E50C Condensing Boiler
Standard Features
Factory installed boiler/system pump Onboard outdoor reset control system with sensor standard Priority DHW standard Built in DHW plate heat exchanger Modulating Ceramic premix burner 6.25:1 turn down ratio Spark ignition
Exceeds SCAQMD 1146.2 Low NO
Stainless Steel Water tube condensing heat exchanger Direct Vent sealed combustion Twin pipe venting adapters included
Approved for room and closet installations
(Zero Clearance to Combustibles)
SPECIFICATIONS
General Specifications
Units
Water content gal 0.9
Max. supply boiler
temperature Max operating pressure psi 45 Relief valve rating MBH 375
°F 176
requirements
x
Boiler Model
E50C
Performance Specifications
Units E50C
Fuel Type NG Input (Heating) MBH 50 Heating Capacity MBH 47 Input (DHW) MBH 85 Minimum Input MBH 13
Max Head Pressure at Flow
Rate
Optional Accessories
RS100 Single zone controller Flue Gas temperature sensor Room Air Filter NG to LP Conversion Kit Flow Switch Conversion Kit Low Loss Header Plumbing Kit Low Loss Header Side Mount Kit
4.6ft* at 5.0GPM
Relief valve pressure rating psi 30 Dry weight lbs 91 Min inlet gas pressure NG "W.C. 3.0" Max inlet gas pressure NG "W.C. 10.5" Min inlet gas pressure LP "W.C. 8.0" Max inlet gas pressure LP "W.C. 14.0”
Max equivalent exhaust
vent length
Max equivalent combustion
air vent length
Approved venting materials
ft 100
ft 100
Polypropylene,
Stainless Steel,
PVC, CPVC
AFUE (I=B=R) % 95.6
Part Load Efficiency
(EN677) DHW flow rate 75°F ΔT gpm 2.1
*4.6ft of Head Pressure is equal to 2 PSI
% 98.8
Electrical Specifications
Units
Electrical Voltage Mains V/Hz 120/60 Electrical Voltage Controls V 24
Power Consumption Max
Load
Power Consumption Stand
by Load
Recommended Circuit
breaker rating
W 145
W 14
A 15
Boiler Model
E50C
Rinnai is continually updating and improving products; therefore, specifications are subject to change without prior
notice. Local, state, provincial and federal codes must be adhered to prior to installation.
© 2013 Rinnai Corporation
E50C SP 7/2013
DIMENSIONS
E50C Condensing Boiler
E50C
inch / mm
A Height B Width 19.7 / 500 C Depth 15.6 / 395 D Left side / vent 13.2 / 335
Center to center / vent and air
E
supply F Back / vent 10.6 / 270 G Left side / gas pipe 9.8 / 250 H Left side / supply pipe 5.9 / 150 J Left side / return pipe 13.8 / 350 K Left side / condensate pipe 15.9 / 405 N Left side / cold water pipe 11.2 / 285 O Left side / hot water pipe 8.5 / 215 P Pipe length of g 0.7 / 19 Q Pipe length of c 1.6 / 40
25.6 / 650
4.7 / 120
Additional Information:
If the boiler is to be installed in a system that utilizes zone
circulators and not zone valves a low loss header plumbing
kit is required to be installed.
If the pressure drop in the loop/system is greater than the
available head pressure from the boiler circulator a Low Loss
Header Plumbing kit part number: 804000061 must be used.
If the boiler is installed in a system with zone valves and the
constant recirculation function is activated then a differential pressure bypass valve or a low loss header plumbing kit is
required to be installed.
R Pipe length of f, k, r, and w 2 / 50
Back / center of pipe c, k, and
S
w T Back / Center of pipe f, g, and r 2 / 50
Pipe length vent co-axial
V
Pipe length vent parallel
1 / 26
3.7 / 95 7 / 177
Clearances
Minimum required
inch / mm inch / mm Top 0 10 / 250 Back 0 0 Front 1 / 25 24 / 600 Left side 0 2 / 50 Right side 0 2 / 50 Floor / Ground 0 30 / 762 Vent 0 0
clearance to
combustibles and
non-combustibles
Recom-
mended
service
clearances
Rinnai Corporation • 103 International Drive • Peachtree City, GA 30269 • Toll-Free: 1-800-621-9419 • Fax: 678-364-8643 • www.rinnai.us