Rinnai Q130SP, Q130SN, Q175CN, Q175CP, Q175SN User Manual

...
User information manual
Highefciencycondensinggasboiler
Q85SN/Q130SN/Q175SN/Q205SN/Q175CN
Q85SP/Q130SP/Q175SP/Q205SP/Q175CP
WARNING!
Installation and service must be
performedbyaqualiedinstaller,
service agency or the gas supplier.
Pictured: Q85SN, Q130SN Q85SP, Q130SP
WARNING!
Ifyoudonotfollowtheseinstructionsexactly,areor
explosion may result causing property damage, personal injury or loss of life.
- Donotstoreorusegasolineorotherammable
vapors and liquids in the vicinity of this or any other appliance.
- Do NOT try to light any appliance.
- Do NOT touch any electrical switch.
- Do NOT use any phone in your building.
- Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
- Ifyoucannotreachyourgassupplier,callthere
department.
Français: voir page 17
Address: 103 International Drive, Peachtree City, GA, 30269
Toll-free: 1-800-621-9419Fax: 678-829-1666www.rinnai.us
Notice! This manual must be retained for future reference.
8W.52.4000/11.09 Changes reserved
Contents of instructions
These instructions contain important information for the safe use of Rinnai Q-Series gas boilers. These user instructions are intended for the owner or responsible tenant of the premises where the boiler is installed.
Subject to technical changes
Changes may be made to the illustrations, process steps and technical data as a result of our policy of continuous improvement without prior notice.
Updating of documentation
Please contact us if you have any suggestions for improvements or corrections.
Find our contact details on the back of this manual.
Operating instructions Rinnai Q-Series
2
Safety and general instructions
!
!
Please observe these instructions in the interest of your own safety.
Designated use
The boiler is designed to heat water for a central heating system and, if applicable, generating domestic hot water. The boiler is delivered with a burner controller pre-installed.The boiler can be tted with a modulating outdoor reset control ARV12 (included), a room controller RS100 (optional), a zone controller (optional) or an On/Off thermostat or relay panel end switch (accessories).
Hazarddenitions
The following dened terms are used throughout
the documentation to bring attention to the presence of hazards of various risk levels. Notices give important information concerning the operation of the product.
DANGER
WARNING
!
CAUTION
NOTICE
i
DANGER: Indicates the presence of hazards that will cause severe personal injury, death or substantial property damage.
WARNING: Indicates the presence of hazards that can cause severe personal injury, death or substantial property damage.
CAUTION: Indicates presence of hazards that will or can cause minor personal injury or property damage.
NOTICE: Indicates special instructions on installation, operation or maintenance that are important but not related to personal injury or property damage.
Operating instructions Rinnai Q-Series
3
These operating instructions describe the operation of the Rinnai Q-Series condensing gas boilers. This manual is for the end user. For installation and servicing there is a installation & servicing instructions manual for the installer.
Read this manual fully before operating the boiler. In case of doubt or errors contact your installer. The manufacturer reserves the right to change
the specications and dimensions without prior
notice.
Work on the boiler must be carried out by a State licenced contractor, (Ref: Gas Safety Installation and Use) using correctly calibrated instruments
with current test certication.
Operating instructions Rinnai Q-Series
4
Safety
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING: If you do not follow these instructions
exactly, a fire or explosion may result causing
property damage, personal injury or loss of life.
A. This appliance does not have a pilot. It is equipped with an ignition device which automatically
lights the burner. Do NOT try to light the burner by hand.
B. BEFORE OPERATING smell all around the appliance area for gas. Be sure to smell next to the floor
because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
- Do NOT try to light any appliance.
- Do NOT touch any electrical switch.
- Do NOT use any phone in your building.
- Immediately call your gas supplier from a neighbor ’s phone. Follow the gas supplier’s instructions.
- If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas control knob. Never use tools.
If the knob will not push in or turn by hand, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any parts have been under water. Immediately call a qualified service
technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above this label.
2. Turn off al electrical power of the appliance.
3. Set the thermostat or other operating control to the lowest setting.
4. This appliance is equipped with an ignition device
which automatically lights the burner. Do NOT try to light the burner by hand.
5. Close main gas shut off valve.
6. Wait (5) minutes to clear out any gas. Then smell for
gas. Including near the floor. If you smell gas, STOP! Follow “B” in the safety information above on this label. If you don’t smell gas, go to the next step.
7. Open main shut off valve.
8. Set the thermostat or other operation control to desired setting.
9. Turn on all electric power to the appliance.
10. If the appliance will not operate, follow the instructions “To Turn Off Gas To Appliance” and call your service technician or gas supplier.
Manual Gas Valve (Main valve)
CLOSE
OPEN
TO TURN OFF GAS TO APPLIANCE
1. Turn off all electric power to the appliance if service is to be performed.
2. Set the thermostat or other operating control to the lowest setting.
3. Close main gas shut off valve.
8U.34.01.00 / 05.09
Operating instructions Rinnai Q-Series
5
!
DANGER
y
Should overheating occur or the gas supply fail to shut off, do not turn off or disconnect the electrical supply to the pump. Instead, shut off the gas supply at a location external to the appliance.
WARNING
!
Protection for corrosion
Do not use any sprays, chlorine containing agents, solvents, paint etc. around the boiler or around the air intake supply entrance of the boiler. These
substances have negative inuences on the boiler
and can lead to corrosion resulting in failure of the boiler.
Products to avoid present in boiler room and/or around combustion air intake
Spray cans containing chloro-/fluorcarbons Ammonium and/or ammonium solutions Permanent wave solutions Chlorinated waxes and/or cleaners Swimming pool chemicals based on chlorine Calcium chloride used for thawing Sodium chloride used for water softening Refrigerant leaks Paint or varnish removers Hydrochloric acid/muriatic acid Cements and glues Antistatic fabric softeners used in clothes dryers Chlorine-type bleaches, detergents, and cleaning solvents found in household laundry rooms
Adhesives used to fasten building products and other similar products
Areas likel
Dry cleaning/laundry areas and establishments Swimming pools Metal fabrication plants Beauty shops Refrigeration repair shops Photo processing plants Auto body shops Plastic manufacturing plants Furniture refinishing areas and establishments New building construction Remodeling areas Garages with workshops
to have contaminants
NOTICE
i
Operating instructions Rinnai Q-Series
6
Checking the water pressure
Check the water pressure in the central heating installation regularly.
Use only potable water for lling.
Additives only after clearance by Rinnai. Contact your installer in case of doubt.
Description of the boiler
The Rinnai Q boiler is a room sealed, condensing and modulating central heating boiler. The Q175C has an integrated domestic hot water feature.
The boiler is provided with a integrated control system. Because an outdoor sensor is connected to the boiler, the boiler works weather dependantly. This means that the boiler control measures the
outside temperature and ow temperature. With this data the boiler calculates the optimal ow
temperature for the installation.
When the boiler is connected to an RS100 room thermostat information can be retrieved from the boiler. For more information about the Rinnai thermostats. Please refer to the user manuals.
RS100
On the bottom left side of the front panel there is a small door. Through the transparent panel you can see the boiler status on the display. After opening
this door you will nd the function buttons.
On the following pages you will nd the explanation
of the function buttons and display messages.
Operating instructions Rinnai Q-Series
7
Explanation of the function buttons
1
3
4
5
6
Only qualied personel who are trained for
NOTICE
i
NOTICE
i
When the pump is switched on continuously it can lead to undesired heating up of the central heating system during the summer.
NOTICE
i
Operating instructions Rinnai Q-Series
8
these boilers are permitted to make alterations in the controller to chronolize the boiler to the installation.
1. Display.
See following pages for further information.
2. ON-OFF Switch
This switch turns the power supply to the boiler
3. Central Heating program button.
Switching the Central Heating on or off (Led
4. Hot Water program button.
Switching the Domestic Hot Water (DHW)
5. Pump program button.
When the pump program LED is ON, the pump
During freezing temperatures it is possible (when there is no outside sensor connected), to manually place the circulation pump in constant circulation mode, thus reducing the chance of freezing pipes (garage, attic or other cold spaces / rooms) which are sensitive to frost.
2
7
8
on or off.
on/off);
facility on or off (Led on/off);
is switched into a continuous circulation mode. When the pump mode is switched OFF, LED is off the pump is control by the boiler processor. In most situations it is best to leave the pump mode OFF and let the boiler control cycle the pump as needed.
6 Mode-button.
Only for Service personel
7 Step-button.
After briey pressing, the water pressure can
be retrieved.
After pressing for 5 seconds it switches from
the Good-state to technical read out and vice versa (see following pages);
8 Reset-button.
When a fault occurs it will be shown by the
ashing E (Error) with a number code after
which the boiler is shut down. After pressing the reset key you can try to start the boiler again. If the error message keeps occurring contact your installer.
WARNING
!
DO NOT attempt to make repairs or remove
any of the boilerpanels. Contact a qualied
service agency to make necessary repairs or adjustments.
Operating instructions Rinnai Q-Series
9
The boiler display
Two boiler displays, “Good or Technical” see below.
Good
or standard read out. During this reading the display will only show what is necessary. Under normal circumstances the display will give a Good reading. In case of a fault this will be shown with, alternate display of
Good, with an E or BL code. See further "Errors, maintenance and warranty" .
Technical
The second way is a technical read out. In normal situations the following will be shown:
• on the left the status in which the boiler is active
(see bottom of this page);
• on the right the supply temperature in °F;
• the water pressure in the installation in PSI.
When a message (E or BL code) is necessary this will be shown instead of the technical read out.
To switch over from the Good-state to the Technical read out (and vice versa):
- Press 5 sec. on the STEP-button.
0 1 2 3 4 5
6 7 8
Operating instructions Rinnai Q-Series
10
9 A
Operation indication
(in the first display position by technical read out)
No heat demand Fan pre/post purge Ignition phase Burner active on central heating Burner active on DHW Fan check Burner off when room thermostat is demanding Pump overrun phase for central heating Pump overrun phase for hot water
Burner off because of to high ow temperature
Automatic de-aeration program (Press no button for 17 min.)
Loading...
+ 22 hidden pages