Rinnai Prestige Close Coupled Systems Operation & Installation Manual

NOT SUITABLE AS A POOL OR SPA HEATER.
NOTE
All Rinnai gas products
are A.G.A. certified.
AS 2712
Lic No.1849
SAI Global
SAI Global
The appliance must be installed, commissioned and serviced by an authorised person in accordance with all applicable local rules and regulations.
Operation / Installation
Manual
Rinnai Prestige® Close Coupled Systems
15401022
IMPORTANT INFORMATION
Rinnai Australia - i - Solar Close Coupled Operating / Installation Manual - Issue 7 - 16/9/10
IMPORTANT INFORMATION & WARNINGS ................................................................................................2
SAFETY & REGULATORY INFORMATION .................................................................................................................. 2
SCALDS HAZARDS ..................................................................................................................................................... 3
OPERATION PRINCIPLE.............................................................................................................................................. 4
SAFETY DEVICES ........................................................................................................................................................ 5
EXCESSIVE DISCHARGE FROM SAFETY DEVICES ................................................................................................ 5
WATER TEMPERATURE .............................................................................................................................................. 6
TURNING ‘OFF’ THE WATER HEATING SYSTEM ...................................................................................................... 6
TURNING ‘ON’ THE WATER HEATING SYSTEM ........................................................................................................ 6
WATER QUALITY.......................................................................................................................................................... 6
DRAINING AND FILLING THE WATER HEATING SYSTEM........................................................................................ 6
MAINTENANCE AND REGULAR CARE ...................................................................................................................... 7
SERVICING AND REPAIR ............................................................................................................................................ 7
SAVE A SERVICE CALL ................................................................................................................................ 8
SPECIFICATIONS ........................................................................................................................................ 10
SYSTEM SPECIFICATIONS ....................................................................................................................................... 10
COLLECTOR SPECIFICATIONS................................................................................................................................ 12
GAS BOOSTER SPECIFICATIONS............................................................................................................................ 12
INSTALLATION INFORMATION.................................................................................................................. 13
REGULATIONS AND OCCUPATIONAL HEALTH AND SAFETY (OH&S).................................................................. 13
LOCATION .................................................................................................................................................................. 13
WATER PIPES ............................................................................................................................................................ 13
WATER SUPPLY ......................................................................................................................................................... 14
HOT WATER DELIVERY TEMPERATURE................................................................................................................. 14
VALVES AND FITTINGS ............................................................................................................................................. 15
SYSTEM ORIENTATION AND INCLINATION............................................................................................................. 16
ROOF MOUNTING OPTIONS .................................................................................................................................... 17
INSTALLATION OF SOLAR COLLECTORS & CYLINDERS...................................................................... 19
STANDARD INSTALLATION....................................................................................................................................... 19
ATTACHING MOUNTING RAIL TO CYLINDER.......................................................................................................... 22
STANDARD INSTALLATION CONTINUED................................................................................................................. 23
ROOF PITCH GREATER THAN 30° ........................................................................................................................... 24
FRAMED INSTALLATIONS - FLAT, REVERSE AND SIDE PITCH .............................................................................25
INSTALLATION & MAINTENANCE - GAS BOOSTED SYSTEMS ............................................................. 34
GAS BOOSTER LOCATION ....................................................................................................................................... 34
GAS SUPPLY .............................................................................................................................................................. 34
HOT WATER DELIVERY TEMPERATURE................................................................................................................. 34
SMARTSTART®.......................................................................................................................................................... 34
CLEARANCES .................................................................................................................................................. 36
INSTALLATION PROCEDURE.................................................................................................................................... 37
FILLING THE SYSTEM ............................................................................................................................................... 38
PRE SOLAR HEATING CHECKS ............................................................................................................................... 38
SOLAR HEATING........................................................................................................................................................ 39
FINISHING THE INSTALLATION ................................................................................................................................ 39
DRAINING INSTRUCTIONS ....................................................................................................................................... 39
INSTALLATION & MAINTENANCE - ELECTRIC SYSTEMS...................................................................... 40
INSTALLATION PROCEDURE.................................................................................................................................... 40
FILLING THE SYSTEM .............................................................................................................................................. 41
PRE SOLAR HEATING CHECKS ............................................................................................................................... 42
SOLAR HEATING........................................................................................................................................................ 42
FINISHING THE INSTALLATION ................................................................................................................................ 42
DRAINING INSTRUCTIONS ....................................................................................................................................... 42
CONTACT INFORMATION........................................................................................................................... 45
TABLE OF CONTENTS
Rinnai Australia - 2 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
IMPORTANT INFORMATION & WARNINGS
SAFETY & REGULATORY INFORMATION
DO NOT operate this system before reading the manufacturers instructions.
This appliance must be installed, commissioned and serviced by an authorised person in accordance with all applicable local rules and regulations.
Access covers of water heating system components will expose 240V wiring and MUST be removed by an authorised person.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
For continued safety of this appliance it must be installed, operated and maintained in accordance with the manufacturers instructions.
Children should be supervised to ensure they DO NOT play with the appliance.
Any power leads from the water heater system components MUST BE plugged into an external weatherproof electrical outlet. If the power supply cord of any water heating components is damaged, it MUST BE replaced by an authorised person in order to avoid a hazard, using genuine replacement parts available from Rinnai. Take care not to touch the power plugs with wet hands.
Care should be taken not to touch the pipe work as it may be HOT! The pipes between the solar collectors and storage cylinder MUST BE copper, or alternative material pipes that may be supplied by Rinnai. Plastic pipe is NOT suited to the water temperatures and pressures that may occur in the system.
DO NOT place articles on or against this appliance.
DO NOT store chemicals or flammable materials near this appliance.
DO NOT operate with collectors or covers removed from this appliance.
DO NOT activate pump unless cylinder is full of water.
NEVER use a flammable spray such as hair spray, lacquer, paint, etc near this unit as this may cause a fire.
NOTICE TO VICTORIAN CONSUMERS
This appliance must be installed by a person licensed with the Plumbing Industry Commission.
Only a licensed person will have insurance protecting their workmanship.
So make sure you use a licensed person to install this appliance and ask for your Compliance Certificate.
For Further information contact the Plumbing Industry Commission on 1800 015 129.
WARNING
Rinnai Australia - 3 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
IMPORTANT INFORMATION & WARNINGS
SCALDS HAZARDS
HOT WATER CAN CAUSE SCALDS.
CHILDREN, DISABLED, ELDERLY AND THE INFIRM ARE AT THE HIGHEST RISK OF BEING SCALDED.
FEEL WATER TEMPERATURE BEFORE BATHING OR SHOWERING.
SCALDS FROM HOT WATER TAPS CAN RESULT IN SEVERE INJURIES TO YOUNG CHILDREN.
SCALDS OCCUR WHEN CHILDREN ARE EXPOSED DIRECTLY TO HOT WATER WHEN THEY ARE PLACED INTO A BATH WHICH IS TOO HOT.
ALWAYS......
Test the temperature of the water with your elbow before placing your child in the bath, also carefully feel water before bathing or showering yourself.
Supervise children whenever they are in the bathroom.
Make sure that the hot water tap is turned off tightly.
CONSIDER.....
Installing child proof tap covers or child resistant taps (both approaches will prevent a small hand being able to turn on the tap).
Installing tempering valves or thermostatic mixing valves which reduce the hot water temperature delivered to the taps. Your local plumbing authority may already require that these be fitted. Contact your installer or local plumbing authority if in doubt.
NEVER…..
Leave a toddler in the care of another child. They may not understand the need to have the water temperature set at a safe level.
Rinnai Australia - 4 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
IMPORTANT INFORMATION & WARNINGS
OPERATION PRINCIPLE
Close Coupled systems are designed to have the solar collectors on the roof and the storage cylinder above the collectors, all mounted using available mounting brackets. Electric and Gas boosted models are available. The system comprises of a hot water storage cylinder and solar collectors. The Close Coupled Solar System uses thermo-syphoning principle to circulate the water through the collectors and then to the storage cylinder without the need for a pump.
Supplementary heating is provided if insufficient heat is available from sun (such as during cloudy or rainy weather or during winter months) either via an electric heating element located inside the storage cylinder or via a Gas booster located external to the storage cylinder. The following diagrams illustrates the Close Coupled Solar Hot Water System set up for both the Electric and Gas boosting.
Figure 1. Close Coupled Gas Boosted Solar Hot Water Systems
Figure 2. Close Coupled Electric Boosted Solar Hot Water Systems
COLLECTORS
STORAGE CYLINDER
COLD WATER SUPPLY
HOT WATER DELIVERY
GAS SUPPLY
GAS BOOSTER
HOT WATER DELIVERY
COLLECTORS
STORAGE CYLINDER
COLD WATER SUPPLY
Rinnai Australia - 5 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
IMPORTANT INFORMATION & WARNINGS
SAFETY DEVICES
The water heating system is supplied with various safety devices including temperature sensors, overheat sensors and switches and a Pressure & Temperature Relief (PTR) valve. These devices must not be tampered with or removed. The water heating system must not be operated unless each of these devices is fitted and is in working order.
EXCESSIVE DISCHARGE FROM SAFETY DEVICES
Pressure & Temperature Relief (PTR) Valve
It is normal and desirable that this valve allows a small quantity of water to be discharged during the heating cycle. If it discharges more than a bucket of water during a 24 hour period or discharges continuously there may be another problem.
If the valve dribbles continuously, try easing the valve gear for a few seconds as described above. This may dislodge any foreign matter and alleviate the problem.
If the valve discharges at high flows, especially at night, it may be as a result of the water pressure exceeding the design pressure of the water heater. Ask your installer to fit a Pressure Limiting Valve (PLV).
Expansion Control Valve (ECV) - if fitted
It is normal and desirable that this valve allows a small quantity of water to be discharged during the heating cycle. If it discharges more than a bucket of water during a 24 hour period or discharges continuously there may be another problem.
If the valve leaks continuously, try easing the valve gear for a few seconds. This may dislodge any foreign matter and alleviate the problem. If this does not alleviate the problem contact Rinnai.
Operate the easing gear regularly to remove any lime deposits and to verify that it is not blocked.
DO NOT tamper with or remove safety devices.
DO NOT operate the water heater unless all safety devices are fitted and in working order.
DO NOT block or seal the PTR Valve and drain pipe.
Pressure & Temperature Relief (PTR) Valve
This valve is located near the top of the water heater and is essential for safe operation. It is normal for the valve to release a small quantity of water through the drain line during heating.
However, continuous leakage of water from the valve and its drain line may indicate a problem with the water heater.
Never block the outlet of the PTR valve or it’s drain line for any reason. The easing gear must be operated at least every 6 months to remove lime deposits and verify that it is not blocked. Failure to do this may result in the water heater failing.
If the valve does not discharge water when the easing gear lever is opened, or does not seal again when the easing gear is closed, attendance by an authorised person must be arranged without delay. The PTR valve is not serviceable.
NEVER replace the PTR valve with one which has a higher pressure rating than is specified for your water heater.
WARNING
Twist cap until water flows from drain line
Lift lever until water flows from drain line (Lower lever gently!)
WARNING
WARNING
Rinnai Australia - 6 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
IMPORTANT INFORMATION & WARNINGS
Gas boosted models
Do not touch the flue outlet or do not insert any objects into the flue outlet.
Keep flammable materials, spray cans, fuel containers, trees, shrubs and pool chemicals etc. well clear of the flue outlet.
Do not use the gas types other than those designated on the data plate. For example, do not use Propane/Butane gas mixtures on appliances marked Propane Gas.
Do not use Propane gas on appliances marked as Natural gas and vice versa.
WATER TEMPERATURE
The water gets heated by the solar energy contributed from the sun and heats the water until the water at the base of the storage cylinder reaches approximately 65°C. At this time water at the hot outlet can be up to 88°C. Continued heating is prevented by the ‘No Load’ protection, a Thermo-arrestor (TA) valve that prevents water passing from the cylinder to the collectors. During periods of low solar gain, supplementary heating occurs to a minimum of 60°C as required.
TURNING ‘OFF’ THE WATER HEATING SYSTEM
If you plan to be away for only a few nights, we suggest you leave the water heating system switched on. If it is necessary to switch off the water heater, do so as outlined below:
Electric Boosted systems
Switch off the electric supply to the supplementary heating element. The switch is usually marked and
located in the electricity meter box of the dwelling.
Switch off the electric supply to the solar controller and pump.
Gas Boosted systems
Switch off the electric supply to the gas booster.
Switch off the electric supply to the solar controller and pump.
TURNING ‘ON’ THE WATER HEATING SYSTEM
Electric Boosted system
Switch on the electric supply to the supplementary heating element(s). The switch is usually marked and
located in the electricity meter box of the dwelling.
Switch on the electric supply to the solar controller pump. Electric and solar water heating will now occur as
required. It may take a number of hours before hot water is available.
Gas Boosted systems
Switch on the electric supply to the gas booster.
Switch on the electric supply to the solar controller and pump. Solar water heating will now occur. Hot
water is available immediately from the gas booster when hot water tap is opened, irrespective of solar heat gain.
WATER QUALITY
The water quality of most public supplies is suitable for the water heating system. The water quality from bore wells is generally unsuitable for the water heating system. Refer to separate 'Warranty Terms and Conditions' document for water quality parameters and how they affect the warranty conditions. If in doubt about the water quality, have it checked against the parameters listed in the warranty conditions. The system is not suitable as a pool or spa heater.
DRAINING AND FILLING THE WATER HEATING SYSTEM
Draining or filling normally occur only during installation or servicing and must be carried out by an
authorised person.
To meet Australian regulatory requirements, supplementary heating temperature settings must be at least 60°C.
HOT!
IMPORTANT
Rinnai Australia - 7 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
MAINTENANCE AND REGULAR CARE
Operate the easing gear of the PTR as described under “SAFETY DEVICES” on page 5.
The overflow tray (supplied by installer) and drain underneath the storage cylinder (if fitted) should be periodically checked to ensure there are no blockages.
SERVICING AND REPAIR
Our Servicing network personnel are fully trained and equipped to give the best service on your appliance. If your appliance needs service, ring one of the service contact numbers on the back of this booklet.
It is recommended that the system be serviced at least every 5 years.
The pressure and temperature relief valve and expansion control valve must be checked for performance or replaced by an authorised person at intervals not exceeding 5 years or more frequently in areas where the water is classified as scaling water (refer to ‘Warranty Terms and Conditions’ document - ‘Water Quality’).
If the electric conduit, power supply cord or plug to the water heater is damaged, they must be replaced by an authorised person in order to avoid a hazard. The power supply cord and plug (if fitted) must be replaced by a genuine replacement part available from Rinnai.
IMPORTANT INFORMATION & WARNINGS
Rinnai Australia - 8 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
SAVE A SERVICE CALL
Before calling Rinnai for service, perform the fault finding steps in the Table 1. If the problem persists, contact Rinnai.
Service calls attending to any condition or fault that is not related to the Rinnai product and components may be chargeable.
Table 1 - Troubleshooting
Problem Cause Remedy
Insufficient or no hot Water Booster heating not operating
Or
Insufficient gas supply for gas boosted heating system
Electric boosted Systems:
Check to ensure the electric isolating switch(es) at the switchboard (usually marked "Hot water" or "water heater") is switched 'ON'. Check to ensure that the electric fuses for hot water at the switchboard are intact.
Gas Boosted Systems:
Check to ensure the power cord of the gas booster is plugged in and the power point switched 'ON'. Check gas is available and turned ON'. Close the hot tap and wait for 10 seconds and open it again. The hot tap must be opened enough to ensure that the flow rate is not less than 2.4 L/min. gas the gas booster burners will not light if it is less than 2.4 L/min. Check the isolation valve in the gas line is opened. If there is gas supply to other appliances in the rest of the house, try lighting another gas appliance. Refer to your plumber to ensure the gas line has been purged of air after installation.
Excessive hot water consumption
Electric Boosted Systems:
If the water goes cold, are you using more hot water than you think? Often end users are surprised at the amount of hot water used, especially when showering. If the amount of hot water used during the day exceeds the storage capacity of the cylinder, it is likely that there will be insufficient hot water. Has your plumber install water saving fixtures and/or flow control or pressure limiting valves to reduce consumption.
Gas Boosted Systems:
Insufficient flow may occur if multiple outlets are in use at the same time and exceed the rated flow capacity of the gas booster. If so, reduce the number of outlets in use. Have your plumber install water saving fixtures and/or flow control or pressure limiting valves to reduce consumption. Check correct size gas booster is fitted.
Incorrect Solar system size Do you have the correct system size and configuration for your requirements? Refer
to Rinnai literature for information.
Temperature and pressure relief valve / Expansion Control valve discharging water continuously
Pressure and Temperature Relief (PTR) valve
It is normal and desirable that this valve allows a small quantity of water to be discharged during the heating cycle. If it discharges more than a bucket of water during a 24 hour period or discharges continuously there may be another problem. If the valve dribbles continuously, try easing the valve gear for a few seconds as described under 'Regular Care'. This may dislodge any foreign matter and alleviate the problem. If the valve discharges at high flows, especially at night, it may be as a result of the water pressure exceeding the design pressure of the water heater. Ask your installer to fit a Pressure Limiting Valve (PLV).
Never replace the PTR valve with one which has a higher pressure rating than is specified for your water heater.
If the valve discharges hot water at high flows, (dumps) there may be a serious problem. Switch off the power supply in the meter box (the switch marked ‘WATER HEATER’ or ‘HOT WATER’) or the isolating switch installed near the water heater and contact Rinnai.
Insufficient or no hot Water Continued
Expansion Control Valve (ECV) - if fitted
It is normal and desirable that this valve allows a small quantity of water to be discharged during the heating cycle. If it discharges more than a bucket of water during a 24 hour period or discharges continuously there may be another problem. If the valve leaks continuously, try easing the valve gear for a few seconds as described under 'Regular Care'. This may dislodge any foreign matter and alleviate the problem. If this does not alleviate the problem contact Rinnai.
WARNING
SAVE A SERVICE CALL
Rinnai Australia - 9 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
Problem Cause Remedy
Insufficient or no hot Water continued
Booster element Thermostat Settings Electric Boosted Systems:
The end user can check the temperature of hot water delivered with a thermometer placed under the closest non tempered outlet (usually the kitchen sink).
CAUTION: Take care to avoid scalding. This test should be done early in the morning after overnight electrical boosting before any hot water is used. The temperature of the water delivered should be at least 55° C (allowing for heat losses in pipe work).
If this is not the case or the temperature needs to be increased contact Rinnai. The thermostat settings of the heating element thermostat can also be confirmed directly by a qualified person as described under 'hot water storage & delivery temperature'. The settings can be increased if required. Contact Rinnai.
Gas Boosted Systems:
The delivery temperature of gas boosted systems is normally 60 or 65°C. Iff temperatures are higher than this, the flow of water through the gas booster will reduce and may result in insufficient flow rate. The end user can check the temperature of hot water delivered with a thermometer placed under the closest outlet (usually the kitchen sink).
CAUTION: Take care to avoid scalding. If the temperature is higher than 65°C the gas booster may be preset incorrectly. Contact Rinnai.
No Water from the hot tap Restriction in the hot tap or failure of the cold water
supply to the water heater.
Check for water flow at the other taps and that the cold water isolation is fully open.
Gas Booster operating too frequently
Insufficient Sunlight - Collectors shaded Ensure the trees or other objects are not shading onto the collector surface (Trim
the trees or relocate the solar collector if the obstruction is permanent). Make sure the glass on the collector is not dirty.
High electricity or gas bill Excessive hot water consumption See entry under 'Insufficient hot water'.
Solar Control unit switched off If the solar control unit is switched off there will be no solar pre-heating of water
resulting in the water being heated entirely by electricity or gas' boosting'. Check the power outlet for the solar control unit is switched on.
Temperature and pressure relief valve / Expansion Control valve discharging water continuously
See entry under 'Insufficient hot water'.
Lack of solar gain Reduced sunlight:
Reduced sunlight due to overcast weather in summer or low solar contribution in winter will result in an increased dependence on electricity or gas boosting. Higher electricity or gas bills under these conditions, especially in winter, are normal. Collectors shaded: If the solar collectors are shaded by trees or other objects, or the glass is dirty, the effectiveness of the collectors is greatly reduced. Arrange for trimming of the trees or relocation of the solar collectors if the obstruction is permanent. Arrange for cleaning of the collector glass. Solar collectors incorrectly positioned Check that positioning and alignment of solar collectors is in accordance with the section 'Location and alignment of solar collectors'. WARNING: Persons working from elevated surfaces such as roofs must be adequately trained an qualified in accordance with local OHS requirements.
High Electricity Tariffs (electric boosted systems only) Electric Boosted Systems
The electricity tariff will determine the running costs of the system. It is important the end user is aware of the applicable tariffs. Contact your electricity supplier to confirm what these tariffs are.
Little or no water circulation in the solar 'flow and return' loop
There are numerous causes of little or no circulation in the solar flow and return circuit the circulation of water through the collectors. These causes must be investigated by a qualified person. Contact Rinnai.
Water flow fluctuations One or more hot taps opened at the same time More than one or two hot taps in use at the same time may cause a decrease in
the hot water flow from the taps. Is there more than one or two hot taps open, or are appliances such as a dishwasher or washing machine, in use at the same time? Ensure only one or two hot taps are on at one time. Check the flow of the water from one tap, eg. the shower. The shower should be adjusted so the hot tap is fully open.
Water Hammer Hot and cold water plumbing in the premises Have a plumber check clipping of hot and cold water pipework and install a
pressure limiting valve and water hammer arrestor as required.
SAVE A SERVICE CALL
Rinnai Australia - 10 - Solar Close Coupled Operating / Installation Manual - Issue 7 - 16/9/10
SYSTEM SPECIFICATIONS
Close Coupled hot water systems are specified according to the cylinder capacity, number of solar collectors and boost type and capacity. Boost capacity for gas boosted system depends on the gas booster model selected. Boost capacity for electrically boosted systems depends on the power rating of the electric heating element.
Specifications and principal dimensions for the various systems are shown below.
Table 2 - Systems Specifications
Connections
- Solar flow and return 3/4”
- PTR Valve 3/4”
- Cold Inlet 3/4”
- Hot Outlet 3/4”
PTR Valve setting (kPa) 850
Rating of PTR Valve supplied (kW) 10
Expansion Control Valve (ECV) setting (kPa) - Supplied by Installer if required
700
Max supply pressure with ECV (kPa) 500
Max supply pressure without ECV (kPa) 700
Pressure limiting valve rating (kPa) - Supplied by Installer if required
500
Electric Element Power Rating for Electric Systems (kW) 24, or 3.6 standard
1.8 or 4.8 available separately
Gas Booster S20, S26 or other Rinnai Infinity
Models converted to Solar.
* (Refer section on gas booster
specification)
SPECIFICATIONS
Rinnai Australia - 11 - Solar Close Coupled Operating / Installation Manual - Issue 7 - 16/9/10
SYSTEM DIMENSIONS
Figure 3 - System Dimensions
1025
1200
1540
2090
2390
2120
(2165)
2090
3385
3215
(3290)
(1050)
600
610
1940
(1965)
2535
(2560)
Dimsensions shown for Enduro and Equinox collectors
Dimensions in brackets “(__)” for Excelsior collectors
2275
1200
2120
(2165)
SYSTEM SPECIFICATIONS
Rinnai Australia - 12 - Solar Close Coupled Operating / Installation Manual - Issue 7 - 16/9/10
COLLECTOR SPECIFICATIONS
Table 4 - Collectors Specifications
GAS BOOSTER SPECIFICATIONS
* Table 5 - Gas Boosters Specifications
Model Name S20 S26
Boost Capacity:
- L/min. @ 20°C rise
- L/min @ 25°C rise
(L/min)
20 16
26 24
Maximum Rated Flow: (L/min) 20 26
Minimum Supply Pressure for Maximum rated flow:
(1)
(kPa) 120 200
Minimum Flow for Operation: (L/min) 2.4 2.4
Frost Protection: Yes Yes
Gas Consumption (Maximum / Minimum): (MJ/Hr.) 125 - 18 188 - 23
Star Rating (AS 4552 - 1998): 5.5 5.0
Hot Water Delivery Temperature:
(2)
60°C 60°C
Dimensions: Height x Width x Depth: (mm) 530 x 350 x 194 530 x 350 x 194
Weight: (kg) 15 21
(1)
- Units will operate at lower pressures but the rated flow with not be achieved.
(2)
- Gas boosters for Solar hot water applications should be preset to deliver a minimum temperature of 60°C.Gas boosters factory pre
set to 60°C or 65°C will be marked as such. If there are no temperature markings on the water heater, on site conversion is required. Other models of Rinnai Infinity Water Heaters (including internal units) can be converted to solar gas boosters. Contact Rinnai for details.
CHARACTERISTICS
Enduro / Equinox
(SP200A) or
(SP200A FTC)
Excelsior
(EXT OR EXT FTC)
TYPE
Flat plate Flat plate
CONSTRUCTION
- Waterways Copper Copper
- Absorber Aluminium Copper
- Selective Surface High Performance Sputtered Titanium Oxide
Maximum Operating Pressure
Casing Material
Overall Dimensions
(L x W x H) (mm)
1940 x 1025 x
80
1964 x 1047 x
81
Weight empty
(STD/FTC) (kg).
33 / 35 35 / 38
Water volume (Litres) 1.3 1.5
Number risers 8 10
Potential Solar Output at
PTR relief conditions (kW)
MODEL NUMBERS AND SPECIFICATIONS
Frost Protection
* Standard version - no frost protection FTC Version - Frost Protection to -5°C
* FOR MORE INFORMATION ON FROST PROTECTION
REFER TO WARRANTY BOOKLET
850 kPa
Aluminium
1.25
SPECIFICATIONS
Rinnai Australia - 13 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
REGULATIONS AND OCCUPATIONAL HEALTH AND SAFETY (OH&S)
LOCATION
System Location
Select suitable areas of roof on which to install the solar collectors and cylinder. It is essential that the roof structure is suitable for the solar collector/cylinder combination and can support the weight of these items when full of water. It is the installers responsibility to ensure the roof can safely support the system and to visually check the roof, and if there is any damage that requires attention (such as cracked tiles etc.), to inform the owner. If this affects the safe installation of any part of the system, installation should not proceed until the damage has been rectified. Collectors should be positioned for optimum solar benefit. Refer to section “SYSTEM ORIENTATION AND INCLINATION” on page 16 for more information.
All system components must be in an accessible location. Sufficient clearances shall allow access to, and removal of, all serviceable parts. Ensure the PTR valve, drain lines, thermostat and elements for electric systems have sufficient clearances and are accessible for service and removal. The information on any data plates must also be readable.
All electrically boosted solar hot water heating elements must be connected to an independent, fused, AC 240V 50 Hz power supply with an isolating switch installed at the switch board.
Gas Booster Location (where applicable)
The S20 & S26 gas booster are designed for 'Outdoor' Installation only. As such, it must be located in an above ground open air situation with natural ventilation, without stagnant areas, where gas leakage and products of combustion are rapidly dispersed by wind and natural convection.
If an internal model which has been converted to a solar gas booster follow information supplied with the unit for location, mounting and flueing requirements.
Installation and commissioning must be performed by authorised persons. Rinnai solar systems must be installed in accordance with these instructions and all regulatory requirements which exist in your area including those in relation to manual lifting, working at heights and on roofs. Applicable publications and regulations may include:
• AS 5601 Gas Installations
• AS/NZS 3500 National Plumbing and Drainage
• AS/NZS 3000 Wiring rules
• Building Codes of Australia (BCA)
• Local Occupational Health and Safety (OH&S) regulations
This appliance is not suitable for use as a domestic spa pool or swimming pool heater.
Solar collectors and cylinders are heavy and bulky items and are usually positioned on the roofs of buildings. Australian State and Territories have a principal Occupational Health and Safety (OH&S) Act which contains requirements relating to the handling of large, bulky or awkward items and the prevention of falls from elevated surfaces. Persons installing solar collectors must be aware of their responsibilities and be adequately trained and qualified, in accordance with local OH&S requirements.
WATER PIPES
All hot water pipework should be insulated with sealed Polyethylene foamed or equivalent insulation to optimise performance and energy efficiency. Such insulation may also be mandatory under local regulations. With the exception of solar collector flow and return pipes, water pipe sizing should be performed in accordance with AS/NZS 3500.
The collector flow and return pipes must be a minimum of 1/2” copper tube or alternative material pipe supplied by Rinnai. Plastic pipe must not be used between collectors and cylinder or booster. Plastic pipe is not suited to the high water temperatures and pressures that may occur in the collector flow and return system.
WARNING
WARNING
INSTALLATION INFORMATION
Rinnai Australia - 14 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
WATER SUPPLY
The minimum and maximum water pressures for the various systems are listed in Table 5. Approved pressure limiting valves may be required if the 'Maximum' rated water supply pressures are exceeded. For gas boosted systems to achieve the rated flow through the outlet of the continuous flow water heater, the minimum water supply pressures must be supplied.
The systems will operate at lower pressures but the rated flow will not be achieved.
Water chemistry and impurity limits are detailed in the separate 'Warranty conditions' document. Most metropolitan water supplies fall within these requirements. If you are unsure about water quality, contact your water authority. If sludge or foreign matter is present in the water supply, a suitable filter should be incorporated in the water supply to the storage cylinder.
HOT WATER DELIVERY TEMPERATURE
Local regulations and/or the requirements of AS/NZS 3500.4 must be considered regarding the temperature limitations of hot water supplied to areas used primarily for personal hygiene. The temperature of water to these areas is limited to 45°C for early childhood centres, primary and secondary schools and nursing homes or similar facilities for young, aged, sick or people with disabilities and 50°C for all other buildings. To comply with these requirements, a temperature limiting device, such as a thermostatic mixing or tempering valve, will be required on all solar hot water systems as detailed in Figures 4 and 5.
Figure 4 - Tempered Gas hot water systems
Figure 5
- Tempered Electric hot water systems
COLD WATER SUPPLY
HEATED WATER FROM STORAGE CYLINDER
GAS SUPPLY
KITCHEN
LAUNDRY
ENSUITE
BATHROOM
TEMPERATURE
LIMITING
DEVICE
HEATED WATER FROM STORAGE CYLINDER
COLD WATER SUPPLY
KITCHEN
LAUNDRY
ENSUITE
BATHROOM
TEMPERATURE
LIMITING
DEVICE
INSTALLATION INFORMATION
Rinnai Australia - 15 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
VALVES AND FITTINGS
Components Supplied by Installer
The following valves & fittings are to be supplied by the installer:
A cold water expansion control valve (ECV). An ECV must be fitted in Western Australia and
South Australia to the cold water supply to the storage cylinder to comply with local regulations. An ECV is recommended in all other geographical areas where the water supply has a tendency to cause scaling. This will reduce hot water discharge from the Pressure and Temperature Relief (PTR) valve which minimises wear on this valve.
A stop cock, non return valve and line strainer. Combination valves incorporating two or more
of these functions (such as 'Trio' valves) are suitable. These are fitted to the cold water supply to the storage cylinder by the installer.
Cold water supply and hot water discharge pipework to and from the storage cylinder.
An isolating valve and connection union for the gas supply to the gas booster.
A approved pressure limiting valve is required if the maximum rated water supply pressure in
Table 2 is exceeded.
Components Supplied with System
The following valves are supplied with your solar hot water system:
A combined pressure and temperature (PTR) relief valve, capacity 10 kW.
Relief valve pressure settings vary with models. This valve is fitted at the top of the storage cylinder. The PTR valve is a safety device and it is mandatory that it is fitted by the installer in all installations.
Thermo-Arrestor (TA) valve. This valve is fitted on the inlet pipe to the Solar Collectors.
For gas boosted systems, elbow connections for the hot, cold and gas supply are fitted at the
bottom of the gas booster.
Fittings as shown in Figures 24 to 27.
INSTALLATION INFORMATION
Rinnai Australia - 16 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
INSTALLATION INFORMATION
SYSTEM ORIENTATION AND INCLINATION
The performance of any solar hot water system is determined by the way that the system is installed.
In Australia, the solar collectors should face the equator (North) as shown below. Where this orientation is not practical, collectors facing within 45 degrees from North (between North-East and North-West) area acceptable, with a reduction in efficiency of approximately 5%. If the bulk of hot water consumption occurs before 2 pm face the collectors in a North - Easterly direction. If the bulk of hot water consumption occurs after 2 pm face the collectors in a North Westerly direction.
Figure 6 - Orientation angle of Collectors
The inclination of the solar collectors should ideally be the same as the latitude angle of the site. Inclinations within 20 degrees of the latitude angle of the site are acceptable, with a reduction in efficiency of approximately 5%. Most roofs within Australia have a slope of between 20° and 25° and provide an appropriately angled mounting surface.
To ensure operation of the system the inclination MUST NOT be less than 10°.
Figure 7 - Inclination of Collector
Table 7: Latitudes of Australian Cities
45
o
45
o
South
East
North
(Ideal gives 3 hours either side of noon day sun
)
City Latitude +/- 20
o
N
orth
City Latitude City Latitude City Latitude City Latitude
Adelaide 35°S Cairns 17°S Hobart 42°S Port Hedland 20°S Alice Springs 24°S Canberra 35°S Mildura 34°S Rockhampton 24°S Brisbane 27°S Darwin 12°S Melbourne 38°S Sydney 34°S Broken Hill 31°S Geraldton 28°S Perth 32°S Townsville 19°S
Rinnai Australia - 17 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
For all installations the collector bank must slope upwards approximately 8 mm per collector from inlet to outlet as shown below:
Figure 8 - Collector Banks
ROOF MOUNTING OPTIONS
For mounting options not shown in Figure 9, for example in areas where the cyclone frame can not be used, consult your nearest Rinnai Branch or Rinnai Representative.
For roofs with a slope of 10° or less a flat roof frame must be used.
Rinnai do not recommend installing Close Coupled systems on roofs with a pitch greater than 30°. An additional strap should be used to prevent the cylinder from tipping over if a system is installed in this manner. Refer page 24.
It is normal to mount the solar collectors down close to the gutter. Roof construction must be checked to ensure that the roof timbers are capable of supporting the additional load. (Refer to AS 3500.4 Appendix H).
For tiled roof installations. Check for cracked or damaged tiles in the area of proposed installation. Replace any faulty tiles. If spare tiles are not available, swap damaged tiles with good ones from along the gutter line.
Figure 9 - Solar Collector Roof Mounting Options
BLANKED OFF CONNECTION
HOT CONNECTION
BLANKED OFF CONNECTION
COLD CONNECTION
COLLECTOR BANK MUST SLOPE
UPWARDS APPROX 8 mm PER COLLECTOR
N
N
FLAT ROOF FRAME
CYCLONE FRAME SIDE PITCH FRAME
N
REVERSE PITCH FRAME
N
STANDARD
N
INSTALLATION INFORMATION
Rinnai Australia - 18 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
TABLE 8 - MOUNTING COMPONENTS
02817,1*&20321(176VXSSOLHGLQWKH,QVWDOODWLRQ.LW
Size of Cylinder / Number of Collectors
180 / 1 180 / 2 330 / 2 330 / 3
Part Name / Number
2 - - -
Mounting Rail Small
14201196
- 2 2 -
Mounting Rail Medium
14201197
- - - 2
Mounting Rail Large 14201198
2*
+
2
#
4* 4* 6*
Collector Mounting Strap
* supplied with collectors, # supplied in collector installation kit 12401012
4 4 4 4
M8 Bolt, Washer and Nut BOLT 22601052
(used to bolt collector mounting WASHER 17401072 strap to mounting rail) NUT 16801062
4 8 8 12
Collector Retainer 26601706
4 8 8 12
BOLT 22601073
M6 Bolt, Washer and Nut WASHER 17401073
(used with collector retainers) NUT 16801007
INSTALLATION OF SOLAR COLLECTORS & CYLINDERS
Rinnai Australia - 19 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
INSTALLATION OF SOLAR COLLECTORS & CYLINDERS
STANDARD INSTALLATION
Cylinder Mounting Component Pre Assembly for a Standard Installation
Assemble the cylinder cradle components and the lower collector rail components as shown in
Figure 10.
Only loosely attach the collector retainers to the rails.
Figure 10 - Cylinder Mounting
This installation is not suitable for use in cyclonic areas. For further details, please contact your local Rinnai Solar distributor.
NOTE
MOUNTING RAIL
COLLECTOR SUPPORT STRAPS
COLLECTOR SUPPORT STRAPS
COLLECTOR RETAINERS M6 BOLT, NUT &WASHER
COLLECTOR RETAINERS M6 BOLT, NUT &WASHER
MOUNTING RAIL
Rinnai Australia - 20 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
STANDARD INSTALLATION CONTINUED
Fastening (Collectors to a Tiled Roof)
This installation is not suitable for in cyclonic areas. For further details, please contact your local Rinnai Solar distributor.
Position the lower collector mounting rail
assembly so that the rail is angled to ensure the collectors have an 8 mm / collector rise.
Attach the collector mounting straps to the
rafter or truss under the tiles as shown in
Figure 11.
Figure 11 - Mount Lower Collector Rail
Place the collector(s) onto the roof above the
lower rail. If more than one collector is being installed then join them together using the compression fittings supplied.
Push down on the collector retainers to clamp
the collector and tighten the nuts as shown in
Figure 12.
Figure 12 - Mount collector on Roof
Position the upper collector rail above the
collectors. Push down on the retainers to clamp the collector and tighten the nuts.
Attach the collector mounting straps to the
rafter or truss under the tiles as shown in
Figure 13.
Figure 13 - Attach Mounting Straps
Replace the tiles and ensure the collector is
secure as shown in Figure 14.
Figure 14 - Replace Tiles
NOTE
Nail strap to rafter
Tiles removed
Nail strap to rafter
Tiles removed
INSTALLATION OF SOLAR COLLECTORS & CYLINDERS
Rinnai Australia - 21 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
STANDARD INSTALLATION CONTINUED Fastening (Collectors to a Metal Roof)
This installation is not suitable for use in cyclonic areas. For further details, please contact your local Rinnai Solar distributor.
Position the lower collector mounting rail
assembly so that the rail is over the roof purlin and the rail is angled ensure the collectors have an 8 mm / collector rise.
Drill through the roof iron and purlin using
the holes in the rail as a guide. Apply some silicone sealant down the holes to ensure no water leakage.
Bolt the rail to the roof purlin using a
suitable fastener as shown in Figure 15.
Figure 15 - Mount Lower Collector Rail
Position the collector(s) onto the roof
above the lower rail. If more than one collector is being installed, join them together using the compression fittings supplied.
Push down on the collector retainers to
clamp the collector and tighten the nuts.
Place the upper collector mounting rail
above the collectors. Push down on the collector retainers to clamp the collector and tighten the nuts.
Drill through the roof iron and purlin using
the upper mounting rail as a guide. Apply some silicone sealant down the holes to ensure no water leakage and secure with suitable fasteners as shown in Figure 16. Alternatively the rail can be attached to the roof using the collector mounting straps.
Figure 16 - Mount Collector on Roof
Figure 17 - Attach Upper Rail
NOTE
Bolt lower mounting rail to roof purlin using a suitable fastener
Bolt upper mounting rail to roof purlin using a suitable fastener
INSTALLATION OF SOLAR COLLECTORS & CYLINDERS
Rinnai Australia - 22 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
ATTACHING MOUNTING RAIL TO CYLINDER
Depending on the packaging, either one or two rails are attached to the cylinder.
The extra rail and fastenings are packed with the cylinder. They are screwed into the rail mounting holes in the cylinder.
Figure 18 - Cylinder with one rail
Attach the rail using the bolts, washers and spring washers in the order shown.
Ensure the feet on the rails face outwards
Ensure that the bolt is tightened sufficiently to flatten the spring washer. This ensures that the bolt is adequately tightened.
Figure 19 - Attachment of rail
Once the rail is attached and suitably tightened, continue the cylinder installation as shown on the next page.
Figure 20 - Cylinder with both rails
Washer
Spring
Washer
Rail
Bolt
INSTALLATION OF SOLAR COLLECTORS & CYLINDERS
Rinnai Australia - 23 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
STANDARD INSTALLATION CONTINUED
STANDARD INSTALLATION CONTINUED
Fastening Cylinder to a Tiled Roof
Lift the storage cylinder onto the roof and locate it above the collector bank. The cylinder’s position should be as central as possible to the collector bank. The lower rail must be on a load bearing surface.
Slide the cylinder support strap into the slots located in the uppermost cylinder support bracket (shown in Figure 21) so that the strap are in line with the rafter or as close as possible to them.
Figure 21 - Cylinder Support Strap
Remove tiles one row up from the storage cylinder. Apply tension to the straps and attach them to the rafters using a suitable fastener.
Replace the tiles
Figure 22 - Cylinder Installation Tiled Roof
Fastening Cylinder to a Metal Roof
Lift the storage cylinder onto the roof and locate it above the collector bank. The cylinder’s position should be as central as possible to the collector bank. The lower rail must be on a load bearing surface.
Slide the cylinder support strap into the slots located in the uppermost cylinder support bracket (shown in Figure 21) so that the strap are in line with a suitable fastening point.
Bolt the lower support rail to the roof using a suitable fastener.
Apply tension to the cylinder support straps and attach them to the rafters using a suitable fastener.
Seal any holes in roof using a suitable sealant to ensure roof is water tight.
Figure 23 - Cylinder Installation Metal Roof
FASTEN STRAP TO RAFTER
TILE REMOVED
LOWER CYLINDER RAIL MUST BE ON A LOAD BEARING SURFACE
BOLT STRAP TO ROOF USING A SUITABLE FASTENER
BOLT RAIL TO ROOF USING A SUITABLE FASTENER
LOWER CYLINDER RAIL MUST BE ON A LOAD BEARING SURFACE
LOWER CYLINDER RAIL MUST BE ON A LOAD BEARING SURFACE
INSTALLATION OF SOLAR COLLECTORS & CYLINDERS
Rinnai Australia - 24 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
ROOF PITCH GREATER THAN 30°
In situations where a Close Coupled System is installed onto a roof with a pitch of 30° or greater, an additional strap must be used to prevent the cylinder tipping over. Builders strapping available from hardware stores is suitable for this. The strapping is attached through the slots in the front cylinder rail, goes over the tank and is then fastened to the roof behind the cylinder.
Tiled Roof Metal Roof
Securely fasten strap to roof using a suitable fastener
Securely fasten strap to roof using a suitable fastener
Attach straps through
slot in cylinder rail.
Attach strap through
slot in cylinder rail.
Securely fasten
strap using a
suitable fastener
Ensure straps are on main section of tank as plastic endcaps are not
loadbearing
Ensure straps are on main section of tank as plastic endcaps are not
loadbearing
Securely fasten straps to roof using a suitable fastener
INSTALLATION OF SOLAR COLLECTORS & CYLINDERS
Rinnai Australia - 25 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
FRAMED INSTALLATIONS - FLAT, REVERSE AND SIDE PITCH
This installation is not suitable in cyclonic areas. For the correct frame for use in cyclone areas, contact your local Rinnai Solar distributor.
Table 9 - Framed Installations
For use on a flat roof or where the roof pitch
is too low.
This frame allows the system to be installed
at a suitable inclination.
Installations instructions are provided in the
Rinnai Frame Installation Manual.
These comprise of a Close Coupled system
flat roof frame and a side/reverse pitch kit.
They can be used when the system need to
be installed in the reverse direction to the direction the roof is facing.
For example, using a reverse pitch frame on
a South facing roof enables the system to be oriented to the North.
Installations instructions are provided in the
Rinnai Frame Installation Manual.
These comprise of a Close Coupled system
flat roof frame and a side/reverse pitch kit.
They can be used when the system need to
be installed side on to the direction the roof is facing.
For example, using a side pitch frame on an
East or West facing roof to enables the system to be oriented to the North.
Installations instructions are provided in the
Rinnai Frame Installation Manual.
FRAMED INSTALLATIONS - CYCLONE FRAME
Assemble cyclone frame and mount
components as described in instructions provide with cyclone frame kit.
NOTE
FLAT ROOF FRAME
REVERSE PITCH FRAME
SIDE PITCH FRAME
INSTALLATION OF SOLAR COLLECTORS & CYLINDERS
Rinnai Australia - 26 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
180 Litre Cylinder with 1 Collector
Figure 24 - 180 Litre Cylinder with 1 Collector
2
1
20
9
10
16
16
21
11 12 13
9
914
4
6
7
8
9
20
3
INSTALLATION OF SOLAR COLLECTORS & CYLINDERS
Rinnai Australia - 27 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
180 litre cylinder with 1 collector
Installation Kit IK180CCT01
Qty Item / Part Number Qty Item / Part Number Qty Item / Part Number
1
P&TR Valve
11004784
*supplied with cylinder
1
Adaptor
M33 x G ¾ (Flexi)
16601065
1
Adapting Nipple
R ¾ x G ¾ (Flexi)
17201006
1
T adaptor hot outlet
19001018
*supplied with cylinder
4
Fibre washer ¾
17401008
2
Stop end assembly
28801025
- 1 G ¾ plug
- 1 ¾ Kinco nut + 1 ¾ Kinco olive)
1
R ¾ Nipple (long)
17201011
1
Elbow assembly
21201013
- 1 x El bow G ¾ (Flexi) x G ¾
(Kinco)
- 1 x Kinco nut and olive ¾
1
Flexi pipe 1930 mm
with insulation
11601099
1
Elbow Rp ¾ x Rp ¾
21201004
1
Kinco nut ¾
16801018
1
Flexi Pipe 600 mm
with Insulation
11601097
1
Reducing Nipple
R1 x R ¾
17201036
1
Kinco olive ¾
33001011
1
TA Valve
11007711
1
Adapting Nipple
G ¾ (Flexi) x G ¾ (Kinco)
17201007
INSTALLATION OF SOLAR COLLECTORS & CYLINDERS
Rinnai Australia - 28 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
180 Litre Cylinder with 2 Collectors
Figure 25 - 180 Litre Cylinder with 2 Collectors
2
1
23
9
10
16
17
16
17
23
67
9
8
10
9
24
9
14
INSTALLATION OF SOLAR COLLECTORS & CYLINDERS
Rinnai Australia - 29 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
180 litre cylinder with 2 collectors
Installation Kit IK180CCT02A
Qty Item / Part Number Qty
Item / Part Number
Qty
Item / Part Number
1
P&TR Valve
11004784
*supplied with cylinder
1
Adaptor
M33 x G ¾ (Flexi)
16601065
2
Stop end assembly
28801025
- 1 G ¾ plug
- 1 ¾ Kinco nut + 1 ¾ Kinco olive)
1
T adaptor hot outlet
19001018
*
supplied with cylinder
4
Fibre washer ¾
17401008
2
Union compression ¾
32201709
-
1 x nipple G3/4
- 2 x Kinco nut and olive ¾
1
Reducing Nipple
R1 x R ¾
17201036
2
Elbow assembly
21201013
- 1 x E lbow G ¾ (Fle xi) x G ¾
(Kinco)
-
1 x Kinco nut and olive ¾
1
Flexi Pipe 2450 mm
with Insulation
11601095
1
TA Valve
11007711
1
Adapting Nipple
R ¾ x G ¾ (Flexi)
17201006
1
Flexi Pipe 670 mm
with Insulation
11601098
INSTALLATION OF SOLAR COLLECTORS & CYLINDERS
Rinnai Australia - 30 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
330 Litre Cylinder with 2 Collectors
Figure 26 - 330 Litre Cylinder with 2 Collectors
2
1
4
6
7
8
9
20
3
20
9
10
16
17
11 12 13
9
16
22
914
17
INSTALLATION OF SOLAR COLLECTORS & CYLINDERS
Rinnai Australia - 31 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
330 litre cylinder with 2 collectors
Installation Kit IK330CCT02A
Qty Item / Part Number Qty Item / Part Number Qty Item / Part Number
1
P&TR Valve
11004784
*supplied with cylinder
1
Adaptor
M33 x G ¾ (Flexi)
16601065
1
Adapting Nipple
R ¾ x G ¾ (Flexi)
17201006
1
T adaptor hot outlet
19001018
*
supplied with cylinder
4
Fibre washer ¾
17401008
2
Stop end assembly
28801025
- 1 G ¾ plug
- 1 ¾ Kinco nut + 1 ¾ Kinco olive)
1
R ¾ Nipple (long) 17201011
1
Elbow assembly
21201013
- 1 x Elbow G ¾ (Flexi) x G ¾
(Kinco)
- 1 x Kinco nut and olive ¾
2
Union compression ¾
32201709
- 1 x nipple G 3/4
- 2 x Kinco nut and olive ¾
1
Elbow Rp ¾ x Rp ¾
21201004
1
Kinco nut ¾
16801018
1
Flexi pipe 1930 mm
with insulation
11601099
1
Reducing Nipple
R1 x R ¾
17201036
1
Kinco olive ¾
33001011
1
Flexi Pipe 480 mm
with Insulation
11601064
1
TA Valve
11007711
1
Adapting Nipple
G ¾ (Flexi) x G ¾ (Kinco)
17201007
INSTALLATION OF SOLAR COLLECTORS & CYLINDERS
Rinnai Australia - 32 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
330 Litre Cylinder with 3 Collectors
Figure 27 - 330 Litre Cylinder with 3 Collectors
2
1
23
9
10
16
17
17
16
17
17
10
9
25
9
14
23
67
9
8
INSTALLATION OF SOLAR COLLECTORS & CYLINDERS
Rinnai Australia - 33 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
330 litre cylinder with 3 collectors
Installation Kit IK330CCT03A
Qty Item / Part Number Qty
Item / Part Number
Qty
Item / Part Number
1
P&TR Valve
11004784
*supplied with cylinder
1
Adaptor
M33 x G ¾ (Flexi)
16601065
2
Stop end assembly
28801025
- 1 G ¾ pl ug
- 1 ¾ Kinco nut + 1 ¾ Kinco olive)
1
T adaptor hot outlet
19001018
*supplied with cylinder
4
Fibre washer ¾
17401008
4
Union compression ¾
32201709
- 1 x nipple G 3/4
- 2 x Kinco nut and olive ¾
1
Reducing Nipple
R1 x R ¾
17201036
2
Elbow assembly
21201013
- 1 x E lbow G ¾ (Fle xi) x G ¾
(Kinco)
- 1 x Kinco nut and olive ¾
1
Flexi Pipe 2450 mm
with Insulation
11601095
1
TA Valve
11007711
1
Adapting Nipple
R ¾ x G ¾ (Flexi)
17201006
1
Flexi Pipe 770 mm
with Insulation
11601096
INSTALLATION OF SOLAR COLLECTORS & CYLINDERS
Rinnai Australia - 34 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
GAS BOOSTER LOCATION
The gas booster is designed for ‘Outdoor” Installation only. As such, it must be located in an above ground open air situation with natural ventilation, without stagnant areas, where gas leakage and products of combustion are rapidly dispersed by wind and natural convection. The location must comply with the clearances specified in AS 5601.
The gas booster must be mounted on a vertical structure with the water and gas connections on the underside pointing downwards. The heated outlet of the cylinder is connected to cold water inlet of the gas booster.
Ensure that the wall or structure on which it is to be mounted are capable of supporting the weight of the appliance and associated pipe work. See Table 5 for individual gas booster weights. For gas boosters installed on elevated structures or under floors specific requirements apply. Refer to AS 5601 for details.
• Attach the gas booster to the wall using screws.
• Location of the gas booster flue terminal must be in accordance with Figure 5.3 of
AS 5601.
• If an internal model which has been converted to a solar gas booster follow information supplied with the unit for location, mounting and flueing requirements.
GAS SUPPLY
The maximum gas consumption of the gas booster and the required gas pressure are shown on the appliance data plate. If the gas pipe sizing is insufficient the customer will not get the full performance benefit. Gas pipe sizing must consider the gas input to the gas booster as well as all the other gas appliances on the premises. The gas meter and regulator must be specified for this gas rate. An approved sizing chart such as the one in AS 5601 should be used. An approved full flow isolation valve and disconnection union must be fitted to the gas supply inlet of the gas booster. Isolation valves must not be fitted directly.
HOT WATER DELIVERY TEMPERATURE
Gas boosters for use in solar hot water systems are preset to deliver a fixed temperature of 60°C in accordance with plumbing regulations. In addition, they contain the warning stating “Rinnai Water Controllers are NOT compatible with solar hot water installations and MUST NOT BE USED” in the vicinity of the temperature controller connections inside the appliance.
SMARTSTART®
Smartstart® Function
The Smartstart® is a separate system that works in conjunction with the Rinnai solar hot water system.
When activated by the manual activation switch, water in the pipework connected between the solar hot water system and the hot water outlets is warmed before any outlets are opened. This results in water savings and added convenience. Refer the Figure 28 for installation details.
Gas Boosters other than models designated “S20”, S26”or “Solar” must not be used.
Gas Boosters marked with the text: “THIS APPLIANCE DELIVERS WATER NOT EXCEEDING 50°C IN ACCORDANCE WITH AS 3498" are incompatible with solar hot water systems and must not be used.
NOTE
INSTALLATION & MAINTENANCE - GAS BOOSTED SYSTEMS
Rinnai Australia - 35 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
Figure 28 - Smartstart® Schematic
Rinnai Smartstart Unit
Rinnai Continuous Flow Water
Heater - Gas Booster
Manual Activation
Switch ONLY
(not supplied)
Water controllers
MUST NOT
be used!
Gas Supply
Return Line
Outlets to Personal Hygiene areas
to be tempered to 50°C as per
AS3500.4
Refer to Rinnai manuals supplied
with appliances for important
installation information.
Installations MUST conform to local
regulataions.
Supply from solar storage cylinder
IMPORTANT
INSTALLATION & MAINTENANCE - GAS BOOSTED SYSTEMS
Rinnai Australia - 36 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
CLEARANCES
Figure 5.3 is reproduced below. Note that AS 5601-2004 was current at time of printing but may have been superseded. It is the installer’s responsibility to ensure current requirements are met.
AS 5601 - Figure 5.3 ‘Clearances’ - Gas Booster Flue Terminal
INSTALLATION MAINTENANCE - GAS BOOSTED SYSTEMS
Rinnai Australia - 37 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
INSTALLATION PROCEDURE
1. Install Solar Collectors and cylinders
• Position and install the solar collectors and cylinder in accordance with the section ‘INSTALLATION OF SOLAR COLLECTORS AND CYLINDERS”.
2. Connect PTR Valve
• Connect the PTR Valve in the location shown in the relevant diagram of Figures 24 to 27. Leave the valve outlet pointing down. Tighten the valve using the spanner flats - never use the valve body.
• The PTR Valve must be adequate for the thermal loading applied to the storage cylinder. In the case of gas boosted systems, the thermal load is applied only by the solar collectors. The continuous flow hot water heater does not apply thermal load to the storage cylinder. The potential solar output for the solar collectors at PTR Valve relief conditions is listed in Table 3.
• The PTR Valve pressure ratings vary according the cylinder specifications. The maximum heater input rating is 10.0 kW. The PTR valve rating MUST EXCEED the total input from the solar collectors. If it does not, the PTR valve MUST be exchanged for a model of higher capacity.
For example, for a gas boosted solar system with 3 x SP200A collectors, the thermal load is
3 x 1.25 = 3.75 kW. This is less than 10.0 kW, hence the supplied PTR valve is of sufficient capacity.
• Use Teflon thread tape on the valve, never use hemp or other sealing materials. Ensure the tape does not protrude past the end of the thread, which could result in it hanging over the end of the thread and blocking the water passage through the valve.
3. Mount Gas Booster
• Mount the gas booster in accordance with the section ‘GAS BOOSTER LOCATION & MOUNTING’.
4. Connect Water to Gas Booster
• Connect the outlet of the storage cylinder to the water inlet of the gas booster.
5. Connect Fittings
• Connect fittings and pipe work as shown in the relevant diagram in Figures 24 to 27.
6. Cold Water Supply
• Connect cold water supply to the inlet ‘T’. Ensure that the relevant valves as described in the section “VALVES AND FITTINGS” are fitted.
• Purge the cold water supply lines to remove air and swarf before final connection.
7. Relief Drain Lines
• Independent 15 mm copper pipes must be fitted to the drain outlets of the PTR and ECV. Each pipe must be open to atmosphere and run with a continual downward grade in a frost free environment to a visible discharge point. Drain lines must not exceed 9 metres in length.
• Valves or other restrictions must not be placed in the relief valve drain outlet line.
8. Hot Water Discharge
• Connect the hot water outlet of the gas booster to the pipe work supplying hot water to the premises.
9. Connect Gas to Booster
• Connect a suitable gas supply and isolating valve to the gas booster. Follow instructions supplied with gas booster. Keep gas booster isolated at this stage.
Some water will drip from the drain lines during heating of the water in the storage cylinder. It is recommended to discharge directly above a drain.
A temperature limiting device may be required as detailed in the section “HOT WATER DELIVERY TEMPERATURE”.
NOTE
WARNING
INSTALLATION MAINTENANCE - GAS BOOSTED SYSTEMS
Rinnai Australia - 38 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
FILLING THE SYSTEM
1. Ensure the gas supply to the continuous flow water heater is isolated.
2. Turn on one or more hot water taps at the sink. Open the stop cock in the cold water mains supply line. The entire system will now be filled with cold water.
3. Turn off the hot tap at the sink when water flows freely without air bubbles or air bursts. Check all connections for leakage and tighten if necessary. This applies especially to fittings in positions not easily assessed such as near the solar collectors. Operate the easing gear of both
the PTR and ECV valves at the storage cylinder to ensure these valves are functional.
PRE SOLAR HEATING CHECKS
Before commencing solar heating of the water in the system ensure the following actions have been completed:
Solar Collectors
1. Are the solar collectors installed with the correct slope and orientation to the sun?
2. Is the installation finished neatly with the roof made good, all tiles and flashings in place?
3. Are the bolts tight on the roof framework?
4. Are all solar collector straps fitted and correctly anchored to the roof structure?
5. If leak testing completed & successful, have any covers been removed from the solar collectors?
Gas Booster
1. Ensure the gas supply is isolated. Remove the test point screw located on the gas inlet
connection and attach a pressure gauge.
2. Turn on the electrical power to the gas booster and turn on the gas supply.
3. Ensure the cold water inlet ('trio') valve on the storage cylinder inlet is open. Open all available hot water taps.
4. Operate ALL other gas appliances at their maximum gas rate, in accordance with manufacturers instructions.
5. With all gas appliances in operation at the maximum gas rate, the pressure should read between 1.13 - 3.0 kPa on Natural Gas. On LPG the pressure should be 2.75 - 3.0 kPa. If the pressure is lower, the gas supply is inadequate and the appliance will not operate to specification. It is the installers responsibility to check the gas meter, service regulator and pipe work for correct operation/ sizing & rectify as required. Note that the gas regulator on the appliance is electronically controlled and factory pre-set. Under normal circumstances it DOES NOT need adjustment during installation. Make adjustments only if the gas booster is not operating correctly and all other possible causes for incorrect operation have been eliminated. Instructions for gas pressure setting are located in the pocket behind the front cover of the gas booster.
6. Close the hot water taps including the shower.
Ensure building occupants are warned to stay clear of the solar system components, building perimeter and roof since hot water or steam may be discharged from pipes or components.
If leaks are detected the system must be drained and leaks repaired before the system is refilled. If this is necessary, temporarily cover the solar collectors with packaging cardboard or a tarp to prevent them from heating which could result in steam or hot water being discharged from fittings.
Ensure building occupants do not have access to hot water outlets during this procedure.
CAUTION
CAUTION CAUTION
INSTALLATION MAINTENANCE - GAS BOOSTED SYSTEMS
Rinnai Australia - 39 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
7. Check the hot water delivery temperature by placing a suitable thermometer at the hot water outlet closest to the gas booster. This is usually the hot water outlet in the kitchen. The delivery temperature should be greater than 55°C (this temperature allows for heat losses in pipe work). If the delivery temperature at the hot water outlet is lower than 55°C, check the delivery temperature at the outlet of the gas booster. It should be within 2°C of the set point, usually 60°C. If not, refer to the section 'Hot Water Delivery temperature' refer to page 34.
8. Close the cold water inlet ('trio') valve on the storage cylinder inlet and inspect and clean the strainer. Repeat for the strainer connected at the inlet of the gas booster. This procedure may need to be repeated to ensure the strainers remains clear, especially on new installations.
9. Confirm the hot water delivery temperature from the gas booster. This is done by checking the hot water delivery temperature at an untempered outlet close to the water heater. This is usually the hot water outlet in the kitchen.The untempered hot water delivery should be between 55°C & 60°C.
Temperature Limiting Devices
1. Commission any temperature limiting devices in accordance with the instructions supplied by
the manufacturer.
2. Confirm the hot water delivery temperature at a tempered water outlet. Tempered water outlets should be those supplying areas primarily used for the purposes of personal hygiene such as bathrooms. The hot water delivery temperature should not exceed 50°C or 45°C as detailed in the section 'Hot Water Delivery temperature' refer to page 34.
SOLAR HEATING
1. Remove any cardboard or tarp covers that may have been placed over the solar collectors to
prevent them from heating water during installation and commissioning.
2. Activate electrical power to the Rinnai gas booster. Solar heating of the water in the cylinder will now commence when sufficient solar radiation is available.
FINISHING THE INSTALLATION
• After testing is completed explain to the householder the functions and operation of solar water heater components. Also explain to the householder the importance of carrying out Maintenance as per separate ‘Warranty Terms and Conditions’ document.
• Leave this Manual with the householder.
• Remind the householder to complete the 'Warranty Certificate' provided in the separate ‘Warranty Terms and Conditions’ document.
DRAINING INSTRUCTIONS
1. The power supply to the gas booster must be switched off.
2. Close the cold water mains supply stop cock.
3. Open a hot tap to relieve pressure.
4. Disconnect the cold water connection to the Thermo-arrest (T/A) valve.
5. Remove the brass plug on the bottom right hand side of the collector bank.
6. Disconnect the ‘water inlet’ and ‘water outlet’ connections at the gas booster.
7. The system will now drain all water.
INSTALLATION MAINTENANCE - GAS BOOSTED SYSTEMS
Rinnai Australia - 40 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
INSTALLATION & MAINTENANCE - ELECTRIC SYSTEMS
INSTALLATION PROCEDURE
1. Install Solar Collectors and Cylinders
Position and install the solar collectors and cylinder in accordance with the section “INSTALLATION OF SOLAR COLLECTORS AND CYLINDER”.
2. Connect PTR Valve
Connect the PTR Valve in the location shown in the relevant diagram of Figures 24 to 27.
Leave the valve outlet pointing down. Tighten the valve using the spanner flats - never use the valve body.
The PTR Valve must be adequate for the thermal loading applied to the storage cylinder. In the case of gas boosted systems, the thermal load is applied only by the solar collectors. The continuous flow hot water heater does not apply thermal load to the storage cylinder. The potential solar output for the solar collectors at PTR Valve relief conditions is listed in Tabl e 3 .
The PTR Valve pressure ratings vary according the cylinder specifications. The maximum heater input rating is 10.0 kW. The PTR valve rating MUST EXCEED the total input from the solar collectors. If it does not, the PTR valve MUST be exchanged for a model of higher capacity.
For example, for a gas boosted solar system with 3 x SP200A collectors, the thermal load is 3 x
1.25 = 3.75 kW. This is less than 10.0 kW, hence the supplied PTR valve is of sufficient capacity.
Use Teflon thread tape on the valve, never use hemp or other sealing materials. Ensure the tape does not protrude past the end of the thread, which could result in it hanging over the end of the thread and blocking the water passage through the valve.
3. Connect Fittings
Connect fittings and pipe work as shown in the relevant diagram in Figures 24 to 27.
4. Cold Water Supply
Connect cold water supply to the inlet ‘T’. Ensure that the relevant valves as described in the section “VALVES AND FITTINGS” are fitted.
Purge the cold water supply lines to remove air and swarf before final connection.
5. Relief Drain Lines
Independent 15 mm copper pipes must be fitted to the drain outlets of the PTR and ECV. Each pipe must be open to atmosphere and run with a continual downward grade in a frost free environment to a visible discharge point. Drain lines must not exceed 9 metres in length.
Valves or other restrictions must not be placed in the relief valve drain outlet line.
6. Hot Water Discharge
Connect the hot water outlet of the storage cylinder to the pipe work supplying hot water to the premises.
Some water will drip from the drain lines during heating of the water in the storage cylinder. It is recommended to discharge directly above a drain.
A temperature limiting device may be required as detailed in the section “HOT WATER DELIVERY TEMPERATURE”.
NOTE
WARNING
Rinnai Australia - 41 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
7. ELECTRIC SUPPLY
• The power supply can be either Off-Peak (overnight), Extended Off-Peak (overnight and day) or continuous, depending on the tariffs available from the local electricity supply authority. The Off­Peak (overnight) power supply minimises the cost of any required electric boosting. Discuss power supply requirements with the end user and electricity supply authority as required.
Connections for elements Figure 29 shows the wiring detail for the water heater.
A flexible 20 mm conduit is required for the electrical cable to the storage cylinder. The conduit is to be connected to the unit with a 20 mm terminator. Connect the power supply wires directly to the terminal block and earth tab connections ensuring there are no excess wire loops inside the front cover.
Figure 29 - Wiring detail
Heating Element Thermostat Temperature Settings
Australian Standards require a minimum thermostat set point of 60°C to inhibit the growth of Legionella Pneumophilia bacteria.
FILLING THE SYSTEM
1. Ensure the electric power supply to the heating element is switched off and fuses removed.
2. Turn ON one or more hot water taps at the sink. Open the stop cock in the cold water mains supply line. The entire system will now be filled with cold water.
3. Turn OFF the hot tap at the sink when water flows freely without air bubbles or air bursts. Check all connections for leakage and tighten if necessary. This applies especially to fittings in positions not easily assessed such as near the solar collectors. Operate the easing gear of both the PTR and
ECV valves at the storage cylinder to ensure these valves are functional.
The power supply to the heating elements must not be activated until the system is filled with water.
Ensure building occupants are warned to stay clear of the solar system components, building perimeter and roof since hot water or steam may be discharged from pipes or components.
If leaks are detected the system must be drained and leaks repaired before the system is refilled. If this is necessary, temporarily cover the solar collectors with packaging cardboard or a tarp to prevent them from heating which could result in steam or hot water being discharged from fittings.
WARNING
WARNING
WARNING
INSTALLATION & MAINTENANCE - ELECTRIC SYSTEMS
Rinnai Australia - 42 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
PRE SOLAR HEATING CHECKS
Before commencing solar heating of the water in the system ensure the following actions have been completed:
Solar Collectors
1. Are the solar collectors installed with the correct slope and orientation to the sun?
2. Is the installation finished neatly with the roof made good, all tiles and flashings in place?
3. Are the bolts tight on the roof framework?
4. Are all solar collector straps fitted and correctly anchored to the roof structure?
5. If leak testing completed and successful, have any covers been removed from the solar collectors?
Electric Heating Element
1. Has the thermostat set point been set to at least 60°C and no greater than 70°C?
Temperature Limiting Devices
1. Commission any temperature limiting devices in accordance with the instructions supplied by the manufacturer.
2. Confirm the hot water delivery temperature at a tempered water outlet. Tempered water outlets should be those supplying areas primarily used for the purposes of personal hygiene such as bathrooms. The hot water delivery temperature should not exceed 50°C or 45°C as detailed in the section "Hot water delivery temperature" of these instructions.
SOLAR HEATING
1. Remove any cardboard or tarp covers that may have been placed over the solar collectors to prevent them from heating water during installation and commissioning.
Auxiliary Energy Supply
1. Connect the electrical element to the power supply (off peak if available).
2. When the system is fully of water turn on electrical supply to element.
FINISHING THE INSTALLATION
After testing is completed explain to the householder the functions and operation of solar water
heater components. Also explain to the householder the importance of carrying out Maintenance as per separate ‘Warranty Terms and Conditions’ document.
Leave this Manual with the householder.
Remind the householder to complete the 'Warranty Certificate' provided in the separate
‘Warranty Terms and Conditions’ document.
DRAINING INSTRUCTIONS
1. The power supply to the element must be switched off.
2. Close the cold water mains supply stock cock.
3. Open a hot tap to relieve pressure.
4. Disconnect ‘cold water inlet’ connection to the T/A valve.
5. Remove the brass plug on the bottom right hand side of the collector bank.
6. The system will now drain all water.
INSTALLATION & MAINTENANCE - ELECTRIC SYSTEMS
Rinnai Australia - 43 - Solar Close Coupled Operating / Installation Manual Issue 7 - 16/9/10
IMPORTANT INFORMATION
Rinnai Australia - 45 - Solar Close Coupled Operating / Installation Manual Issue 7, 16/9/10
Head Office
10-11 Walker Street, Braeside, Victoria 3195 P.O. Box 460 Tel: (03) 9271 6625 Fax: (03) 9271 6622
National Help Line
Spare Parts & Technical Info Tel: 1300 555 545* Fax: 1300 300 141*
*Cost of a local call Higher from mobile or public phones.
Hot Water Service Line Tel: 1800 000 340
Australia Pty. Ltd.
ABN 74 005 138 769
Internet: www.rinnai.com.au E-mail: enquiry@rinnai.com.au
123 45678 90123 4
Rinnai has a Service and Spare Parts network with personnel who are fully trained and equipped to give the best service on your Rinnai appliance. If your appliance requires a service, please call our National Help Line.
15401022
CONTACT INFORMATION
Loading...