Rinnai Rice Cooker REU-PVA Installation Manual

REU-PVA Pressure Activated Valve
INSTALLATION INSTRUCTIONS
Application
Pressure activation valves (PVA’s) can be used to manifold 2 to 5 Rinnai water heaters in order to produce a stable water temperature and allow the water heaters to run efficiently. PVA’s can be used to manifold indoor or outdoor models. See Figure 1.
Figure 1
Unit 1 Unit 2 Unit 3 Unit 4 Unit 5
Installation
Install the PVA valve at the inlet of the water heater in the correct orientation as shown in Figure 2.
In a manifolded system, PVA valves will be installed on all but one unit. Set each PVA to a different activation pressure, except on the 4th and 5th unit. This allows each unit to come on as necessary to meet the demand for hot water. Set the activation pressure on the second unit to its lowest activation point. Set the third unit to the second lowest activation point, and so forth. If 5 units are manifolded then set the 4th and 5th unit to the same activation point. See Figure 3.
How to Adjust the Activation Pressure
1. Unlock the adjusting rod by removing one screw and loosen the other screw that holds the stopper in place. See Figure 2.
2. Move the stopper and pull the rod out to reduce the activation pressure. (3 notches will be visible when completely extended). Push the rod in to increase the activation pressure. Do not push the rod completely into the valve.
NOTICE
Figure 2
Figure 3
Water heaters should be at the same temperature setting.
WATER HEATER INLET
STOPPER
ADJUSTMENT ROD
3. Install the stopper with 2 screws to lock the adjusting rod.
2nd Unit 3nd Unit 4th and
5th Unit
02/2008 100000068
Loading...