Rice Lake UMC600IS User Manual

UMC 600IS
Intrinsically Safe Weight Indicator
Installation Manual
58645
Contents
About This Manual................................................................................................................................... 1
1.0 Introduction.................................................................................................................................. 1
1.1 Factory Mutual Approval . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 System Limitations and Restrictions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
1.3 Front Panel Keypad and Annunciators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.0 Installation and Wiring................................................................................................................ 4
2.1 Hazardous Area Installation of the UMC 600IS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1.1 Conduit System (Supplied by Customer). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2 Cable Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.3 AC Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.4 Battery Option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.4.1 Modes of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.4.2 Configuration for Battery Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.5 Instrumentation Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
2.6 Load Cell Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.7 Serial Port Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.8 Troubleshooting and Testing the 600IS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
2.8.1 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
3.0 Configuration.............................................................................................................................. 11
3.1 Digital Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.1.1 Parameter Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.1.2 Configuration Procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.1.3 Digital Configuration Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.2 Serial Port Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.3 Options Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.3.1 Option 1 – Expanded Resolution. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.3.2 Option 2 – Analog Output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
3.3.3 Option 3 – Time and Date. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
3.3.4 Option 4 – Auto Shutoff Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.3.5 Option 6 – Five-Point Linear Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.3.6 Option 7 – Smart Serial I/O. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3.4 Setting Up Custom Transmits (Smart I/O) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3.4.1 Enabling Option 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
4.0 Calibration.................................................................................................................................. 30
4.1 Zero Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.2 Single Slope Span Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.3 Five-Point Linear Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
4.4 Calculations Example. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
5.0 Normal Weighing Mode Operations.......................................................................................... 32
5.1 Display Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.1.1 Display Check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.1.2 EPROM Verification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.2 LED Annunciators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.3 Function Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.4 Gross/Tare/Net Weighing Operations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.4.1 Display Mode on Power Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.4.2 ZERO Key Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Specifications subject to change without notice.
May 2002
ii
5.4.3 TARE Key Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.4.4 Overload and Underrange Conditions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.4.5 Lb/Kg Conversion. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.5 Fixed Tare Entry. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.6 Serial Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.6.1 Serial Data Formats . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.6.2 Demand Mode versus Continuous Data Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
6.0 Appendix.................................................................................................................................... 36
6.1 Error and Status Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6.2 Parameter Control Code Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
6.3 ASCII Character Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
6.4 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
UMC 600IS Limited Warranty................................................................................................................. 43
IQ 700IS Installation Manual
About This Manual
The UMC 600IS digital weight indicator represents the latest in state-of-the-art microprocessor technology specifically applied to the weighing marketplace. This manual provides information on installation, calibration, configuration, and operation of the UMC 600IS.
The installer should be familiar with the National Electrical Code and RP 12.6 ( Recommended Practice ) requirements for installation of equipment in hazardous areas (NEC Article 504, Intrinsically Safe
Systems ) published through the Instrument Society of
America.
Warning
modifications are made to the installation procedure, the enclosure is opened, or the instrumentation is changed in any way, Factory Mutual approval is void and the customer becomes fully responsible for such modifications.
This instrument and accompanying equipment must be installed and serviced by an authorized technician in accordance with the instructions provided in this manual. Improper specification, installation, or service of this equipment could result in personal injury or property damage.
The UMC 600IS is a Factory Mutual-approved system. This approval is valid only if the installation conforms to the guidelines described in this manual. If
Authorized distributors and their employees can view or download this manual from the Condec distributor site at
www.4condec.com
.
1.0 Introduction
The UMC 600IS is a single-channel digital weight indicator designed and approved to operate as an intrinsically safe system in a wide variety of scale and weighing applications. The indicator is housed in a NEMA 4X stainless steel sealed case. The standard unit is equipped with a tilt stand base for tabletop or wall mounting applications. The indicator front panel consists of a 21-button keypad, six digit, seven-segment display and 11 LED annunciators (see Figure 1-1 on page 2).
Features of the UMC 600IS include:
Full front panel digital configuration and calibration
Zero and span temperature compensation to ensure compliance with NTEP temperature range requirements (–10 to 40°C)
•Nonvolatile memory stores data for calibration, temperature compensation, configuration parameters, auto or fixed tare values, and PAZ and AZM values
•T
en-thousand displayed graduations;
80,000 graduation expansion available
NOTE:
undesirable display instability in some applications.
Use of more than 20,000 graduations may cause
•Analog sensitivity to 0.3
µ
V/grad at 20,000
graduations
•Ten updates per second, with selectable digital averaging and auto averaging; 5 Hz active analog filter for smooth response
Excitation for four 350
load cells at 5 VDC
•Operable from DC power supply or optional battery
•Time and date print selection
1.1 Factory Mutual Approval
The UMC 600IS is Factory Mutual (FM) approved for:
Classes I, II, and III,
•Divisions 1 and 2, and
•Groups A, B, C, D, E, F and G
The Factory Mutual (FM) approval is a system approval for all devices connected directly to the UMC 600IS digital weight indicator.
Other devices that have FM Entity Approval cannot be used with this system unless specifically listed in this manual as part of the Condec Factory Mutual systems approval. Failure to comply with this voids the FM approval. The control drawing is the guide to the installation of this system.
Introduction
1
2
1.2 System Limitations and Restrictions
The following items represent limitations and restrictions on the use of the UMC 600IS:
•All instrumentation must have identification nameplates in compliance with the control drawing.
•All wiring, connections, conduit and grounds must comply with the National Electrical Code.
The cable type and cable length must comply with the specifications in the control drawing
•No modifications can be made in the field.
•Factory Mutual Approval required (see Section 1.1 on page 1).
It is mandatory to return the UMC 600IS to Condec for service.
•Component level repair is not permitted on Factory Mutual Approved equipment.
Standard unit configuration is without local sense jumpers installed. Therefore, use either six-conductor loadcell cable or externally jump +SEN to +EXC and –SEN to –EXC.
1.3 Front Panel Keypad and Annunciators
Figure 1-1 shows the UMC 600IS front panel. The UMC 600IS display consist of a six digit, seven-segment display. Table 1-1 lists the front panel keys and their functions.
lb kg MOTION
PRINT
POINT
POINT
1 SET
2 SET
ZERO
TARE
RECALL
ZERO
NET
GROSS
CAPACITY
NET
GROSS
600 x 0.1
TARE
162738495
0
lb/kg
CONV
CE
ENT
Figure 1-1. UMC 600IS Front Panel
Panel Key
ZERO Provides push-button auto zero (PAZ) over ±1.9% or 100% full scale capacity. Operates only in gross
weighing mode. NET/GROSS Switches the unit between gross and net weighing modes. TARE
PRINT Provides a manual print function if unit is wired to serial printer or other data device. lb/kg CONV Switches the displayed weight unit between pounds and kilograms. TARE RECALL Press to recall tare value; LED annunciator flashes when tare value is displayed. ON/OFF Provides power to the indicator. SETPOINT 1 & 2 No function. Setpoints are not supported for this indicator. 0–9, CE, ENT Numeric keyboard for entry of manual tare and calibration data. Includes CE (Clear Entry) and ENT (Enter)
Provides push-button tare entry over 100% of scale capacity. Pressing
and enters tare.
keys.
Function
TARE
key switches to net mode
UMC 600IS Installation Manual
Table 1-1. Front Panel Key Functions
Table 1-2 summarizes the front panel annunciator functions.
Annunciator
LOW BATTERY On when DC input voltage drops below normal operating range. (Located in the display window of
the 600IS).
ZERO On when scale weight is within ±0.25 displayed graduations of zero. Used in gross weighing mode
only. NET On when the indicator is in net weighing mode. GROSS On when the indicator is in gross weighing mode. lb/kg lb or kg LED is lit to show the current displayed weight units. MOTION On when scale is in motion. 1 SETPOINT
2 SETPOINT TARE RECALL Part of the TARE RECALL key, LED flashes when tare value is displayed.
No function.
Function
Table 1-2. Front Panel Annunciators
Introduction
3
4
2.0 Installation and Wiring
This section describes the procedures for installing the UMC 600IS indicator, including load cell, digital input, and serial communications cabling.
It is mandatory to return the UMC 600IS to Condec for service. Component level repair is not
Caution
!
2.1 Hazardous Area Installation of the UMC 600IS
The following information is provided to help the installer use the correct conduit and load cells for installation of the UMC 600IS.
Drawings Required for this Installation
Table 2-1 shows the UMC 600IS control drawing numbers and titles. The UMC 600IS drawings are included in the back of this manual.
permitted on Factory Mutual Approved equipment by other than the manufacturer.
Control Drawing Title
54136, Sheet 1 Installation Drawing I.S. system 54136, Sheet 2 Interconnect Diagram 54136, Sheet 3 Interconnect Diagram, Battery Operated 54136, Sheet 4 Standard Unit Dimensions 54136, Sheet 5 Battery Powered Unit Dimensions 54136, Sheet 6 Unit Mounting Diagram 54136, Sheet 7 Power Supply Mounting Diagram 54136, Sheet 8 Junction Box Diagram 54136, Sheet 9 Junction Box Diagram, Battery Operated
53146, Sheet 10 I/O Interface Mounting Diagram
56804 Summing Box Diagram, 2-4 Load Cells 56810 Summing Box Diagram, 5-8 Load Cells
65476, Sheet 1-5 Approved Load Cell List
Table 2-1.
2.1.1 Conduit System (Supplied by Customer) Power Supply to Indicator
UMC 600IS
Conduit is not required for this installation. However, a separate conduit system is recommended. The type suggested for this application is 3/4 inch rigid steel conduit with pull boxes located at required intervals. The conduit provides additional noise protection for the low level signals, while automatically complying with the requirements for 2 inch separation between intrinsically safe circuits and other electrical cables. Conduit seals are required where a gas tight seal is required between the hazardous area and the safe area.
UMC 600IS Installation Manual
Drawing Number Identification
To protect the watertight integrity of the I/O barrier and junction box, the conduit should terminate adjacent to the respective enclosure with a union providing the proper thread to accept a Hubbel or Crouse Hinds cord connector for the cable to exit the conduit. All conduit, fittings, and conduit accessories are provided and installed by the customer.
NOTE:
installation of all conduit seals in compliance with all National Electrical Code regulations.
AC Line Voltage Feed
The customer is responsible for the correct
The installer must comply with Condec installation drawings as well as the National Electrical Code for installation of equipment in hazardous areas (NEC Article 504, Instrinsically Safe Systems ).
2.2 Cable Requirements
Intrinsically safe cables used in the hazardous area are specified on the Control Drawings 54136, Sheets 2 and 3. Since all cables have internal inductance and capacitance, only the cables listed are safe to use with this
intrinsically safe system. Table 2-2 provides specifications for maximum cable length based on group classification. A list of Factory Mutual approved cables is shown in Table 2-3.
FM-Approved
load cells
(Up to 4)
RECALL
Junction
Box
ZERO
NET
GROSS
ZERO
TARE
CAPACITY
NET
TARE
GROSS
162738495
Cable 3
Load Cell
600 x 0.1
lb kg MOTION
lb/kg
PRINT
CONV
1 SET POINT
CE
2 SET
ENT
0
POINT
Cable 2
Power
Cable 1
Divisions I and 2 Class I, Groups A, B, C, D Class II, Groups E, F, G Class III
Serial I/O
Safe AreaHazardous Area
I/O
Isolation
Barrier
Power
Supply
115 VAC
Battery Power
Supply Models
Only
Figure 2-1. Intrinsically Safe System Diagram
Either power supply or battery can be used, but not both simultaneously.
Note:
Maximum Cable Length,
Group Cable 1 Cables 2 & 3
A, B 75' 800'
C 300' D 500'
E, F, G
Table 2-2. Maximum Cable Lengths
Factory Mutual Approved Cable
Cable Type Condec PN Belden P/N
1 Power 2 Serial I/O 3 Load Cell
(
) = feet in increments of 50
x
45897 ( 45898 ( 45898 (
x x x
Battery
Charger
) ) )
8618 9942 9942
!
Caution
Table 2-3. FM Approved Cable Lengths
Use only Factory Mutual approved cables.
Installation and Wiring
5
6
2.3 AC Power Wiring
Standard units are powered by 115 VAC into Condec DC output power supply (Condec PN 58805).
2.4 Battery Option
The battery operated version of the UMC 600IS is powered by a 6-volt 10-ampere-hour battery that is enclosed in a stainless steel housing. It is mounted below the indicator and is removable for charging in the safe area.
Caution
!
The battery is approved for use in hazardous environments and provides up to 51 hours of continuous operation in a four by 350 system. Table 2-4 illustrates estimated operating times based on a fully charged battery.
Load Cell Size
load cell 1 70 hours
350
load cell 1 74 hours
700
The battery pack is ideal for limited use operations such as bench scales and platform scales. A low battery LED annunciator indicates when the battery needs to be recharged (see Figure 2-2). The recommended initial battery charge time is 10 hours.
Caution should be used when considering a battery powered unit for control applications where a discharged battery would cause serious problems.
load cell
Quantity of cells Operating Time
2 62 hours 3 56 hours 4 51 hours
2 70 hours 3 66 hours 4 62 hours
Table 2-4. Operating Time
The battery pack is designed for easy removal and can be recharged in a safe area in eight hours or less. The indicator also contains a programmable auto shutoff to power off the indicator when not in use.
Caution
!
2.4.1 Modes of Operation
All wiring must be done by qualified personnel and meet all appropriate safety and NEC electrical codes as noted on Condec Control Drawing
33476.
The UMC 600IS battery powered unit has three modes of operation:
Push on-off (controlled from the front panel on button).
Push on with auto turn off after selected time (one to nine minutes).
•Auto turn off, same as above with restart of time cycle if motion is detected on the scale (prevents the scale from turning off while in use).
2.4.2 Configuration for Battery Operation
The configuration for battery operation is as follows:
1. The clock function in Option 3 must be enabled and set if Option 4 is to be used (see Section 3.3.3 on page 22).
2. Option 4 must be set as follows (see Section
3.3.4 on page 23 for further details).
A. Option 4 off (unit operates as push on - push off) B. Option 4 on (the turn off timer is enabled) C. Parameter 4.1 selects the turn off time (1 to 9 minutes) D. Parameter 4.2 set to off runs normally/turns off at end of
time cycle. E. Parameter 4.2 set to on will restart timing function when
unit is timing and motion is detected on the scale.
Table 2-5. Configuration of Battery Operation
Low Battery Annunciator
ZERO
NET
GROSS
ZERO
TARE
RECALL
Figure 2-2. Low Battery LED Annunciator
UMC 600IS Installation Manual
CAPACITY
NET
GROSS
600 x 0.1
TARE
162738495
lb/kg
CONV
CE
ENT
0
lb kg MOTION
PRINT
1 SET
POINT
2 SET
POINT
2.5 Instrumentation Setup
All indicators are configured and tested prior to shipment to ensure that they are fully functional. The unit can be turned on immediately after connecting the input power and the load cells.
The UMC 600IS operates with the program KDA—49 programmed onto a 27C512 EPROM. To verify the program installed in the indicator, turn on the indicator and observe the displayed value at the EP prompt (see Figure 2-3). The EP prompt displays the family, set, and version level of the installed EPROM.
Set 49
Where: EP. = EPROM Program
49. = Set 49 within the KDA 1921 family X=The version level of Set 49
Figure 2-3. Example of EPROM Display
Version
Exceeding rated load cell load or
!
Caution
shorting excitation wires may damage power supply.
NOTES:
•Test weights or a water meter calibration can be used to verify scale performance.
The tilt stand should be secured with 1/4-20 inch screws. The location should be selected to offer some degree of protection for the indicator and its associated hardware.
•Unprotected cable runs need to be installed in a method to protect the cable from damage.
•All wiring must conform to the National Electrical Code and RP 12.6.
See control drawing 54136, Sheet 2, in the back of this manual for system interconnection details.
NOTE:
with the sleep timer enabled. When connecting the battery pack, press the ON/OFF button in the lower left hand corner of the indicator turning the unit on. At the end of the programmed time the unit automatically turns off. The factory preset power off time delay is configurable under option 4 and can be lengthened or shortened for the operators specific application.
Battery operated units are set up in the factory
To ensure that the UMC 600IS is in proper operating condition, the indicator can be tested in a safe area with a load cell simulator. The input signal should be as close as possible to the normal system millivolt value. Figure 2-4 shows the simulator-to-indicator wiring connection in a six-wire configuration. See Section 2.6 on page 8 for more information.
NOTE:
lead be shorted to +EXC and the –SEN lead be shorted to –EXC at the simulator only.
Six-wire configuration requires that the +SEN
LOAD CELL
SIMULATOR
–EXC
+EXC
+SIG
–EXC –SEN
+EXC +SEN
+SIG
TO J1
CONNECTOR
UMC 600IS
–SIG
–SIG
Figure 2-4. Wiring Connection to Simulator
Installation and Wiring
7
2.6 Load Cell Wiring
All units are equipped with a six-wire load cell connector. Condec supplies load cell cable in various lengths (see Table 2-3 on page 5). One end of the cable attaches to the indicator; the other end has stripped and tinned wires for connection to a junction box. The UMC 600IS is supplied with a blank six-pin connector that can be attached to existing load cell cables by the installer.
Figure 2-5 shows the load cell output connector and the location of J1 on the back of the indicator. Table 2-6 shows the load cell connector pin assignments.
Pin
Function
A +EXCITATION
B –EXCITATION C +SIGNAL D –SIGNAL E +SENSE
F –SENSE
Table 2-6. Load Cell Connector Pin Assignments
For four-wire load cell connections, short the sense lines to the excitation lines as shown in Figure 2-6.
Six-Pin Female
8
J1
Load Cell Connector
J1
J2 J3
B
C
A
F
E
D
Figure 2-5. J1 Load Cell Connector-facing
Jumper wires
A (+EXC) to E (+SEN) B (–EXC) to F (–SEN)
P1
E
A
C
B
F
D
Connector shell or chassis ground
A
F
B C
E
D
4-Wire Configuration 6-Wire Configuration
+SEN
+EXC
+SIG
–EXC
–SEN
–SIG
No connection
Figure 2-6. Load Cell Wiring
P1
A
F
B C
E
D
Check load cell color code for proper wiring
UMC 600IS Installation Manual
2.7 Serial Port Wiring
Serial Port 1 is a bidirectional (full duplex) port supporting active 20 mA current loop communications. Port 1 is optically isolated through the intrinsically safe I/O barrier.
The UMC 600IS serial port can be configured to communicate directly to a printer, remote display, or other device using 20 mA communications through the I/O interface barrier (see Figure 2-7). Since the I/O barrier is totally passive (not powered), the receiving device must also provide an active 20 mA current loop interface.
ZERO
NET
GROSS
CAPACITY
NET
ZERO
GROSS
TARE
RECALL
162738495
Cable 3
FM-Approved
load cells
(Up to 4)
Junction
Box
Load Cell
Supply Models
Figure 2-7. Intrinsically Safe System using Serial Communications
NOTE: The serial communications capability of the UMC
600IS is dependent on the product specifications of the receiving device. All serial communications applications should be tested with the I/O barrier in place.
600 x 0.1
lb/kg
TARE
CONV
CE
ENT
0
Battery Power
Only
Power
Cable 1
lb kg MOTION
PRINT
1 SET POINT
2 SET POINT
Cable 2
Serial I/O
Divisions I and 2 Class I, Groups A, B, C, D Class II, Groups E, F, G Class III
J3 Pin Function
Safe AreaHazardous Area
I/O
Isolation
Barrier
Power Supply
Battery
Charger
115 VAC
I/O Barrier
TB4 TB5
End Unit
Access to this serial communication port is through the five-pin female connector (J3) located on the back of the UMC 600IS indicator (see Figure 2-8). See the output connector diagram in Figure 2-8 and Table 2-7 for connector and wire identification.
J3
Port 1 (Full Duplex) Serial Communication
J1
Figure 2-8. Serial Port, J3 Connector
J2 J3
D –RCVR
C +RCVR
B –XMTR
A +XMTR
A +XMTR 21 28 RXDCL+ B –XMTR 22 27 RXDCL– C +RCVR 23 26 TXDCL+ D –RCVR 24 25 TXDCL–
E—
SHIELD
Table 2-7. Serial Port Connector Wiring
Serial Port configuration is explained in greater detail in Section 3.2 on page 16 of this manual.
Installation and Wiring 9
2.8 Troubleshooting and Testing the 600IS
Troubleshooting the system components in a safe area can be done in the normal manner utilizing any test equipment that is necessary . However, prior to any test or measurement that is done in a hazardous area, the plant manager or safety official must be notified to obtain permission or specific instructions.
The following basic procedures should be observed to provide a safe installation.
•Follow all plant safety procedures.
•Verify what type test equipment is allowed in the hazardous area.
•Do not bring into the hazardous area any inductive continuity testers.
•Do not bring any capacative discharge type devices into the hazardous area.
•Ask the plant authority if the use of non-sparking tools are required.
2.8.1 Troubleshooting
The following should be a guide during the installation of the weighing system in a hazardous location.
•Troubleshooting should only be done by qualified field service scale installation personnel.
•Component level repair is not permitted on Factory Mutual approved equipment.
•A factory trained technician can replace plug-in IS barrier equipment in the safe area.
It is manditory to return the UMC 600IS to the factory for repair and full testing.
•Tampering with the intrinsically safe equipment voids the Factory Mutual approval.
Safe area voltage measurements are as follows: Field replaceable parts are listed below for the UMC
Power Supply Output Voltage
No load 8.0 +/- 0.2 VDC One load cell 7.6+/- 0.2 VDC Four load cells 6.5 +/- 0.2 VDC
Table 2-8. Output Voltage
The power supply output voltage can be measured at the following terminals:
•TB2-4 +VDC (positive lead)
•TB2-5 DC Com (negative lead)
Shorting these terminals will blow the fuse in the intrinsically safe barrier module 59267.
!
Caution
600IS digital weight indicator.
Condec Part
Number
58805 Power supply 65004 Power supply board assembly 59267 Plug-in barrier 59942 Fuse, 0.25A 55683 I/O barrier 57415 I/O barrier board assembly 54966 Plug-in I/O barrier 56214 Battery pack module 54087 Battery charger 52216 Tilt stand (battery unit) 54074 Load cell connector (6 pin) 54080 Power connector (3 pin) 54084 I/O connector (5 pin)
Description
10 UMC 600IS Installation Manual
Table 2-9. Field Replaceable Parts
3.0 Configuration
162738495
0
CE
ENT
TARE
RECALL
ZERO
NET
GROSS
TARE
lb/kg
CONV
PRINT
1 SET POINT
2 SET POINT
CAPACITY
600 x 0.1
ZERO
NET
GROSS
lb kg MOTION
DEAD LOAD (3)
CONF (2)
CAL (1)
342
1 OPEN
NORM
Parameter Identifier
Selected Data
ZERO
NET
GROSS
TARE
lb/kg
CONV
Prior to calibration, the UMC 600IS must be digitally configured, or assigned a set of operating parameters. The first three parameters are directly related to calibration and must be set before proceeding to calibration mode.
3.1 Digital Configuration
3.1.1 Parameter Overview
Table 3-1 on page 12 lists configuration parameters and describes their values. The following paragraphs give the procedure for configuring the UMC 600IS.
3.1.2 Configuration Procedure
1. Unscrew the two screws on the face plate bracket (See Figure 3-1). The bracket drops down, exposing four program switches on the left.
ZERO
NET
GROSS
342
1
OPEN
ZERO
TARE
RECALL
CAPACITY
NET
GROSS
162738495
TARE
600 x 0.1
lb/kg
CONV
0
Figure 3-1. Accessing the Program Switches
2. Temporarily remove the unit’s flexible black display panel by gently pushing down and lifting the panel up and out at its center to expose the configuration and calibration instructions printed on the surface below. The switch function table defines the appropriate front panel switch settings for the CONF and CAL modes.
3. Close switch SW1-2, marked CONF (2), by moving to the up position (see Figure 3-2). A prompt appears with a parameter number and data value.
The parameter identifier is a number, 1–14, that correlates to the CONFIG chart on the upper left of the switch map panel. Selected data represents the value being entered into the unit configuration data. For example, 1 100 sets the indicator to 10,000 graduations (see Table 3-2 on page 13).
lb kg MOTION
CE
ENT
PRINT
1 SET
POINT
2 SET
POINT
When configuration is complete, set SW1-2 open (down) to return the unit to normal operating mode.
Figure 3-2. Closing Switch 2
The function keys shown in the table in Figure 3-3 have alternate functions during digital configuration.
Zero Net/Gross Tare lb/kg Conv
Parameter Select Parameter Data
Select
Subparameter
Select
Subparameter
Data Select
Figure 3-3. Front Panel Key Functions
NOTE: The TARE RECALL key functions as a previous
screen key in CONFIG mode.
3.1.3 Digital Configuration Parameters
Table 3-2 on page 13 lists the configuration display prompts (Prompt 1) and their value selections for displayed graduations. Prior to calibration, the UMC 600IS must be digitally configured, or given its set of operating parameters. The first three parameter selections are directly related to calibration and must be set up before proceeding to the calibration mode. These parameters include the number of graduations, the resolution, and the decimal point location in the weight data, all of which define the scale capacity.
Table 3-3 lists Prompts 2 and 3 and Table 3-4 has Prompts 5, 6, and 7. Prompts 8, 9, and 10 are shown in Table 3-5 and Prompts 11 through 14 are listed in Table 3-6 both on page 15.
Configuration 11
Loading...
+ 32 hidden pages