AC CURRENT SWITCHES
RIBXGH Series
Enclosed Self-Powered Split Core 120 Vac Switching AC Current Sensors
Wire Clamp
Sensor
2.000”
Contact
.52” x .52” – Opening for
Wire Being Monitored
2.520”
Removable Mounting Tab
SPECIFICATIONS
Operating Temperature:
Humidity Range:
Temperature Derating:
Max Sense Voltage:
Sensor Contact Status:
Threshold Adjust
2.000”
1.100”
1.750”
FUNCTIONAL DEVICES CERTIFIED FOR USE WITH ECMS
-30 to 140° F
5 to 95% (noncondensing)
1 Amp up to 50˚ C, 0.5 Amp up to 60˚ C
600 Vac
Current below threshold: Open
Current above threshold: Closed
LED 2
LED 1
(if present)
Approvals:
Mounting/
Installation:
RIBXGHF
Wire Being Monitored
Wht/Blk
Wht/Blk
UL Listed, UL916, C-UL
Removable mounting tab provided. The
wire clamp locks against the wire being
monitored, securing the unit in place.
Notes:
• Use Sensor Contact to switch 120 Vac loads only.
• For testing purposes, Sensor Contact will
measure approximately 250 Ω when closed
and > 10 MΩ when open.
• The Sensor Contact is a Solid State Contact.
RIBXGHTF
Wire Being
Monitored
Made in USA
Meets
“Buy American”
of ARRA 2009
RIBXGH SERIES SELECTION GUIDE
Model#
RIBXGHF .50-150 Amp Split Core Fixed, .50 Amp Solid State Switch SPST 120 Vac Only 1 Amp Max Wht/Blk 16˝ 18 AWG Wire Leads
RIBXGHTF .50-150 Amp Split Core Fixed, .50 Amp Solid State Switch SPST 120 Vac Only 1 Amp Max Terminal Strip, Accepts #14-22 AWG Wire
RIBXGHA .75-150 Amp Split Core Adjustable Solid State Switch SPST 120 Vac Only 1 Amp Max Wht/Blk 16˝ 18 AWG Wire Leads Over Trip Point Under Trip Point
RIBXGHTA .75-150 Amp Split Core Adjustable Solid State Switch SPST 120 Vac Only 1 Amp Max Terminal Strip, Accepts #14-22 AWG Wire O ver Trip Point Under Trip Point
Sensing
Range
Type Threshold
Sensor
Contact
Type
Switching
Voltage
Range
Maximum
Switching
Current
Sensor Contact
Termination
LED 1 LED 2
010816