Flange with insulating gasket No. 1 Screws and nuts for flange to be fixed to boiler .No. 4
Screw and nuts for flange No. 1 Flexible oil pipes with nipples . . . . . . . . . . . . . . No. 2
Remote reset connection . . . . . . . . . . No. 1
1.2ACCESSORIES
DIAGNOSTIC SOFTWARE KIT
A special kit is available that detects the life of the burner through optical connections with a PC showing
the duty hours, number and types of lockout, control box serial number etc...
Do the following to display the diagnostic:
³
Connect the kit supplied separately to the appropriate socket on the control box.
The information is read after the software program in the kit is booted.
REMOTE RESET KIT
The burner is fitted with a remote reset kit (RS) consisting of a connection to which a button can be con-
nected up to a distance of 20 meters.
For the installation, remove the protection block installed in the factory and install the block that is supplied
with the burner (see wiring diagram on page 6).
3260
GB
2
2.TECHNICAL DATA
2.1TECHNICAL DATA
TYPE377T1
Output – Thermal power4
FuelLight oil, viscosity 4
Electrical supplySingle phase,
− 10 kg/h–47− 119 kW
− 6 mm
50Hz 230 V ± 10%
~
2
/s at 20°C
MotorRun current 0.8A –2750 rpm.–288 rad/s
Capacitor4 µF
Ignition transformerSecondary8 kV–16 mA
PumpPressure: 8
− 15 bar
Absorbed electrical power0.18 kW
2.2OVERALL DIMENSIONS
202115189
ø95
255
°
5
4
106
11
8383
230
10
D5707
28
2.3FIRING RATE, (as per EN 267)
1.2
1.0
0.8
0.6
0.4
chamber – mbar
0.2
Pressure in combustion
°
280
5
4
140
168
3260
0
345Light oil output – kg/h
D5416
354555Thermal power – kW
67
6575
85
891011
95105115125
GB
3
3.INSTALLATION
THE BURNER MUST BE INSTALLED IN CONFORMITY WITH LEGISLATION AND LOCAL STANDARDS.
3.1WORKING POSITION
The burner is designed to work only in the positions, 1 and 2.
Installation 1 is preferable, as it is the only one that allows performing maintenance operations as described in this manual.
Installations 2 allow working operations but not maintenance with hooking to the boiler.
Any other position could compromise the correct working of the appliance.
Installations 3, 4 and 5 are forbidden for safety reasons.
12345
D7088
3.2BOILER FIXING
To install the burner on the boiler, do the following:
³
Put on the flange (1) the screw and two nuts (see fig. 3).
³
Widen, if necessary, the insulating gasket holes (5 fig.).
³
Fix the flange (1) to the boiler door (4) using screws (2) and (if necessary) the nuts (3) interposing the
insulating gasket (5), (see fig. 2).
Fig. 2
Fig. 3
3260
S7209
GB
4
3.3HYDRAULIC SYSTEMS
ATTENTION:
³
The burner is designed to accomodate the installation of
light oil supply pipes on either side of the burner.
³
It is necessary to install a filter on the fuel supply line.
³
The pump is designed for use with a two-pipe system.
In order to obtain one-pipe working, it is necessary to
unscrew the return plug (2), remove the by-pass screw (3)
and then screw the plug (2) up again, (see fig. 4).
³
Before starting the burner make sure that the return pipeline is not clogged. An excessive back pressure would
cause the damage of the pump seal.
On the system in fig. 5 it is sufficient to loosen the suction gauge connection
(5, fig. 4) and wait until oil flows out.
On the systems in fig. 6 and 7 start the burner and wait for the priming.
Should lockout occur prior to the arrival of the fuel, await at least 20 seconds before repeating the operation.
The pump suction should not exceed a maximum of 0.4 bar (30 cm Hg).
Beyond this limit gas is released from the oil. Oil pipes must be completely tight.
In the vacuum systems (fig. 7) the return line should terminate within the oil tank
at the same level as the suction line. In this case a non-return valve is not
required. Should however the return line arrive over the fuel level, a non-return
valve is required. This solution however is less safe than previous one, due to the
possibility of leakage of the valve.
Fig. 6Fig. 7
H
H
max. 4 m
H
meters
0
0.5
1
1.5
2
3
3.5
max. 4 m
L meters
ø i
8 mm
35
30
25
20
15
8
6
ø i
10 mm
100
100
100
90
70
30
20
H
H
D5711
ONLY FOR ITALY: Automatic cut-off device as per Ministry of Internal Affairs’ regulation n° 73 dated 7/29/71.
H = difference of level; L = max. length of the suction line; ø i = internal diameter.
3260
GB
5
3.4ELECTRICAL WIRING
MO550
CONTROL BOX
D4684
WARNING:
³
Do not swap neutral and phase over, follow the diagram shown carefully and carry out a good earth connection.
³
The cross section of the wires must be at least 1 sq. mm.
(Unless requested otherwise by local standards and legislation).
³
The electrical wiring carried out by the installer must comply with the rules in force in the country.
TESTING
³
Check the burner has stopped by opening
the thermostats.
³
Check the burner's lockout during operation by interrupting the flame detector.
KEY TO LAY-OUT:
C– Capacitor
E– Electrode
F– Flame detector
h1– Hour counter
MV – Motor
CONTROL BOX, (see fig. 8)
To extract the control box from the burner it is necessary:
³
to disconnect all the connectors connected to it, the 7 pin plug, and
the earth wire (TB);
³
undo the screw (A) and pull out the control box in the direction of
the arrow.
For the installation of the control box it is necessary:
³
to tighten up the screw (A) with a torque of 1 to 1.2 Nm;
³
connect all the connectors that were previously connected.
NOTE:
The burners have been approved for intermittent operation.
This means that they must stop once every twenty four hours to permit
the electrical control box to check its efficiency at start up.
Normally the boiler's limit thermostat (TL) ensures the stopping of the
burner. If this is not the case, it is necessary to apply in series with
(TL) a timer switch that turns off the burner at least once every twentyfour hours.
3260
GB
6
4.BURNER OPERATION
ATTENTION
!
QUALIFIED PERSONNEL WITH THE RIGHT INSTRUMENTS MUST HANDLE THE BURNER'S
START-UP.
4.1COMBUSTION ADJUSTMENT
In conformity with Efficiency Directive 92/42/EEC, the application of the burner on the boiler, adjustment and
testing must be carried out by observing the instruction manual of the boiler, including verification of the CO
and CO
boiler. To suit the required appliance output, choose the proper nozzle and adjust the pump pressure, the
setting of the combustion head, and the air damper opening in accordance with the following schedule.
The values shown in the table are measured on a CEN boiler (as per EN 267), and they refer to 12.5 % CO
at sea level and with light oil and room temperature of 20 °C.
concentration in the flue gases, their temperatures and the average temperature of the water in the
2
2
NozzlePump pressure
GPHAnglebarkg/h ± 4%Set-pointSet-point
1.0060°124.000.9
1.1060°124.413.1
1.2560°125.023.4
1.5060°126.033.8
1.7560°127.044.5
2.0060°128.054.9
2.2560°149.866.0
Burner
output
Combustion head
adjustment
Air damper
adjustment
4.2RECOMMENDED NOZZLES
Delavan W - B type;Danfoss S - B type;
Monarch R type;Steinen S - Q type.
For nozzles of 1.75 - 2.00 - 2.25 GPH, it is advisable to use full cones.
4.3PUMP PRESSURE
It leaves the factory set at 12 bar. To change it act on pump pressure screw (4, fig. 4, page 5).
4.4ELECTRODE ADJUSTMENT, (see fig. 9)
ATTENTION
MEASURES MUST BE RESPECTED
Lean the diffuser disc-holder assembly (1) on the nozzle-holder (2) and
lock it by screw (3).
For prospective adjustments loosen
screw (4) and move the electrode assembly (5).
To access the electrodes do the following described in chapter “4.5 MAINTE-NANCE POSITION” (page 8).
3260
GB
7
0
4.5 – 0.5 mm
4
5
Fig. 9
4 to 5 mm
123
D5537
4.5MAINTENANCE POSITION, (fig. 10 and 11)
ACCESSIBILITY TO THE NOZZLE, THE DIFFUSER DISC AND THE ELECTRODES IS MADE EASY IN 2 WAYS:
³
Unscrew and remove the fixing nuts to the
flange and remove the burner from the boiler.
³
Hook the burner onto flange (1), loosen the
screws (3) and remove the nozzle (2).
³
Remove the small cables (4) from the electrodes, loosen the screw (3 fig. 9 page 7) and
remove the diffuser disc-holder assembly (5)
from the nozzle-holder assembly (7).
³
Screw up the nozzle (6) holding the nozzle support with a spanner.
³
Refit following the operations in the reverse
order to the one described above.
Fig. 10
2
3
³
Undo the wires (4) from the control box, the
flame detector (8) and undo the nut (9) from the
pump.
³
Loosen the screws (10) and extract the nozzle
holder assembly (7) by turning to the right.
³
Remove the small cables (4) from the electrodes, loosen the screw (3 fig. 9 page 7) and
remove the diffuser disc-holder assembly (5)
from the nozzle-holder assembly (7).
³
Screw up the nozzle (6) holding the nozzle support with a spanner.
³
Refit following the operations in the reverse
order to the one described above.
Fig. 11
410
5
8
6
1
4
9
7
5
7
6
E9316
E9315
Fig. 12
ATTENTION
During the reassembly of the nozzle-holder assembly
screw the nut (9) as shown in fig. 12.
3260
TIGHTEN WITHOUT MOVING
BACKWARDS TO THE END
GB
8
9
D5684
4.6COMBUSTION HEAD ADJUST-
MENT, (see fig. 13)
The adjustment of the combustion head varies
depending on the burner output.
Do the following to adjust it:
³
Rotate the setting screw (11) clockwise or counterclockwise until the set-point marked on the
regulating rod (12) is level with the outside plane
of the nozzle-holder assembly (7).
³
In the example the regulating rod (12) is set at
notch 3; this means that the burner is regulated
for an output of 6 Kg/h with pump pressure at 12
bar and with the use of a nozzle of 1.50 GPH, as
indicated in the reference table.
Fig. 13
1411
13
12
4.7AIR DAMPER ADJUSTMENT,
(see fig. 13)
To regulate the air damper, do the following:
³
Loosen the nut (13) and set the air damper by turning the screw (14).
³
When burner shuts down the air damper automatically close still a max. chimney depressure of
0.5 mbar.
³
When the adjustment is completed do the nut (13) up again.
7
3260
GB
9
4.8OPERATING PROGRAMME
4.8.1NORMAL OPERATION WITH PREHEATING
P
TL
t
MV
V1
I
LED
LED
1
t
2
M
F
Loss of flame during operation (Recycle max. 3 attempts)
MV = stopped
F
D7359
t
3
t
4i
t
s
t
Green
YellowYellow
Green
YellowYellowYellow
No signal needs to be received
5i
t
4l
.
Lockout
Red
KEY TO LAY-OUT
F– Flame detector
I– Ignition transformer
LED – Reset button LED indicating operating
status
MV – Fan motor
TL – Limit thermostat
V1 –Oil valve
Red
Green + Yellow slow blinking
Green + Yellow fast blinking
Green
Green + Yellow medium blinking
Red + Yellow fast blinking
Yellow fast blinking
OPERATING TIMES
t1max1t4i-8
t1Imax30t5i-3
t2-3t4Imax1
t3-15t6max360
t3Imax1t6Imax30
ts-5t7-120
3260
Waiting time of a control box input signal: reaction time,
t1
the control box stands still for the time t1.
Presence of extraneous light before the heat request: if
t1I
the presence of light during the t1l time, a block follows.
Wait time after a request for heat:
t2
the control box stays still for the t2 time.
Pre-purging time:
t3
start of the fan motor.
Presence of an extraneous light during pre-purging:
t3I
immediate block.
Safety time: if at the end of the ts time there is no flame,
ts
a block follows.
10
Time is expressed in seconds
Transformer turn on time:
t4i
total turn on time ts + t5i.
Transformer post- turn on time:
t5i
additional turn on time after ts.
Flame loss in operation: maximum oil valve drop reac-
t4I
tion time, after three recycle attempts a block follows.
Post-purging time:
t6
additional purging time on the opening of the heat limit
thermostat (TL)
Presence of an extraneous light during post-purging. if
t6I
the presence of light lasts the t6l time, a block follows.
Long pre-purging time:
t7
pre-purging time more than t3.
GB
4.8.2LOCKOUT DUE TO FIRING FAILURE
P
TL
t
MV
V1
I
LED
1
t
2
M
F
t
3
Green
t
4i
t
s
Green+Yellow
Red
D7360
KEY TO LAY-OUT
F– Flame detector
I– Ignition transformer
LED – Reset button LED indicating operating
status
MV – Fan motor
TL – Limit thermostat
V1 –Oil valve
Red
Green + Yellow slow blinking
Green + Yellow fast blinking
Green
4.8.3LOCKOUT DUE TO EXTRANEOUS LIGHT
DURING PRE-PURGING
Extraneous light during standbyYellow blinkingFast0.30.3
Extraneous light during post or continuous purging (*)Green + Yellow blinkingFast0.30.3
Extraneous light during lockoutRed + Yellow blinkingFast0.30.3
LockoutRed
Lockout with continuous purging (*)Red + Green
(*) only for applications provided for.
Blinking
speed
ONOFF
Seconds
4.8.4LOCKOUT TYPES AND TRIGGERING TIMES IN CASE OF BURNER MALFUNCTION
DESCRIPTION OF THE FAULT TYPESBLOCK
Extraneous light when the burner is turned on and offAfter max. 30 seconds
Extraneous light detected during pre-purgingWithin 1 second
Extraneous light detected during post-purging or continuous purging (*)After max. 30 seconds
Flame goes out during operationAfter 3 recycles
No flame is detected after safety timeImmediate
(*) only for applications provided for.
4.8.5CONTROL BOX RESET
To reset the control box, proceed as follows:
³
Press and hold the reset button for between 1 and 2 seconds. If the burner does not restart, you must
make sure the limit thermostat (TL) is closed.
³
If the control box reset button continues to blink signalling the cause of the failure (RED LED), it is
necessary to press the button again for no more than two seconds.
4.8.6RECYCLE FUNCTION
The control box allows a recycle, i.e. complete repetition of the start-up programme, making up to 3 attempts, in
the event the flame goes out during operation.
If the flame goes out again, this will cause the burner to lock out. If there is a new demand for heat during the recycle, the 3 attempts are reset when the limit thermostat (TL) switches.
4.8.7LOGGING OF BURNER OPERATING PARAMETERS
With this control box, data - i.e. the number of blocks that have occurred, the type of block that has occurred
(just the last one) and the oil valve opening operating time - can be logged even when there is no power supply.
That way, you can determine how much fuel has been consumed during operation.
To display these parameters, it is necessary to connect the software diagnosis kit as described in paragraph
(1.2) page 2.
3260
GB
12
4.9ADDITIONAL, PROGRAMMABLE CONTROL BOX FUNCTIONS
4.9.1POST-PURGING FUNCTION (t6)
Post-purging is a function that keeps air purging on even after the burner switches off. The burner switches off
when the limit thermostat (TL) opens, consequently cutting off the fuel supply to the valves. To use this function
the reset button must be pressed when the limit thermostat is not switched over (burner switched off).
Post-purging time can be set to a maximum of 6 minutes, proceeding as follows:
³
Press and hold the reset button for at least 5 seconds till the LED indicator changes to red.
³
Set the desired time by pressing the button the appropriate times: once = post-purging for 1 minute.
³
After 5 seconds the control box automatically shows the minutes set by the red LED blinking: 1 led pulse =
post-purging for 1 minute.
To reset this function, press and hold the button for at least 5 seconds at least, till the LED indicator changes to red
then release it without carrying out any operation, then wait for 20 seconds for the burner to start again.
If during post-purging there is a new request for heat, post-purging time is halted and a new burner operating cycle starts when the limit thermostat (TL) switches.
If during post-purging there is an extraneous light the burner blocks after thirty seconds.
The control box's factory settings are as follows: 0 minutes = no post-purging.
4.9.2CONTINUOUS PURGING FUNCTION, (only for applications in which this is provided for)
Continuous purging is an operation that maintains the air purging regardless of whether there is a request for the
burner to turn on or not. From the moment it is set, the motor keeps running whether the limit thermostat (TL) has not
been switched (burner off), or when the burner is blocked.
Only when the limit thermostat (TL) is switched does the motor stop for the standby time of four seconds (stand-
by position = t2 + t1).
The function can be set from the reset button when the limit thermostat (TL) is not switched (burner off), by
following the procedure in the post-purging function paragraph 4.9.1 by pressing the button 7 times = con-
tinuous purging.
To reset this function, press and hold the button for at least 5 seconds at least, till the LED indicator changes to red
then release it without carrying out any operation, then wait for 20 seconds for the burner to start again.
If when the limit thermostat (TL) switches, there is an extraneous light the motor stops as long as the extraneous light is there followed by the block.
The control box's factory settings are as follows: 0 minutes = no continuous post-purging.
4.9.3LONG PRE-PURGING (t7) FUNCTION
The long pre-purging makes it possible too lengthen the purging of the air by the switching of the limit thermostat (TL) on the ignition of the flame for up to two minutes. The function can be set from the reset button
when the limit thermostat (TL) is not switched (burner off), by following the procedure in the post-purging
function paragraph 4.9.1 by pressing the button 8 times = long pre-purging.
To reset this function, press and hold the button for at least 5 seconds at least, till the LED indicator changes to
red then release it without carrying out any operation, then wait for 20 seconds for the burner to start again. The
control box's factory settings are as follows: 0 minutes = no long pre-purging.
4.9.4FUNCTION SETTING PROCEDURE USING RESET BUTTON
Control box function
CONTROL BOX
Reset1 to 2 secondsAfter control box lockout
Visual diagnostics of lockout causes
(5.1)
Post-purging (4.9.1)
Continuous purging (4.9.2) (only for
applications provided for).
Long pre-purging (4.9.3)
Resetting set functions5 seconds
Resetting operating parameters5 seconds
3260
Action with the reset buttonReset button inabled status
3 secondsAfter control box lockout
5 seconds then press
once = 1 minute
5 seconds then press
7 times = continuous purging
5 seconds then press
8 times = long pre-purging
GB
13
With limit thermostat (TL) not
switched (burner off)
With limit thermostat (TL) not
switched (burner off)
With limit thermostat (TL) not
switched (burner off)
With limit thermostat (TL) not
switched (burner off)
With limit thermostat (TL) switched
during pre-purging
5.MAINTENANCE
Before carrying out any cleaning or control operation, cut off the electricity supply to the burner using
the system's main switch and close the oil cut off valve.
The burner requires periodic maintenance carried out by a qualified and authorised technician in conformity
with legislation and local standards.
Periodic maintenance is essential for the reliability of the burner, avoiding the excessive consumption of fuel and consequent pollution.
THE BASIC CHECKS ARE:
³
Check that there are no obstructions or kinks in the supply or return oil pipes, in the air intake regions
and the combustion product discharge tubes.
³
Check the proper positioning of the combustion head and its fixing to the boiler.
³
Clean the combustion head in the oil outlet area.
³
Clean the filter in the oil suction line and in the pump.
³
Check that the electrical wiring of the burner have been made properly.
³
Clean the flame detector.
³
Check the correct oil consumption.
³
Check that the combustion head (fig. 13 page 9) and the air damper (fig. 13, page 9) have been regulated properly.
³
Replace the nozzle (fig. 10 and 11, page 8) if necessary and check the correct position of electrodes
(fig. 9, page 7).
³
Clean the fan.
Leave the burner working without interruptions for 10 min. and set all the components stated in this manual
properly. Then carry out the analysis of the scale combustion by checking:
- Smoke index as per Bacharach;- CO
Percentage (%);
2
- CO Content (ppm);
- NOx content (ppm);- Smoke temperature at the chimney.
5.1VISUAL DIAGNOSTICSCONTROL BOX
The control box features a diagnostics function through which any causes of malfunctioning can be identified (indicator: RED LED).
To use this function, you must press and hold the reset button for at least 3 seconds once it has entered the
safety condition (lockout).
The control box generates a sequence of led pulses, which is repeated at constant 2-second intervals.
RED LED illuminated
press reset for 3 sec.
The sequence of led pulses issued by the control box identifies the possible types of malfunction, which are
listed in the table below.
Interval
2sPulsesPulses
2 pulses
4 pulses
3260
SIGNALPROBABLE CAUSE
The flame does not stabilise at the end of the safety time:
– flame detector faulty or dirty;
Light present in the chamber before the burner’s switching on or off:
– presence of extraneous light before or after the limit thermostat switching over;
– presence of extraneous light during pre-purging;
– presence of extraneous light during post-purging.
GB
14
SIGNALPROBABLE CAUSE
7 pulses
Loss of flame during operation:
– poor burner regulation;
– oil valve faulty or dirty;
– flame detector faulty or dirty.
8 pulses
ATTENTION
To reset the control box after the diagnostics display, press the lockout-reset button.
Check and monitor oil heater (if fitted):
– check the correct position of the bridge socket "P".
6.FAULTS / SOLUTIONS
Here below you can find some causes and the possible solutions for problems that could cause a failure to start
or a bad working of the burner.
A fault usually makes the lockout lamp light which is situated inside the reset button of the control box (3, fig. 1,
page 2).
When lock out lamp lights the burner will attempt to light only after pushing the reset button. After this if the burner functions correctly, the lockout can be attributed to a temporary fault. If however the lock out continues, the
cause must be determined and the remedies shown in the following table adopted.
6.1START-UP PROBLEMS
FAULTPOSSIBLE CAUSESSOLUTION
The burner does not
start when the limit
thermostat closes.
The burner goes in
safety lockout
before or during the
pre-purging.
Burner runs normally in the prepurge
and ignition cycle
and locks out after 5
seconds ca.
Check presence of voltage in the
L1 - N clamps of the 7 pin plug.
Lack of electrical supply.
Bridge socket “P” missing or disconnected.
The connections in the control box
are wrongly inserted.
The flame detector sees extraneous
light.
The flame detector is dirty.Clear it.
The flame detector is faulty.Replace it.
Flame moves away or fails.
Check the conditions of the fuses.
Check that safety thermostat is not lock
out.
Connect it up properly.
Check and connect completely all the
plugs.
Eliminate the light.
Check pressure and output of the fuel.
Check air output.
Change nozzle.
3260
15
Check the coil of solenoid valve.
GB
FAULTPOSSIBLE CAUSESSOLUTION
The ignition electrodes are wrongly
positioned.
Burner starts with an
ignition delay.
Air output is too high.
Nozzle dirty or worn.Replace it.
6.2OPERATING IRREGULARITIES
FAULTPOSSIBLE CAUSESSOLUTION
Flame disappears four times.
Burner locks out
during operation.
Does not shut down.
Adjust them according to the instructions of this manual.
Set the air output according to the instructions of this manual.
Clean or replace the flame detector.
Replace the dirty or deteriorated nozzle.
Check efficiency of flame detector.
Check efficiency pressure regulator’s piston.
Check efficiency of pump’s on-off valve.
3260
16
GB
7.SAFETY WARNINGS
The dimension of the boiler’s combustion chamber must respond to specific values, in order to guarantee a
combustion with the lowest polluting emissions rate.
You are therefore advised to consult the Technical Assistance Department before choosing this type of burner for the combination with a boiler. Qualified personnel are those with the professional and technical requirements indicated by law no. 46 dated March 5, 1990 n° 46.
The commercial organisation has a widespread network of agencies and technical offices whose personnel
participates periodically in instructional and refresher courses at the company training centre.
This burner must only be used for the purposes it has specifically been designed for.
All contractual and other liability on the part of the manufacturer is excluded for injury caused to people, animals or damage caused to property due to faulty installation, calibration, adjustment, maintenance or improper use.
7.1BURNER IDENTIFICATION
The Identification Plate on the product gives the serial number, model and main technical and performance
data. Tampering with, removal or absence of the Identification Plate will mean it is not possible to identify
the product with certainty and therefore make any installation or maintenance difficult and/or dangerous.
7.2BASIC SAFETY RULES
³
Children or inexpert persons must not use the appliance.
³
Under no circumstances must the intake grids, dissipation grids and ventilation vents in the installation
room be covered up with cloths, paper or any other material.
³
Unauthorised persons must not attempt to repair the appliance.
³
It is dangerous to pull or twist the electric leads.
³
Cleaning operations must not be performed if the appliance is not disconnected from the main power supply.
³
Do not clean the burner or its parts with inflammable substances (e.g. petrol, alcohol, etc.). The cover
must be cleaned with soapy water.
³
Do not place anything on the burner.
³
Do not block or reduce the size of the ventilation vents in the installation room.
³
Do not leave containers and inflammable products in the installation room.
3260
17
GB