Rinnai RS100 Operating And Installation Instructions

Control system
For the heating specialist Operating and installation instructions
Room control unit RS100
Rinnai
2
Contents
General safety instructions...........................................................3
Safety measures for electric - compliant installation .................3
Installation of the room control unit............................................. 5
Mounting location .................................................................................................5
Mounting instructions ...........................................................................................5
Electrical connection ............................................................................................6
Electrical connection at boiler...............................................................................6
Accessories ....................................................................................7
Outdoor sensor ....................................................................................................7
Resistance values of outside sensor.....................................................................7
Co m m i s s i o n i n g o f t h e ro o m c on tr o l u n it.........................................8
Language .............................................................................................................8
Code input............................................................................................................8
Site information..........................................................................10
Parameter synoptic......................................................................11
Overview of installer parameters and adjustment options.................................12
3
General safety instructions
All electrical connections and safety measures have to be carried out by a specialist in due consideration of valid standards as well as the local regulations.
The electrical connection has to be done according to the specications of the respective boiler manufacturer.
Safety measures for electrical­compliant installation
1. Cables with 120 V voltage must be generally routed separately from sensor lines and data bus cables. A minimum distance of 0.8 in (2 cm) between the lines is mandatory. Crossing of lines is permitted.
2. When installing the room control unit a minimum distance of 15.75 in (40 cm) must be maintained to other electrical utilities with electromagnetic emissions, such as power contactors, motors, transformers, dimmer switches, microwave ovens and televisions, loudspeakers, computers, mobile phones etc.
3.
15.75 in 40 cm
Fig. 2: Minimum distance to oth er elec tric
instruments
Only connect heating room lighting and sockets on separate power circuit!
Room control unit
Control unit 16 A
Heating room emergency switch
Boiler
Fig. 3: Electric routing in heating room
Fig. 1: Min im um di stanc es for e le ctric al c onn ecti on
5.9 in 15 cm
Mains 120 V~
Data bus line 12 V~
0.8 in 2 cm
WARNING
Indicates an imminently hazardous situation which, if not avoided, could result in death or serious injury.
WARNING
Disconnect power before opening. Making connections under voltage may damage the control or cause dangerous electrical shocks. 120 volts is supplied to the control.
The main connection for the heating system (i.e. boiler - control unit) must be designed as an independent electrical circuit. Do not connect uorescent lamps or other electrically powered devices which could be a source of electrical interference. Even the possibility of such connections/interference should be ruled out.
4
4. It is suggested to use a shielded cable for all installations.
5. The shielding of the cable has to be connected with earth potential, i.e. boiler covering, connecting terminals ­for earth potential etc. Multiple grounding is not permitted (humming loop).
In star shaped networks it is not permitted to ground cables on both sides. They should be grounded in the center.
6. The outside sensor may not be installed close to transmitting or receiving equipment (on garage walls close to receivers for radio-controlled garage door openers, amateur radio antennas, radio controlled alert systems or close to large scale radio transmission equipment).
Recommended cable cross-sections and maximum permitted cable lengths:
A – Sensor lines
For all low voltage cables such as sensors, external selectors, bus and analogue in- and outputs, heat requiring by means of external contact, modem connection cables, etc.: 0.0008 in (0.5 mm )
2
Maximum permitted cable length: 164 ft (50 m). Longer connecting cables should be avoided in order to reduce the risk of electrical interference.
B – Data bus lines
Recommended cable: J-Y(St)Y 2 x 0.0009 in (0.6 mm )
2
Maximum permitted cable length: 164 ft (50m)
Longer connecting cables should be avoided in order to reduce the risk of electrical interference.
Fig. 5: Grounding in star shaped networks
Screen
2-wire
data bus line
Distribution terminal
Distribution box
Do not ground here!
Fig. 4: Screen grounded in centr e
Boiler control in boiler control unit
Connection, depending on version, directly or via suitable interface
2
2
(18 AWG)
(18 AWG)
5
Installation of the room control unit
Mounting location
a – for applications without room sensor
If the internal room sensor is not to be activated the unit may be mounted at any location indoors.
b – for applications with room sensor
The activated room sensor should be xed at a height of approx. 4-5 ft (1.2-1.5 m) at a place most representative of all rooms. It is recommended to choose a partition wall in the coolest day room. In order to ensure sucient air circulation at the room station, it must be mounted to the wall with a gap in between.
The unit must not be mounted:
– at locations subjected to direct solar
radiation (consider the position of the sun during winter).
– close to heat-generating appliances,
such as televisions, refrigerators, wall lamps, radiators etc.
– on walls with heating or domestic hot
water pipes or chimneys behind.
– on non-insulated outside walls – in corners or wall recesses, shelves or
behind curtains (insucient ventilation)
– close to doors of unheated rooms
(inuence of low temperatures)
on unsealed ush-type boxes
(inuence of external low temperatures due to the chimney eect of installation tubes)
– in rooms with radiators controlled by
thermostatic valves (mutual inuence).
Mounting instructions
After removing the front panel by pressing the locating lug the wall mounting base can be taken o and mounted at the desired location using the enclosed dowel pins and screws. The data bus line must thereby be routed through the bottom cable gland.
Recommended connecting cable:
J-Y(ST)Y 2 x 0.0009 in (0.6 mm ) (18 AWG / 2 conductor twisted pair shielded cable)
2
(2 wires not in use). Maximum cable length: 328 ft (100 m)
Note:
For new installations, a ush-mounting switch box is recommended to ensure perfect routing of the cable.
Locking lug
2
6
Electrical connection
The 2-strand data bus cable is connected to terminals A and B of the 2-pole terminal strip on the bottom plate.
Socket (unit removed)
Important!
The connections are not interchangeable and must be installed in the socket in compliance with the identification A and B.
Once the electrical connection is completed, the room control unit is hooked in flush at the top of the wall mounting base and folded down until the locking lug audibly clicks into the wall mounting base.
Electrical connection at boiler
The electrical connection depends on the type and version of the respective heating generator and takes place directly at the terminals A and B in the corresponding boiler control or interface.
Further detailed information can be found in the documentation for the
corresponding boiler.
A B
7
Accessories
Outdoor sensor
Mounting Location
The outdoor sensor should be mounted on the most exposed and coldest side of the building (north or north-east) at a height of min. 79 in (2 m) above ground.
Exception: If the preferred living area is
situated in a dierent direction, the outside sensor should be mounted on the respective side of the building accordingly.
When mounting the sensor consider external heat sources (heated chimneys, warm hot air from air shafts, installation on black surfaces, thermal bridges in the wall, etc.) which could falsify the measuring value. The cable outlet must always be directed downwards in order to avoid the penetration of moisture.
Installation and electrical connection
1– Route the sensor cable to the chosen
mounting location.
2– Loosen lid screws from sensor case
and remove top.
3– Mount sensor base with enclosed
central fastening screw. Use sealing ring! The cable outlet must be directed downwards!
4– Insert the sensor cable so that the
cable jacket is fully enclosed by the sealing lip.
5– Establish the electrical connection. To
this end, preferably use a 2-strand cable with a minimum cross-section of 1 mm
2
(18 AWG). The connection is made at the 2 screw terminals inside the sensor case and may be interchanged.
6– Attach the lid again and screw it
rmly onto the base. Ensure correct t of sealing ring.
Resistance values of outside sensor
For outside sensor AF 120:
T (°C) R (k
)
- 20
- 15
- 10
- 5
± 0
5
10
15
20
25
30
98.93
76.02
58.88
45.95
36.13
28.60
22.88
18.30
14.77
12.00
9.804
Note:
If other outside sensors are in use, the respective resistance values, depending on the temperature, can be found in the technical documentation of the boiler manufacturer.
The electrical connection of the respective
sensor in the boiler is described
in the respective installation instructions of
the boiler.
Outdoor sensor AF 120
T (°F)
- 4
- 5
14
23
32
41
50
59
68
77
86
8
Commissioning of the room control unit
Language
During the rst activation or with each return of voltage after a power failure all segments available in the display will appear:
The desired language can be selected.
Ff Language
This is followed by the equipment version and the current version number of the software.
If there is no alarm present, the standard display with date, time and current
boiler temperature will appear thereafter.
An active summer switch-o is identied by a sunshade symbol (
).
An active frost protection function is represented by a ice crystal symbol (
).
Code input
Installer code
After entering the installer code all parameters determined for the heating specialist are released and can be edited in accordance with the system version.
In order to enter the installer code, the keys
and must be pressed
simultaneously for approx. three seconds, until the code input appears in the display.
+
Each ashing digit is set by using the rotary pushbutton in accordance with the code number and is conrmed by pressing the button. All other digits are edited in the same way.
After the code has been entered correctly,
the acknowledgement INSTALLER OK will
appear upon conrmation of the last digit,
after a wrong entry, the message CODE ERROR will appear.
The factory set installer code is :
Note: If the code is not accepted
you should consult the manufacturer!
Attention: Enabled parameters will be
blocked again if no further action takes place over a period of ten minutes. In this case the installer code must be entered again.
40 5
0 2 4 6 8 10 12 14 16 18 20 22 24
°C
Segment test
Unit version
Interface version and version number
Summer shutdown
active
Frost protection
active
CODE
0
000
INSTALLER
OK
CODE ERROR
V3 .0
D
°C
1 2 3 4
Standard display
Wed. Aug. 25, 2004 16:32 hrs Temp. 40.5°
C

°C KWh Min %
°C KWh Min %
0 2 4 6 8 10 12 14 16 18 20 22 24
40 .5
0 2 4 6 8 10 12 14 16 18 20 22 24
°C
40 5
0 2 4 6 8 10 12 14 16 18 20 22 24
°C
9
Alarm messages
In order to be able to perform an exact diagnose in case of a problem the control system is equipped with a comprehensive fault alarm system. Depending on the nature of the fault a corresponding alarm message will appear in the display of the room control unit.
The display and processing of logic alarms is deactivated in the factory and can be
activated in the SYSTEM level by enabling
Parameter 13 (= Logic alarm). The entry into the level selection and the entry into the levels is shown in the Parameter synoptic (see page 11).
Further processing of errors:
– Errors appear in the standard display of the
control
– System errors appear in the info-level at the
corresponding info-value
– Errors may be taken over into the error
message register (see description opposite).
Detailed information about errors of the
boiler can be found in the documentation of the boiler.
Alarm messages from boiler control
If boiler controls are used in the respective
boiler, the alarm messages are
divided into: A - permanent faults (permanent locking)
with error code E-XX
B - temporary faults (self-eliminating
locking) with error code B-XX
Fault category A Locking E-XX
Fault category B Blockage B-XX
Alarm message register
The room control unit is provided with an alarm message register, which is able to hold maximum 20 alarms. The alarms are displayed with date, time, and nature of fault (error number), the errors are polled in the sequence of their occurrence in the
level ALARM.
The latest (= up-to-date) alarm is prioritized at first position, alarms that have arrived before appear in the order of their occurrence. Upon arrival of a new alarm the last (20.) alarm will be deleted.
Alarm messages from condensing boiler
controls represent a special feature. If enabled (SYSTEM parameters 27 and
28), these will be written into an own alarm message memory.
10
Site information
After accessing the information level using the information key
, all available site- and system temperatures can be requested one by one by turning the rotary pushbutton clockwise or counter-clockwise. Entry occurs at the respective outside temperature.
A - Site and system temperatures
If set value is displayed in the following
table in the category "display value", it will appear when the rotary pushbutton is pushed.
The following displays only appear under the specied display conditions.
INFORMATION DISPLAY VALUE DISPLAY CONDITIONS
Outside temperature
Actual value/
Set value = mean value
If outside sensor is connected
Outside temperature
Minimum/maximum value (0.00 to 24.00 h)
If outside sensor is connected
Boiler
temperature
Actual value/ set value
Boiler
return ow temperature
Actual value If return ow sensor is present
Flue gas temperature Actual value If ue gas sensor is present Hydraulic pressure Actual value If pressure sensor is present
Hot water generator
Actual value/ set value
If hot water generator os present
Room temperature Direct circuit
Actual value/ set value
If room sensor is enabled
B - Oper ating sta tes
After entering the information level by means of the information key
all available operating
states and usage data such as
counter readings, specied performance data etc. can be requested after each other by turning the rotary push-button counter-clockwise.
INFORMATION DISPLAY VALUE COMMENTS
Status Direct circuit
AUTO P2 DAY HC ON
Operating mode /
-program/ heating mode
status of heating pump
Status domestic hot water circuit
AUTO DAY DHW OFF
Operating mode /
-program/ heating mode
status of heating pump
Status
Boiler
HEAT GENER. ON
switching condition of boiler(ON/OFF)
Starts
Boiler
STARTS 1483
Sum of boiler starts
Operating hours
Boiler
OPER. HOURS 485
Sum of boiler operating hours
Thermostat function Direct circuit
THERMOSTAT
HC OFF
Room thermostat function is active Room temperature limitation currently ON/OFF
11
Parameter synoptic
Entry into the level selection: Hold rotary push-button pressed for approx. 3 seconds - automatic call of time programs
Select required level via rotary push-button and conrm, enter code if necessary
Programming Configuration Control circuits Service
Param. No.
TIME-
DATE
TIMEPRO-
GRAMS
HYDRAULIC
SYSTEM
DHW
UNMIXED
CIRC
HEAT
GENER.
ALARM
ALARM 2
SENSOR
ADJ.
1
TIME
(h/min)
LANGUAGE
DHW-NIGHT
temperature
RED.
HEATING
ERR-1 ERR- 1
Room sensor Unmixed circ.
2
YEAR
Output SOL-P
TIME PROGRAM
LEGION. PROT. DAY (week-day)
HEAT.SYSTEM
ERR-2 ERR-2
Outdoor
sensor
3
DAY-
MONTH
CONTROL
MODE
Legionella
protection (time)
Room sensor
ERR-3 ERR-3
4
CHANGE
Su-Wi AUTO
SUMMER
(switch-o)
Legionella protection
(temperature)
Room eect
factor
ERR-4 ERR-4
5
Output
HC
System frost
protection
Adaptation
heating curve
Boiler set
back
ERR-5 ERR-5
6
See
instructions
DHW max. l imit
Inrush
Optimization
ERR-6 ERR-6
7
Heating limit
ERR-7 ERR-7
8
Room frost
protection
temperature
ERR-8 ERR-8
9
Climate zone
Room thermostat
function
ERR-9 ERR-9
10
Building
ERR-10 ERR-10
11
Time for
automatic exit
Constant
control unit
ERR-11 ERR-11
12
Min-limit
heating circuit
ERR-12 ERR-12
13
Logical error
message
Max-limit
heating circuit
ERR-13 ERR-13
14
Excess
boiler
ERR-14 ERR-14
15
ERR-15 ERR-15
16
Screed
function
ERR-16 ERR-16
17 ERR-17 ERR-17
18
Release
Cycle temperature
ERR-18 ERR-18
19
Frost protect.mode
Constant/cycl ic
operation
ERR-19 ERR-19
20 ERR-20 ERR-20
21
22
23
Anti-blocking
protection
Room control
P-range
24
Fahrenheit range
Room control
Adaptation time
25 HC name Out-lock
26 .
27
Alarm messages
boiler control
28 Alarms 2
RESET to factory
values
RESET
Oper.data
Parameters without background color: User Parameter, accessible without code Parameters with light grey background: Installer Parameter, only accessible with installer code Parameters with dark grey background: Only accessible with installer code and certain settings
12
Overview of installer parameters and adjustment options HYDRAULIC Level
The parameters of this level refer to the general hydraulic system of the boiler as well as to the functionality and conguration of the programmable inputs and outputs for the corresponding boiler components.
Parameter Designation Setting range / Setting values
Fact.
setting
Individual
setting
02
Function assignment of output for DHW-loading pump
OFF No function
1 DHW-loading pump
1
05
Function assignment of output for unmixed circuit pump
OFF No function 2 Unmixed circuit pump 6 Constant control unit
2
SYSTEM Level
The parameters in this level refer to the general limiting parameters and setting values in the heating system to be used.
Parameter
Designation Setting range / Setting values
Fact.
setting
Individual
setting
LANGUAGE
Font language selection
DE German CZ Czech GB English PL Polish FR French RO Romanian IT Italian RU Russian NL Dutch TR Turkish ES Spanish S Swedish PT Portuguese N Norwegian HU Hungarian
D
TIME
PROGRAM
Number of enabled time programs
P1 Only one time program enabled
(unmarked)
P1-P3 Three time programs enabled,
(marked)
P1
CONTROL
MODE
Enabling of separate control mode setting
1 Common adjustment for all
Heating circuits
2 Separate adjustment for every
individual heating circuit
1
SUMMER
Limit temperature for summer switch o
OFF no function System frost protection…86°F (30 °C)
20 °C
05
System frost protection
OFF no function
-4°F (-20°C)...Summer switch-o
3 °C
09
Climate zone -4°F..32°F (-20..0.0°C)
-12 °C
10
Type of building
1 light construction 2 medium construction 3 heavy construction
2
11
Time for automatic exit
OFF No automatic return 0,5...5 after adaptation time, autom. (min) return to standard display
2 min
13
Logical error message OFF, ON OFF
18
Release cycle temperature OFF, ON ON
19
Frost protection mode
OFF Permafrost protection according to Adj.
Param. 5
0,5...60 min c yclic o peration
OFF
23
Anti-blocking protection OFF (0000), 0001...9999 OFF
68 °F 37 °F
10 °F
13
24
Fahrenheit range OFF, ON OFF
27*
Alarm messages system handling Automatic boiler control
1 Shown on display screen only 2 Message from system interlocks 3 Messages from interlocks and blockages into the system 4 Message from interlocks, blockages and warnings into the system
OFF
28
Alarm message memory 2 OFF, ON
OFF
RESET
Reset to factory values
in dependence on access code only to released parameters
* Function dependent upon support from boiler control system
DHW level
This level contains all parameters which are necessary to program the DHW circuit with the exception of the DHW time programs.
PARAMETER
Designation Setting range / Setting values
Fact.
setting
Individual
setting
DHW NIGHT D HW e co n om y t e mp e ra t u re
41°F (5 °C) ... DHW maximum temperature
OT OFF ... DHW Day
40 °C
LEGION.PROT. DAY
DHW legionella protection - day (to enable, select weekday)
OFF No legionella protection
Mo...Su Legionella protection on the
specied weekday
ALL Legionella protection every weekday
OFF
03
DHW legionella protection - time (only appears if Parameter LEGION.PROT. DAY is enabled)
00:00...23:00 o'clock
02:00
04
DHW-legionella protection-temp. (only appears if Parameter LEGION.PROT. DAY is enabled)
50°F (10°C)
1)
... DHW maximum temperature
1)
65°C
1)
06
DHW- maximum temperature limit
68°F (20°C)
1)
... Boiler maximum
temperature
1)
65°C
1)
1)
Setting ranges and maximum temperatures, depending on the version, are set by the boiler control
Level UNMIXED CIRCUIT
This level contains all necessary parameters for the programming of the unmixed heating circuit with the exception of the time programs.
PARAMETER Designation Setting range / Setting values
Fact.
setting
Individual
setting
RED. HEATING
Type of reduced operation
ECO - switch-o operation RED - set-back operation
ECO
HEAT.SYSTEM Heating system (exponent) 1.00 … 10.00
1,3
03
Room intrusion (in connection with room sensor)
OFF - without room sensor 1 - room sensor enabled 3 - room sensor only for room-temp­ display
OFF
04 Room eect factor OFF, 10 ... 500 %, RC (only room control)
OFF
104 °F
149 °F
149 °F
14
05 Adaptation heating curve OFF, ON (not during HC = constant control)
OFF
06 Inrush optimization
OFF, 1 ... 16 h
OFF
07 Heating limit
OFF, 0,5...40,0 K (not during HC= constant contr.)
OFF
08
Room frost protection temperat ure
5 ... 30 °C
10 °C
09 Room thermostat function OFF, 0.5 ... 5 K
OFF
11 Constant control unit 10 ... 95°C (only if Par. 05 – Hydraulic =6)
20 °C
12 Minimum temperature limit
10 °C ... setting Maximum temperature limit (Parameter 13)
20 °C
13 Maximum temperature limit
Minimum temperature limit (Parameter 12) ... 95 °C
75 °C
14
Temperature excess boiler
heating circuits
-5 ... 20 K
0 K
16 Screed function OFF, 1, 2, 3 (only if funct. SPL = OFF)
OFF
23*
Room control P-range (K-factor)
1 ... 100 (only if Parameter 4 = RC)
8
24*
Room control Adaptation time Tn
5 ... 240 (only if Parameter 4 = RC)
35
HC-name
Heating circuit name 00000 … ZZZZZ empty
* only if remote unit is room controller (PARAMETER 04 = RC)
Level HEAT GENER.
This level contains all parameters which are necessary to program the heating generator.
PARAMETER Designation Setting range / Setting values
Fact.
setting
Individual
setting
05
Limiting mode WE-minimum temperature
1 = Minimum limitation depending on demand 2 = Limited minimum limitation 3 = Unlimited minimum limitation
1
25 Outside temperature limit OFF, -20 ... +30
OFF
31 Reset operation data SET
--
Level ALARM M ESSAGE
In this level up to 20 alarm messages can be stored, these are permanently updated.
Parameter
Designation Setting range / Setting values
Fact.
setting
Individual
setting
01 Alarm message #1
Last alarm message
02 Alarm message #2 Next to last alarm message
… …
20
Alarm message #20 First alarm message
15
ALARM 2 Level (..C..)*
In this level up to 20 alarm messages can be stored, these are permanently updated.
Parameter
Designation Setting range / Setting values
Factory
preset
Individual
setting
01 Alarm message #1
Last alarm message
02 Alarm message #2 Next to last alarm message
… …
20
Alarm message #20 First alarm message
* only in connection with a H-GEM interface and SYSTEM-parameter 28=ON
Level SENSOR CALIBRATION
In this level all sensors connected to the central control unit can be corrected by ± 5 K with respect to the factory settings.
PARAMETER Designation Setting range / Setting values
Fact.
setting
Individual
setting
01 Room sensor adaptation
- 5 K ... + 5 K
02
Outside temperature adaptation
- 5 K ... + 5 K
16
Notes
100000157 9/2009