Rinnai SFD01 Installation Guide

RINNAI SIDEWAYS FLUE DIVERTER SFD-01
INSTALLATION INSTRUCTIONS
General Information
Rinnai sideways flue diverter SFD-01 fits the following Rinnai Continuous Flow water heater models: REU-V2626WG - INFINITY 26
REU-VM2630WD - INFINITY 26 Plus REU-VM2630WC - HD 200e REU-V2426WS - S26 REU-V2426WB - V1500
component of the water heater appliances with which it is compatible. For the certification number see the data plate on the appliance.
Installation of heater and flue system shall be in accordance with:
IMPORTANT
• Manufacturers Installation Instructions.
• Current AS 5601 Gas Installations.
• Local Regulations and Municipal Building Codes. Installation, service and removal by an Authorised Person only. Continuous flow water heater to be installed in accordance with the 'Operation / Installation Manual' supplied with the appliance.
Applications
The Rinnai sideways flue diverter is intended for fitting to Rinnai continuous flow water heaters installed on balconies, patios or similarly enclose d areas to facilitate free products out of the enclosed area. This may not occur if the appliance is installed without the sideways flue diverter.
Rinnai external continuous flow water heaters mounted against a wall without the sideways flue diverter, will expel flue products in a horizontal direction outwards and away from the wall against which the appliance is mounted. Fitment of the sideways flue diverter results in the flue products being expelled from the appliance in a sideways direction, along the wall as shown in Figure 1.
Installation Requirements
Figure 2 (on page 2) shows the location conditions and clearances which apply when Rinnai continuous flow water heaters are fitted with the sideways flue diverter and installed on balconies, patios or similarly enclosed areas. Other relevant clearances in Figure 5.3 of AS5601 continue to apply when the sideways flue diverter is fitted.
• Fitment of the Rinnai sideways flue diverter is suitable ONLY when all f lue products
IMPORTANT
result in being expelled freely into an above ground open-air situation with natural ventilation, without stagnant areas where products of combustion are rapidly dispersed by wind and natural convection.
• The Rinnai sideways flue diverter is not suitable for Rinnai continuous flow water heaters installed in recess boxes.
• Rinnai sideways flue diverter SFD-01 is suitable for single wate r heater applications only. It is not suitable for multiple installations of Rinnai continuous flow water heaters on one balcony, patio or similarly enclosed space.
• The Rinnai sideways flue diverter is certified for use only with the Rinnai c ontinuous flow water heater models listed in this Instruction. It is not compatible with any other Rinnai or other manufacturers' appliances.
explusion of combustion
Rinnai 1 SFD01 Installation Instruction
A
LOCATION CONDITIONS AND CLEARANCES
APPLICATIONS
INSTALLATION
i
Preparation
1. Unpack the diverter assembly from it’s packaging.
2. Remove the two retaining screws from the front of the box panel .
3. Separate the mounting bracket from the rear of the box panel .
Rinnai 2 SFD01 Installation Instruction
B
C
B