KEYS = [5][2]
1. Using the / keys, select [ACCOUNTS] and press .
2. Using the
/ keys, select the relevant Partition and press .
3. Using the
/ keys, select [FOR ACR 1] and press .
4. Using the numeric keys, enter the Site Code/ID for Partition 1 / MS 1 and press
.
5. Using the
button, select ‘Y’ or ‘N’ to apply the Site Code/ID to all partitions and
press
.
Note:
If each partition requires a different Site Code/ID, repeat step 3 - 5 selecting the relevant partition
DIALER - Communication Format (Transmission protocol to MS)
QUICK KEYS = [5][3]
1. Using the / keys, select [COMM FORMAT] and press .
2. Using the
/ keys, select [FOR MS 1] and press .
3. Using the numeric keys, enter the transmission format code and press
.
Note:
0420 for Contact/Point ID – 0700 for SIA
4. Using the / keys, select [FOR MS 2] and press .
5. Using the numeric keys, enter the transmission format code and press
.
Note:
0420 for Contact/Point ID – 0700 for SIA
18 ProSYS Quick Programming Setup
DIALER - Control (Yes/No Options for the Dialer)
QUICK KEYS = [5][5]
1. Using the / keys, select [CONTROL] and press .
2. Using the
/ keys, select [MS ENABLE].
3. Using the
key, change ‘N’ (No) to ‘Y’ (Yes) and press .
4. Using the
/ keys, select [UD ENABLE].
5. Using the
key, change ‘N’ (No) to ‘Y’ (Yes) and press .
6. Using the
/ keys, select [FM ENABLE].
7. Using the
key, change ‘N’ (No) to ‘Y’ (Yes) and press .
DIALER - Auto Codes (MS Report Codes)
QUICK KEYS = [5][0][1]
1. Using the / keys, select [AUTO CODES] and press .
2. Using the
/ keys, select [CONTACT ID] or [SIA] and press .
3. Using the
key, change ‘N’ (No) to ‘Y’ (Yes) and press .
Note:
The ‘AutoCodes’ function should ONLY be performed after all Zone programming has been completed.
Once the Auto Codes function is performed, the ProSYS will quickly look through all current zone parameters and automatically fill in the correct MS codes for the relevant zone programming. Any subsequent zone parameter changes will require you to perform Auto Codes again.
DIALER - Follow Me (Used to define events to Follow Me phones be phone, SMS or
Email)
QUICK KEYS = [5][7][4]
1. Using the / keys, select a Follow Me number and press .
2. Define the following parameters for each Follow Me number:
Type: Configure the format of the message sent to the Follow Me destination, in an
occurrence of an event.
Partitions: Specify the partitions that will initiate the Follow Me report due to a
certain event that occurred in the assigned partitions.
Events and their restore: Specify which events will activate this Follow Me
destination in the partitions assigned to the Follow Me destination.
Programming: PROG OUTPUTS
The bold sub headings below are ‘Main Menu’ headings.
The
key is pressed to move into the various sub menus.
To return to the ‘Main Menu’ headings at any time, press [*] repeatedly.
PROG OUTPUTS - Define (Example for STU)
QUICK KEYS = [3][1]
1. Using the numeric keys, enter the ‘UO’ (Utility Output) number and press .
Note:
Outputs 1-6 are on main ProSYS panel.
ProSYS Quick Programming Setup 19
2. By using the / keys, select the Category in which this output will activate and
press
.
3. By using the
/ keys, select the Event in which this output will activate and
press
.
4. By using the numeric keys, select the Partitions that will cause this output to activate and
press
.
5. By using the
/ keys, select the Switching Mode that this output will follow
and press
.
6. By using the
key, select the Partition(s) Condition when this output will activate
and press
.
7. By using the
key, select the Partition(s) Condition when this output will deactivate
and press
.
8. Using the keys listed on page 10, enter the required text for the Output description and
press
.
9. Repeat steps 1-9 for all Outputs that require programming.
Codes (Changing the Installer code)
Press [*] repeatedly to return to the ‘Main Menu’.
QUICK KEY = [4]
1. Using the / keys, select [CODES] and press .
2. Using the
/ keys, select [INSTALLER] and press .
3. Enter a new Installer code and press
.
4. Repeat the new Installer code and press
to confirm.
System Backup
1. Fit the 12V Rechargeable Battery and secure the ProSYS Panel lid.
Exiting Programming Mode
1. Press [*] repeatedly to return to ‘Main Menu’.
2. Press [0]
to EXIT and SAVE your settings.
Note:
The system will not allow exit from the Installer mode if a ‘Tamper’ or ‘System Fault’ condition exists. Correct any tamper and/or system fault conditions before attempting to exit the Installer mode.
The system is now programmed and ready for use. For more comprehensive and detailed instructions, please refer to the ProSYS Installation Manual (5IN1383). For User Functions, please refer to the ProSYS User Manual.
20 ProSYS Quick Programming Setup
Installer Programming Menu Maps
[1] System
[11] Time Define
[111] Ex/En Delay 1 [115] S. Aux Break [119] More [112] Ex/En Delay 2 [116] WL MOD. Times [1191] Phone Line Cut
Delay Time [113] Bell Timeout [117] Z. Test Times [1192] Guard Delay [114] Bell Delay [118] AC Off Delay
[12] System Control
[1201] Quick Arm [1215] Code GM [1229] GM AUT/PAR [1202] Quick UO [1216] Audible Jam [1230] Double Code [1203] Allow Bypass [1217] Technician
Tmpr
[1231] Disarm Stop FM
[1204] Quick Bypass [1218] Technician
Reset
[1232] Global Follower
[1205] False Code Trouble
[1219] N/A [1233] Area
[1206] Bell Sqk [1220] Day Light
Saving
[1234] DIS Keypad Auto
Disarm Exists [1207] Bell 30/10 [1221] Forced KSW [1235] Aud Prx TMP [1208] Alm Phone
Cut
[1222] Pager [1236] AM=Tamper
[1209] 3 Min Bypass [1223] Arm Prewrn [1237] Prox AM=Tamper [1210] Dbl Ver Fire
Al
[1224] L.Batt.Arm [1238] SIRN AUX=TMP
[1211] Aud Panic [1225] ENG Tamper [1239] GSM Pre-Alarm [1212] Buzz->Bell [1226] Blank Display [1240] Dis. GSM Bat
[1213] Alarm ZE Cut [1227] 24H Bypass
[1241] Exit restart
[1214] Fire Temp
Pattern
[1228] IMQ Install
[1241] Auto Stay
[13] Set Clock
[131] System Date [132] System Time
[14] Windowing
[141] Window Start [142] Window Stop [143] Window Days
[15] System Labels [16] Tamper Sound
[161-5] Tamper Sound
[17] Default Enb/Disb
[18] Service Info
[181] Service [182] Service Phone
[19] System Version
ProSYS Quick Programming Setup 21
[2] Zones
[21] One by One [22] Partitions/Group [23] Zone Type
[23zz00] Not used [23zz08] I+Ex(Op)/En [23zz16] Special [23zz01] Ex/En1 [23zz09] I+En
Follower
[23zz17] Pulsed KSW
[23zz02] Ex/En2 [23zz10] I+Instant [23zz18] Exit Termination [23zz03] Ex(Op)/En [23zz11] UO Trigger [23zz19] Latch KSW [23zz04] En Follower [23zz12] Day Zone [23zz20] EN.Fol+Stay [23zz05] Instant [23zz13] 24 Hours [23zz21] KSW Delay [23zz06] I+Ex/En1 [23zz14] Fire [23zz22] Latched KSW Dly [23zz07] I+Ex/En2 [23zz15] Panic
[24] Zone Sound
[241] Silent [243] Buzzer Only [245] Door Chime [242] Bell Only [244] Bell+Buzzer [246] Bell/A Buz/D
[25] Termination
[2501] N/C [2505] BUS Zone [2509] BZ Input DEOL [2502] EOL [2506] TEOL [2510] BZ Input N/O [2503] DEOL [2507] BZ Input N/C [2511] BZ Input TEOL [2504] N/O [2508] BZ Input EOL
[26] Loop Response [27] Cross Zone
[271] Zone Crossing
[28] Labels [29] Maintenance
[291] Copy Zone [294] Delete Par. [297] WL Comm. Test [292] Delete Zone [295] WL Calibrate [298] Zone Self Test [293] Add/Copy Par. [296] WL Zone Alloc [299] Soak Test
[20] Miscellaneous
[201] Forced Arming [202] Pulsed Counter [203] BUS Zone Prms.
22 ProSYS Quick Programming Setup
[3] Utility Output
[30] Nothing [31] System
[3101] Bell Follow [3107] AC Loss Fol [3113] D Key Reader
Comm [3102] No Tel Line [3108] Sensors Test [3114] Switch AUX [3103] Comm. Fail [3109] Voice Module [3115] GSM Error [3104] Trouble Follow [3110] Battery test [3116] GSM:PSTN Loss [3105] GND Pulse [3111] Bell Burglary [3117] GSM:Low Bat [3106] Low Bat. Fol [3112] Scheduler
[32] Partition
[3201] Ready Follow [3209] Buzzer Follow [3217] Disarm Follow [3202] Alarm Follow [3210] Chime Follow [3218] Bell Follow [3203] Arm Follow [3211] Ex/En Follow [3219] Bell Stay Off [3204] Burglary Follow [3212] Fire Trouble
Follow
[3220] Zone Bypass
[3205] Fire Follow [3213] Day (Zone)
Follow
[3221] Auto Arm Alarm
[3206] Panic Follow [3214] Gen Trouble
Follow
[3222] Zone Loss Alarm
[3207] Special Emergency Follow
[3215] Stay Follow
[3208] Duress Follow [3216] Tamper Follow
[33] Zone
[331] Zone Follow [333] Arm Follow [334] Disarm Follow [332] Alarm Follow
[34] User Code
[3401] Pulse N/C [3403] Pulse N/O [3404] Latch N/O [3402] Latch N/C
[4] Code Maintenance
[41] Authority [42] Partition [43] Grand Master [44] Installer [45] Sub-Installer [46] Code Length
ProSYS Quick Programming Setup 23
[5] Dialer
[51] Link Up
[511] MS Link Up [512] U/D Phones
[52] Cust. Accounts No.
[53] Comm Format
[54] Access & ID
[541] Access Code [542] ID Code [543] MS Lock
[55] Control
[5501] MS Enable [5507] User Initiate [5513] Show Handshake
[5502] FM Enable [5508] Callback U/D [5514] Audible Kissoff [5503] U/D Enable [5509] Autobatch [5515] UD GSM Enable
[5504] Call Delay [5510] Answer
Machine
[5516] X.Modem Enable
[5505] Dial Tone [5511] UL Installation
[5506] Call Save [5512] Show Kissoff
[56] Parameters
[561] MS Retries [564] Dial Tone Time [567] Pulse Duty Cycle
[562] FM Retries [565] Redial Wait [568] Swinger Limit [563] Rings to U/D [566] Dial Method [569] VM Retries
[57] Report Split
[571] MS Arm/Disarm [573] MS Non Urgent [575] Email (See Email
table)
[572] MS Urgent [574] Follow Me [576] Event Log
[58] Alarm Restore
[581] On Bell Time Out [582] Follow Zone [583] At Disarm
[59] Periodic Test
[591] MS Test [592] UD Test
[50] More
[501] Auto Codes [502-6] ACM
Parameters (See ACM table)
[6] Report Codes
[61] Emergency Key [62] Zones [63] Accessory
Tamper [64] Main Trouble [65] PS Trouble [66] Arm Codes [67] Disarm Codes [68] Miscellaneous [69] Special Comm [60] Accessory Code
24 ProSYS Quick Programming Setup
[7] Accessories
[71] Add/Delete module
[711] Keypad [717] Printer Module [7194] Siren [712] Zone Expander [718] Access Control [7195] BUS Zones [713] Utility Output [719] More [7196] GSM [714] Power Supply [7191] Dig Key
Reader
[7197] X. Modem
[715] Event Logging [7192] Advanced
Digital Voice
[716] WL Button [7193] ACM
[72] Verify Module [73] BUS Test [74] BUS Scanning [75] Auto Settings
[8] Miscellaneous
[81] Keyfobs
[811] WL Button Param [812] WL Button
Allocation
[82] Siren
[821] Strobe Control [823] Strobe Arm SQK [826] Proximity Level [822] Strobe Blink [824] Siren LED [827] Bat. Load Test
[83] GSM
(See GSM table)
[9] Access Control
[91] Door Define
[91dd1] Partitions [91dd3] Door Fire [91dd5] Door Label [91dd2] Door Time [91dd4] Door Input
[92] Card Code Pos. [93] Special Code
ACM
[502] ACM Parameters
[5021] ACM IP Address
[5027] Gateway IP [50203] DNS 1 IP
[5022] ACM UD Port [5028] Software
Update IP
[50204] DNS 2 IP
[5023] ACM AUX1 Port [5029] Software
Update Port
[50205] NTP IP
[5024] ACM AUX2 Port [5020] More [50206] NTP Port [5025] ACM AUX3 Port [50201] U/D IP Mask [50207] NTP UPD Time [5026] Subnet IP Mask [50202] ACM Net
Name
[503] ACM Control
[5031] ACM Config [5033] ACM AUX1
Config
[5035] ACM AUX3 Config
[5032] ACM UD Config [5034] ACM AUX2
Config
[504] ACM MS Polling
[5041] ACM MS Primary
[5042] ACM MS Secondary
[5043] ACM MS Backup
[505] ACM Function [506] View ACM
Config
ProSYS Quick Programming Setup 25
Email
[575] Email
[5751] Mail IP Address
[5754] Email Prefix [5757] SMTP Password
[5752] Mail SMTP Port
[5755] Email Domain
[5753] Mail POP3 Port
[5756] SMTP User Name
[83] GSM
[831] GSM Parameters
[8311] GSM Mode [83111] GSM Backup [83112] GSM Only [83113] GSM Main [8212] GSM Times [83121] PSTN Lost [83122] GSM Lost [83123] SIM Expire Date [8313] Prefix [8313 1 to 2] PBX Prefix [8313 3 to 8] Prefix
Constant [83139] Remove Prefix [83130] Add Prefix [8314] PIN Code [8315] GPRS [83151] APN Code [83152] GPRS User
Name [83153] GPRS Password [83154] GPRS MS
Polling [831541] GPRS Primary [831542] GPRS
Secondary [831543] GPRS Backup [8316] Email [83161] SMTP IP
Address [83162] SMTP Port [83163] SMTP User
Name [83164] SMTP Password [83165] SMTP Email
Prefix [83166] SMTP Email
Domain [8317] Caller ID [8318] RSSI Level
[832] GSM Control
[8321] Disable In. Call
26 ProSYS Quick Programming Setup
Technical Specifications
Main
Input Power:
16.5VAC 40VA by an external class 2 listed AC/AC adapter)
Current Consumption:
60 mA, typical / 70 mA, maximum
Notes:
1. For US installations, use a listed AC/AC adapter 120VAC 60 Hz, to 16.5VAC 40VA.
2. The main unit current consumption does not include the Aux and the Battery charge.
Rechargeable Standby Battery:
12 Volts up to 17.2 Amp-Hours (AH), typical
Power Outputs: Auxiliary Power: 12 Volts DC @ 600 mA, maximum (from all AUX
terminals) Bell/LS (External): 12 Volts DC @ 900 mA, maximum (For UL installation 300mA maximum)
Programmable Voltage: UO1: Relay (programmable output) (24V, 3 Amps)
UO2: 12V 500 mA transistor UO3-UO6: Open Collector Active Pull-Down, 70 mA, max
8 LED Keypad (Not UL Listed)
Current Consumption:
13.8VDC +/-10%; 75 mA maximum
16 LED Keypad (Not UL Listed)
Current Consumption:
13.8VDC +/-10%; 75 mA maximum
LCD Keypad
Current Consumption:
13.8VDC +/-10%; 100 mA maximum
Proximity LCD Keypad
Current Consumption:
13.8VDC +/-10%; 250 mA maximum
Touchscreen Keypad
Current Consumption:
13.8VDC +/-10%; 30 mA typical / 180 mA maximum
Touchscreen Keypad with Proximity
Current Consumption:
13.8VDC +/-10%; 30 mA typical / 280 mA maximum
8 zone expansion module
Current Consumption:
13.8VDC +/-10%; 25 mA, typical / 30 mA, maximum
16 zone expansion module
Current Consumption:
13.8VDC +/-10%; 27 mA, typical / 45 mA, maximum
BUS Zone Expansion
Current Consumption:
13.8VDC +/-10%; 20 mA, typical
8,16 wireless zone expansion module (Not UL Listed)
Current Consumption:
13.8VDC +/-10%; 40 mA maximum
Frequency:
868.6-868.7 MHz (narrowband operation in EU) or 433.92 MHz
4 relay output expansion module
Current Consumption:
13.8VDC +/-10%; 25 mA typical / 160 mA maximum
Contacts:
4 Form C (SPDT) Relays.
Contact rating:
5 A / 24V DC
8 transistor output expansion module
Current Consumption:
13.8VDC +/-10%; 25 mA typical / 40 mA maximum
Contacts:
Open Collector, Active Pull-Down, 70 mA maximum
1.5A Power Supply Expansion Module (Not UL Listed)
Input Power:
16.5 Volts AC @ 40 VA (via transformer)
Current Consumption:
180 mA maximum
Rechargeable Standby Battery:
12 Volts up to 17 Amp-Hours (AH), typical
Power Outputs:
Auxiliary Power: 12 Volts DC @ up to 1.5A* Bell/LS (External) Sounder Output:12 Volts DC @ 900 mA, maximum *: Total current Bell+Aux=1.5A
ProSYS Quick Programming Setup 27
Fuses:
F1: Battery power 3.0 A F2: Auxiliary power 2.0 A F3: Bell/loudspeaker power 1.0 A
3A Power Supply Expansion Module
Input Power:
16.5VAC @ 50VA (via 230VAC / 16.5VAC/50Hz transformer)
Rechargeable Standby Battery:
12V Up To 21 Amp-Hours (AH)
Power Outputs:
Auxiliary Power: 3A @13VDC Bell/LS (External) Sounder Output: 1.7A @13VDC
Overload Protection:
Automatic Electronic Protection
On board Utility Outputs:
2 relays, 12VDC @ 3A max Dry Contact Relays
Event Log Expansion Module
Current Consumption:
13.8VDC +/-10%; 30 mA, maximum
Printer Module (Not UL Listed)
Current Consumption:
13.8VDC +/-10%; 10 mA, maximum
X-10 Transmitter Module (Not UL Listed)
Current Consumption:
13.8VDC +/-10%; 30 mA maximum
Access Control Module (Not UL Listed)
Current Consumption:
13.8VDC +/-10%; 100 mA maximum
Input power:
13.8V DC + 10%
Readers Consumption:
5V / 150 mA maximum
Relay:
24V DC / 1 A maximum
Proximity Key Reader (Not UL Listed)
Current Consumption:
13.8VDC +/-10%; 70 mA, typical / 180 mA maximum
Advance Digital Voice Module
Current Consumption:
13.8VDC +/-10%; 38 mA typical / 70 mA maximum
Voice Message Unit
Input Power:
8V DC to 14V DC
Current Consumption:
9 mA (standby) / 60 mA (active speaking - normal volume) / 130 mA (active speaking - full volume)
GSM/GPRS Communication Module
Input Power:
13.8VDC ±10% Battery: Lead Acid (rechargeable), 12VDC/1.2Ah
Current Consumption:
During Communication - 300mA, During Standby - 70mA
Advanced Communication Module (ACM)
Current Consumption:
9-16 VDC +/-10%; 300mA@13VDC
Fast PSTN Modem 2400 BPS (Not UL Listed)
Current Consumption:
100 mA maximum
CE Declaration of Conformity
Hereby, RISCO Group declares that this control panel (ProSYS 128, ProSYS 40, ProSYS 16), with wired accessories (including cables) and wireless accessories, is in compliance with the essential requirements and other relevant provisions of Directive 1999/5/EC.
For the CE Declaration of Conformity please refer to our website: www.riscogroup.com.
Compliance Statement
Hereby, RISCO Group declares that the ProSYS series of control panels and accessories are suitable for use in systems designed to comply with PD6662:2004 Security Grade 3, Environmental Class II. (Security Grade 2 when using Wireless accessories). The ProSYS series of control panels and accessories comply with the relevant parts of the EN50131 series of standards. The ProSYS series of control panels and accessories comply with DD243:2004.
28 ProSYS Quick Programming Setup
RISCO Group Limited Warranty
RISCO Group and its subsidiaries and affiliates ("Seller") warrants its products to be free from defects in materials and workmanship under normal use for 24 months from the date of production. Because Seller does not install or connect the product and because the product may be used in conjunction with products not manufactured by the Seller, Seller cannot guarantee the performance of the security system which uses this product. Seller's obligation and liability under this warranty is expressly limited to repairing and replacing, at Seller's option, within a reasonable time after the date of delivery, any product not meeting the specifications. Seller makes no other warranty, expressed or implied, and makes no warranty of merchantability or of fitness for any particular purpose. In no case shall seller be liable for any consequential or incidental damages for breach of this or any other warranty, expressed or implied, or upon any other basis of liability whatsoever. Seller's obligation under this warranty shall not include any transportation charges or costs of installation or any liability for direct, indirect, or consequential damages or delay. Seller does not represent that its product may not be compromised or circumvented; that the product will prevent any personal injury or property loss by burglary, robbery, fire or otherwise; or that the product will in all cases provide adequate warning or protection. Seller, in no event shall be liable for any direct or indirect damages or any other losses occurred due to any type of tampering, whether intentional or unintentional such as masking, painting or spraying on the lenses, mirrors or any other part of the detector. Buyer understands that a properly installed and maintained alarm may only reduce the risk of burglary, robbery or fire without warning, but is not insurance or a guaranty that such event will not occur or that there will be no personal injury or property loss as a result thereof. Consequently seller shall have no liability for any personal injury, property damage or loss based on a claim that the product fails to give warning. However, if seller is held liable, whether directly or indirectly, for any loss or damage arising under this limited warranty or otherwise, regardless of cause or origin, seller's maximum liability shall not exceed the purchase price of the product, which shall be complete and exclusive remedy against seller. No employee or representative of Seller is authorized to change this warranty in any way or grant any other warranty.
WARNING: This product should be tested at least once a week.
Contacting RISCO Group
RISCO Group is committed to customer service and product support. You can contact us through our website www.riscogroup.com or as follows:
United Kingdom
Tel: +44-(0)-161-655-5500 support-uk@riscogroup.com
Belgium (Benelux)
Tel: +32-2522-7622 support-be@riscogroup.com
Brazil
Tel: +55-11-3661-8767 support-br@riscogroup.com
Italy
Tel: +39-02-66590054 support-it@riscogroup.com
USA
Tel: +1-631-719-4400 support-usa@riscogroup.com
China (Shanghai)
Tel: +86-21-52-39-0066 support-cn@riscogroup.com
Spain
Tel: +34-91-490-2133 support-es@riscogroup.com
Poland
Tel: +48-22-500-28-40 support-pl@riscogroup.com
China (Shenzhen)
Tel: +86-755-82789285 support-cn@riscogroup.com
France
Tel: +33-164-73-28-50 support-fr@riscogroup.com
Israel
Tel: +972-3-963-7777 support@riscogroup.com
All rights reserved. RISCO Group reserves the right to amend the software and features without prior notice. No part of this document may be reproduced in any form without prior written permission from the publisher.
© RISCO Group 04/11 5IN1286 C
Loading...