RIB,Relay In A Box,Functional Devices RIBTW2401B-WIUI-N4 Data Sheet

RELAYS
RIBTW2401B-WIUI-N4
Power Input (Use one):
24 Vac = Terminal Strip (20 Vac min. ; 28 Vac max.) 24 Vdc = Terminal Strip (24 Vdc min. ; 28 Vdc max.) 120 Vac = Terminal Strip
Device Settings by Network:
Note: There will be no security if password eld is left blank. A password may be entered that will secure the webpage as well as Controller Commands. Eight alpha-numerical characters case-sensitive.
Yellow LED = Infrastructure Status
CAUTION: Remove all connections to UI 1 and UI 2 when setting input.
Universal Input: Congurable by internal device web page, accessible in either Ad-Hoc or Infrastructure.
• Analog value returned, user congurable min. and max. scale, and label, 0-5 Vdc, 0-10 Vdc, or 4-20 mA
• Direct temperature reading from Type T2 Thermistor. Connect between +5 Vdc and UI input.
• Digital Input, connect between +5 Vdc and UI input.
Wi IEEE 802.11 b/g Network Enclosed I/O Device: One Discrete Output (20 Amp Relay SPDT + Override), One Discrete Input (Dry Contact, Class 2); Two Universal Inputs; 24 Vac/dc, 120 Vac Power
Universal Input 1
+ 5V UI1 COM
UI1 420
COM
24Vac
24Vdc
Universal Input 2
+ 5V UI2 COM
24V Optional Power Input
SPECIFICATIONS
# Relays & Contact Type:
Expected Relay Life:
Operating Temperature:
Operate Time:
Pink LED:
Yellow LED:
Green LED:
Red LED:
Dimensions:
Approvals:
Housing Rating:
Gold Flash:
Relay Override Switch:
Wi:
Security:
RESET to Factory
Defaults Pushbutton
Relay
Operation
AUTO
OFF
ON
SW 1
X
UI2 420
SW 2
Term A: (Not used)
Term A: 120 Vac
Term B: (Not used)
Term C: Neut
(Activate with insulated tool)
General
COM
Purpose Dry Contact
DI
Input
120 Vac Optional Power Input
One (1) SPDT Continuous Duty Coil 10 million cycles minimum mechanical
-30 to 140° F 18ms Digital Input Status Wi Ad-Hoc Status Wi Infrastructure Status Device Status Relay Status
4.28˝ x 7.00˝ x 2.00˝ with .75˝ NPT Nipple UL Listed, UL916, C-UL FCC, Wifi Certified ASD Device UL Accepted for Use in Plenum, NEMA 4X No DIP Switch Control IEEE 802.11 b/g/n Compatible, (G) 54 Mbps Data Rate –95 dBm Sensitivity +16 dBm Output Power (WPA-PSK or WPA-2-PSK Available) Supports PING and ARP DSSS Modulation Customer can choose to have C
ontroller Commands authentication-secured
Webpage and
with Username and Password.
Pink LED = DI Status
Relay Contacts
COM
N/C
Green LED = Ad-Hoc Status
N/O
Shown
With
Cover
Red LED = Relay Status
Green LED = Device Status
Contact Ratings:
20 Amp Resistive @ 277 Vac 5 Amp Resistive @ 480 Vac 20 Amp Ballast @ 277 Vac 16 Amp Electronic Ballast @ 277 Vac (N/O) 10 Amp Tungsten @ 120 Vac (N/O) 1110 VA Pilot Duty @ 277 Vac 770 VA Pilot Duty @ 120 Vac 1 HP @ 120 Vac 2 HP @ 277 Vac
Power Input Ratings:
158 mA Max @ 24 Vac 110 mA Max @ 24 Vdc 55 mA Max @ 120 Vac
Available TCP/IP Settings:
IP Address (Static)
Port Number
Subnet Mask
Gateway Address
Ad-Hoc mode (Default)
Infrastructure mode
Scan for wireless networks
Code Version 4.7.1.1.0
Device Settings:
Local Override
Reset to Network Defaults Pushbutton
Power up default relay state Host name and location labels Relay bound to digital input Username and Password security:
Setup instructions available
on website.
http://www.functionaldevices.com/pdf/ bulletins/B1783_393223.pdf
Or scan QR code with your smart phone.
Made in USA
Meets
Buy American
of ARRA 2009
Wi-Fi RIB
4-20 mA, when used, requires jumper to be installed on UI set for 4-20 mA input. Jumper MUST be removed when UI input used as anything other than 4-20 mA.
For application manual, please visit: www.functionaldevices.com
, connect between UI and Com.
*