Rinnai RHFE-201FA, ES08 Owner's Operation And Installation Manual

Page 1
Do not store or use gasoline or other flammable vapors and
liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance. Do not touch any electrical switch; do not use any phone in your building. Immediately call your gas supplier from a neighbor s phone. Follow the gas supplier s instructions. If you cannot reach your gas supplier, call the fire department.
Installation and service must be performed by a qualified
installer, service agency or the gas supplier.
WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
Owner s Operation and Installation Manual for the
RHFE-201FA
Energysaver
Gas Direct Vent Wall Furnace
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
Table of Contents ...........2
Safety Information...........3
Operating Instructions.....6
Care and Maintenance....10
Fault Codes ....................13
Installation Instructions ...14
Consumer Support..........36
Register your product at www.rinnairegistration.com or call 1-866-RINNAI1 (746-6241)
Page 2
2
Rinnai Corporation RHFE-201FA
This appliance may be installed in an aftermarket, permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
Consumer Safety Information
Safety Definitions ........................................ 3
Safety Behaviors and Practices.................. 3
Safety Features........................................... 4
Specifications
Appliance Specifications......................... 4, 5
Features...................................................... 5
Flue Manifolds............................................. 5
Operating Instructions
Getting to Know your RHFE-201 ............... 6
Control Panel .............................................. 7
Operating Information
Turning ON and OFF............................. 8
Adjusting the temperature ..................... 8
Economy Mode...................................... 8
Function Lock ........................................ 9
Adding Water to the Humidifier.............. 9
Adjusting Air Flow Direction ................... 9
Sensible Temperature Control............... 9
Care and Maintenance
Maintenance ........................................ 10
Care of Exterior.................................... 10
Snow Accumulation ............................. 10
Filters ................................................... 10
Visual Inspection of Flame .................. 10
Before Making a Service Call ....................11
Troubleshooting.........................................12
Fault Codes ...............................................13
Installation Instructions
General Instructions ..................................14
Gas Connection.........................................15
Clearances to Combustibles .....................15
Installation Parts .......................................16
Drilling Flue Hole .......................................17
Dimensions................................................17
Flue Terminal Clearances ...................18, 19
Flue Manifold Installation.....................20, 21
Connecting the Appliance .........................22
Operating Instructions ...............................23
Cut-Away Diagram ....................................24
Wiring Diagram..........................................25
Ladder Diagram.........................................26
Flow Diagram ............................................27
Parts List.............................................. 28-35
Consumer Support
Warranty Information.................................36
Limited Warranty ..................................36,37
Table of Contents
This appliance may be installed as an OEM installation in a manufactured home (USA only) or mobile home and must be installed in accordance with the manufacturer’s instructions and the Manufactured Home construction and
Safety Standard, Title 24 CFR, Part 3280, in the United States, or the Mobile Home Standard, CAN/CSA Z240 MH Series, in Canada. This appliance is only
for use with types of gas indicated on the rating plate. A conversion kit is supplied with the appliance.
This equipment is made for use as a heater in a residential building or a light commercial building. Do not use in locations where there are spray, chemicals, or large amounts of dust. Using hair treatment products containing silicon may cause ignition error, flame extinction, or other malfunctions.
Page 3
Safety Behavior and Practices
Do not block the warm air discharge. Do not allow anyone to sleep directly in front of the appliance.
Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.
Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns or clothing ignition.
Young children should be carefully supervised when they are in the same room as the appliance.
Clothing or other flammable material should not be placed on or near the appliance.
Any safety screen or guard removed for servicing must be replaced prior to operating the appliance.
Do not insert items into the louvers.
Do not spray aerosols near the appliance while it is operating. Most aerosols contain butane gas which is flammable.
Do not unplug the appliance while it is operating or while the fans are on.
CAUTION
Keep the area around the appliance clear and free from combustible materials, gasoline, and other flammable vapors and liquids.
Never store liquid propane containers indoors.
Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
This appliance is equipped with a three-prong plug for your protection against shock hazard and should be plugged directly into a properly grounded three-prong receptacle. Do not cut or remove the ground prong from this plug.
Any alteration to the appliance or its controls can be dangerous.
Do not operate appliance with the panels removed, cracked or broken. Replacement of the panels should be done by a licensed or qualified service person.
WARNING
Consumer Safety Information
Safety Definitions
This is the safety alert symbol. This symbol alerts you to potential hazards that can kill or hurt
you and others.
Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It may also be used to alert against unsafe practices.
CAUTION
WARNING
DANGER
3
Rinnai Corporation RHFE-201FA
Page 4
4
Rinnai Corporation RHFE-201FA
Application For manufactured home (USA only) or mobile home or residential or
light commercial installation convertible for use with natural gas and liquefied petroleum gases when provision is made for the simple conversion from one gas to the other.
General Description Forced combustion, forced convection, flued gas furnace
Operation Push button electronic
Gas Connection 1/2 in female NPT
Gas Control Electronic
Burners Stainless steel Bunsen burner
Temperature Control Electronic thermostat
Ignition System Electronic spark ignition
Flue System The flue must be terminated to atmosphere with only flue
components listed with the appliance’s certification. Warranty will be voided if non listed components are installed.
Humidifier Tray Capacity - 1.5 pints (700 cc)
Electrical Connection AC 120V, 60 Hz, 42 watts
Weight 39.4 lbs (17.9 kg)
Noise Level 27-34 dB
AFUE Rating Natural Gas: 80.6% Propane: 83%
Fan CFM output Low 48.3 - High 70.6
Specifications
Rinnai is continually updating and improving products. Therefore, specifications are subject to change without prior notice.
The efficiency rating of this appliance is a product thermal efficiency rating determined under continuous operating conditions and was determined independently of any installed system.
Safety Features
Overheat: The appliance will automatically shut down when the appliance exceeds a predetermined temperature.
Flame Failure: The appliance will automatically shut down if the burner flame is extinguished.
Power Failure: The appliance will cut off the gas if it loses electrical power.
Power Surge Fuse: A glass fuse on the PC board protects against overcurrent. If the fuse blows then all indicator lamps will be off.
Spark Detector: The appliance automatically shuts down if there is an abnormal spark at ignition.
Fusible Link: In case the overheat feature prevents the temperature from rising then the fusible link will break shutting off the appliance.
Appliance Specifications
Page 5
5
Rinnai Corporation RHFE-201FA
Features
Clean Heating Forced Flue Type
Easy Operation One-Touch Ignition
Sensible Temperature Control Feature
Comfortable Room Temperature Control and Display
Warm Air Outlet at Floor Level (keeps your feet warm)
Function Lock
Room Temperature Setting Memory
Clean the Air Filter - Indicator Lamp
Energy Saving Economy Setting
Humidifier Tray
Air Flow Directional Louvers
Direct Vent Easily Installed
Proportional Heating Variable Capacity
Hush! Quiet Operation
Modern Design Minimizes Floor Space Requirements
Failure Message Display
See the installation instructions for the parts list of the vent kit.
The A Vent Kit is included with the appliance.
The following flue manifold sizes are available:
Name
Kit No. fits walls
S Vent Kit FOT-150 3 - 4 1/2 in (75 - 115 mm)
A Vent Kit FOT-151 4 1/2 - 9 1/2 in (115 - 240 mm)
B Vent Kit FOT-152 9 1/2 - 15 3/4 in (240 - 400mm)
C Vent Kit FOT-153 15 3/4 - 23 5/8 in (400 - 600 mm)
D Vent Kit FOT-154 23 5/8 - 31 1/2 in (600 - 800 mm)
Flue Manifolds
Natural Gas Propane Gas
Minimum supply gas pressure 4.5 in (114 mm) W.C. 8.0 in (203 mm) W.C.
Maximum supply gas pressure 10.5 in (267 mm) W.C. 13.0 in (330 mm) W.C.
Manifold test pressure-High 3.3 in (85 mm) W.C. 6.0 in (152 mm)W.C.
Manifold test pressure-Low 0.6 in (15 mm) W.C 0.9 in (24 mm) W.C.
BTU/hour input Low 3000 - High 8000
BTU/hour output Low 2400 - High 6400
Appliance Specifications
Page 6
6
Rinnai Corporation RHFE-201FA
Getting to know your new RHFE-201
Operating Instructions
CONTROL PANEL OPERATION/ TEMPERATURE CONTROL DISPLAY
OPERATION LAMP
RATING PLATE MODEL NUMBER, SERIAL NUMBER, GAS TYPE, ETC.
WARM AIR OUTLET
HUMIDIFIER TRAY OPEN THE DOOR AND POUR WATER INTO THE TRAY.
VENT TERMINAL COMBUSTION/ EXHAUST
COMBUSTION AIR INTAKE HOSE
EXHAUST PIPE
AIR FILTER
THERMISTOR
GAS CONNECTION 1/2" NPT
POWER CORD
PLUG 120V AC
FILTER LAMP
Page 7
7
Rinnai Corporation RHFE-201FA
Control Panel
All buttons beep when operated.
RoomTemp
Set Temp
ON
ON/OFF
Filter
Function
Lock
Economy
Temp
Control
FUNCTION LOCK Lamp is "green" when this feature is on.
FILTER LAMP Flashes when filter is dirty.
OPERATION LAMP This lamp turns "green" when power is on. Lamp will change to "red" when burner is on.
TEMPERATURE BUTTONS
adjust temp. to
lower setting.
adjust temp. to
a higher setting.
ENERGY SAVING BUTTON Lamp is
green when this feature is activated.
ON/OFF BUTTON Easy operation One touch ignition
Page 8
8
Rinnai Corporation RHFE-201FA
Operating Information
Turning the heater ON
When you press the ON/OFF button, the LED display will illuminate, the spark will ignite the main burner and the combustion fan will begin to run.
This heater has an automatic ignition system. When the main burner has lit, the combustion lamp will glow red, and the spark will stop.
If ignition does not occur after 15 seconds, the appliance will automatically turn off and fault code 11 will be displayed on the control panel. This may occur when using the appliance for the first time or if it has not been used for a while. Try operating the appliance again.
There may be a smell of burning dust or oil the first time the heater is lit or when the heater has been out of operation for a long time.
The appliance may make noises after ignition or when it is turned off. This is normal and is due to the thermal expansion or contraction of its components.
Adjusting the Temperature
The temperature setting and the room temperature are indicated by the L.E.D. display on the control panel. When the appliance is turned on the temperature setting will be displayed for 10 seconds. The display will then show the room temperature. The default temperature setting is 72 F.
To change the temperature setting press one of the temperature control buttons once. The Set Temp should light up and the display will show the current temperature setting. Continue to press the control buttons until the desired temperature setting is reached. After 10 seconds the display will return to showing the room temperature.
The thermostat automatically modulates the burner and the fan to maintain the temperature setting.
The temperature settings available are:
LO - burner is on minimum combustion
60 F - 80 F in two deg ree increments
HI - burner is on maximum combustion
Turning the heater OFF
Press the ON/OFF button. Do not turn off by unplugging at the power outlet.
The fan will continue to run for a short time to prevent the internal components from overheating.
Economy Mode
Pressing the Economy button will cause the appliance to go into Economy Mode and the green lamp will glow. This results in the temperature setting being reduced by 2 F, 30 minutes after the room temperature has reached the temperature setting. After another 30 minutes the temperature setting is reduced another 2 F. This could result in the temperature setting being reduced by a maximum of 4 F. The intent of this mode is to save energy.
ON
ON/OFF
Filter
ON/OFF
RoomTemp
Set Temp
Temp
Control
Economy
Page 9
9
Rinnai Corporation RHFE-201FA
Operating Information
Function Lock
This feature locks the buttons to prevent unintended operation.
Press the Function Lock button to activate and the lamp will glow. Pressing and holding the Function Lock button for two seconds will disengage the function lock.
If the Function Lock is engaged while the unit is operating, all buttons will be disabled except for the ON/OFF button.
If the Function Lock is engaged while the unit is off, then all buttons will be disabled.
Adjusting Air Flow Direction
The vertical louvers may be adjusted to move the air flow more to the right or to the left.
Use a screw driver or similar object to bend each louver to the desired position.
Do not bend repeatedly (no more than 5 times) or else the louver will break.
The horizontal louver (which determines the vertical air flow direction) is fixed and cannot be adjusted.
CAUTION
Do not adjust the air flow
louvers while warm air is flowing.
Sensible Temperature Control
The sensible temperature control feature allows comfortable heating which matches the conditions in the room.
Based on the information collected by the room temperature thermistor when the heating starts, the heating capacity is automatically adjusted to achieve a comfortable heating effect and to reach the temperature setting quickly.
Adding Water to the Humidifier
Warm air is humidified when it passes over the water in the tray.
Remove the bottom trim panel below the louvers by pulling on both sides. Pull the tray out and fill with water. Push the tray back in and attach the bottom trim panel.
During operation a small amount of condensation is produced in the flue system and drains into the humidifier tray.
CAUTION
Do not remove the
bottom trim panel or the humidifier tray while warm air is flowing.
Function
Lock
Page 10
10
Rinnai Corporation RHFE-201FA
Care and Maintenance
Filters
Dirty filters reduce the air flow and the appliance’s ability to produce heat. The filters should be cleaned frequently during the heating season. If the filters become blocked the filter indicator lamp will flash red. Eventually the appliance will turn off and display fault code 14 on the control panel display.
To clean the filters, the appliance should be OFF and cool. Remove the filter and clean it using a soft dry cloth or vacuum. If the filter is greasy wash with warm soapy water, rinse, and dry completely.
Maintenance
Repairs should be performed by a qualified service technician. The appliance should be inspected annually by a qualified service technician. More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. It is imperative that control compartments, burners, and circulating air passage ways of the appliance be kept clean.
Any screen or guard removed for servicing the appliance must be replaced prior to operating the appliance. Clean as follows:
1. Turn heat off. Allow to cool for one hour.
2. Remove the front panel by removing six screws.
3. Use pressurized air to remove dust from the main burner, heat exchanger, and fan blades.
4. Use soft dry cloth to wipe cabinet.
Do not use wet cloth or spray cleaners on the burner.
The flue should be inspected annually for blockages or damage.
Motors are permanently lubricated and do not need periodic lubrication. Keep fan and motor free of dust and dirt by cleaning annually.
Verify proper operation after servicing.
Visual Inspection of Flame
Check that the burner flames are operating normally. The flame can be seen through the
circular window through the louvers.
When operating normally the burner flame should appear as long, clear, blue, stable, streaks. Yellow flames or an orange color is abnormal and maintenance is required.
NORMAL
ABNORMAL
Care of Exterior
Dampen soft cloth with warm water. Wring water out well and wipe the unit.
Do not use volatile substances such as benzene or thinners. They cause fading of the paint and deformation of the resin.
CAUTION
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
Snow Accumulation
Keep the area around flue terminal free of snow and ice. The appliance will not function properly if the intake air or exhaust is impeded by obstructions.
Flame Rod
Yellow flames or orange color
Long, clear, blue, stable flames
Flame Rod
AIR FILTERS
Page 11
11
Rinnai Corporation RHFE-201FA
Before Making a Service Call
Before making a service call please check the following:
At Ignition:
Heater does not operate.
Warm air does not flow when the burner lights.
Smoke or strange smells are produced on the first trial light up after installation.
Sharp clicking noises at ignition, or when unit cuts down on the thermostat, or goes out.
During Combustion:
Clunking noise when the thermostat operates.
Unit is not heating room.
Air filter is blocked or the louvers are blocked or obstructed.
Heater will not re-ignite after overheating.
When the unit is turned off.
Convection fan continues to run after turning OFF.
Other Points:
Steam is discharged from the flue terminal.
Unit cuts off without apparent reason.
Power Failure.
Is the heater plugged in? Have the fuses or breaker blown at the switch board? Is there a power failure? Is the air filter blocked? Is anything blocking the outlet for the hot air? Is the flue blocked?
The fan is started automatically after a short delay. This is to allow the heat exchanger to warm up, helping to avoid cold draughts.
This is caused by grease or oil and dust on the heat exchanger and will stop after a short time.
This is simply expansion noise from the heat exchanger.
This is the sound of the solenoid gas valves opening and closing.
Is the air filter blocked? Is the set temperature high enough? Is the warm air outlet blocked by anything? Are the doors and windows of the room closed? Was the appliance correctly sized for the space?
Allow heater to cool, clean air filter, operate again.
Even after unit has cooled down, the heater does not ignite again. Repair is necessary. Contact your local agent or Rinnai for a Service call.
This is to remove the residual heat from the heat exchanger. The fan will stop when the heater cools down.
High efficiency appliances tend to discharge water vapor on cold days. This is normal.
Check whether filters are blocked. Dirty filters will cause the heater to overheat.
Switch OFF, then ON again when power is restored to re-set controls.
Page 12
12
Rinnai Corporation RHFE-201FA
Troubleshooting
Problem
Remedy
Cause
Not Plugged In
Power Failure
(Initial Installation) Air In Gas Pipe
Gas Filter Blocked
Miss Ignition
Flue terminal obstructed
Flue manifold not connected
Louver obstructed
Air filter blocked
Gas Escape
Function Lock Set
Gas turned off at meter, tank, or valve.
Plug In
Push On/Off button to attempt restart after power is restored.
Purge air (Installer)
Service Call
Service Call
Clear obstruction
Service Call
Clear obstruction
Clean filter
Service Call
Cancel Function Lock
Turn gas on
No ON indicator
Burner doesn’t ignite
Unusual combustion
Combustion stops
during operation
Smell of gas
Noisy ignition
Takes too long to
warm the room
Page 13
Fault Codes
If there is a malfunction the appliance may shut down as a safety precaution and display a fault code to assist in diagnosing the problem. The fault code will flash in the display on the control panel. When making a service call, this code will assist with diagnosing the fault.
You may be able to clear the fault code by turning the heater off and then on again. If the fault code remains or returns on the next operation, contact Rinnai or your nearest service agent and arrange for a service call.
13
Rinnai Corporation RHFE-201FA
CODE DISPLAYED FAULT REMEDY
Ignition failure
Flame failure
Overheat
Room overheat
Room Temperature
Sensor faulty
Overheat Temperature
Sensor faulty
Sparker failure
Combustion fan failure
Faulty ON/OFF switch
Faulty solenoids
Faulty Flame Rod
Communication Error
Check gas is turned ON.
Service call if repeated.
Check gas is turned ON.
Service call if repeated.
Clean filter
Service call if repeated. [1]
Service call.
Service call.
Service call.
Service call.
Service call.
Service call.
Service call.
Turn heater OFF,
then ON again.
Lower room temperature
to less than 104°F(40°C).
Flue block
Check around flue terminal [2]
11
12
14
16
31
32
33
34
53
61
70
71
72
73
49
99
Sensor breakdown
Service Call.
[1] Remove any obstructions. The flue needs to be kept clear to expel exhaust gases. If the appliance
fails to operate contact a qualified service agency.
[2] If the fusible link needs replacement, it must be done by a qualified service agency. In addition, the
cause of the overheat needs to be determined. The fusible link is a one use safety device that breaks to shut off the appliance.
Page 14
Installation Instructions
A qualified service technician should install the appliance and inspect it before use.
If you move, check the gas type in your new area. The local gas authority will be able to advise on local regulations.
The installation must conform with local codes or, in the absence of local codes, with the
National Fuel Gas Code, ANSI Z223.1/NFPA 54, or the Natural Gas and Propane Installation Code, CSA B149.1.
A manufactured home (USA only) or mobile home OEM installation must conform with the
Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or, when
such a standard is not applicable, the standard for Manufactured Home Installations, ANSI/
NCSBCS A225.1, or the standard for Gas Equipped Recreational Vehicles and Mobile Housing, CSA Z240.4.
The appliance, when installed, must be electrically grounded in accordance with local codes or, in the absence of local codes, with the National Electrical Code, ANSI/NFPA 70, or the Canadian Electrical Code, CSA C22.1.
Appliance input ratings are based on sea level operation and need not be changed for operation up to 2000 ft (609.9 m) elevation. For operation at elevations above 2000 ft (609.9)
The appliance must be isolated from the gas supply piping system by closing its equipment shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.5 kPa).
If the flooring is carpet, tile, or other combustible material other than wood, then the appliance must be installed on a metal or wood panel extending the full width and depth of the appliance.
This appliance discharges a large volume of warm air next to the floor. Any particles in the air such as cigarette smoke could cause discoloration in carpet. The warm air flow could discolor nylon carpets containing dyes or vinyl surfaces. To prevent discoloration of the floor covering a mat may be placed under the appliance which extends about 30 inches (750 mm) in front of it.
This appliance is not designed to built in.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases unless a certified kit is used. If a conversion of the unit is needed, conversions must be performed by a qualified service provider at the owners expense.
This appliance must not be connected to a chimney flue serving a separate solid-fuel burning appliance.
Rinnai suggests that a dedicated electrical circuit with a 120VAC, 60 hz, 10 amp power source be used.
Two 1/8 in test plugs are provided for testing of manifold differential pressure.They are located
General Instructions
WARNING
Do not use substitute materials.
Use only parts certified with the appliance.
The appliance should be correctly sized for the space it required to heat.
Follow the installations instructions and those in Care and Maintenance for adequate combustion and ventilation air.
The flow of combustion and ventilation air shall not be obstructed.
Clearances to access the appliance during servicing are 2 inches (50 mm) from the sides, 40 inches (1 m) from the front, and 9 inches (225 mm) from the top.
, refer to the Conversion Manual.
The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.5 kPa).
on the modulating gas valve and on the burner manifold.
14
Rinnai Corporation RHFE-201FA
Page 15
Gas Connection
The gas supply line shall be gas tight, sized and so installed as to provide a supply of a gas sufficient to meet the maximum demand of the heater without loss of pressure.
A shut off valve and appliance connector valve should be installed in the upstream of the gas line to permit servicing.
Flexible pipe and any appliance connector valve used for gas piping shall be types approved by nationally recognized agencies.
Any compound used on the threaded joint of the gas piping shall be a type which resists the action of liquefied petroleum gas.
Check the gas supply pressure immediately upstream at a location provided by the gas company. Supplied gas pressure must be within the limits shown in the Specifications section.
After completion of gas pipe connections all joints including the heater must be checked for gas tightness by means of leak detector solution, soap and water, or an equivalent nonflammable solution, as applicable. (Since some leak test solutions, including soap and water, may cause corrosion or stress cracking,
the piping shall be rinsed with water after testing, unless it has been determined that the leak test solution is non-corrosive.)
Refer to an approved pipe sizing chart if in doubt about the size of the gas line.
Install manual gas cut-off valve so that it can be accessed for easy operation. Do not conceal manual cut-off valve behind back spacer.
Clearances to Combustibles
When determining where to install the appliance the clearances to combustibles shown in the figure must be followed. Also refer to the Safety Behaviors an to combustibles from the top is zero.
d Practices section. The clearance
15
Rinnai Corporation RHFE-201FA
zero
2"(50mm)
40"(1m)
2"(50mm)
Page 16
16
Rinnai Corporation RHFE-201FA
The following items are included with the appliance.
Owner s Operation and Installation Manual
Conversion Manual
Conversion Kit
A Vent Kit
Manual valve set, backspacers, screws, pipe stoppers, and hardware listed below
Installation Parts
Flue Manifold 1 Spare rubber seal 1
(AFlue units only)
(For weatherboard installations)
Back Spacer
Set
1
1
1
2
1
1
3
10
2
1
1
1
Insulation
Clip
Plastic tie
for air inlet
Clamp
Wall Bracket
Spacer
Bracket
Pipe Stopper
Manual Valve
Set
Screw
Screw
Screw
Owners Manual Conversion Manual
(For Back Spacer)
(For Flue Manifold)
(For Clamp)
5Screw
(For Wall Bracket
and Flue manifold)
Page 17
17
Rinnai Corporation RHFE-201FA
Drilling Flue Hole
Check for water and gas pipes as well as electric cables. Drill the flue hole using a 3 1/8 inch (80 mm) drill. The center of the hole must be located exactly at the specified point.
A maximum of one elbow (FOT-158) may be used to raise the flue manifold s position by 6 in (154 mm) relative to the appliance. Rotate the
flue elbow 90°toaverticalpositionandattach
theFOT-158sothatitopenstow ardthe centeroftheappliance.If theFOT-158is  usedthendonotusethetem plate.The centerofthew allopeningw illbe161/2in (418.5mm)abovethebaseoftheappliance.
See diagram. For weatherboard walls, drill through the center of the weatherboard from the outside first and then through the plasterboard. A template is provided.
Dimensions
3 7/16" (88)
4 5/16"
(109.5)
4 3/4" (121)
WALL OPENING
POSITION
GAS CONNECTION
26 5/8" (676.5)
3 1/8" (φ80)
10 3/8" (264.5)
24 1/4" (616)
16 3/4" (425)
FLUE
ELBOW
4 1/2" (114)
6 1/2" (165)
3 3/8" (85)
1 5/8" (41.2)
1" (25)
12 1/16" (306.5)
4 9/16" (116.5)
GAS CONNECTION
4 5/16" (109.5)
WALL OPENING
POSITION
3 1/8"
(φ80)
10 3/8" (264.5)
FLUE
ELBOW
4 1/2" (114)
inches (mm)
Page 18
18
Rinnai Corporation RHFE-201FA
Flue Terminal Clearances
INSIDE
CORN ER DE TAI L
FIXED
CLOSED
OPERABLE
FIXED
CLOSED
OPERABLE
B
B
B
A
J
B
M
C
F
B
B
E
D
L
G
A
H
K
I
X
V
AIR SUPPLY INLET
VENT TERMINAL AREA WHERE
TERMINAL IS NOT
PERMITTED
Page 19
19
Rinnai Corporation RHFE-201FA
Ref
Description
Canadian Installations US Installations
A
Clearance above grade, veranda, porch,
deck, or balcony
12 inches (30 cm) 12 inches (30 cm)
B
Clearance to window or door that may be
opened
6 inches (15 cm) 6 inches (15 cm)
C Clearance to permanently closed window * *
* D
Vertical clearance to ventilated soffit,
located above the terminal within a
horizontal distance of 2 feet (61 cm) from
the center line of the terminal
*
E Clearance to unventilated soffit * *
F Clearance to outside corner * *
G Clearance to inside corner 20 inches (50 cm) 20 inches (50 cm)
H
Clearance to each side of center line
extended above meter/regulator assembly
3 feet (91 cm) within a
height 15 feet (4.5 m)
above the meter/
regulator assembly
*
I Clearance to service regulator vent outlet 3 feet (91 cm) *
*
J
Clearance to nonmechanical air supply
inlet to building or the combustion air inlet
to any other appliance
6 inches (15 cm) 6 inches (15 cm)
K
Clearance to a mechanical air supply inlet
6 feet (1.83 m)
3 feet (91 cm) above if
within 10 feet (3 m)
horizontally
L
Clearance above paved sidewalk or
paved driveway located on public property
7 feet (2.13 m)
①
M
Clearance under veranda, porch, deck, or
balcony
12 inches (30 cm) to
non-flammables
24 inches (60 cm) to
flammables
12 inches (30 cm) to
non-flammables
24 inches (60 cm) to
flammables
Flue Terminal Clearances
A vent shall not
terminate directly above
a sidewalk or paved
driveway that is located
between two single
family dwellings and
serves both dwellings.
Permitted only if
veranda, porch, deck, or
balcony is fully open on
a minimum of two sides
beneath the floor.
For clearances not
specified in ANSI
Z223.1/NFPA 54 or CSA
B149.1, clearances are
in accordance with local
installation codes and
the requirements of the
gas supplier.
Clearance to opposite
wall is 24 inches (60 cm)
for Canada and US.
①
②
*
Page 20
20
Rinnai Corporation RHFE-201FA
Flue Manifold Installation
1. Disassemble the flue manifold
The flue consists of 3 parts:
sleeve
inside connection
outside terminal
Disassemble the flue manifold by first pulling out the inside connection. To remove the outer terminal pull and release the two internal ties and then pull out the outer terminal.
Clearance to combustibles for the sleeve and flanges is zero inches.
2. Adjust the sleeve length
Measure wall thickness through previously drilled 3 1/8 inch (80 mm) hole.
The end of the sleeve should protrude 3/16 ­3/8 inch (5-10 mm) from the outside wall.
The sleeve is threaded for adjustment. Adjust the sleeve length to wall thickness plus 3/16 ­3/8 inch (5-10 mm).
NOTE: Do not extend beyond the red line.
For other than the S type flue manifold, if a shorter length is necessary an extension can be removed. Cut the plastic and remove the extension.
The flue manifold must exhaust to the outside. Do not exhaust into other rooms.
The flue is not designed to be positioned under floors or below the heater.
This appliance can only be used with one of the five types of Rinnai flue kits. The flue kits and their dimensions are listed in the Specifications section.
Refer to the Flue Terminal Clearances section.
3 screws
sleeve should extend 3/16 - 3/8 in (5-10 mm)
3. Attach the sleeve
Attach to the inside wall using 3 screws arranging the flange so that the marking TOP is at the top.
The flange is offset 2 to allow the condensate drain to the outside.
Inside Connection
Sleeve
Terminal
Remove extension if necessary
Page 21
21
Rinnai Corporation RHFE-201FA
Flue Manifold Installation
6. Lock the ties
Pulling hard on the left and right hand ties,
clip the ties over the notches inside the sleeve. You should be able to pull the ties 2 or 3 notches past the starting point. Cut the ties, leaving about 3/4 inch (20 mm) past the notch. Bend the ties back into the sleeve and parallel to the wall.
7. Insert Inside Connection Assembly
Push the assemble into the terminal tube, ensuring that the seal is in place on the inner tube.
Attach the inside connection with 3 screws. The inner connection can still be turned to install the screws.
4. Install the Terminal
Check that the terminal seal is in place. For
weatherboard walls, add the second seal next to the terminal seal to compensate for weather board angle.
From the outside insert the terminal into the
sleeve with the marking TOP at the top. The left hand side locking tie should be marked LEFT .
Terminal seal
Locking tie
Terminal
Locking ties
Sleeve
3 screws
Page 22
22
Rinnai Corporation RHFE-201FA
Connecting the Appliance
1. Attach the air inlet hose to the flue manifold on either inlet position a or b .
The unused inlet is plugged with the rubber cap supplied on the manifold.
2. Connect the flue elbow to the manifold while moving the appliance into position.
3. Fit the pipe stopper over the connection between the flue elbow and the manifold. Engage the hook and rotate it until it snaps against the body of the clamp.
4. Slide the insulation sleeve up to the flue manifold and slip the securing clip over the sleeve as shown.
5. Install the bracket on the rear of the top spacer by tightening 2 screws.
6. Install the wall bracket with two screws. Install the top spacer by clipping the spacer into the wall brackets and attaching it to the heater with 2 screws.
a
b
Flue Manifold
Pipe stopper
Elbow
Manifold
Hook
Pipe stopper
Fit Clip
Slide
Sock
Screw
Top spacer
Spacer bracket
Spacer
Spacer bracket
Wall bracket
Top spacer
Spacer bracket
Wall bracket
Screw
Page 23
23
Rinnai Corporation RHFE-201FA
Operating Instructions
FOR YOUR SAFETY READ BEFORE OPERATING
WARNING
If you do not follow these instructions exactly, a fire or explosion
may result causing property damage, personal injury or loss of life.
A. This appliance does not have a pilot. It is
equipped with an ignition device which automatically lights the burner. Do not
try to
light the burner by hand.
B. BEFORE OPERATING smell all around the
appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance. Do not touch any electric switch; do not use any phone in your building. Immediately call your gas supplier from a neighborís phone. Follow the gas suppliers instructions.
If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push in or turn the gas
control knob. Never use tools. If the knob will not push in or turn by hand, donít try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been
under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
TO TURN OFF GAS TO APPLIANCE
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance using the ON/OFF button.
3. Locate the manual gas valve on the side of the heater. Turn the manual valve clockwise to the full OFF position.
NOTE: The fan will continue to operate until the
appliance is cool. Do not turn the appliance off by unplugging it from the wall. Keep burner and control compartment clean. See installation and operating instructions.
OPERATING INSTRUCTIONS
1. STOP! Read the safety information above.
2. Set the thermostat to lowest setting.
3. Turn off all electric power to the appliance using the ON/OFF button.
4. This appliance is equipped with an ignition device which automatically lights the burner. Do not
try to light the burner by hand.
5. Locate the manual gas valve on the side of the heater. Turn the manual valve clockwise to the full OFF position.
6. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow B in the safety information above. If you don’t smell gas, go to the next step.
7. Turn the manual gas valve counterclockwise to the full ON position.
8. Turn on all electric power to the appliance using the ON/OFF button.
9. Set the thermostat to desired setting.
10. Combustion indicator glows red when the burner is lit and flashes when the burner fails to ignite. If the appliance will not operate, follow the instructions To Turn Off Gas To Appliance and call your service technician or gas supplier. See manual for additional information.
CLOSE
Manual Valve
OPEN
Page 24
24
Rinnai Corporation RHFE-201FA
Cut-Away Diagram
Page 25
25
Rinnai Corporation RHFE-201FA
Wiring Diagram
CONTROL DISPLAY UNIT
MS
TEST
OH.TH
R.TH
BL
POV
TF
OHS1OHS2
FM
SV2 SV1
FR
TR
ER
SP
SW
PS
rbl
1
4
1
4
1
2
1
2
1
81 10
bl rbl
r
1
3
8
5
6412
7
1
1
2
6
1
3
8
1
bk
bk
bk
bl
r
bk
gy gy
r
gr/y
bk
gr
AC120V
w
3A
F
bl
bk
r
y
gy
yy
or
bl
r
r
gr/y
bl
w
w
w
y
y
w
w
w
y
r
gy
gy
w
bl
If any of the original wires as supplied with the appliance must be
replaced, it must be replaced with a wire of a least a 194°F
temperature rating and number 18AWG or its equivalent.
CAUTION: Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dangerous operation.
Verify operation after servicing
MARK
PS
FR
F
TR
SV1,2
ER
SP
FM
OHS1,2
TF
POV
BL
R.TH
OH.TH
PARTS NAME
PRESSURE SENSOR
FLAME ROD
FUSE
TRANSFORMER
SOLENOID VALVE 1,2
ELECTRODE
SPARKER
CONVECTION FAN MOTOR
OVERHEAT SWITCH1,2
THERMAL FUSE
MODULATING VALVE
COMBUSTION FAN MOTOR
THERMISTOR
OVERHEAT THERMISTOR
CODE
COLOR
black
blue
green
green/yellow
bk
bl
gr
gr/y
red
r
white
w
yellow
y
gray
gy
orange
or
Page 26
26
Rinnai Corporation RHFE-201FA
Ladder Diagram
MODULATING SOLENOID VALVE
TRANSFORMER
ELECTRODE
OVER HEAT THERMISTOR
FUSE
THERMAL FUSE
THERMISTOR
MAIN SWITCH
PARTS NAME
FLAME ROD
MARK
FR
MS
R.TH
TF
F
ER
POV
TR
OH.TH
COMBUSTION FAN MOTOR
SOLENOID VALVE 1〜2
SPARKER
CONVECTION FAN MOTOR
FM
SP
SV1〜2
BL
FCC FAN CONTROL CIRCUIT
CF CONVECTION FAN
CPU CENTRAL PROCESSING UNIT
MAIN BURNERMB
PS PRESSURE SENSOR
OHS.1〜2
OVERHEAT SWITCH 1〜2
CPU
CONTROL DISPLAY UNIT
TEMP CONTROL CIRCUIT
CONTROL DISPLAY CIRCUIT
SOLENOID VALVE CIRCUIT
MODULATING VALVE CIRCUIT
POWER SUPPLY CIRCUIT
CONVECTION FAN CIRCUIT
FM
F(3A)
AC120V
 TF 216℃
R.TH OH.TH
TF DETECTING CIRCUIT
POV
GAS
MB
FR
CF
MS
SV2
SV1
IGNITION CIRCUIT
SP
ER
FLAME ROD CIRCUIT
PS
BL
FCC
COMB.FAN CIRCUIT
COMB.FAN SIGNAL CIRCUIT
IGNITION SIGNAL CIRCUIT
AC 38VAC200VAC19V
AC 120V
A
B
A
B
B A B
A
BB
A
B A
PS CIRCUIT
A
SAFETY DEVICE CIRCUIT
OHS.2 70℃
OHS.1 130℃
B
AC 100V
TR
A:DC5V B:DC12V
Page 27
27
Rinnai Corporation RHFE-201FA
Flow Diagram
Page 28
28
Rinnai Corporation RHFE-201FA
Parts List
For replacement parts call Rinnai at 1-800-621-9419.
Page 29
29
Rinnai Corporation RHFE-201FA
Parts List
Page 30
30
Rinnai Corporation RHFE-201FA
Parts List
Page 31
31
Rinnai Corporation RHFE-201FA
Parts List
Page 32
32
Rinnai Corporation RHFE-201FA
Parts List
Page 33
Parts List
33
Rinnai Corporation RHFE-201FA
Page 34
Parts List
34
Rinnai Corporation RHFE-201FA
Page 35
Parts List
35
Rinnai Corporation RHFE-201FA
709 CP-90466-3 POWERSUPPLYCORD 1 710 308F-2045 MOTORLEADASS'Y 1 711 308F-2046 THERMISTORASS'Y 1 712 431F-1430 FRLEADASS'Y 1 713 308F-2047 SV.IGLEADASS'Y 1 714 1004F-2053 SENSORLEADASS'Y 1 715 AU131-236-b CORDPACKINGB 4 716 AU131-236-a CORDPACKINGA 1 717 RC-329-1033
POWERSUPPLYCORDBRACKET
1 718 308F-534 TFLEADASS'Y 1 800 201F-2050 OWNER'SMANUAL 1 801 201F-2052 CONVERSIONMANUAL 1 802 CP-74167-17 RATINGPLATE 1 802 CP-74167-18 RATINGPLATE 1 803 CP-74168-17 RATINGPLATE 1 803 CP-74168-18 RATINGPLATE 1 804 CP-72062B-13 SPECIFICATIONMARK 1 805 431F-1860 POWERSUPPLYCORDLABEL 1 806 431F-1840 PROPANESTICKER 1 806 431F-1841 NGSTICKER 1 807 556F-2065 CAUTIONLABEL 1 808 1001F-1656 CAUTIONMARK 1 809 308F-2063 OPERATIONLABEL 1 810 1001F-1654 EXHAUSTCAUTIONLABELB 1 811 550F-1418 WATERLINELABEL 1 812 431F-1830 EXHAUSTCAUTIONLABEL 1 813 431F-1862 GASCHECKLABEL 1 813 431F-1863 GASCHECKLABEL 1 814 BRR37-244 ON-OFFVALVEASS'Y 1 815 308F-2070-3 CONVERSIONKIT(FORNG) 1 815 308F-2070-4 CONVERSIONKIT(FORLPG) 1 816 CP-74255-3
RATINGPLATESUPPORTLABEL
1 816 CP-74255-4
RATINGPLATESUPPORTLABEL
1 817 CP-74256-3
RATINGPLATESUPPORTLABEL
1 817 CP-74256-4
RATINGPLATESUPPORTLABEL
1 900 CP-30310 SCREW 901 CP-30408 SCREW 902 CP-30421-1 SCREW 904 ZAA0316SZ SCREW 905 ZAA0422SZ SCREW 906 ZBA0408SZ SCREW 908 ZBB0410SC SCREW 909 ZBD0408SZ SCREW 910 ZDAA0410SZ SCREW 911 ZEAB0406SC SCREW 912 ZEAB0408SC SCREW 913 ZEAB0408SZ SCREW 914 ZEAB0408UK SCREW 915 ZEDB0408SB SCREW 916 ZEDB0408SZ SCREW 917 ZEDB0410SZ SCREW 918 ZEDB0412SZ SCREW 919 ZHAA0406SZ SCREW 920 ZHAA0410SZ SCREW 921 CP-30486-2 SCREW
No. PARTNo. PARTNAME
QTY
Page 36
36
Rinnai Corporation RHFE-201FA
Consumer Support
Warranty Information
Limited Warranty
RHFE-201FA Gas Direct Vent Wall Furnace
What is covered?
This Warranty covers any defects in materials or workmanship, subject to the terms stated below. This Warranty extends to the original purchaser and subsequent transferees, but only while the product remains at the site of the original installation. This Warranty only extends through the first installation of the product and terminates if the product is moved or reinstalled at a new location.
How long does coverage last?
Item Period of Coverage
Heat Exchanger 10 years from date of purchase *
All Other Parts 5 years from date of purchase
Reasonable Labor 2 years from date of purchase
The installer is responsible for your heaters correct installation.
Please complete the information below to keep for your records:
Purchased from:
Address: Phone:
Date of Purchase:
Model No.:
Serial No.:
Installed by: Installers License No.:
Address: Phone:
Date of Installation:
Page 37
37
Rinnai Corporation RHFE-201FA
Limited Warranty - continued
What will Rinnai do?
Rinnai will repair any part or component that is defective in materials or workmanship as set forth as follows. All repair parts must be genuine Rinnai parts. All repairs or replacements must be performed by an individual or servicing company that has been authorized by Rinnai. Rinnai will pay reasonable labor charges associated with the repair or replacement of any part or component.
Replacement of the product may be authorized by Rinnai only. Rinnai does not authorize any person or company to assume for it any obligation or liability in connection with the replacement of a product. If Rinnai determines that repair of a product is not possible, Rinnai will replace the product with a comparable product, at Rinnai’s discretion.
* If the Heat Exchanger fails due to a
defect in material or workmanship within the sixth (6) through the tenth (10) year from the date of purchase, Rinnai will make the following allowances toward the purchase of a replacement Heat Exchanger:
How do I get service?
You must contact a qualified/authorized service provider for the repair of a product under this Warranty. For the name of a qualified/authorized service provider please contact your place of purchase, visit the Rinnai website (www.rinnai.us
), call Rinnai at 1-800-621-9419 or write to Rinnai at 103 International
Drive, Peachtree City, Georgia 30269.
Proof of purchase is required to obtain warranty service. You may show proof of purchase with a dated sales receipt, or by registering within 30 days of purchasing the product. To register your appliance, please visit www.rinnairegistration.com. For those without internet access, please call 1-866-RINNAI1 (746-6241). Receipt of Registration by Rinnai will constitute proof-of-purchase for this product. However, Registration is not necessary in order to validate this Warranty.
What is not covered?
This Warranty does not cover any failures or operating difficulties due to accident, abuse, misuse, alteration, misapplication, force majeure, improper installation, improper conversion*, improper maintenance or service, or for any other causes other than defects in materials or workmanship. This Warranty does not apply to any product whose serial number or manufacture date has been defaced.
* Improper conversion includes conversions for inventory adjustment.
Rinnai is not liable for any special, incidental, indirect or consequential damages that may arise, including damage to person or property, loss of use, or inconvenience. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation may not apply to you.
Limitation on implied warranties
Any implied warranties of merchantability and fitness arising under state law are limited in duration to the period of coverage provided by this limited Warranty, unless the period provided by state law is less. Some states do not allow limitations on how long an implied Warranty lasts, so the above limitation may not apply to you.
This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
Year of Failure Allowance
6
7
8
9
10
50%
40%
30%
20%
10%
Heat Exchanger
Page 38
38
Rinnai Corporation RHFE-201FA
Page 39
Page 40
201F-2050×03(00) Printed in Japan 2008.09
103 InternationalDrive,
PeachtreeCity,Georgia30269 Tel:1-800-621-9419 Fax:1-888-474-6624 www.rinnai.us
Register your product at www.rinnairegistration.com or call 1-866-RINNAI1 (746-6241)
Loading...