Analog Input
nvo Analog
NV1
nci Max SendT1
nci Min Send T1
nci Min Delta
Closed Loop Actuator
nvi Value
NV1
nvo Value Fb
NV2
nci Default
nci Max Receive T
Open Loop Sensor Object
(Binary Output) (Binary Input)
nvo Value
NV1
nci Invert
nci Max Send T
nci Min Send T
Node Object
nvi Request nvo Status
NV1 NV2
LON
LON
Class 2
Dry Contact
Binary Input
Analog-In
AI Com
Com
OPEN
1 2
5 V
10 V
CLOSED
OPEN
AUTO
Selectable
Jumper Wire
Service Button
GREEN LED = Network Status
RED LED = Relay Activated
YELLOW LED = Service
PINK LED = Binary Input Status
+ 5 V
(typically not used)
0-5Vdc or 0-10 Vdc
Temperature,
Humidity, Pressure
Transducer
AI Com
AI
10K
Analog
Input
Half-Wave Device
Com
24 Vac/dc
Com
24 Vac
24 Vac
RIBMW24SB-LNAI or RIBTW24SB-LNAI
Channel:
Transceiver Type:
Transceiver Compatibility:
Functional Blocks:
Downloadable Files:
The relay will go to the default state when the communication timer times out. Setting the timer value
to zero will cause the communication to never time out.
It is recommended to put a value in nci Max Send T to ensure the RIB re-synchronizes itself on the network after power loss. It is the responsibility of the user to ensure this value does not cause conicts in
network trac. (No value = No “heartbeat” updates / no re-sychronization; Low Value = Many updates
but may cause many trac collisions; High value = Few updates but many less collisions.)
Notes:
• Order with P1 option by adding “-P1” to end of model
number. T
he P1 option is pre-programmed to allow dry
contact binary input to command the relay. Contact closure
on the BI will activate relay.
• Normally Open or Normally Closed selected by yellow
jumper wire.
• Order NEMA 4 housing by adding “-N4” to end of model
number. (RIBTW24SB-LNAI-N4)
• Close DIP switch 1 for 0-5 Vdc Analog Input.
Close DIP switch 2 for 0-10 Vdc Analog Input.
• When connecting 24 Vac to both the RIB(s) and a half-wave
device, damage to device can occur. Option 1: Use separate
transformers for each device. Option 2: Add diode between
devices, see Option 2 note below. ^^
• See page 71 for -LNT2 or -LNT3 models if using a
thermistor. If using a thermistor on the Analog Input, set
DIP switches to the 0-5 Vdc setting. A look-up table must
also be made.
# Relays & Contact Type:
Expected Relay Life:
Operating Temperature:
Humidity Range:
Operate Time:
Green LED:
Red LED:
Yellow LED:
Pink LED:
Dimensions:
Track Mount:
Approvals:
Housing Rating:
Gold Flash:
Override Switch:
One (1) SPST Continuous Duty Coil
10 million cycles minimum mechanical
-30 to 140° F
5 to 95% (noncondensing)
18ms
Network Status
Relay Status
Service Status
Binary Input Status
4.00˝ x 4.00˝ x 1.50˝ (RIBMW24SB-LNAI)
4.28˝ x 7.00˝ x 2.00˝ with .75˝ NPT Nipple
(RIBTW24SB-LNAI)
MT4-4 Mounting Track Provided
FCC, LonMark®
UL Listed, UL916, C-UL
UL Listed, NEMA 1, C-UL, CE Approved,
UL A
ccepted for Use in Plenum,
Also available NEMA 4 / 4X
No
Yes
TP/FT-10
FT5000 Smart Transceiver
FT3120 / FT3150, FTT-10 / FTT-10A, and
LPT-10 / LPT-11 Tranceivers
0000 Node Object
0004 Closed Loop Actuator Object
0001 Open Loop Sensor Object
0520 Analog Input
PDF, XIF, APB, VSS and NXE
available on website.
Contact Ratings:
20 Amp Resistive @ 277 Vac
20 Amp Ballast @ 120/277 Vac (N/O)
10 Amp Ballast @ 120/277 Vac (N/C)
Not rated for Electronic Ballast
10 Amp Tungsten @ 120 Vac (N/O)
1110 VA Pilot Duty @ 277 Vac
770 VA Pilot Duty @ 120 Vac
2 HP @ 277 Vac
1 HP @ 120 Vac
Power Input Ratings:
111 mA @ 24 Vac
81 mA @ 24 Vdc
Power Input:
24 Vac/dc ; 50-60 Hz *
RIBMW24SB-LNAI
4.00˝ Track Mount LonWorks® Twisted-Pair FT-10
Network Three I/O Device; One Binary Output
(20 Amp Relay SPST + Override), One Binary
Input (Dry Contact, Class 2); One Analog Input
(0-5Vdc / 0-10 Vdc); 24 Vac/dc Power Input
RIBTW24SB-LNAI
Enclosed LonWorks® Twisted-Pair FT-10 Network
Enclosed Three I/O Device; One Binary Output
(20 Amp Relay SPST + Override), One Binary
Input (Dry Contact, Class 2); One Analog Input
(0-5Vdc / 0-10 Vdc); 24 Vac/dc Power Input.
LON
LON
Class 2
Dry Contact
Binary Input
Analog-In
AI Com
Com
OPEN
1 2
5 V
10 V
CLOSED
OPEN
AUTO
Selectable
Jumper Wire
Service Button
GREEN LED = Network Status
RED LED = Relay Activated
YELLOW LED = Service
PINK LED = Binary Input Status
+ 5 V
(typically not used)
Analog Input
nvo Analog
NV1
nci Max SendT1
nci Min Send T1
nci Min Delta
Open Loop Sensor Object
nvo Value
NV1
nci Invert
nci Max Send T
nci Min Send T
Analog Input
nvo Analog
NV1
nci Max SendT1
nci Min Send T1
nci Min Delta
Closed Loop Actuator
nvi Value
NV1
nvo Value Fb
NV2
nci Default
nci Max Receive T
Open Loop Sensor Object
(Binary Output) (Binary Input)
nvo Value
NV1
nci Invert
nci Max Send T
nci Min Send T
Analog Input
nvo Analog
NV1
nci Max SendT1
nci Min Send T1
nci Min Delta
DESCRIPTION SNVT NAME SNVT TYPE
Command to open/close relay nvi Value SNVT_switch
Command status of relay nvo Value Fb SNVT_switch
Default state of relay on/o nci Default SNVT_switch
Communication timer nci Max Receive T SNVT_elapsed_tm
Status of Binary Input nvo Value SNVT_switch
Invert status of Binary Input nci Invert SNVT_lev_disc
Max time between updates nci Max Send T SNVT_elapsed_tm
Min time between updates nci Min Send T SNVT_elapsed_tm
Value of Analog-In nvo Analog SNVT_lev_percent
Max time between Analog updates nci Max Send T1 SNVT_elapsed_tm
Min time between Analog updates nci Min Send T1 SNV T_elapsed_tm
Min change in Analog before updates nci Min Delta SNVT_lev_percent
Add diode on 24 Vac power (Com) interconnection
between devices. Band on diode faces towards RIB(s).
^^ Option 2:
Made in USA
Meets
“Buy American”
of ARRA 2009
SPECIFICATIONS
NETWORK COMPATIBLE RELAY / CURRENT SENSOR COMBOS