4 | A-Series CFWH installation guide 01-18
Before installation
• Check for damage: Unpack the appliance and check for damage. DO NOT install any
damaged items.
• Check components and gas type: Check all components have been supplied and that you
have the correct gas type.
• Read these instructions: Get an overview of the steps required before starting the
installation. Failure to follow these instructions could cause a malfunction of the appliance.
This could result in serious injury and property damage.
• Applicable models: These instructions apply only to the Rinnai A-Series continuous flow
water heater models listed on the cover page of this guide.
Appliance location
This appliance is designed for outdoor
installations only. It MUST BE located above
ground in open air with natural ventilation,
without stagnant areas, where gas leakage
and products of combustion can be rapidly
dispersed by wind and natural convection.
The appliance MUST BE mounted on a vertical
structure with the water and gas connections
on the underside pointing downwards.
Location of the flue terminal MUST BE in
accordance with Section 6 and Figure 6.2 of
the AS/NZS 5601.
The appliance MUST BE placed as close
as practicable to the most frequently
used hot water outlet or outlets to reduce
the delay time for hot water delivery1. For
installations where the distance between the
water heater and the outlets is considerable,
a flow and return system can be used to
minimise the waiting time for hot water
delivery. Alternatively multiple appliances can
be strategically placed to serve outlets with
minimal delay time.
An AC 230 V, 10 A earthed power point must
be provided adjacent2 to the appliance. This
power point must be weatherproof. It must be
clear of the gas and water connections to the
appliance and also the flue exhaust and water
pressure relief valve. The power cord of the
appliance is 1.5 m long.
All appliances MUST BE installed to ensure
access can be gained without hazard or undue
difficulty for maintenance and servicing.
Sufficient clearances shall allow access and
removal of all serviceable components.
Appliances should not be mounted more than
2.5 m above the ground or floor level unless
the customer can arrange permanent and safe
access, or can provide another means of safe
access.
Horizontal obstructions
AS/NZS 5601 states a minimum horizontal
clearance of 500 mm between a building
structure and obstruction facing the terminal.
At 500 mm the obstruction needs to be the
full height of the unit (as shown), and not a
partial obstruction. A partial obstruction of
less than 1 m could result in wind pushing the
flue gases back into the flue terminal.
500 mm
At 500 mm the obstruction
needs to be the full height of
the unit.
500 mm
DO NOT
1
Rinnai recommend a maximum pipe run of 10 m.
2
Power point can be within the pipe cover if a pipe cover is installed—must comply with AS/NZS Wiring rules