LOW COIL INPUT RELAY
RIBTE02B
Enclosed Relay Hi/Low Separation 20 Amp SPDT,
208-277 Vac Power Input + 5-25 Vac/dc
Control Input
5-25 Vac/dc
CONTROL INPUT
Wht/Brn
208-277 Vac
POWER INPUT
Wht/Brn
SPECIFICATIONS
Power Input:
# Relays & Contact Type:
Operating Temperature:
Control Input:
Expected Relay Life:
Humidity Range:
Operate Time:
Relay Status:
Dimensions:
Wires:
Approvals:
Housing Rating:
Gold Flash:
Override Switch:
Blu - N/C
Yel - Comm
Org - N/O
208-277 Vac, 50-60 Hz
5-25 Vac/dc, 50-60 Hz
One (1) SPDT Continuous Duty Coil
10 million cycles minimum mechanical
-30 to 140° F
5 to 95% (noncondensing)
18ms
LED On = Activated
4.00˝ x 4.00˝ x 1.80˝ with .50˝ NPT Nipple
16˝, 600V R
ated
UL Listed, UL916, UL864, C-UL California
State Fire Marshal
UL Accepted for Use in Plenum, NEMA 1
No
No
Contact Ratings:
20 Amp Resistive @ 277 Vac
5 Amp Resistive @ 480 Vac
1110 VA Pilot Duty @ 277 Vac
770 VA Pilot Duty @ 120 Vac
20 Amp Ballast @ 277 Vac
16 Amp Electronic Ballast @ 277 Vac (N/O)
10 Amp Tungsten @ 120 Vac (N/O)
240 Watt Tungsten @ 120 Vac (N/C)
2 HP @ 277 Vac
1 HP @ 120 Vac
Power Input Ratings:
69 mA @ 208-277 Vac
Made in USA
Meets
“Buy American”
of ARRA 2009
Control Input Ratings:
.4 mA @ 5 Vdc
.9 mA @ 10 Vdc
1 mA @ 12 Vdc
2 mA @ 24 Vdc
3 mA @ 24 Vac
(Non Polarized)