RIB,Relay In A Box,Functional Devices RIBXG420 Series Data Sheet

CURRENT
SENSORS
AC TRANSDUCERS
RIBXG420 Series
Enclosed Self-Powered Split Core 20, 50, and 100 Amp Current Transducers with Loop Powered 4-20 mA Output (Pre-Wired)
Wire Clamp
2.000”
.52” x .52” Opening for Wire Being Monitored
2.520”
1.100”
1.750”
Removable Mounting Tab
Made in USA
Meets
Buy American
of ARRA 2009
2.520”
SPECIFICATIONS
Operating Temperature:
Humidity Range:
Sensor Type:
Accuracy:
Linearity:
Max Output Current:
Max Sense Voltage:
Approvals:
Mounting/Installation:
RIBXG420 SERIES SELECTION GUIDE
Model# Sensing Range Sensor Output Span 20% – 100% Span 10% – 100% Span 0% – 100%
RIBXG420-20 0-20 Amps Loop Powered 4-20 mA Transmitter (Pre-Wired) 99% 99% 95%
RIBXG420-50 0-50 Amps Loop Powered 4-20 mA Transmitter (Pre-Wired) 99% 97.5% 92%
RIBXG420-100 0-100 Amps Loop Powered 4-20 mA Transmitter (Pre-Wired) 99% 97% 91%
-30 to 140° F 5 to 95% (noncondensing)
Wires:
Red (positive) & Black (negative), 16˝, 18 AWG, 600V Rated Internal, with 4-20 mA Transmitter Output 0-20 Amps, 0-50 Amps, or 0-100 Amps (See Selection Guide Below) Refer to chart below.
99% FS (20%-100% Span)
30 mA 600 Vac UL Listed, UL864, UL508, C-UL, California State Fire Marshal Removable mounting tab provided. The wire clamp locks against the wire being monitored, securing the unit in place.
OUTPUT LOAD
RESISTANCE
Maximum Minimum Maximum
800 ohms 24 Vdc 35 Vdc 500 ohms 18 Vdc 35 Vdc 350 ohms 15 Vdc 35 Vdc 250 ohms 13 Vdc 35 Vdc 200 ohms 12 Vdc 35 Vdc 100 ohms 10 Vdc 35 Vdc
50 ohms 9 Vdc 35 Vdc
SUPPLY VOLTAGE
ACCURACY
RIBXG420-20
20
16
12
Output (mA)
8
4
0 4 8 12 16 20
Current (A)
Supply Voltage
Output Load
Resistance
-
+
IDEAL
ACTUAL
8
7.5
7
6.5
6
5.5
5
4.5
4
0 1 2 3 4
+
-
RIBXG420
Red +
Black
-
081017