Q85S / Q130S Condensing Boiler
Standard Features
• Onboard outdoor reset control system with sensor standard
• Prebuilt plumbing kit with insulated Low Loss Header
• Priority DHW standard ( 3 way valve not included)
• Domestic hot water plate warming
• Modulating Ceramic premix burner
• 5:1 turn down ratio
• Spark ignition
• Exceeds SCAQMD 1146.2 Low NO
• Stainless Steel Water tube condensing heat exchanger
• Direct Vent sealed combustion
• Concentric and twin pipe venting adapters included
• Approved for room and closet installations
requirements
x
SPECIFICATIONS
General Specifications
Boiler
Water content gal 0.9 1.3
Max. supply boiler
temperature
Max operating pressure psi 45 45
Relief valve rating MBH 375 375
Relief valve pressure rating psi 30 30
Units
°F 176 176
Model
Q85S Q130S
Boiler
Model
Optional Accessories
• 3 way valve DHW kit
• RS100 Single zone controller
• Flue Gas temperature sensor
• Room Air Filter
• NG to LP conversion Kit
• LP to NG Conversion Kit
Performance Specifications
Units
Fuel Type NG/LP NG/LP
Input MBH 85 130
Heating Capacity MBH 78 119
AFUE (I=B=R) % 96.5 96.1
Part Load Efficiency
(EN677)
% 98.8 98.2
Boiler Model
Q85S Q130S
Dry weight lbs 110 117
Electrical Specifications
Min inlet gas pressure NG "W.C. 4.0" 4.0"
Max inlet gas pressure NG "W.C. 10.5" 10.5"
Min inlet gas pressure LP "W.C. 8.0" 8.0"
Max inlet gas pressure LP "W.C. 14.0” 14.0”
Max equivalent exhaust
vent length
Max equivalent combustion
air vent length
Approved venting materials
Rinnai is continually updating and improving products; therefore, specifications are subject to change without prior
notice. Local, state, provincial and federal codes must be adhered to prior to installation.
© 2011 Rinnai Corporation
ft 100 100
ft 100 100
Polypropylene,
Stainless Steel,
PVC, CPVC
Units
Electrical Voltage Mains V/Hz 120/60 120/60
Electrical Voltage Controls V 24 24
Power Consumption Max
Load
Power Consumption Stand
by Load
Recommended Circuit
breaker rating
Q85S / Q130S SP 2/2011
W 137 144
W 14 14
A 15 15
Boiler Model
Q85S Q130S
DIMENSIONS
Q85S / Q130S
A Height 26.8 / 680
B Width 19.7 / 500
C Depth 15.2 / 385
D Left side / vent 13.2 / 335
Center to center / vent and air
E
supply
F Back / vent 10.6 / 270
G Left side / gas pipe 2.6 / 65
H Left side / supply pipe 7.3 / 185
J Left side / return pipe 11.2 / 285
K Left side / condensate pipe 14.6 / 370
P Pipe length of g 0.7 / 18
Q Pipe length of c 2 / 50
R Pipe length of e, f, k, r, and w 2.3 / 60
S Back / center of pipe c 1 / 25
T Back / Center of pipe g 1.6 / 40
Q85S, Q130S
inch / mm
4.7 / 120
2.0”
50mm
2.1”
54mm
142
[5.6”]
17.6”
448mm
219mm
4.7”
119mm
5.2”
131mm
8.6”
360mm
3.9”
100mm
229mm
14.2”
416mm
9”
16.4”
Back, / center of pipe e, f, k, r,
U
and w
Pipe length vent co-axial
V
Pipe length vent parallel
Clearances
Minimum required
Top 2 / 50 10 / 250
Back 0 0
Front 6 / 150 24 / 600
Left side 2 / 50 2 / 50
Right
side
Floor /
Ground
Vent 0 0
clearance to
combustibles and
non-combustibles
2 / 50
2.6 / 65
5.8 / 147
Recommended
service
clearances
inch / mm
2 / 50 2 / 50
12 / 300 30 / 762
inch / mm
Rinnai Corporation • 103 International Drive • Peachtree City, GA 30269 • Toll-Free: 1-800-621-9419 • Fax: 678-364-8643 • www.rinnai.us