RIB,Relay In A Box,Functional Devices RIBTWX2401SB-LN Data Sheet

RELAYS
The relay will go to the default state when the communication timer times out. Setting the timer value to zero will cause the communication to never time out.
It is recommended to put a value in nci Max Send T to ensure the RIB re-synchronizes itself on the net­work after power loss. It is the responsibility of the user to ensure this value does not cause conicts in network trac. (No value = No “heartbeat” updates / no re-sychronization; Low Value = Many updates but may cause many trac collisions; High value = Few updates but many less collisions.)
Notes:
Normally Open or Normally Closed selected by yellow
jumper wire.
Order NEMA 4 housing by adding “-N4” to end of model
number. (RIBTWX2401SB-LN-N4)
Order with grey lid by adding “-GY” to end of model
number. (RIBTWX2401SB-LN-GY)
Order NEMA 4 housing with grey lid by adding “-N4-GY”
to end of model number. (RIBTWX2401SB-LN-N4-GY)
When connecting 24 Vac to both the RIB(s) and a
half-wave device, damage to device can occur. Option 1: Use separate transformers for each device. Option 2: Add diode between devices, see Option 2 note below. ^^
Contact Ratings:
20 Amp Resistive @ 277 Vac 20 Amp Ballast @ 120/277 Vac (N/O) 10 Amp Ballast @ 120/277 Vac (N/C)
Not rated for Electronic Ballast
10 Amp Tungsten @ 120 Vac (N/O) 1110 VA Pilot Duty @ 277 Vac 770 VA Pilot Duty @ 120 Vac 2 HP @ 277 Vac 1 HP @ 120 Vac
Power Input Ratings:
105 mA @ 24 Vac 78 mA @ 24 Vdc 105 mA @ 120 Vac
Current Sensor Range:
0.25 - 20 Amps
Threshold xed at .25 Amps.
RIBMNWX2401SB-LN
2.75˝ Track Mount LonWorks® Twisted-Pair FT-10
Network Dual I/O Device; One Binary Output (20 Amp Relay SPST + Override); One Binary Input (Current Sensor 0.25 - 20 Amp, Relay Load Sensing), 24 Vac/dc or 120 Vac Power Input
RIBTWX2401SB-LN
Enclosed LonWorks® Twisted-Pair FT-10 Network
Dual I/O Device; One Binary Output (20 Amp Relay SPST + Override); One Binary Input (Current Sensor 0.25 - 20 Amp, Relay Load Sensing), 24 Vac/dc or 120 Vac Power Input
LON
LON
Internal Current
Sensor
Open Loop
Sensor Object *
CLOSED
OPEN
AUTO
Selectable Jumper Wire
Not used
GREEN LED = Network Status
RED LED = Relay Activated
YELLOW LED = Service
PINK LED = Current Flow
Service Button
24 Vac/dc
Com
120 Vac
Com
Channel:
Transceiver Type:
Functional Blocks:
Downloadable Files:
# Relays & Contact Type:
Expec
ted Relay Life:
Operating Temperature:
Humidity Range:
Operate Time:
Green LED:
Red LED:
Yellow LED:
Dimensions:
Track Mount:
Approvals:
Housing Rating:
Gold Flash:
Override Switch:
One (1) SPST Continuous Duty Coil 10 million cycles minimum mechanical
-30 to 140° F 5 to 95% (noncondensing) 18ms Network Status Relay Status Service Status
6.00˝ x 2.75˝ x 1.75˝ (RIBMNWX2401SB-LN)
7.00˝ x 4.28˝ x 2.00˝ with .75˝ NPT N
ipple (RIBTWX2401SB-LN) MT212-6 Mounting Track Provided FCC, LonMark® UL Listed, UL916, C-UL UL Listed, NEMA 1, C-UL, CE Approved, UL Accepted for Use in Plenum, Also available NEMA 4 / 4X No Yes
TP/FT-10 FT5000 Smart Transceiver 0000 Node Object 0004 Closed Loop Actuator Object 0001 Open Loop Sensor Object PDF, XIF, APB, VSS and NXE available on website.
Made in USA
Meets
Buy American
of ARRA 2009
Node Object
nvi Request nvo Status
NV1 NV2
DESCRIPTION SNVT NAME SNVT TYPE
Command to open/close relay nvi Value SNVT_switch
Command status of relay nvo Value Fb SNVT_switch
Default state of relay on/o nci Default SNVT_switch
Communication timer nci Max Receive T SNVT_elapsed_tm
Status of Binary Input nvo Value SNVT_switch
Invert status of Binary Input nci Invert SNVT_lev_disc
Max time between updates nci Max Send T SNVT_elapsed_tm
Min time between updates nci Min Send T SNVT_elapsed_tm
Closed Loop Actuator
Node Object
nvi Value
NV1
nvo Value Fb
NV2
nci Default
nci Max Receive T
nvi Request nvo Status
NV1 NV2
(Binary Output)
Closed Loop Actuator
Node Object
nvi Value
NV1
nvo Value Fb
NV2
nci Default
nci Max Receive T
* Open Loop Sensor Object
nvo Value
NV1
nvi Request nvo Status
nci Invert nci Max Send T nci Min Send T
NV1 NV2
(Binary Output)
(Binary Input)
SPECIFICATIONS
NETWORK COMPATIBLE RELAY / CURRENT SENSOR COMBOS
Half-Wave Device
RIBMNWX2401SB-LN or RIBTWX2401SB-LN
Com
24 Vac/dc
Com
24 Vac
24 Vac
IN4004
Add diode on 24 Vac power (Com) interconnection between devices. Band on diode faces towards RIB(s).
^^ Option 2: