RIB,Relay In A Box,Functional Devices RIBR24D, RIBR24SD Data Sheet

RELAYS
10 AMP PILOT CONTROL RELAYS
RIBR24D
DIN Mount Relay 10 Amp DPDT with 24 Vac/dc Coil
24Vac/dc COM
NC1 NC2
Specications
# Relays & Contact Type:
Expected Relay Life:
Operating Temperature:
Humidity Range:
Replacement Relay:
Not Used
Open Lid this SideOpen Lid this Side
Operate Time:
Relay Status:
Dimensions:
Terminal Strip:
Approvals:
Accessories:
One (1) DPDT Continuous Duty Coil 10 million cycles minimum mechanical
-30 to 140° F 5 to 95% (noncondensing) 8mS LED On = Activated
3.88˝ x 2.76˝ x 0.78˝ 14-22 AWG wire UL Listed, UL916, C-UL AR24D ADIN35, ADIN35ES
NO2 NO1
RIBR24SD
DIN Mount Relay 10 Amp DPDT + Override 24 Vac/dc Coil
CLOSED
OPEN
AUTO
Override Switch
PWR CTRL COM
Not Used
Open Lid this SideOpen Lid this Side
Contact Ratings:
10 Amp Resistive @ 30 Vdc 10 Amp General Use @ 277 Vac 1/2 HP @ 120-240 Vac (N/O) 1/3 HP @ 120-240 Vac (N/C) B300 Pilot Duty 120Vac 30A Make 3A Break (360 VA) 240Vac 15A Make 1.5A Break (360 VA) 208Vac 17.3A Make 1.73A Break (360 VA) 277Vac 13A Make 1.3A Break (360 VA) 24Vac 30A Make 5A Break (120VA) 5A Max
C2 C1
NC1 NC2
Apply Continuous Power(24Vac/dc) to PWR and COM.
Apply Coil Control(24Vac/dc) to CTRL and COM.
NO2 NO1
C2 C1
Models ADIN35 and ADIN35ES sold separately. See data sheet on website for more product information.
Made in USA
Meets
Buy American
of ARRA 2009
Power and Control Current:
24 mA @ 18 Vac 32 mA @ 24 Vac 40 mA @ 30 Vac
20 mA @ 20 Vdc 24 mA @ 24 Vdc 36 mA @ 24 Vdc
Coil Voltage Input:
24 Vac/dc ; 50-60 Hz Drop Out = 3 Vac / 3.8 Vdc Pull In = 18 Vac / 20 Vdc
ADIN35
DIN Rail Perforated 35mm x 7.5mm x 1m
ADIN35ES
Pair of End Stops for 35mm DIN Rail