Rinnai R85i Installation Instructions Manual

* For clearances not specified in ANSI Z223.1 / NFPA 54 or CAN/CGA­B149, please use clearances in accordance with local installation codes and the requirement of the gas supplier. ** 4 feet for units other than Direct-Vent Appliance.
1
10) Thread the cable through the access hole at the base of the unit and connect the wires to the controller terminals on the right hand side bottom of the PCB.
11) Secure the controller cable using the clamp provided.
12) Replace plastic cover over PCB and then replace the front cover of the Rinnai Water Heater.
Suggested temperatures are:
Kitchen 120°F - 130°F, Shower 98°F - 110°F, Bath fill 102°F - 114°F These temperatures are suggestions only. You may find higher or lower temperatures more comfortable. Maintaining lower temperatures helps save energy. To obtain water temperatures lower than 98°F, simply add cold water. Deluxe Controllers are an optional extra. ‘Controller’ and ‘Deluxe’ Controllers can be installed together. Controllers allow temperature selection only. ‘Deluxe’ Controllers have temperature selection, bath fill and clock functions. Controllers allow the water temperature to be set from the various locations where they are installed. The temperature selected will be available to all outlets. Below are the combination of Controllers that are offered by Rinnai:
Controllers Combination Pattern
**See controller manual in controller carton box for more infomation detail.
Water Smart / Bath Fill Temperature Table
2
The vent pipe has a negative slope/grade to the outside of three degrees (3°) or 5/8" per foot of vent pipe. If the vent pipe is sloped back towards the appliance as some code may require, provisions SHALL be made to collect all condensation to drain off and away from the appliance to a proper drain source. See local code for details.
 □ You have no more than three bends in your vent system and the length
does not exceed Rinnai specifications.
Thesettingsbelow arefactorydefault settings.Pleaseensure themodel numberand gastype oftheunityouhave, matchesthe modelnumber and gas type listed below; before settings any switches. If youneed assistance,contactRinnaiat(800)621-9419beforeproceeding.
WARNING
In appropriate Dip Switch setting can damage the Rinnai water heater and may void the warranty of this unit
9. Set the Infinity to ‘Forced Low’ combustion by setting No.7 dip switch of the (SW1) set of dip switches to ‘ON’.(Fig.3).
10. Check the burner test point pressure.
11. Remove rubber access plug and adjust the regulator screw on the modulating valve (Fig.4) as required in Table 1. Replace rubber access plug.
12. Set the Rinnai Water Heater to ‘Forced High’ combustion by setting both No. 7 and No. 8 dip switches of the bottom (SW1) set to ‘ON’. (Fig.5). Ensure maximum water flow !
13. Check the burner test point pressure.
14. Adjust the high pressure Potentiometer (POT) on the Printed Circuit Board (PCB) as required to the pressure shown in Table 1.
IMPORTANT: Set dip switches 7 and 8 on the bottom (SW1) to ‘OFF’ to return the appliance to 'Normal' combustion. (Fig. 6).
15. Close hot water tap.
16. Turn ‘OFF’ the gas supply and 120V power supply.
17. Remove pressure gauge & replacing sealing screw.
18. Turn ‘ON’ the gas supply and 120V power supply.
19. Operate unit and check for gas leaks at test point.
20. Replace the front cover of the appliance.
3
4
Top of Heater Back of Heater Front of Heater Sides of Heater Floor Vent/Air Intake
6 inches 0 inch 6 inches 2 inches 12 inches 0 inch
INSTALLER'S INSTALLATION INSTRUCTIONS
Remote Controllers- General
The remote controls for the Rinnai Water Heater allow the customer to control the functions of the water heater and to diagnose certain fault conditions.
Before installing the remote controllers, determine the most convenient location(s). When deciding on the best location for the remote controllers, please consider the following items:
1) Place the controllers out of reach of small children.
2) Avoid locations where the controller(s) will become hot. (over the stove, near the oven or a radiant heater.
3) Avoid direct sunlight. (The digital monitor can be difficult to read in direct sunlight)
4) Avoid areas where the remote can be splashed with cooking water, oil or sauce.
5) The remote controller cables carry low voltage, 12VDC digital.
The controllers can be wired in series or in parallel depending on the distance from the Rinnai Water Heater to the controllers.
Every installation is different
REMOTE CONTROLLER OPERATION
GENERAL CONTROLLER INFORMATION
DIAGNOSTIC USE OF CONTROLLER
1. To Display Maintenance Codes: Press ‘On/Off’ button. To sequence through stored maintenance codes, press ‘On/Off’ followed by the thermostat button.
2. To Display Water Flow through water heater: Press thermostat button, hold for 2 seconds and simultaneously press ‘On/Off’ button.
3. To display Outlet Water Temperature: Press ‘thermostat button’, hold for 2 seconds and simultaneously press ‘On/Off’ button.
TO CHANGE TEMPERATURES FROM °F to °C
1. Press and hold ‘On/Off’ button for 5 seconds while water heater is OFF.
2. To change back from °C to °F, please repeat step 1.
MUTE
To eliminate the beeping sound, press and hold and button simultaneously until a ‘beep’ is heard (approximately 5 seconds).
Temperature controllers allows precise temperature control by the user. When used correctly, the hot water unit will deliver the selected temperature, even when the water flow is varied, or more than one tap is in use. Each Temperature Controller can be individually programmed, however the water heater unit can only deliver one set temperature at any time. The available temperatures (°F) are as follows:
Temperature Table by Models
□▲
□▲
□▼
□▲ □▼
GAS PRESSURE SETTING AND DIAGNOSTICS
INFORMATION
NOTE: For additional installation and commissioning information refer to Operation / Installation Manual
APPLIANCE OPERATING PRESSURES
COMMISSIONING
With all gas appliances in operation at maximum gas rate, the flowing inlet pressure at the incoming test point on the Rinnai Water Heater should read 6"W.C. - 10.5"W.C. on Natural Gas and 10"W.C. - 13.5"W.C. on Propane Gas. If the pressure is lower, the gas supply is inadequate and the appliance unit will not operate to specification. Check gas meter, regulator and pipework for correct operation/sizing and rectify as required.
GAS PRESSURE SETTING
(Ensure gas pressure check under Commissioning above has been completed first !) The regulator is electronically controlled and factory pre-set. Under
normal circumstances it does not require adjustment during installation. Make adjustments only if the unit is not operating correctly and all other possible causes for incorrect operation have been eliminated.
1. Turn ‘OFF’ the gas supply.
2. Turn ‘OFF’ 120V power supply.
3. Remove the front cover from the appliance.
4. Check gas type switches (Fig.1) are in the correct position (dip switch 1 of SW2 ‘ON’ = NG, ‘OFF’ = LPG)
Note: ‘ON’ towards front, ‘OFF’ towards rear.
5. Attach pressure gauge to burner test point, located on the gas control. (Fig.2).
6. Turn ‘ON’ the gas supply.
7. Turn ‘ON’ 120V power supply.
8. If remote controllers are fitted, turn the unit ‘ON’ at the kitchen controller, select the maximum delivery temperature and open all available hot water taps full including the shower. (CAUTION: Ensure building occupants do not have access to hot water outlets during this procedure).
THIS APPLIANCE MUST BE INSTALLED, SERVICED
AND REMOVED BY AN AUTHORISED PERSON
DURING PRESSURE TESTING OF THE CONSUMER PIPING
ENSURE GAS COCK SITUATED BEFORE UNIT IS SHUT-OFF.
FAILURE TO DO SO MAY RESULT IN SERIOUS
DAMAGE TO THE APPLIANCE AND POSSIBLE INJURY.
WARNING
Nat.G Prop.G Nat.G Prop.G Nat.G Prop.G
REU-V2532FFUD REU-V2532FFUCD REU-V2520FFUD REU-V2520FFUCD
150PSI
6"W.C.
10.5"W.C.
10"W.C.
13.5"W.C.
0.77"W.C. 0.93"W.C.
3.7"W.C. 4.2"W.C.
Table 1.
Water
Inlet Min.
Gas Inlet
Min./ Max.
Forced Low Forced High
No code or
blank
display
Nothing happens when water
flows through water heater.
Clean inlet filter screen and ensure you have at least the minimum flow rate required to fire unit. Check for pipe dope inside water flow control turbine. On new installations, ensure hot and cold water lines are not crossed. Check for bleed over. Isolate unit from building by turning off hot water line to building. Then open your pressure relief valve, if unit fires, thereís a bleed over in your plumbing. If a circulating system is in use, it must be isolated also.
Remote control does not light up but you have 12 VDC at the terminals for controls: Disconnect water flow control motor, then turn on hot water, if unit fires replace water flow control assembly.
Code
Displayed
00
Fault
When checking maintenance code history,
“00” is substituted for “LC”
Build up of lime scale in heat exchanger - needs to be flushed.
03
Power interruption during Water Smart/Bath Fill
(Hot water will not flow when power returns)
Turn off all hot water taps. Press ON/OFF twice.
33
Heat exchanger outlet water temperature
faulty
Check H.E. outlet sensor or wiring. Measure resistance of sensor. Clean sensor of scale build-up
34 52
Modulating Solenoid Valve signal abnormal
Check gas control wiring harness and measure resistance of valve coil in ohms.
61
Combustion Fan Failure
Combustion fan or wiring harness faulty. Make sure motor/fan turns freely. Measure resistance of motor winding.
71
SV0, SV1, SV2 or SV3
Solenoid Valve Circuit Faulty
Check all gas solenoid wiring harness and connections. Measure resistance of each solenoid valve coil.
LC Scale build-up in Heat Exchanger
Build up of lime scale in heat exchanger ñ needs to be flushed.
02
No burner operation during freeze
protection mode
Verify that gas supply is turned on to the water heater and valve at meter or tank is open. Verify proper gas type and supply pressure. Bleed air from gas line. Verify all ignition component/wires are connected.
10
Air intake supply or exhaust blockage
Check for a restriction in exhaust or intake vent, verify proper dip switch settings. Ensure only Rinnai approved venting components are used.
14
Thermal Fuse
Ensure high and low fire manifold gas pressures are properly set. Verify dip switch settings are correct. Measure resistance in ohms of safety circuit.
11 No Ignition
Verify that gas supply is turned on to the water heater and at meter or tank. Verify proper gas type and supply pressure. Bleed air from gas line. Verify all ignition component/wires are connected.
32
Outlet water temperature sensor reading
out of expected range
Check outlet temperature sensor or wiring for damage. Measure resistance of sensor. Clean sensor of scale build ­up.
65
Water Flow Servo Faulty
(Does not stop flow properly)
Water Flow Servo or wiring faulty. Check Water Flow Servo wiring harness conection. Measure resistance of Water Flow Servo wiring.
16 Over Temperature Warning
Verify dip switch settings, check manifold pressure and verify gas type for water heater. Check for clogged heat exchanger. Check for low water flow in a circulating system causing short-cycling.
72 Flame Sensing Device Faulty
Check flame rod and wiring harness connections. Measure micro amp output of sensor circuit with flame present. Clean flame sensor of any build-up. Check for debris in burner chamber that may block flame from sensor.
12 Flame Failure, poor ground connection
Make sure gas is turned on at the water heater; check for obstructions in exhaust vent. Ensure only Rinnai approved venting components are used. Verify proper grounding. Check for debris or moisture in burner area.
Items to Inspect
INSTALLER'S INSTALLATION INSTRUCTIONS
-Warnings-
This manual must be followed exactly.
The Rinnai Water Heater is not suitable for use in pool or spa applications. Installer must install a Pressure relief valve. Pipe pressure relief discharge to
a drain or outside environment.
Maintain proper space around the unit for proper servicing and operation. Minimum clearances from combustible materials are listed below.
RECOMMENDED VENT/AIR INTAKE TERMINAL POSITION
Terminals should be so positioned as to avoid products of combustion entering openings into buildings or other flues or vents.
REF
U.S. Installations
Candadian Installations
DESCRIPTION
K 3 feet 6 feetClearance to a forced air inlet into a building
N 2 feet 2 feetVent FIue from wall (FIat or Pitched Roof)
P 1 foot 1 footClearance between two vertical flue on the same pIane Q 1 foot 1 footHorizontal between two terminals on the same wall
S 4 feet 4 feetClearance from terminal facing a terminal
R 5 feet 5 feet
Clearance between two Vertical flue on pitched roof above each other
O 5 feet 5 feet
Vertical between two terminals on the same wall above each other
M
3 feet 3 feetClearance under deck, veranda, porch, or balcony
(open on 3 sides)
L * 7 feet
Clearance above paved sidewalk or paved driveway located on public property
J **1 foot 1 foot
Clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliance
INSTALLER'S INSTALLATION INSTRUCTIONS
Locating the vent terminal
REF
U.S. Installations
Canadian
Installations
DESCRIPTION
A 1 foot 1 footClearance above grade, veranda, porch, deck, or balcony B **1 foot 1 foot
**
Clearance to window or door that may be opened C Clearance to permanently closed window D 3 feet 3 feetVertical clearance to ventilated soffit, eaves or overhang E 3 feet 3 feetClearance to unventilated soffit, eaves or overhang F 1 foot 1 footClearance to outside corner G 2 feet 2 feetCIearance to inside corner
I * 3 feetClearance to service regulator vent outlet
H
*
3 feet within a height
15 feet. above the
meter/reguIator
assembly
Clearance to each side of center line extended above
meter/regulator assembly
INSTALLER'S INSTALLATION INSTRUCTIONS
Remote Controllers - Installation
1) Determine a suitable location for the controller.
2) Make three holes on the wall as shown.
3) Run the cable between the controller and the Rinnai Water Heater or the controller and the other controller.
4) Remove the face plate from the remote controller.
5) Connect the cable to the remote controller.
6) Mount the controller to the wall using the holes drilled in step 2.
7) Disconnect the power from the Rinnai Water Heater.
8) Remove the cover of the Rinnai Water Heater.
9) Remove the plastic cover from the PCB and electrical connections. DO NOT ATTEMPT TO CONNECT THE REMOTE CONTROLLERS WITH THE POWER ON, THERE'S 120 VOLT POTENTIAL, NEXT TO THE REMOTE CONTROLLER CONNECTIONS INSIDE THE UNIT. All service and wiring should be performed by a certified installer.
1
11 32
"
3
5 16
"
model
REU-V2532FFUD REU-V2520FFUD(°F)
REU-V2520FFUCD(°F)
REU-V2532FFUCD(°F)
9898100
100
102
102
104
104
106
106
108
108
110
110
115
115
120
120
120
125
125
125
130
130
130
135
135
135
140
140
140
150
150
160
160
185
Approx. temperature(°C)
37 38 39 40 41 42 43 46 49 52 54 57 60 66 71 85
185
temperature
water smart/ bath fill temperature (°F)
Approx. temperature (°C)
49
120481184711646114441124311042108411064010439102381003798
temperature
1 +
+ + + + +
+ + + + + +
+ + + + + +
MC-91-1US MC-91-1US MC-91-1US MC-91-1US MC-91-1US MC-91-1US MC-91-1US BC-100V MC-100V
MC-100V
MC-91-1US **MC-91-1US
MC-91-1US
BC-100V
MC-91-1US
MC-91-1US
MC-91-1US2 3 4 5 6
Remote and Deluxe Controllers
(M) Water Flow Control Device Servo or Geared Motor:
NOTE: The grey wire listed above turns to black at B connector on the PCB, the orange wire turns to red. (QS) Water Flow Sensor:
By-pass Flow Control: (REU-V2532FFU/FFUC ONLY)
(IG) Ignition System:
(FM) Combustion Fan Motor:
Set your meter to the hertz scale. Reading across the red and yellow wires at terminals 2 and 3 you should read between 60 and 350 hertz.
Thermal Fuse:
Overheat Switch:
Flame Rod:
Place one lead of your meter to the flame rod and the other to earth or ground. With the unit running you should read between 5 ~ 150 VAC. Set your meter to the µ amp scale, series your meter in line with the flame rod. You should read 1µ or greater for proper flame circuit. In the event of low flame circuit remove the flame rod and check for carbon and/or damage.
Heat Exchanger, Air Temperature, and Outgoing Water Temperature Thermistors:
Check all thermistors by inserting meter leads into each end of the thermistor plug. Set your meter to the 20K scale and read resistance. You should be able to apply heat to the thermistor bulb and see the resistance decrease. Then apply some ice to the thermistor and the resistance should increase. See below for examples of temperatures and resistance reading at those temperatures.
Example: 59°F = 11.4 ~ 14K 86°F = 6.4 ~ 7.8K 113°F = 3.6 ~ 4.5K 140°F = 2.2 ~ 2.7K 221°F = 0.6 ~ 0.8K
Outgoing Water Thermistor:
Heat Exchanger Temperature Thermistor:
Surge Protector:
With the power off you can check the continuity through the surge protector. Place one meter lead on the top pin #1 of the surge protector and pin #2 on the bottom of the surge protector. Then check across top pin #3 and bottom pin #1, if you read continuity across these two points the surge protector is good. If you do not get continuity, replace the surge protector.
Remote Controls:
Frost Protection:
This unit has four frost protection heaters mounted at different points inside the unit, to protect the water heater from freeze ups. There are two heaters located on the outlet hot water line next to the thermistor. Using a voltage meter set on the 200 ohm scale, you should have a resistance reading of 26 ~ 30 ohms through each of these heaters. The heater located on the heat exchanger piping should have a resistance reading of 81 ~ 86 ohms and the one located in the water flow sensor valve has a resistance reading of 16 ~ 19 ohms. Voltage throughout this circuit should be 120 VAC.
Amp Fuses:
This unit has two inline (3) amp glass fuses. Remove the fuse and check continuity through it. If you have Continuity through the fuse, it is good. If you can not read continuity, the fuse is blown and must be replaced.
SERVICEMAN'S TROUBLESHOOTING INFORMATION
for the RINNAI WATER HEATERS
IMPORTANT SAFETY NOTES:
There are a number of (live) tests that are required when fault finding this product. Extreme care should be used at all times to avoid contact with energized components inside the water heater. Only trained and qualified service agencies should attempt to repair this product. Remember, before checking for resistance readings, you should disconnect the power source to the unit and isolate the item to be checked from the circuit (unplug it).
(TR) Transformer:
(SV1, SV2, SV3 and POV) Gas valve and Modulating solenoids: (Set meter above 2K)
Wire color Black ~ White Blue ~ Brown
Voltage 90 ~ 100 VAC 108 ~ 132 VAC
Resistance 51 ~ 63 ohms 51 ~ 63 ohms
Connector # F9 F7
Pin #'s 1 ~ 2 1 ~ 3
Red ~ Black White ~ Black Yellow ~ Black
6 ~ 45 VDC 5 ~ 10 VDC 11 ~ 13 VDC
N/A
9.2K ~ 9.4K
3.5K ~ 3.9K
A1 A1 A1
1 ~ 2 2 ~ 4 2 ~ 3
(Main) Pink ~ Black (SV1) Black ~ Yellow (SV2) Black ~ Blue
80 ~ 100 VDC 80 ~ 100 VDC 80 ~ 100 VDC
1.7K ~ 2K ohms
1.7K ~ 2K ohms
1.7K ~ 2K ohms
E1 E2 E3
1 ~ 2 2 ~ 3
2 ~ 4 (SV3) Black ~ Brown 80 ~ 100 VDC 1.7K ~ 2K ohms E4 2 ~ 5 (POV) Pink ~ Pink 2 ~ 15 VDC 67 ~ 81 ohms C2 3 ~ 4
Grey ~ Grey 90 ~ 100 VAC N/A A1 1 ~ 2
Red ~ Red 12 VDC Below 1 ohm B ~ C B6 ~ C1
Red ~ Red 12 VDC Below 1 ohm B ~ C B6 ~ C1
White ~ White N/A See example above B B3 ~ B4
White ~ White N/A See example above B B3 ~ B12
Terminals D1, D2 10 ~ 13 VDC digital 1.5K ~ 1.9K ohms H 1 ~ 3
Black ~ White Blue ~ Brown
108 ~ 132 VAC 108 ~ 132 VAC
N/A N/A
Surge Protector D1 Surge Protector D2
1 ~ 3 1 ~ 2
Brown ~ White Orange ~ White Yellow ~ White Red ~ White/ Ground
2 ~ 6 VDC
Unit in operating mode
15 ~ 35K
G4 ~ G5 G2 ~ G5
4 ~ 5
2 ~ 5 G1 ~ G5 G3 ~ G5
1 ~ 5
3 ~ 5
Red ~ Blue Grey ~ Brown Grey ~ Yellow
11 ~ 13 VDC 4 ~ 6 VDC N / A
22 ~ 26 ohms N / A N / A
B2 B2 B2
9 ~ 10
5 ~ 7
Black ~ Red Yellow ~ Black
11 ~ 13 VDC 4 ~ 7 VDC
5.5K ~ 6.2K 1 meg ~ 1.4 megB4B4
5 ~ 6
1 ~ 5
5 ~ 8
Grey ~ Orange 11 ~ 14 VDC N / A B2 5 ~ 6
REU-V2532FFUD-US REU-V2532FFUCD-US REU-V2520FFUD-US REU-V2520FFUCD-US 
U245-3245(00)
In Use Indicator
Indicates that a hot water tap is open and that control of the temperature has been taken at another controller.
Digital Monitor
Indicates the selected water temperature. Error messages flash in the event of a failure.
Thermostat
Increases or decreases the desired water temperature.
Priority Indicator
Indicates whether this controller has priority control over the water temperature
Priority
Pressing takes control of the water temperature by this controller.
ON/OFF
Used to switch the water heater on and off
Attention Installer! - Have You Checked Everything?
For full details - Always Refer to Rinnai Installation Instructions
HOT (outlet) and COLD (inlet) water lines are not crossed to the unit and are leak free.
 □ You have installed isolating valves, unions, and drain down vales on the
cold water inlet line and hot water outlet lines. (These components are used for servicing and/or removing the appliance quickly).
 □ COLD water inlet filter was cleaned after installation. (The filter MUST
be cleaned after installing the unit)
 □ A pressure relief valve is installed and is rated for 200,000 Btu's at 150
PSI per local code.
 □ 120 VOLTS A.C. is connected to the unit, it is properly GROUNDED
and circuit is turned on.
 □ Gas supply system is properly sized. All gas meters, regulators, gas
line types, tanks, etc. have a BTU value. Please confirm that all components meet the gas requirements at this location. Verify the system is functioning correctly by connecting your manometer to the gas pressure test port on the Rinnai unit. Operate all gas appliances in the facility. The inlet gas pressure must not drop below that listed in the ownerís manual specification sheet or appliance rating plate.
Proper gas type and pressure is supplied to the unit. (See owner's manual for correct inlet gas pressures in the specification section. Normal inlet gas pressures are 7" to 10" of water column for natural gas, and 11" to 13" of water column for propane gas).
Gas supply pipe is purged of foreign material before connection.  □ Proper model controllers are used, connected and functioning.  □ Instructed the customer how to operate the Controllers.  □ Verify proper clearances around the unit and all vents and air intakes.
(See owner's manual for all clearance requirements.)
 □ Explained to the customer to never store anything around the vent
terminals or block the air and/or exhaust ports to the unit.
For Internal models only
 □ Ensure you used the proper venting materials for the unit you have
installed.
Rinnai Water Heaters
Dip Switch Default Settings
Fig. 3
Fig. 5 Fig. 6
ON
ON
SW1
ON
SW1
Fig. 2Fig. 1
Fig. 4
Regulator adjustment screw access plug
Burner test point
GAS
COLD water inlet filter
inlet GAS test port
WATER INLET
(COLD)
WATER OUTLET
(HOT)
CLAMP
REMOTE CONTROL CABLE
REMOTE CONTROL CONNECTION TERMINALS
Water Smart / Bath Fill temperature cannot exceed 120°F for the following commercial models with no by-pass : REU-V2520FFUCD
◆REU−V2532FFUD
◆REU−V2532FFUCD
NAT.GLPG LPG NAT.G NAT.GLPG LPG NAT.G
◆REU−V2520FFUD
◆REU−V2520FFUCD
Residential Units Commercial Units
Dip Switch Settings Dip Switch Settings
Residential Units
Dip Switch Settings
Commercial Units
Dip Switch Settings
1
O F F
2 3 4 5 6 7 8
ON
→
O F F
2 3 4
1
→
ON
1
O F F
2 3 4 5 6 7 8
→
ON
O F F
2 3 4
1
→
ON
1
O F F
2 3 4 5 6 7 8
→
ON
O F F
2 3 4
1
→
ON
1
O F F
2 3 4 5 6 7 8
→
ON
O F F
2 3 4
1
→
ON
1
O F F
2 3 4 5 6 7 8
ON
→
O F F
2 3 4
1
→
ON
1
O F F
2 3 4 5 6 7 8
→
ON
O F F
2 3 4
1
→
ON
1
O F F
2 3 4 5 6 7 8
→
ON
O F F
2 3 4
1
→
ON
1
O F F
2 3 4 5 6 7 8
→
ON
O F F
2 3 4
1
→
ON
Sensor or wiring faulty. Verify fan blade is mounted securely to shaft. Check for airflow restrictions in venting system.
(Indoor Units Only) Combustion air sensor
reading out of expected range
OFF/ON
Vent/air intake piping length
See Owner's manual for more in informd detail.
12345678
070 00012 31445 7
PARTS LIST
Part Number U245-3150-1 U245-3150-2 U242-111-11 U242-111-9 CF79-41020-A U245-3160 U245-107 U245-3110-3 U245-3110-4 U245-3118-2 U245-3118-1 MC-91-1US-S-FL U245-3134 U245-3121 U245-3122 AH59-772 AU169-126 AH59-772 C36E-41-S AU39-965 CU195-1866 H73-110 CH51-209 H73-112 BH51-218 B3A7-1
CH51-221 H73-115 U245-200-A U245-200-B AU155-207-2 H73-214 C10D-5 U245-260 U245-261 H73-120 AH41-216 AH66-398 AH66-393 U245-262 U242-312 AU161-665-C U245-550 U245-555 BH29-606 AU183-562 U245-560
Quantity V2532FFUD/FFUCD 1 1 1 1 1 1 1 1 1 1 2 1 1 2 4 1 1 1 1 2 1 1 1 1 1 16
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V2520FFUD/FFUCD 1 1 1 1 1 1 1 1 1 1 2 1 1 2 4 1 1 1 1 2 1 1 1 1 1 16
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
V2520FFUD/FFUCD 1 1 1 1 1 1 1 1 1 2 1
­1 1
­1 1
-
­1 1 1 1 1 1 1 1 1
­1 1 1 1 1 1 1 1 1 2 1 5 1 1 1 1 2 1 1
V2520FFUD/FFUCD 1 1 1 1 1 1 1 1 1 1 1 8 4 4 3 1 2 2 1 1 1 2 1 1 1 2 1 1 1 1 1 1
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Description Casing Assembly (Residential model) Casing Assembly (Commercial model) Wall Fitting Bracket-8 (Residential model) Wall Fitting Bracket-9 (Commercial model) Rubber Bushing Connection Reinforcement Panel Heat Protection Plate Front Panel (Residential model) Front Panel (commercial model) Front Panel Packing Front Panel Packing Side Remote Controller Remote Controller Support Plate Side Panel Side Panel Cap Quick Controller Connection Cable Seal Packing Connection Support Clip Gas Control Assembly Screw Gas Connection (3/4""NPT) Burner Unit Assembly Burner Case Front Burner Case Bottom Panel Packing Lean and Rich Bunsen Burner Assembly Burner Case Back Panel Damper Manifold Assembly -A (LPG) Manifold Assembly -B (Nat.G) Paking of Combustion Chamber Lower Packing of Combustion Chamber Screw Combustion Chamber Front Plate Assembly Combustion Chamber Front Plate Electrode Flame Rod Electrode Packing Electrode Holder Upper Packing of Combustion Chamber Tube Joint Pressure Tube Blower Motor All Assembly Fan casing Assembly Fan Connecting Bracket Fan Connecting Packing Blower Motor
Number 001 001 002 002 003 004 005 006 006 007 008 009 010 011 012 013 014 015 100 101 102 103 104 105 106 107
108 109 110 110 111 112 113 114 115 116 117 118 119 120 121 122 125 126 127 128 129
Quantity V2532FFUD/FFUCD 1 1 1 1 1 1 1 1 1 2 1 1
­1 1
­1 1 2
­1 1 1 1 1 1 1 1 1
­1 1 1 1 1 1 1 1 1 1 5 1 1 1 1 2 1 1
Part Number U245-558 U245-566 U245-255 U245-400 U245-408 U245-409 U245-567 U245-410 U245-434 U245-435 U245-419 U245-690 U245-2240 H73-501-2 M8E-15 M8E-14 M8D1-15 M6J-1-3 AH69-310 AU195-321 H73-512 H98-511 H98-510 U245-865-3 AU162-1876 AU103-413 AU142-444 H98-510-S U245-500 U245-2260 BBF9-630 U245-774 BU168-707 ET-281 U245-257 El-189 BH38-710-240 AU206-218 BH45-650 CP-90172 U217-676 U242-511 U245-620 U245-621 U245-622 CF29-742 AU111-653 AU100-721
Number 130 131 132 135 136 137 138 139 140 141 142 145 145 400 401 401 402 403 404 404 405 406 407 408 409 410 411 412 700 700 701 702 703 704 705 706 707 708 709 710 711 712 713 714 715 716 717 718
Description Bell Mouth Bellows Connecting Bracket/Intake Duct Combustion Chamber Bracket Air Inlet Box Assembly Bellows Connecting Bracket/Fan Bellows Bellows Clamping Ring Air Inlet Box Assembly Exhaust Bracket Exhaust Bracket Holder Air Inlet Box Cover Heat Exchanger Complete Assembly Heat Exchanger Complete Assembly Water Inlet (3/4""NPT) Water Flow Servo & Sensor Assembly Water Flow Servo & Sensor Assembly Rectifier By-pass Servo Assembly Stop Bracket Stop Bracket Plug Band Water Filter Assembly Filter Plug Hot Water Outlet (3/4""NPT) Stop Bracket Plug Band Small Drain Valve Water Filter All Assembly PCB PCB Surge Protector PCB Cover-Side PCB Cover-Front Transformer Assembly PCB Bracket Ignitor High Tension Cord Electrode Sleeve Thermistor Thermistor Clip Large Thermal Fuse Clip Frost Sensing Switch 120V Anti-Frost Heater Assembly Heater Connecting Harness 120V Valve Heater Assembly Anti-Frost Heater Clip Anti-Frost Heater Clip A Anti-Frost Heater Clip
Part Number BH50-730-2 BU195-1630 U245-601 U245-602 U245-603-6 U245-603-9 U245-3190 BU129-821-2 U245-3173
U242-780 ZIHD0510UK CP-30580 CF83-41430 CP-21478-412 U217-449 ZAA0408UK M10B-2-4 M10B-2-3 M10B-13-4 M10B-2-18 M10B-2-16 M10B-2-14 M10B-2-7 M10B-1-24 C36E1-6 U245-2602 PWB-261 BU195-1865 MC-91-1US MC-100V-1US BC-100V-1US 50710327 50223098B
224064 184118 224069 146141 50171948 50171960 50171953 224051 224052 224053 224063 224050 169044
Quantity V2532FFUD/FFUCD 1 1 1 1 1 1 1 1 1 1 1 8 4 4 3 1 3 2 1 1 2 2 2 1 1 2 1 1 1 1 1 1
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Description Inlet Air Thermistor Fuse Harness 100V Harness Solenoid Valve Harness Sensor Harness Sensor Harness Thermal Fuse Harness Mold-Type Over Heat Switch Remote Controller Harness Power Surprise Cable Remote Controller Cable Screw Screw Washer Screw Screw Screw O-ring O-ring O-ring O-ring O-ring O-ring O-ring O-ring Packing Owner's Manual Package Spec Sheet Manual 3/4"" gas control valve Remote Controller (include) Deluxe Controller (optional) Deluxe Bathroom Controller (optional) Horizontal Discharge Adapter Wall Discharge Terminal (for wall thicknesses from 4"" to 20"") Vertical Discharge Adapter Roof Discharge Terminal Condensate Collector Roof Flashing - Flat Roof Roof Flashing - 1/12 to 6/12 Pitch Roof Flashing - 6/12 to 12/12 Pitch Roof Flashing - 12/12 to 16/12 Pitch 10"" Pipe Extension
19.5"" Pipe Extension 39"" Pipe Extension 90 Degree Vent Pipe Elbow 45 Degree Vent Pipe Elbow Vent Pipe Clamp
Number 719 721 722 723 724 724 725 726 727 728 729 800 801 802 803 804 805 810 811 812 813 814 815 816 817 818 888
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
801
802
012
011
007
005
009
010
001 
002
800
003
006
800
004
008
006
MC-91-1US(include)
MC-100V-1US(optional)
BC-100V-1US(optional)
131
116
118
803 110
115
708
707
113 812
120
117
105 108 121
122
705
706
125
811
719
103
139
141
716 710135 709
810
138
132
726
718
717
136
712
137
142
140
141
143
104
106
112
111
109
107
119
130
126
128
127
129
711
100
401
101818
818
701
727
813
403
815
815
704
817
402
813
406
407
412
013
014
015
102
101
400
405814
700
805
804
814
409
709
810
715 408
410 816 411
702
703
404
805
725
724
709
719
709
726
713
712
715
715
727
723
722 729
727
728
721
714
724
EXPLODED VIEW - CABINET EXPLODED VIEW - INTERNALS
EXPLODED VIEW - ELECTRICALEXPLODED VIEW - INTERNALS
Loading...