RELAYS
Channel:
Transceiver Type:
Transceiver Compatibility:
Functional Blocks:
Downloadable Files:
The relay will go to the default state when the communication timer times out. Setting the timer value
t
o zero will cause the communication to never time out.
It is recommended to put a value in nci Max Send T to ensure the RIB re-synchronizes itself on the network after power loss. It is the responsibility of the user to ensure this value does not cause conicts in
network trac. (No value = No “heartbeat” updates / no re-sychronization; Low Value = Many updates
but may cause many trac collisions; High value = Few updates but many less collisions.)
Notes:
• Order with P1 option by adding “-P1” to end of
model number. T
he P1 option is pre-programmed to
allow dry contact binary input to command the relay.
Contact closure on the BI will activate relay.
• When connecting 24 Vac to both the RIB(s) and a
half-wave device, damage to device can occur.
Option 1: Use separate transformers for each device.
Option 2: Add diode between devices, see Option 2
note below. ^^
# Relays & Contact Type:
Expected Relay Life:
Operating Temperature:
Humidity Range:
Operate Time:
Green LED:
Red LED:
Yellow LED:
Pink LED:
Dimensions:
Wires:
Approvals:
Housing Rating:
Gold Flash:
Override Switch:
One (1) SPST Continuous Duty Coil
10 million cycles minimum mechanical
-30 to 140° F
5 to 95% (noncondensing)
18ms
Network Status
Relay Status
Service Status
Binary Input Status
4.00˝ x 4.00˝ x 1.80˝ with .50˝ NPT Nipple
16˝, 600V Rated
FCC, LonMark®
UL List
ed, UL916, C-UL
UL Accepted for Use in Plenum, NEMA 1
No
Yes
TP/FT-10
FT5000 Smart Transceiver
FT3120 / FT3150, FTT-10 / FTT-10A, and
LPT-10 / LPT-11 Tranceivers
0000 Node Object
0004 Closed Loop Actuator Object
0001 Open Loop Sensor Object
PDF, XIF, APB, VSS and NXE
available on website.
Contact Ratings:
20 Amp Resistive @ 277 Vac
20 Amp Ballast @ 120/277 Vac (N/O)
10 Amp Ballast @ 120/277 Vac Vac (N/C)
Not rated for Electronic Ballast
10 Amp Tungsten @ 120 Vac (N/O)
1110 VA Pilot Duty @ 277 Vac
770 VA Pilot Duty @ 120 Vac
2 HP @ 277 Vac
1 HP @ 120 Vac
Power Input Ratings:
111 mA @ 24 Vac
96 mA @ 120 Vac (RIBTW2401SB-LN)
105 mA @ 208-277 Vac (RIBTW2402SB-LN)
81 mA @ 24 Vdc
Power Input:
24 Vac/dc ; 120 Vac ; 50-60 Hz (RIBTW2401SB-LN)
24 Vac/dc ; 208-277 Vac ; 50-60 Hz (RIBTW2402SB-LN)
RIBTW2401SB-LN
LonWorks® Twisted-Pair FT-10 Network Enclosed
Dual I/O Device: One Binary Output (20 Amp
Relay SPST + Override), One Binary Input
(Dry Contact, Class 2); 24 Vac/dc or 120 Vac
Power Input
RIBTW2402SB-LN
LonWorks® Twisted-Pair FT-10 Network Enclosed
Dual I/O Device: One Binary Output (20 Amp Relay
SPST + Override), One Binary Input (Dry
Contact, Class 2); 24 Vac/dc or 208-277 Vac
Power Input
Wht/Yel
Neutral or
Other Phase
Wht/Brn
208-277 Vac
Org
Org
CLOSED OPEN AUTO
24 Vac/dc
Com
Class 2 Dry Contact Binary Input
LON
LON
Service Button
GREEN LED = Network Status
PINK LED = Binary Input Status
RED LED = Relay Activated
YELLOW LED = Service
Selectable
Jumper Wire
Org
Org
CLOSED OPEN AUTO
Wht/Yel
Neutral
Wht/Blk
120 Vac
24 Vac/dc
Com
Class 2 Dry Contact Binary Input
LON
LON
Service Button
GREEN LED = Network Status
PINK LED = Binary Input Status
RED LED = Relay Activated
YELLOW LED = Service
Selectable
Jumper Wire
DESCRIPTION SNVT NAME SNVT TYPE
Command to open/close relay nvi Value SNVT_switch
Command status of relay nvo Value Fb SNVT_switch
Default state of relay on/o nci Default SNVT_switch
Communication timer nci Max Receive T SNVT_elapsed_tm
Status of Binary Input nvo Value SNVT_switch
Invert status of Binary Input nci Invert SNVT_lev_disc
Max time between updates nci Max Send T SNVT_elapsed_tm
Min time between updates nci Min Send T SNVT_elapsed_tm