RIB,Relay In A Box,Functional Devices RIBX243PV Data Sheet

Page 1
RELAYS
RELAY & AC TRANSDUCER COMBO
RIBX243PV
Enclosed Internal 0-20 Amp to 0-10 Vdc DC Trans­ducer + Relay 20 Amp 3PST with 24 Vac/dc Coil
Blu - N/O
Blu - N/O
Yel - N/O
Yel - N/O
Org - N/O
V
24 Vac/dc Comm
Comm 0-10 Vdc
SPECIFICATIONS
# Relays & Contact Type:
Expected Relay Life:
Operating Temperature:
Humidity Range:
Operate Time:
Relay Status:
Dimensions:
Wire Length:
Approvals:
Housing Rating:
Gold Flash:
Override Switch:
Coil Current:
210 mA @ 24 Vac 154 mA @ 30 Vdc
One (1) 3PST Continuous Duty Coil 10 million cycles minimum mechanical
-30 to 140° F 5 to 95% (noncondensing) 20ms Red LED On = Activated
4.00˝ x 4.00˝ x 1.80˝ with .50˝ NPT Nipple 16˝, 600V Rated UL Listed, UL916, C-UL California State Fire Marshal UL Accepted for Use in Plenum, NEMA 1 No No
Org - N/O
Coil Voltage Input:
24 Vac/dc ; 50-60 Hz Drop Out = 3 Vac / 3.8 Vdc Pull In = 20 Vac / 22 Vdc
Contact Ratings:
20 Amp Resistive @ 300 Vac, 28 Vdc 20 Amp Ballast @ 277-480 Vac
Not rated for Electronic Ballast
15 Amp Resistive @ 600 Vac 770 VA Pilot Duty @ 120 Vac, 1 Phase 1158 VA Pilot Duty @ 240 Vac, 1 Phase 1110 VA Pilot Duty @ 277 Vac, 1 Phase 1640 VA Pilot Duty @ 480 Vac, 1 Phase 1466 VA Pilot Duty @ 240 Vac, 3 Phase 2112 VA Pilot Duty @ 480 Vac, 3 Phase Heavy Pilot Duty @ 600 Vac
7.5 HP @ 480 Vac, 3 Phase 5 HP @ 240 Vac, 3 Phase 3 HP @ 480-600 Vac, 1 Phase 2 HP @ 240-277 Vac, 1 Phase 1 HP @ 120 Vac, 1 Phase
Made in USA
Meets
Buy American
of ARRA 2009
Sensor Type:
Internal, with voltage output. Current sensing on orange wires
Sensor Range:
0-20 Amps
Sensor Feedback Output:
Min. Input Impedance = 30K ohms
Accuracy +/– 1% full scale
Vripple < 10m Vac
Notes:
Order Normally Closed by adding “-NC” to end of
model number
Can be ordered with 0-5 Vdc voltage output -
Consult factory.
071717