Rinnai Q175C User Manual

Q175C Condensing Boiler
Standard Features
Onboard outdoor reset control system with sensor standard
Priority DHW standard (3 way valve not included)
Domestic hot water plate warming
Built in DHW 6.6 gallon indirect tank
Modulating Ceramic premix burner
5:1 turn down ratio
Spark ignition
Exceeds SCAQMD 1146.2 Low NO
Stainless Steel Water tube condensing heat exchanger
Direct Vent sealed combustion
Concentric and twin pipe venting adapters included
Approved for room and closet installations
requirements
x
SPECIFICATIONS
General Specifications
Units Water content gal 1.8 Max. supply boiler
temperature Max operating pressure psi 45 Relief valve rating MBH 375 Relief valve pressure rating psi 30 Dry weight lbs 196
°F 176
Optional Accessories
RS100 Single zone controller
Flue Gas temperature sensor
Room Air Filter
NG to LP conversion Kit
LP to NG Conversion Kit
Performance Specifications
Units Fuel Type NG/LP Input MBH 175 Heating Capacity MBH 161 AFUE (I=B=R) % 95.7 Part Load Efficiency (EN677) % 98.5 DHW flow rate 75ºF ΔT
Gpm 4.1
Min inlet gas pressure NG "W.C. 4.0" Max inlet gas pressure NG "W.C. 10.5" Min inlet gas pressure LP "W.C. 8.0" Max inlet gas pressure LP "W.C. 14.0” Max equivalent exhaust vent
length Max equivalent combustion
air vent length
Approved venting materials
Rinnai is continually updating and improving products; therefore, specifications are subject to change without prior notice. Local, state, provincial and federal codes must be adhered to prior to installation.
© 2011 Rinnai Corporation
ft 80
ft 80
Polypropylene,
Stainless Steel,
PVC, CPVC
Electrical Specifications
Units Electrical Voltage Mains V/Hz 120/60 Electrical Voltage Controls V 24 Power Consumption Max Load W 210 Power Consumption Stand by Load W 14 Recommended Circuit breaker rating A 15
Q175C SP 2/2011
DIMENSIONS
2.0”
50mm
4.7”
120mm
15”
381mm
10.2”
260mm
Q175C
inch / mm A Height 26.8 / 680 B Width 39.4 / 1000 C Depth 15.2 / 385 D Left side / vent 19.5 / 495
Center to center / vent and
E
air supply F Back / vent 10.6 / 270 G Left side / gas pipe 2.6 / 65 H Left side / supply pipe 7.3 / 185 J Left side / return pipe 17.5 / 445 K Left side / condensate pipe 20.9 / 530 L Left side / expansion pipe 23.2 / 590 N Left side / cold water pipe 34.8 / 885 O Left side / hot water pipe 37.6 / 955 P Pipe length of g 0.7 / 18 Q Pipe length of c 2 / 50 R Pipe length of e, f, k, r, and w 2.3 / 60 S Back / center of pipe c 1 / 25 T Back / Center of pipe g 1.6 / 40
Back, / center of pipe e, f, k,
U
r, and w
Pipe length vent co-axial
V
Pipe length vent parallel
4.7 / 120
2 / 50
2.6 / 65
5.8 / 147
Clearances
Minimum required
18.6”
474mm
2.1”
54mm
[5.6”
142mm
5.2”
133mm
17.2”
438mm
12”
305mm
19.7”
501mm
Rinnai Corporation • 103 International Drive • Peachtree City, GA 30269 • Toll-Free: 1-800-621-9419 • Fax: 678-364-8643 • www.rinnai.us
Top 2 / 50 10 / 250 Back 0 0 Front 6 / 150 24 / 600 Left side 2 / 50 2 / 50 Right
side Floor /
Ground Vent 0 0
clearance to combustibles and non-combustibles
inch / mm
2 / 50 2 / 50
12 / 300 30 / 762
clearances
inch / mm
Recom­mended
service
Loading...