In any correspondence concerning this instrument, please always quote the type number and serial
number as given on the type plate.
As the instrument is an electrical apparatus, it may be operated only by trained personnel.
Maintenance and repairs may only be carried out by qualified personnel.
Bitte beachten
Bei Schriftwechsel über dieses Gerät wird gebeten, die Typennummer und die Seriennummer
anzugeben. Diese befinden sich auf dem Typenschild.
Wichtig
Da das Gerät ein elektrisches Betriebsmittel ist, darf die Bedienung nur durch eingewiesenes Personal
erfolgen. Wartung und Reparatur dürfen nur von geschultem, fach- und sachkundigem Personal
durchgeführt werden.
Dans votre correspondance et dans vos réclamations se rapportant à cet appareil, veuillez toujours
indiquer le numéro de type et le numéro de série inscrits sur la plaque signalétique.
Important
Comme il s’agit d’un équipement électrique, la maintenance doit être effectuée par du personnel
qualifié. De même, l’entretien et les réparations sont à confier au personnel qualifié.
3 Technical Data ................................................................................................................................ 5
3.1 General ............................................................................................................................................................ 5
4.1 General .......................................................................................................................................................... 14
4.2 Installation of the Upper Load Disc for Max Capacity of 500 kg…50 t .................................. 15
5.1 General .......................................................................................................................................................... 16
9 Spare Parts and Accessories ....................................................................................................... 24
EN-2 Sartorius
Installation Manual Compression Load Cell PR 6201
* do not constrain this position
1 Safety Instructions
The PR 6201 with the relevant mounting kits must be used only for the weighing applications for which it
is intended. The dimensions of all mounting and structural components must be calculated so that
sufficient overload capacity is ensured for loads which may occur while taking the relevant standards into
account. In particular, upright weighing objects (vessel etc.) must be safeguarded against the weighing
installation turning over or being shifted, thus eliminating danger to humans, animals or goods even in the
case of a break in a load cell or mounting element.
Installation and repair work must be carried out only by qualified personnel.
2 Design Recommendations
2.1 Positioning of Load Cells and Constrainers
The supporting structure of the scale (i.e. the load cell support) and the vessel must be stable enough to
withstand the maximum design loads, horizontal (check with spirit level!) and flat. Vessels should preferably be
supported by 3 load cells, platforms and weigh bridges by 4 or 6 load cells (see figure).
Parasitic forces, horizontal forces and torques are disturbances which can generate measuring failures and
in case of exceeding the specified limits may damage the load cell.
An accurate constraining of the object prevents of damages and measuring errors without affecting the
required space for movement. Therefore special attention should be paid to the design, arrangement and
condition of the constrainers. Thermal expansion and contractions of the object are to be taken into
account which may affect the required space for vertical movement and thus influence the measuring
results.
Sartorius EN-3
Compression Load Cell PR 6201 Installation Manual
2.2 Location of Load Cells and Pivots
2.3 Lift-off Protection
For safety reasons, a lift-off protection has to be provided generally in all systems of tank and hopper
weighing. It can be realized separately or with the help of mounting kits. The simplest design requires a
threaded rod, three nuts, one serrated lock washer and one washer.
2.4 Capacity Selection
The load cell PR 6201 has a high overload capacity due to the fact that the stress in the measuring element
is low (1 mV/V). Forces which are exceeding the max. load without damage limit may change the
characteristic of the load cell or in the worst case damage the electrical part. If an exceeding of a.m. limit is
possible, e.g. falling loads, a mechanical overload protection (limit stop) is strongly recommended.
EN-4 Sartorius
Installation Manual Compression Load Cell PR 6201
max
max
Length
E
>10 t: 12 m
Cross section
Bending radius
≥
3 Technical Data
3.1 General
Restoring force For each mm of displacement that the top of the load cell is shifted from the
vertical axis, a horizontal restoring force is generated:
E
E
E
E
≤10 t:
E
≥20 t:
= 100 t 1.23 % of the vertical load on the load cell
max
= 200 t + 300 t 0.65 % of the vertical load on the load cell
max
= 520 t 1.20 % of the vertical load on the load cell
max
Housing Stainless steel 1.4301, hermetically sealed welded, filled with inert gas
Degree of
protection
IP 68 (water of 1.5 m in depth; 10,000 h) acc. to IEC 60529 (correspond to NEMA 6)
IP69K acc. to DIN 40050
Protection type Intrinsic safety for PR 6201/..E + ..DBE
Cable Diameter 5 mm
The Dual Bridge load cell has two separate measuring circuits, which are independent of each other. The
measuring circuits are adjusted in two separate adjustment chambers; cable connections see Chapter 5.4.2.
3.3 Certificates
Zone Marking Certificate no. for
0 and 1 II 1G Ex ia IIC T6 PTB 02 ATEX 2059 only PR 6201/..E + ..DBE
20 and 21 II 1 D IP65 T85°C TÜV 03 ATEX 2301X PR 6201/..L, ..LE, ..D1, ..D1E,
..C3-C6, ..C3E-C6E, ..N, ..NE
2 II 3G Ex nA II T6 Manufacturer certificate PR 6201/..L, ..LE, ..D1, ..D1E, ..C3-
The scope of delivery
does not include these
parts!
Load disc set PR 6143/55
see Chapter 9
3.5.5 Load Cell PR 6201/15 DB (max. capacity 100 t)
all dimensions in mm
Pos. Description
1 Lower load disc
2 Rubber ring
Ring for
3
all dimensions in mm
lower load disc
Sartorius EN-9
Compression Load Cell PR 6201 Installation Manual
3.5.6 Load Cell PR 6201/25 DB (max. capacity 200 t), PR 6201/35 DB (max. capacity 300 t)
Pos. Description
1 Lower load disc
2 Rubber ring
3 Ring for
lower load disc
3.5.7 Load Cell PR 6201/520t DB (max. capacity 520 t)
all dimensions in mm
Pos. Description
1 Upper/lower
load disc
2 Ring for
upper load disc
3 Rubber ring
4 Ring for
lower load disc
The equipment supplied
does not include these
parts!
Load disc set PR 6143/55
see Chapter 9
all dimensions in mm
EN-10 Sartorius
Installation Manual Compression Load Cell PR 6201
3.6 Technical Data for Max. Capacity 500 kg…50 t
Sartorius EN-11
Compression Load Cell PR 6201 Installation Manual
3.7 Technical Data for Max. Capacity 100 t, 200 t, 300 t, 520 t
EN-12 Sartorius
Installation Manual Compression Load Cell PR 6201
3.8
Technical Data for Dual Bridge; Max. Capacity 100 t, 200 t, 300 t, 520 t
Sartorius EN-13
Compression Load Cell PR 6201 Installation Manual
10.5
400
Figure: Flexible copper strap
4 Installation
4.1 General
Caution!
All electrical welding at the weighing facility must be finished before mounting the
load cells!
Directly when installing the load cell, bypass the load cell with the flexible copper
strap provided for this purpose (see figure), to prevent welding or lightning stroke
current from passing through the load cell and damaging it!
In case electrical welding is required subsequently in the neighborhood of the load
cell
• disconnect the load cell cable from the measuring instrument,
• bypass the load cell carefully with the above-mentioned flexible copper strap,
• take care that the grounding clamp of the welding set is fitted as closely as
possible to the welding joint in order to prevent a current flow through the load
cell.
• Do not lift the load cell on its cable.
• Avoid shock stress (falling down, hard shocks)
• The load cell must be installed so that its axis is vertical.
• The load direction must be as close as possible to measuring axis of the load cell.
• All contact points between load cell and load disc must be adequately greased.
Caution!
Changes of temperature >15 K/h may influence the measuring accuracy. To prevent
the load cells from direct heating or cooling effects (sun, wind, heat radiation) heat
protection shields or heat protection housings are to be installed if necessary.
all dimensions in mm
To prevent force shunts, all connections of the weighing facility to the surrounding
construction (pipes, cables, bellows) must be coupled as flexibly as possible.
Even the best load cells must be handled carefully and installed correctly in order to
permanently guarantee good weighing results. It is therefore extremely important to
comply with the rules described here!
EN-14 Sartorius
Installation Manual Compression Load Cell PR 6201
4.2 Installation of the Upper Load Disc for Max Capacity of 500 kg…50 t
small radius (15 mm) big radius (35 mm)
500 kg…10 t 20…50 t
Figure: for LC radius 15 mm Figure: for LC radius 35 mm
Note:
Further installation instructions can be found in the manuals of the respective mounting
kits.
Sartorius EN-15
Compression Load Cell PR 6201 Installation Manual
bu =
blue
5 Connection
5.1 General
Caution!
The load cell cable end is protected against contamination and moisture by a
protective sheathing.
Remove the protective sheathing only shortly before connecting!
• Protect the cable ends against contamination. No moisture must penetrate into the open cable end.
• Do not shorten the load cell cable. Connect the prepared cable end and roll up the remaining cable.
• The screen of the load cell cable and the screen of the connecting cable must not be connected
electrically inside the junction box, if connection of both ends is not permissible according to the
regulations for installation in the explosion-hazarded area.
• The measuring cables should be kept away from power equipment.
• The distance between the measuring cables and the power cables should be at least 1 m.
• The measuring cables should be laid in separate cable conduits or steel pipes.
• Power cables should be crossed at right angles.
5.2 Load Cell
5.2.1 Standard (Type L, D1/N, D1E/NE, C3, C3E)
Color Code
rd = red
gn = green
gy = grey
+ Supply voltage
+ Meas. voltage / + Load cell output
– Supply voltage
– Meas. voltage / – Load cell output
Screen
EN-16 Sartorius
Installation Manual Compression Load Cell PR 6201
out
5.2.2 Load Cell with Integrated Amplifier (Type LA)
Caution!
The maximum distance between load cell and electronic instrument is 500 m.
Color Code
rd = red
bu = blue
gn = green
gy = grey
5.2.2.1 Connection of Single Load Cell
GAIN, connected to
+ Supply voltage 20…28 V DC
– Supply voltage 0 V
+ Supply voltage 20…28 V DC
+ Load cell output I
+ Load cell output I
= 4…20 mA
out
= 2…10 mA
– Supply voltage 0 V
– Load cell output
single load cell mode
two load cell mode
single load cell mode
two load cell mode
Color Code
rd = red
bu = blue
gn = green
gy = grey
Sartorius EN-17
Compression Load Cell PR 6201 Installation Manual
5.2.2.2 Connection of Two Load Cells
Color Code
rd = red
bu = blue
gn = green
gy = grey
EN-18 Sartorius
Installation Manual Compression Load Cell PR 6201
5.3 Connecting Cable
For connection from the junction box to the weighing electronics, we recommend using following connecting
cables:
- PR 6135
- PR 6136 (for installation inside the explosion-hazarded area)
- PR 6135A (armored)
- PR 6136A (armored, for installation inside the explosion-hazarded area)
5.4 Cable Connections
5.4.1 Load Cells with one Measuring Circuit
Sartorius EN-19
Compression Load Cell PR 6201 Installation Manual
5.4.2 Load Cells with two Separate Measuring Circuits
EN-20 Sartorius
Installation Manual Compression Load Cell PR 6201
Junction box
Has moisture penetrated the junction box?
Connecting cable
Is the sheath damaged?
6 Preparing for Calibration
Note:
For calibration of the measuring system, please refer to the manual of the weighing
instrument.
Caution!
A warming-up time of at least 30 minutes for the load cell is required before calibration
of the weighing installation.
6.1 Mechanical Height Adaptation
Before starting calibration it has to be ensured that the load cells are equally loaded. Therefore a height
adaptation has to be performed.
• Place the dead load (e.g. empty hopper) on the load cells.
• Energize the load cells by means of a stabilized voltage of e.g. 12 V DC.
• Measure the output voltage of each individual load cell by means of a high-accuracy digital voltmeter and
compare the individual values.
The load cell output with the lowest voltage must be increased by putting shims between mounting plate and
weighing construction.
• Lift weighing facility near the load cell.
• Put a thin, deburred sheet of metal (0.5 mm to 2 mm thick) between the upper mounting plate and
weighing construction.
• Measure the output voltage of the load cells again and correct the height of this load cell or another
one.
7 Fault finding hints
The following hints will enable a technician for a first diagnostic or help in case of wrong or not
reproducible weighing results after commissioning and calibration.
7.1 Visual check
Weighing facility Are all pipes, hoses, and cables connected as flexibly as possible?
Are devices which are rigidly connected to the weighing facility in direct
contact with the surrounding installation?
Is there friction between the weighing facility and its surrounding (e.g. dirty
apertures etc.)?
Do the screw connections show a good contact?
Has moisture penetrated the cable end?
Mounting kit Is there a contact between lift-off protection and the weighing facility
itself?
Are the constrainers stuck?
Load cell Does the load cell stand vertically?
Is the housing damaged?
Is the sheath of the cable damaged?
Has moisture penetrated the cable end?
Sartorius EN-21
Compression Load Cell PR 6201 Installation Manual
≥
7.2 Checks with Multimeter
7.2.1 Check Zero Output Signal of Load Cell
• Unload load cell.
• Disconnect the load cell outputs.
• Check whether the output voltage without load is within the limits.
Type Zero output signal
L 0 mV ±0,02 mV/V
D1/N/C3 0 mV ±0,01 mV/V
(at PR 6201/54.. 0 mV ±0,02 mV/V)
LA 3,2…4 mA
GAIN connected to +Supply Voltage 24 ±4 V, see chapter 5.2.2.1
7.2.2 Check the Strain Gauge Bridge
Note:
• Do not exceed the test voltage.
• Check whether the values of the resistors are within the permissible limits.
Maximum test voltage Standard industrial 32 V DC
Intrinsically safe version (PR …/..E) 25 V DC
• Never apply the test voltage between the cores of the load cell cable (danger of destroying the load
cell).
• Insulate the load cell cores.
maximum test voltage standard industrial 100 V DC
Intrinsically safe version (PR …/..E) 500 V AC
insulation impedance core - housing
core - screen
screen - housing
Not for load cells type LA.
>5000 MΩ
>5000 MΩ
>5000 MΩ
7.2.4 Check Insulation Impedance of Connecting Cable
• Disconnect connecting cable and load cells.
• Insulate the cores of the connecting cable.
insulation impedance core - core
core - screen
≥600 MΩ× km
600 MΩ × km
EN-22 Sartorius
Installation Manual Compression Load Cell PR 6201
8 Repair/Maintenance
8.1 Repair
Caution!
The load cells PR 6201 are designed as robust as possible for the required
measuring accuracy and have a high reliability. In case of an electrical or
mechanical defect the load cell must be replaced.
A load cell repair is not possible.
8.2 Maintenance
Load cell PR 6201 needs no maintenance.
Pollution on the load cells and on the moveable parts of the weighing installation have to be cleaned in
due time
- if the pollution influences the weighing or
- if the pollution is aggressive against the different materials of the installation.
The contact surfaces between load cell and load discs are to be protected by grease. The load cell is
surrounding with off shore all weather protection spray in aggressive pollution.
Sartorius EN-23
Compression Load Cell PR 6201 Installation Manual
11
Rubber ring
100 t
5322 532 30408
15
Rubber ring
200 t, 300 t
5322 532 30409
19
Mounting kit PR 6001/00N*
0.5…10 t
9405 360 01001
9 Spare Parts and Accessories
Pos. Description Max. capacity Order number
1 Lower load disc with rubber ring 0.5…10 t 5322 693 91416
2 Lower load disc with rubber ring 20 t, 30 t, 50 t 5322 693 91165
3 Lower load disc with rubber ring PR 6143/24S* 0.5…10 t 9405 361 43242
4 Lower load disc with rubber ring PR 6143/54S* 20 t, 30 t, 50 t 9405 361 43542
5 Rubber ring, standard 0.5…50 t 5322 532 70298
6 Rubber ring, food resistance 0.5…50 t 5322 532 70317
7 Upper load disc, standard PR 6143/50N* 0.5…50 t 9405 361 43501
8 Upper load disc, PR 6143/50S* 0.5…50 t 9405 361 43502
9 Lower load disc 100 t 5322 466 81611
10 Ring for lower load disc 100 t 5322 466 81609
12 Upper load disc 100 t 5322 520 10552
13 Lower load disc 200 t, 300 t 5322 466 81613
14 Ring for lower load disc 200 t, 300 t 5322 466 81612
16 Upper load disc 200 t, 300 t 5322 520 10553
17 Load disc set PR 6143/55N* 520 t 9405 361 43551
18 Flexible copper strap 400 mm long 5322 310 30581