RIB,Relay In A Box,Functional Devices RIBMX24 Series Data Sheet

CURRENT
SENSORS
RELAY & AC CURRENT SWITCH COMBOS
RIBMX24 Series
4.00˝ Track Mount 20 Amp Relay/AC Sensor Combinations, with 24 Vac/dc Coil
RIBMX24BA, RIBMX24BF+
Sensor Feedback
Current Sensor Status
Comm
N/O
RIBMX24BV^
0-10 Vdc
0-5 Vdc
Comm
Made in USA
Meets
Buy American
of ARRA 2009
V
V
Comm
N/O
Comm
RIBMX24SBA, RIBMX24SBF+
Sensor Feedback
Current Sensor Status
Selectable Jumper Wire
Comm
SPECIFICATIONS
Expected Relay Life:
Operating Temperature:
Humidity Range:
Operate Time:
Relay Status:
Dimensions:
Track Mount:
Approvals:
Gold Flash:
10 million cycles minimum mechanical
-30 to 140° F 5 to 95% (noncondensing) 18ms Red LED On = Activated
2.95˝ x 4.00˝ x 1.25˝
4.000˝, See MT4 Series on page 152
MT4 Mounting Track Sold Separately
UL Listed, UL916, UL864, C-UL California State Fire Marshal, CE, RoHS No
CLOSED
OPEN AUTO
N/C
Not Used
Comm
N/C
RIBMX24SBV^
0-10 Vdc
0-5 Vdc
Comm
Comm
V
V
Selectable Jumper Wire
Not Used
CLOSED
OPEN AUTO
FUNCTIONAL DEVICES CERTIFIED FOR USE WITH ECMS
Coil Current:
50 mA @ 18 Vac 83 mA @ 24 Vac 33 mA @ 22 Vdc 35 mA @ 24 Vdc 47 mA @ 30 Vdc
Coil Voltage Input:
24 Vac/dc ; 50-60 Hz Drop Out = 3 Vac / 3.8 Vdc Pull In = 18 Vac / 22 Vdc
Sensor Contact: +
When current sensor status is o (open), leakage
<30 uA @ 30Vac/dc
When current sensor status is on (closed), voltage drop
< .3 Vac/dc @ .1 Amp < 1.6 Vac/dc @ .4 Amp
Sensor Feedback Output: ^
Voltage output is proportional to current sensor range.
Min. Input Impedance = 30K ohms
Accuracy +/– 1% full scale
Vripple < 10m Vac
RIBMX24 SERIES SELECTION GUIDE
Model#
RIBMX24BF .50-20 Amps
RIBMX24BA .50-20 Amps
RIBMX24BV 0-20 Amps
RIBMX24SBF .50-20 Amps
RIBMX24SB
RIBMX24SBV 0-20 Amps
Sensing
Range
ECMS
ECMS
ECMS
ECMS
A .50-20 Amps
= FDI Certied for use with electronically commutated motorsECMS
Type Threshold Sensor Output Resistive
Internal w/
contact
status
Internal w/
contact
status
Fixed,
.50 Amp
Adjustable
Solid State Contact 30 Vac/dc, 0.4 Amp
Solid State Contact 30 Vac/dc, 0.4 Amp
Internal w/
voltage
Analog
output
Internal w/
contact
status
Internal w/
contact
status
Fixed,
.50 Amp
Adjustable
Solid State Contact 30 Vac/dc, 0.4 Amp
Solid State Contact 30 Vac/dc, 0.4 Amp
Internal w/
voltage
Analog
output
0-5 Vdc
0-10 Vdc
0-5 Vdc
0-10 Vdc
C
Override
Switch
ontact Type
20 Amp No SPDT
20 Amp No SPDT
20 Amp No SPDT
20 Amp Yes SPST
20 Amp Yes SPST
20 Amp Yes SPST
Contact Ratings Notes
20 Amp Resistive @ 277 Vac 20 Amp Ballast @ 277 Vac 16 Amp Electronic Ballast @ 277 Vac (N/O) 10 Amp Tungsten @ 120 Vac (N/O) 1,110 VA Pilot Duty @ 277 Vac 770 VA Pilot Duty @ 120 Vac 240 Watt Tungsten @ 120 Vac (N/C) 2 HP @ 277 Vac 1 HP @ 120 Vac
20 Amp Resistive @ 277 Vac 20 Amp Ballast @ 277 Vac (N/O) 10 Amp Ballast @ 277 Vac (N/C)
Not rated for Electronic Ballast
10 Amp Tungsten @ 120 Vac (N/O) 1,110 VA Pilot Duty @ 277 Vac 770 VA Pilot Duty @ 120 Vac 240 Watt Tungsten @ 120 Vac (N/C) 2 HP @ 277 Vac 1 HP @ 120 Vac
Normally Open
or Normally Closed selected by yellow jumper wire
071417
Loading...