RIB,Relay In A Box,Functional Devices RIBTW2402B-BC Data Sheet

NETWORK COMPATIBLE RELAYS
IN4004
RIBTW2401B-BC
Enclosed BACnet® MS/TP Network Relay Device; One Binary Output (20 Amp Relay SPDT + Over­ride); One Binary Input (Dry Contact, Class 2); 24 Vac/dc or 120 Vac Power Input, Optional End
of Line Resistor (EOL) Included.
}
REF
}
A(–)
B(+)
1 2 3 4 5 6 7 8 9 10 11 12
0
MSTP
Dry Contact
Binary Input
24 Vac/dc
Common
Wht/Yel Neutral
SPECIFICATIONS
# Relays & Contact Type:
Expected Relay Life:
Operating Temperature:
Humidity Range:
Housing Rating:
Relay Override Switch:
Network Media:
1
Connect Jumper for EOL. Disconnect for no terminating resistor.
Blu
Wht/Blk
N/C
120 Vac
Operate Time:
Green LED:
Red LED:
Dimensions:
Wires:
Approvals:
Gold Flash:
Terminations:
Polarity:
Baud Rate:
LSB
MSB
MS/TP ADDRESS
Yel
Comm
Relay
Rate
Baud
Org N/O
One (1) SPDT Continuous Duty Coil 10 million cycles minimum mechanical
-30 to 140° F 5 to 95% (noncondensing) 18ms Network Communication Relay Status
4.00˝ x 4.00˝ x 1.80˝ with .50˝ NPT Nipple 16˝, 600V Rated UL Listed, UL916, C-UL
ccepted for Use in Plenum, NEMA 1
UL A No DIP Switch Control
Twisted Pair 22-24AWG, shielded recommended Functional Devices product installed at both ends of the MS/TP network – Use 120 Ω end of line resistors. All other cases – Follow instructions from the device installed at the end of the MS/TP network. Network is polarity sensitive 9600, 19200, 38400, 57600, 76800, 115200 (DIP Switch Selectable)
RIBTW2402B-BC
Enclosed BACnet® MS/TP Network Relay Device; One Binary Output (20 Amp Relay SPDT + Over­ride); One Binary Input (Dry Contact, Class 2); 24 Vac/dc or 208-277 Vac Power Input, Optional
End of Line Resistor (EOL) Included.
}
REF
A(–)
B(+)
}
Override
Dry Contact
Binary Input
24 Vac/dc
Common
Wht/Yel Neutral
MSTP
Wht/Brn
208-277 Vac
1 2 3 4 5 6 7 8 9 10 11 12
0
1
MSB
Connect Jumper for EOL. Disconnect for no terminating resistor.
Blu N/C
Contact Ratings:
20 Amp Resistive @ 277 Vac 20 Amp Ballast @ 277 Vac 16 Amp Electronic Ballast @ 277 Vac (N/O) 10 Amp Tungsten @ 120 Vac (N/O) 1110 VA Pilot Duty @ 277 Vac 770 VA Pilot Duty @ 120 Vac 2 HP @ 277 Vac 1 HP @ 120 Vac
Power Input Ratings:
81 mA @ 24 Vdc 111 mA @ 24 Vac 96 mA @ 120 Vac (RIBTW2401B-BC) 121 mA @ 208-277 Vac (RIBTW2402B-BC)
Power Input:
24 Vac/dc ; 120 Vac ; 50/60 Hz (RIBTW2401B-BC) 24 Vac/dc ; 208-277 Vac ; 50/60 Hz (RIBTW2402B-BC)
Notes:
When connecting 24 Vac to both the RIB(s) and a
half-wave device, damage to device can occur. Option 1: Use separate transformers for each device. Option 2: Add diode between devices, see Option 2 note below. ^^
LSB
MS/TP ADDRESS
Yel
Comm
Made in USA
Meets
Buy American
of ARRA 2009
Relay
Rate
Baud
Override
Org N/O
BACnet® Details:
MS/TP Address & Baud Rate must be set
prior to power up via DIP switches.
Device ID will default to 277XXX where
XXX is the MS/TP Address. Examples:
MS/TP Address - 004 Device ID - 277004
MS/TP Address - 121 Device ID - 277121
Device ID can be changed via network
command. Once changed, it will no longer default to 277XXX. (MS/TP Address & Device ID must be unique.)
This model utilizes: BO 1 (Relay output),
BI 1 (Dry contact binary input).
Device Instance changed via Object Identier
Property of Device Object
PIC Statement available on website.
http://www.functionaldevices.com/pdf/ pics/RIBTW240xB-BC_PICS.pdf
Or scan QR code with your smart phone.
DIP SWITCHES* BAUD RAT E
8 9 10
0 0 0
0 0 1
0 1 0
0 1 1
1 0 0
1 0 1
9600
19200
38400
57600
76800
115200
DIP SWITCHES* RELAY STATE**
11 12
1 0
X 1
0 0
* 0 = Open ; 1 = Closed ** Device must be powered for override
All other combinations=9600 baud
Dry contact binary input is a general purpose input that is not tied to the relay
internally. Can be used with any dry contact switching device, such as a current sen­sor, to report back to the network.
Auto
Override on
Override o
24 Vac
^^ Option 2:
RIBTW2401B-BC or RIBTW2402B-BC
24 Vac/dc
Com
Half-Wave Device
24 Vac
Com
Add diode on 24 Vac power (Com) interconnection between devices. Band on diode faces towards RIB(s).