Rinnai EHPA315VMA, EHPA250VMAH, EHPA315VMAH, EHPA250VMA, EHPA250VMAW Installation and Operation Guide

...
Models:
EHPA250VMA EHPA250VMAW EHPA250VMAH EHPA250VMAWH EHPA315VMA EHPA315VMAW EHPA315VMAH EHPA315VMAWH
This manual does NOT suit any other models
Enviroflo Heat Pump Hot Water Systems
Operation & Installation Manual
This appliance must be installed in accordance with:
• Manufacturer’s Installation Instructions
• Current AS/NZS 3500
• Plumbing Code of Australia (PCA)
• Local Regulations and Municipal Building Codes including local OH&S requirements
This system must be installed, commissioned, serviced, maintained and removed ONLY by an Authorised Person.
NOT SUITABLE AS A POOL OR SPA HEATER
For continued safety of this appliance it must be installed and maintained in accordance with the manufacturer’s instructions.
AS3498 Lic W00169
SAI Global
Rinnai 2 EHPA_A Heat Pump OIM
AS/NZS 2712
Lic No. 1849
SAI Global
TABLE OF CONTENTS
Warnings and Important Information 4
Safety and Regulatory Information ����������������������������������������������������������������������������������������������������������������� 4
Transport and Storage of Appliance ��������������������������������������������������������������������������������������������������������������� 5
Scald Hazards ��������������������������������������������������������������������������������������������������������������������������������������������������� 6
Operation Principle ������������������������������������������������������������������������������������������������������������������������������������������ 7
Safety Devices �������������������������������������������������������������������������������������������������������������������������������������������������� 8
Pressure & Temperature Relief (PTR) Valve �������������������������������������������������������������������������������������������������� 8
Excessive Discharge from Safety Devices ���������������������������������������������������������������������������������������������������� 8
Pressure & Temperature Relief (PTR) Valve �������������������������������������������������������������������������������������������������� 8
Expansion Control Valve (ECV) - if required �������������������������������������������������������������������������������������������������� 8
Hydrogen Gas ��������������������������������������������������������������������������������������������������������������������������������������������������� 9
Turning O󰀨 the Water Heating System ����������������������������������������������������������������������������������������������������������� 9
Turning On the Water Heating System ����������������������������������������������������������������������������������������������������������� 9
Draining and Filling ������������������������������������������������������������������������������������������������������������������������������������������ 9
Maintenance and Regular Care ����������������������������������������������������������������������������������������������������������������������� 9
Save a Service Call 10
Specications 12
System Specications ����������������������������������������������������������������������������������������������������������������������������������� 12
Dimensions ����������������������������������������������������������������������������������������������������������������������������������������������������� 13
Clearances ������������������������������������������������������������������������������������������������������������������������������������������������������ 14
Installation 15
Regulations and Occupation Health and Safety (OH&S) ���������������������������������������������������������������������������� 15
Location ���������������������������������������������������������������������������������������������������������������������������������������������������������� 15
Internal Installation ��������������������������������������������������������������������������������������������������������������������������������������� 15
Condensation ����������������������������������������������������������������������������������������������������������������������������������������������� 16
Drainage ������������������������������������������������������������������������������������������������������������������������������������������������������� 16
Water Supply ���������������������������������������������������������������������������������������������������������������������������������������������������16
Storage Temperature ������������������������������������������������������������������������������������������������������������������������������������� 16
Hot Water Delivery Temperature ������������������������������������������������������������������������������������������������������������������� 16
Valves and Fittings ����������������������������������������������������������������������������������������������������������������������������������������� 16
Transport and Handling ��������������������������������������������������������������������������������������������������������������������������������� 17
Positioning the Heat Pump ���������������������������������������������������������������������������������������������������������������������������� 17
Connect the PTR Valve ����������������������������������������������������������������������������������������������������������������������������������18
Plumbing Connections ���������������������������������������������������������������������������������������������������������������������������������� 18
Connect Cold / Hot Water Supply ����������������������������������������������������������������������������������������������������������������� 18
Connect Condensate Drain line �������������������������������������������������������������������������������������������������������������������� 19
Electrical Tests ����������������������������������������������������������������������������������������������������������������������������������������������� 19
Conducting Insulation (Megger) Tests ���������������������������������������������������������������������������������������������������������� 19
Electrical Connections ����������������������������������������������������������������������������������������������������������������������������������� 19
Filling the System ������������������������������������������������������������������������������������������������������������������������������������������� 20
Finishing the Installation ������������������������������������������������������������������������������������������������������������������������������� 21
Operation Sequence of Controller ��������������������������������������������������������������������������������������������������������������� 21
Controller LED Flashing Codes �������������������������������������������������������������������������������������������������������������������� 22
Contact 24
Rinnai 3 EHPA_A Heat Pump OIM
WARNING
WARNING
WARNINGS AND IMPORTANT INFORMATION
SAFETY AND REGULATORY INFORMATION
DO NOT operate this system before reading the manufacturers instructions.
This appliance must be installed, commissioned and serviced by an authorised person in accordance with all applicable local rules and regulations.
Access covers of water heating system components will expose 240V wiring and MUST only be removed by an authorised person.
This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
For continued safety of this appliance it must be installed, operated and maintained in accordance with the manufacturer’s instructions.
Children should be supervised to ensure they DO NOT play with the appliance.
The unit is rated at 15 amps (2 core and earth) so the power mains supplying the unit must have a
15 amp minimum double pole circuit breaker tted. If the power supply cord is damaged, it MUST
BE replaced by an authorised person in order to avoid a hazard. Take care not to touch the power connections or plugs with wet hands.
Care should be taken not to touch the pipe work as it may be HOT!
RISK OF FIRE
DO NOT place articles on or against this appliance.
DO NOT store chemicals or ammable materials near this appliance.
DO NOT operate with collectors or covers removed from this appliance.
DO NOT activate heat pump unless cylinder is full of water.
NEVER use a ammable spray such as hair spray, paint, etc near this unit as this may cause a
re.
This appliance uses R290 (propane) refrigerant, which is a ammable gas class 3 according to AS
5149 and MUST be handled by a refrigeration mechanic with appropriate Australian refrigerant handling licence.
WARNING Risk of re / ammable material. If the refrigerant is leaked, together with an external
ignition source, there is a possibility of ignition.
MANDATORY INSPECTION PRIOR TO INSTALLATION
Immediately report any damage or discrepancies to the Supplier of the appliance. This
appliance was inspected and tested at the time of manufacture and packaging, and released for transportation without known damage. Upon receipt, inspect the exterior for evidence of rough handling in shipment. Ensure that the appliance is labelled correctly for the gas and electrical
supply, and/or other services it is intended to be connected to.
For safety and warranty purposes, appliances that may be damaged or incorrect must not be
installed or operated under any circumstances. Installation of damaged or incorrect appliances
may contravene local government regulations. Rinnai disclaims any liability or responsibility whatsoever in relation to the installation or operation of damaged or incorrect appliances.
NOTICE TO VICTORIAN CONSUMERS
This appliance must be installed by a person licensed with the Victorian Building Authority.
Only a licensed person will have insurance protecting their workmanship.
So make sure you use a licensed person to install this appliance and ask for your Compliance Certicate.
For further information contact the Victorian Building Authority on 1300 815 127
Rinnai 4 EHPA_A Heat Pump OIM
TRANSPORT AND STORAGE OF APPLIANCE
IMPORTANT
WARNING
The refrigerant used in the heat pump is a ammable gas.
WARNINGS AND IMPORTANT INFORMATION
RISK OF FIRE
The appliance(s) shall be stored and transported in an area without ignition sources (for example:
open ames, an operating gas appliance or an operating electric heater)
DO NOT pierce or burn the appliance.
Be aware that refrigerants may not contain an odour.
Compliance with AS/NZS 5149 MUST be observed while storing the appliance.
National and state regulations exist for storage, handling and transport of hazardous goods
including ammable gasses. The maximum number of pieces of equipment or the conguration of the equipment, permitted to be transported or stored together will be determined by the
applicable regulations.
IMPORTANT
DO NOT TILT
45°
MORE THAN 45
FROM VERTICAL°
The Rinnai Enviroo Electric Heat Pump must be transported at an angle no greater that 45º from vertical. As the
compressor unit is located at the top of the electric heat pump, should the heat pump be tilted at a greater angle
than 45º from vertical, the lubrication oil within the compressor can run down into the mufers. This will leave the compressor motor without sufcient lubrication and lead to premature failure of the compressor unit.
As a general good practice it is better to keep the compressor upright as much as possible to avoid any risks.
Returning the Rinnai Electric Heat Pump to a vertical position will not allow the oil to properly ow back into the
compressor motor.
Tilting Rinnai Hoto Electric Hot Water beyond 45º from vertical will also place undue strain on compressor motor
mounts and associated piping
Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.
The appliance shall be stored in a room without continuously operating ignition sources. For
example, open ames, an operating gas appliance or an operating electric heater.
Do not pierce or burn.
Be aware that refrigerants may not contain an odour.
Rinnai 5 EHPA_A Heat Pump OIM
WARNINGS AND IMPORTANT INFORMATION
SCALD HAZARDS
HOT WATER CAN CAUSE SCALDS.
CHILDREN, DISABLED, ELDERLY AND THE INFIRM ARE AT THE HIGHEST RISK OF BEING SCALDED.
FEEL WATER TEMPERATURE BEFORE BATHING OR SHOWERING.
SCALDS FROM HOT WATER TAPS CAN RESULT IN SEVERE INJURIES TO YOUNG CHILDREN.
SCALDS OCCUR WHEN CHILDREN ARE EXPOSED DIRECTLY TO HOT WATER WHEN THEY ARE PLACED INTO A BATH WHICH IS TOO HOT.
ALWAYS......
Test the temperature of the water with your elbow before placing your child in the bath, also carefully feel water before bathing or showering yourself.
Supervise children whenever they are in the bathroom.
Make sure that the hot water tap is turned o󰀨 tightly.
CONSIDER.....
Installing child proof tap covers or child resistant taps (both approaches will prevent a small hand being
able to turn on the tap).
Installing tempering valves or thermostatic mixing valves which reduce the hot water temperature delivered to the taps. Your local plumbing authority may already require that these be tted. Contact
your installer or local plumbing authority if in doubt.
NEVER….
Leave a toddler in the care of another child. They may not understand the need to have the water
temperature set at a safe level.
Rinnai 6 EHPA_A Heat Pump OIM
WARNINGS AND IMPORTANT INFORMATION
OPERATION PRINCIPLE
The operation of an electric heat pump is very similar to a refrigerator, but in reverse. A heat pump operates by transferring heat from the ambient outside air into the water. Electricity is just used to operate the system, but not
to directly heat the water. Because of this energy consumption is signicantly reduced as compared to an electric element hot water system. The warmer the climate in which the heat pump is installed, the more efcient the heat
pump system will be at heating water.
The heat pump unit includes a circulation pump which draws water from the bottom of the storage tank and returns it to the tank at a higher temperature. A temperature sensor in the tank is used to control the heat pump operation to achieve suitable tank temperatures.
During the occasional times when the ambient weather conditions aren’t suitable for the heat pump to operate, the electric element will provide heating to ensure a supply of hot water.
7
3
2
8
1. Cold water inlet pipe
2. Circulation Pump
6 5
12
11
13
12
1
13
4
10
9
8. Compressor
9. Heating Element
3. Plate Heat Exchanger
4. Hot Water from Heat Exchanger to the Tank
5. Intake Air
6. Discharge Air
10. Water Temperature Sensor
11. PTR Valve
12. Display & Control Panel
13. Mode Button
7. Fan Coil Unit
There are four indicators on the Display & Control Panel (12) which display the current operational mode /status of the heat pump. To select one of the three available operation modes described below, press the Mode Button (13) until the desired mode is illuminated.
MAX
For fast recovery the water will be heated to 60°C using a combination of the compression system and the heating element.
MID
ECO
ERR
The water will be heated to 57°C using the compression system only.
The water will be heated to 55°C by economical use of the compression system (this is the factory default).
This will ash red only if an error is detected with the heat pump operation, please call Rinnai for assistance
if this should occur, and refer to “Save a Service Call” on page 10 for additional information.
Rinnai 7 EHPA_A Heat Pump OIM
WARNING
WARNING
WARNING
WARNINGS AND IMPORTANT INFORMATION
SAFETY DEVICES
The water heating system is supplied with various safety devices including temperature sensors, overheat sensors and switches and a Pressure & Temperature Relief (PTR) valve. These devices must not be tampered with or
removed. The water heating system must not be operated unless each of these devices is tted and is in working
order.
DO NOT tamper with or remove safety devices.
DO NOT operate the water heater unless all safety devices are tted and in working order.
DO NOT block or seal the PTR Valve and drain pipe.
Pressure & Temperature Relief (PTR) Valve
This valve is located near the top of the water heater and is essential for safe operation. It is normal for the valve to release a small quantity of water through the drain line during heating.
Lift lev er until w ate r flows fr om d rain line
(L o w er lever g enlty !)
However, continuous leakage of water from the valve and its drain line may indicate a problem with the water heater.
NEVER block the outlet of the PTR valve or it’s drain line for any reason. The easing gear MUST be operated at least every 6 months to remove lime deposits and verify that it is not blocked. Failure to do this may result in the water heater failing.
If the valve does not discharge water when the easing gear lever is opened, or does not seal again
when the easing gear is closed, attendance by an authorised person MUST be arranged without
delay. The PTR valve is not serviceable.
EXCESSIVE DISCHARGE FROM SAFETY DEVICES
Pressure & Temperature Relief (PTR) Valve
It is normal and desirable that this valve allows a small quantity of water to be discharged during the heating cycle. If it discharges more than a bucket of water during a 24 hour period or discharges continuously there may be another problem.
If the valve dribbles continuously, try easing the valve gear for a few seconds as described above. This may dislodge any foreign matter and alleviate the problem.
If the valve discharges at high ows, especially at night, it may be as a result of the water pressure exceeding the design pressure of the water heater. Ask your installer to t a Pressure Limiting Valve (PLV).
NEVER replace the PTR valve with one which has a higher pressure rating than is specied for your
water heater.
Expansion Control Valve (ECV) - if required
It is normal that this valve allows a small quantity of water to be discharged during the heating cycle. If it discharges more than a bucket of water during a 24 hour period or discharges continuously there may be another problem.
If the valve leaks continuously, try easing the valve gear for a few seconds. This may dislodge any foreign matter and alleviate the problem. If this does not alleviate the problem contact Rinnai.
Operate the easing gear regularly to remove any lime deposits and to verify that it is not blocked.
Rinnai 8 EHPA_A Heat Pump OIM