2. Cool and Heat Function:
In cool mode:
A. Cooling systems works in below situation:
The measuring temperature ^ the set temperature + the temperature differential
B. Cooling systems stop working in below situation:
The measuring temperature ^ the set temperature
In heat mode:
A. Heating systems works in below situation:
The measuring temperature ^ the set temperature - the temperature difference;
B. Heating systems stop working in below situation:
The measuring temperature ^ the set temperature
3. Delay Time:
When power on for the first time, if The measuring temperature ^ the set temperature + the
temperature differential or The measuring temperature ^ the set temperature - the
temperature difference, the output will not be activated immediately, and will be activated after
the delay time.
If the time period between the previous stop and this starts is longer than the delay time, the
output will be activated immediately; if it is shorter than the delay time, the output will be
activated after the delay time. The delay time is calculated from the previous output stop.
4. High and low temperature limit:
HS and LS can set the high and low limit of the setting temperature:
For example: HS is +15, LS is -10, the temperature only can be set between -10~+15*C; so if
you want to set a value beyond this range, please reset the HS and LS firstly.
1. Sensor error alarm
When the controller is in power on status, if sensor open circuit, LED flash and display"
__",if sensor short circuit, display "HH". When in sensor error status, the output load will run as
the cycle: stop 15 minutes, then work 15 minutes.
2. Over temperature alarm
When the sensor temperature>99*C, display HH: When the sensor temperature<--40'C,
display LL.