AC TRANSDUCER
RIBXGTV10
Enclosed Self-Powered Spilt Core Multi-Range (0-20A, 50A, or 100A) AC Transducer
with 0-10Vdc Terminal Output
Wire Clamp
2.000”
.52” x .52” Opening for
Wire Being Monitored
2.520”
Removable Mounting Tab
SPECIFICATIONS
Operating Temperature:
Humidity Range:
Accuracy:
Loading:
2.000”
1.100”
1.750”
-30 to 140° F
5 to 95% (noncondensing)
96.8% Full Scale
RIBXGTV10, (0-20 Amp), 5% Error @ 67 kΩ
RIBXGTV10, (0-50 Amp), 5% Error @ 31.6 kΩ
RIBXGTV10, (0-100 Amp), 5% Error @ 18.1 kΩ
Output: Terminal Strip
Accepts 14-22 AWG wire
DIP Switches
Max Sense Voltage:
Mounting/Installation:
Approvals:
Sensor Type:
600 Vac
UL Listed, UL916, UL864, California
State Fire Marshal, C-UL, CE, RoHS
Removable mounting tab provided.
The wire clamp locks against the wire
being monitored, securing the unit
in place.
Split core with voltage output
Made in USA
Meets
“Buy American”
of ARRA 2009
DIP SWITCH
1 2 Sensing Range
OFF OFF 0-20 Amp
OFF ON 0-50 Amp
ON OFF 0-100 Amp